D3-2. Table of Contents DISPLACEMENT VENTILATION

Similar documents
D1-2. Table of Contents MODULAR CORE DIFFUSERS. 1240, Introduction & Product Description... D1-3. Dimensional Information...

6490, These perforated. ceiling returns feature a. square neck. Aluminum or steel perforated face. is available. 6600, 56600, 6600FR

B1-2. Table of Contents LOUVERED FACE DIFFUSERS

Front panel Perforated galvanised steel Stainless steel AISI 316 as option Casing Galvanised steel Stainless steel AISI 316 as option

K1-2. Table of Contents LINEAR BAR GRILLES 1500, 1500MC, 1800, 1800MC

ROUND DIFFUSERS G1. RM, RA Series Cone Diffusers. Introduction: RM, RA Series ROUND DIFFUSERS R M - R A S E R I E S

A1-2. Table of Contents ARCHITECTURAL & PLAQUE DIFFUSERS

6490, These perforated. ceiling returns feature a. square neck. Aluminum or steel perforated face. is available. 6600, 56600, 6600FR

J1-2. Table of Contents RETURN GRILLES

4880 This heavy duty, double deflection, supply grille features 1/2 front and 3/4 back blade. spacing. Available in steel construction only.

L1-2. Table of Contents SECURITY GRILLES 1310, 1310TF, Introduction & Dimensional Information... L1-13

SUPPLY ROUND DIFFUSERS TABLE OF CONTENTS ROUND DIFFUSERS. M-2 Excellence in Air Distribution MODELS RM1/5RM1/RM2/5RM2/RM4/5RM4/RA2/RA4

GRD PRODUCT CATALOG DISPLACEMENT VENTILATION PRODUCTS

TRB - Conical Ceiling Diffuser. Halton TRB. Conical Ceiling Diffuser

OVERVIEW Combination Supply/Return Diffuser (SARM)

B1-2. Table of Contents LOUVERED FACE DIFFUSERS

DFA - Conical Ceiling Diffuser. Halton DFA. Conical Ceiling Diffuser

B1-2. Table of Contents LOUVERED FACE DIFFUSERS

M1-2. Table of Contents INDUSTRIAL GRILLES. 680, 5680, 6880, 56880, 680MP, 5680MP Introduction... M1-3 Dimensional Data... M1-4

CRNRR, 5CRNRR These concentric ring nozzles feature a stub duct mounting frame for smaller duct work

J1-2. Table of Contents RETURN GRILLES

THB - Perforated Ceiling Diffuser. Halton THB. Perforated Ceiling Diffuser

INDEX. Chapter1 0. air master. Round Ceiling Diffusers

TBV - Terminal Unit. Halton TBV. Terminal Unit

C O L M A N. Air Distribution LINEAR SLOT DIFFUSERS CD SERIES SERIES

PRODUCT BROCHURE. Rectangular Displacement Diffuser RDW-FD RDW-FD : smartemp.com

E3-22. FDD Round Diffuser, Displacement Air Pattern. Introduction: FDD UNDERFLOOR PRODUCTS F D D

LINEAR SLOT DIFFUSERS

ISSUE B, OCT Architectural Square Ceiling Diffusers. UNI & AUNI Diffusers. Advanced Air

Accessories. Front vane panel Coupling sleeve with gasket Galvanised steel Gasket of rubber compound

LINEAR DIFFUSERS AND BAR GRILLES

DKR - Multi-nozzle Ceiling Diffuser. Halton DKR. Multi-nozzle Ceiling Diffuser

SINGLE DUCT TERMINAL UNITS 30X/HQX SERIES

THL - Conical Ceiling Diffuser. Halton THL. Conical Ceiling Diffuser

EAGLE Wall. Wall air diffusers with discs for supply air and flush mounting QUICK FACTS

Wall air diffusers with discs for supply air and flush mounting. Quick guide COLIBRI WALL

HIGH CAPACITY LINEAR SLOT DUFFUSERS

DKS - Multi-nozzle Ceiling Diffuser. Halton DKS. Multi-nozzle Ceiling Diffuser

C O L M A N. Air Distribution PERFORATED FACE DIFFUSERS P SERIES SERIES

FALCON Ceiling. Circular ceiling air diffuser for supply air QUICK FACTS

C O L M A N. Air Distribution LINEAR SLOT DIFFUSERS CE SERIES SERIES

DRUM JET DIFFUSERS TYPE: DJA DJB DJAP DJBP

500-YCI SERIES FAN-POWERED AIR TERMINAL UNIT FORM EG2 (404)

EYELASH DIFFUSERS E SERIES. Quality and efficiency without compromise

C O L M A N. Air Distribution JET DIFFUSERS DCJ SERIES DCJ SERIES

500-YH SINGLE DUCT AIR TERMINAL UNIT FORM EG1 (1101)

INDEX. Chapter3. air master. Linear Bar Grilles

WGA Long throw nozzle grille

EX C E L L E N C E ISO 9001 CERTIFIED COMPANY LINEAR BAR GRILLES.

FIRE RATED PRODUCTS FIRE RATED PRODUCTS

F1-2. Table of Contents PLENUM SLOT DIFFUSERS PTBS. Introduction & Dimensional Information... F1-3. Accessories... F1-54. Reference Charts...

Ceiling swirl diffusers

Perforated Face Ceiling Diffusers

Ceiling diffusers. Type VDR. For large temperature differences in heating mode, high penetration of air, with adjustable air control blades

Slot diffusers, Round duct diffusers. IMP Klima

DCS - Ceiling Diffuser. Halton DCS. Ceiling Diffuser

DFB - Conical Ceiling Diffuser. Halton DFB. Conical Ceiling Diffuser

PELICANTM. Wall. Rectangular perforated wall air diffusers for supply air. Quick guide

TCM - Conical Ceiling Diffuser. Halton TCM. Conical Ceiling Diffuser

CornerAir. CornerAir. Active chilled beam

PELICAN Ceiling. Square ceiling air diffuser for supply air and extract air QUICK FACTS

LINEAR SLOT DUFFUSERS

SLLS Linear Ceiling Diffuser

500-YVI PARALLEL FAN-POWERED AIR TERMINAL UNIT FORM EG3 (404)

Optima EXHAUST GRILL AND AIR LOUVER. Perforated Ceiling Diffusers. Features: Standard square sizes:

DAC - Conical Diffuser. Halton DAC. Conical diffuser

DIR. VARIZON Displacement unit with adjustable spread pattern. Quick guide

LINEAR SLOT DIFFUSERS PLENUMS

C O L M A N. Air Distribution LINEAR BAR GRILLES T SERIES SERIES

COLIBRI Ceiling QUICK FACTS. Square ceiling diffuser with discs for supply air

HORD HOSPITAL OPERATING ROOM AIR CURTAIN

SINGLE DUCT AIR TERMINAL UNITS

PELICAN Ceiling HF. Square extract air diffuser QUICK FACTS

High Performance Fan Coils FCHG Genesis Series Horizontal

fsfdfsdfsdfssfsf OMNI DIFFUSER

LINEAR BAR GRILLES T SERIES. Quality and e!ciency without compromise

Single Wall Round. Double Wall Round. Flat Oval. Comfort. Silencer. Industrial

Variable Air Volume (VAV) Pressure Independent Control

DRUM LOUVERS DRUM LOUVERS 45DL SERIES. Models: 45DL1 Single Vanes 45DL2 Split Vanes G151 HIGH CAPACITY LONG THROW ALUMINUM CONSTRUCTION

Wall and Ceiling Grille

critical environment diffusers

FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design

AIRODYNE CATALOGUE VOLUME CONTROL TAMPERS CONSTRUCTION / MATERIALS

PURELINE18 PARTICULARLY SLIM DIFFUSER FACE, AVAILABLE IN NUMEROUS VARIANTS FOR MANY DIFFERENT INSTALLATION SITUATIONS

HORD HOSPITAL OPERATING ROOM AIR CURTAIN

Ceiling swirl diffusers

Catalog Swirl diffuser DAL 358

RPD ROUND PLAQUE DIFFUSER

ADJUSTABLE SLOT DIFFUSER TYPE: SE800

CADENZA. Sound attenuator with tapered acoustic baffles for rectangular ducts QUICK FACTS

Accessories. Balancing plenum PRI For balancing & equalising the airflow and attenuating the duct noise

INDEX. Chapter1 1. A. Jet diffusers 1. Jet diffuser...: AJD-P

VAV TERMINAL UNIT KYODO-ALLIED TECHNOLOGY PTE LTD

ceiling swirl diffuser DQJ

483 mm (19 ) Server Cabinet Unique Series. Abstract. Features. 1.5 mm strong steel sheet. Load capacity up to 1000 kg. Standard colors grey and black

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc.

Ventilation grilles for installation into walls, sills or rectangular

UNDERFLOOR PRODUCTS E3

Ceiling swirl diffusers with perforated face plate

FAN POWERED TERMINAL UNITS

Transcription:

D3 Table of Contents This rectangular unit is ideal for wall or ceiling installations. B The U-shaped 180 discharge pattern and high capacity is ideal for retail spaces, commercial, or lobbies. ENGINEERING Displacement Ventilation System...D3-3 pplication Overview...D3-5 System Design...D3-6 References...D3-8 Introduction...D3-9 Dimensional Data...D3-11 Reference Chart & Performance Data...D3-12 Engineering Specifications...D3-13 C The round, 360 discharge pattern is ideal for central spaces or column installations. D The rounded triangle design makes this a great choice for high profile areas. E This flat faced unit is ideal for shallow and flush mount applications. The half flat oval, shallow design is ideal for offices, classrooms, and waiting areas. P The half round, 180 discharge pattern makes it ideal for column integration. This unit is ideal for high capacity corner applications. B Introduction...D3-14 Dimensional Data & Reference Chart...D3-16 Performance Data...D3-17 Engineering Specifications...D3-18 C Introduction...D3-19 Dimensional Data & Reference Chart...D3-21 Performance Data...D3-22 Engineering Specifications...D3-23 D Introduction...D3-24 Dimensional Data & Reference Chart...D3-26 Performance Data...D3-27 Engineering Specifications...D3-28 E Introduction...D3-29 Dimensional Data & Reference Chart...D3-31 Performance Data...D3-32 Engineering Specifications...D3-32 Introduction...D3-33 Dimensional Data & Reference Chart...D3-35 Performance Data...D3-36 Engineering Specifications...D3-37 P Introduction...D3-38 Dimensional Data...D3-39 Reference Chart & Performance Data...D3-40 Engineering Specifications...D3-41 Introduction...D3-42 Dimensional Data & Reference Chart...D3-44 Performance Data...D3-45 Engineering Specifications...D3-46 D3-2 www.krueger-hvac.com Excellence in ir Distribution

D3 Corner Round, Low-Velocity Supply Introduction: The Krueger by Halton provides a 90 discharge pattern which is well suited for corner installations with a curved face, the is able to handle high capacities at low sound levels. The detachable face facilitates cleaning of the internal baffle and duct connections. MODEL - Corner Round, Low-Velocity Supply Unit ETURES 20 gage front panel. Horizontal low velocity discharge at floor level. Corner installation with a 90 supply angle. Detachable front plate and removable baffle enables cleaning of the unit and duct work. Round duct connection with integral gasket on top or bottom of the diffuser. OPTIONS Stainless steel (ISI 316) design. 16 gage front panel. Duct cover (solid or perforated). Installation base (2, 4, 6 ). Vinyl trim in white or black. lat face. Metal trim (painted to match). INISHES Standard is Polyester Painted White (RL 9010). Custom colors available. pplication UNCTION ir is discharged into the space through the front panel of the unit, normally at a slightly lower temperature than setpoint. The supply air flows at floor level and gradually pervades through the occupied space before rising due of the convection of warm surfaces. The low velocity flow pattern is quarter-circular (90 ). NOTES: The flow pattern data has been defined for floor installation. (1) Duct cover is for covering the duct work and is optional. (2) Installation base is used to raise the unit off the floor and is also optional. D3-42 www.krueger-hvac.com Excellence in ir Distribution

D3 Corner Round, Low-Velocity Supply Installation INSTLLTION EXPLODED VIEW INSTLLTION Perform the installation in order. 1. ix mounting brackets (4 places) to low velocity unit. 1 B 4 3 7 6 C 9 G D E E 2. Remove trim (E) from unit. 3. Locate unit against wall and secure through mounting brackets. 4. ix duct cover support brackets () to wall between unit and ceiling. 5. Position base against lower flange of the unit. 6. fter installation of duct work, locate duct cover as follows: Locate duct cover section () on top flange (G) of unit and firmly push into support brackets fixed to wall (B). 2 DUCT INSTLLTION 1 WLL WLL W1 W1 3 5 Size (Unit Size) 8 1 W1 08 x23 4 13/16 3 7/16 10 x23 5 1/2 3 7/8 12 x31 5 15/16 4 3/16 14 x47 7 1/2 5 5/16 16 x47 9 6 3/8 19 x59 10 13/16 7 5/8 24 x71 13 3/16 9 5/16 29 x71 16 9/16 11 3/4 36 x71 20 1/8 14 3/16 7. Secure duct cover with screws through cover into support brackets. 8. Re-fit trim between duct cover and unit, and between base and unit by bending trim back on itself (E) and pressing bead into groove in flange (G). 9. When multiple sections of duct cover are used (D), an aluminium coupling flange (C) is needed. Service & Maintenance SERVICING Open the front panel (2) by first removing the trim (1) and unscrewing the screws. Pull out the front panel. If required, the internal baffle (3) can be detached by unscrewing the fixing screws. Pull out the inner structure. Clean the parts with a brush or damp cloth. fter cleaning, reassemble in reverse order. Code Description 1 Trim 2 ront Panel 3 Internal Baffle 4 ssembly Brackets 5 Casing Providing You With ir Distribution Solutions D3-43

D3 Corner Round, Low-Velocity Supply Dimensional Information RONT ND TOP VIEWS ØD - 1/8 2 1/2 H IRLOW DIMENSIONL REERENCES Size (Unit Size) W H ØD 08 x23 8 1/16 23 5/8 8 13/16 4 10 x23 9 1/4 23 5/8 10 1/16 5 12 x31 10 13/16 31 1/2 11 3/4 6 14 x47 13 47 1/4 14 8 16 x47 15 3/8 47 1/4 16 7/16 10 19 x59 18 11/16 59 1/16 19 9/16 12 24 x71 23 1/16 70 7/8 24 1/4 16 29 x71 28 9/16 70 7/8 29 13/16 20 36 x71 35 1/16 70 7/8 36 7/16 24 LT CE DIMENSIONL REERENCES W RONT VIEW LT CE TOP VIEW DØ - 1/8 TOP VIEW W IRLOW Size (W x H) W H ØD 24 x24 24 24 12 8 24 x36 24 36 12 8 24 x48 24 48 12 8 24 x60 24 60 12 8 24 x72 30 72 12 8 30 x24 30 24 15 8, 10 30 x36 30 36 15 8, 10 30 x48 30 48 15 10 30 x60 30 60 15 10 30 x72 36 72 15 10 36 x24 36 24 18 10, 12 36 x36 36 36 18 12 36 x48 36 48 18 12 36 x60 36 60 18 12 36 x72 36 72 18 12 Reference Chart IRLOW VS. NC LEVEL: SERIES 2800 2600 irflow (CM) 2400 2200 2000 1800 1600 1400 1200 1000 800 600 Neck Size 24" 20" 16" 12" 10" 4" 8" 6" 5" 4" 400 200 0 15 17 19 21 23 25 27 29 31 33 35 Sound Level, NC D3-44 www.krueger-hvac.com Excellence in ir Distribution

D3 Corner Round, Low-Velocity Supply Performance Data IP/METRIC DT: SERIES Unit Size 08 x23 10 x23 12 x31 14 x47 16 x47 19 x59 24 x71 29 x71 36 x71 Neck Vel ir low IP Data Near T 50 @ 4 ft T 50 @ loor Neck Vel Metric Data NOTES: Throw values are given for terminal velocities of 50 fpm (0.25 m/s). Throw values are given for -6 (-3 C) T conditions. N.C. values are based on Octave Band 2-7 sound power levels minus a room absorption of 4dB. Dash in space denotes a NC or db value of less than 10. Data was obtained from tests conducted in accordance with NSI / SHRE Standard 70-1991. ir low Near T.25 @ 1.1 m T.25 @ loor Pt Ps Pt Ps Octave Band, db NC PM CM "WG "WG ft ft m/s L/s Pa Pa m m 2 3 4 5 6 7 450 39.035 0.022 0 3 11 2.29 19 8.6 5.5 0.0 1.0 22 19 23 11 - - 700 61.084 0.053 0 5 22 3.56 29 20.9 13.3 0.1 1.6 24 28 32 26 14-950 83.154 0.098 1 7 30 4.83 39 38.5 24.5 0.2 2.1 26 34 38 36 28 17 1150 100.211 0.128 1 8 35 5.84 47 52.5 31.9 0.3 2.4 27 38 42 42 36 24 475 65.049 0.035 0 5 11 2.41 31 12.2 8.7 0.1 1.5 18 25 22 13 - - 700 95.107 0.076 0 7 23 3.56 45 26.5 18.9 0.1 2.3 25 32 32 26 17-900 123.176 0.126 1 10 30 4.57 58 43.8 31.3 0.2 2.9 29 37 39 35 29 17 1050 143.111 0.043 1 11 35 5.33 68 27.7 10.6 0.3 3.4 32 40 43 40 36 22 600 118.057 0.035 1 5 11 3.05 56 14.3 8.7 0.2 1.6 23 29 23 14 - - 850 167.115 0.070 2 8 22 4.32 79 28.7 17.4 0.5 2.3 28 34 31 26 17-1100 216.193 0.117 3 10 30 5.59 102 48.0 29.2 0.8 3.0 31 37 37 35 29 17 1300 255.280 0.175 4 12 35 6.60 120 69.7 43.5 1.1 3.5 33 40 41 41 36 24 675 235.046 0.018 2 8 12 3.43 111 11.5 4.4 0.5 2.4 25 29 23 16 - - 850 296.073 0.028 3 10 20 4.32 140 18.2 6.9 0.8 3.1 30 33 30 25 14-1100 384.122 0.047 5 12 29 5.59 181 30.4 11.6 1.4 3.8 35 38 37 35 27 20 1300 453.453 0.348 6 13 35 6.60 214 112.9 86.7 2.0 4.1 39 41 42 41 34 26 525 286.046 0.028 1 7 11 2.67 135 11.4 7.1 0.4 2.2 24 25 20 15-11 700 382.081 0.051 2 10 21 3.56 180 20.2 12.6 0.7 2.9 29 31 28 25 15 17 925 504.142 0.088 4 11 30 4.70 238 35.3 22.0 1.2 3.4 33 37 36 35 28 22 1075 586.237 0.165 6 12 35 5.46 277 58.9 41.0 1.7 3.6 36 40 40 40 36 25 325 255.028 0.022 2 7 12 1.65 120 7.1 5.4 0.5 2.2 24 19 - - - 18 600 471.097 0.074 6 13 24 3.05 222 24.0 18.5 1.9 4.1 33 32 26 20 13 23 850 667.194 0.149 10 16 31 4.32 315 48.3 37.1 2.9 4.8 38 39 37 35 28 25 1050 824.310 0.242 12 18 35 5.33 389 77.3 60.2 3.6 5.4 42 43 43 44 37 27 575 802.068 0.047 7 16 12 2.92 379 16.9 11.7 2.3 4.9 25 30 22 19 11-700 977.100 0.070 11 19 21 3.56 461 25.0 17.4 3.4 5.9 30 34 29 27 21-800 1116.131 0.091 15 22 28 4.06 527 32.6 22.7 4.4 6.8 33 36 34 33 27 14 950 1325.371 0.314 20 26 35 4.83 626 92.3 78.3 6.2 8.0 37 40 40 41 36 24 475 1036.064 0.049 9 20 12 2.41 489 15.8 12.3 2.8 6.1 22 28 24 17 - - 575 1254.093 0.072 14 22 20 2.92 592 23.2 18.0 4.2 6.8 28 32 30 25 14-700 1526.138 0.107 20 25 28 3.56 720 34.4 26.7 6.2 7.5 34 37 36 33 25 14 850 1853.000-0.045 27 27 36 4.32 875 0.0 (11.2) 8.1 8.3 41 41 43 42 36 22 400 1363.066 0.056 13 23 12 2.03 643 16.4 13.9 4.0 6.9 23 28 21 - - - 510 1737.107 0.091 21 29 21 2.59 820 26.6 22.6 6.3 8.8 31 34 30 22 12-625 2129.160 0.136 25 32 29 3.18 1005 39.9 33.9 7.7 9.9 38 39 38 33 21-725 2470.216 0.183 29 35 35 3.68 1165 53.7 45.6 9.0 10.6 43 43 44 40 27 - Providing You With ir Distribution Solutions D3-45

D3 Corner Round, Low-Velocity Supply Suggested Specification & Configuration urnish and install Krueger by Halton displacement diffuser as indicated on the drawings and diffuser schedule. 1. MODEL: (XXX) - Corner Round, Low-Velocity Supply Unit The corner round low velocity diffuser shall be made of galvanized steel with a polyester powder coat finish. The unit shall include a detachable perforated front panel and include an internal equalization baffle. The front panel shall have holes on a staggered pattern providing a well-balanced appearance and enhancement to performance. Both the internal baffle and diffuser face shall be attached securely to the extruded aluminum frame or galvanized housing. The diffuser design will be robust, rigid and sturdy with a 20ga. face and cabinet. The unit shall have a round duct connection as required by the diffuser schedule. Round inlets shall include a fixed rubber gasket located near the edge of the inlet ensuring a proper seal of the attached duct work. The horizontal edges of the diffuser shall include a vinyl or metal trim for aesthetic appeal. Mounting brackets shall be included with the unit for installation. BSE urnish and install the base as indicated on the drawings and diffuser schedule. The base shall be manufactured of 20ga. steel to match the footprint of the displacement diffuser. The base height will be indicated on the drawings and diffuser schedule. The base will be independently removable from the diffuser allowing access to the duct if supplied from below; or to the area beneath the diffuser. The base finish will match the diffuser. DUCT COVER urnish and install the duct cover as indicated on the drawings and diffuser schedule. The duct cover will be supplied in either a solid or perforated 20ga. steel material. The perforated material will match the diffuser in pattern and stagger. The duct cover will be supplied with mounting angles and trim pieces for installation. The duct cover finish will match the diffuser. PERORMNCE Unit performance shall be tested in accordance with the following standards: ir flow rate, EN-ISO 5167-1; Pressure Difference, EN-ISO 5135; Sound Power Level, EN-ISO 7235. 2. UNIT SIZE: (XXxXX) 08x23 - Nominal 10x23 - Nominal 12x31 - Nominal 14x47 - Nominal 16x47 - Nominal 19x59 - Nominal 24x71 - Nominal 36x71 - Nominal See Krueger s selection software for additional sizes. 3. CE: (XXX) STD - Standard Curve LT - lat ace 4. INLET: (XX) * 4, 5, 6, 8, 10, 12, 16, 20, 24 5. MTERIL: (XX) GS - Steel SS - 316 Stainless Steel ** 6. RONT PNEL THICKNESS: (XX) 20-20 Gage (Standard) 16-16 Gage 7. TRIM: (XXX) WHT - White BLK - Black MTL - Metal, Painted to Match 8. DUCT COVER: (XX) 00 - None DP - Perforated Duct Cover DS - Solid Sheet Duct Cover 9. DUCT COVER LENGTH: (XXX.XXX) xxx.xxx - Length in Inches 10. INSTLLTION BSE: (XX) 00 - None B2-2 Base Cover B4-4 Base Cover B6-6 Base Cover 11. INISH: (XX) 44 - White (RL-9010) 90 - Polished *** 35 - Black 07 - Custom D3-46 www.krueger-hvac.com Excellence in ir Distribution * See dimensional information for unit and inlet size offerings. ** Material Code SS (316 stainless steel) not available with ront Panel Thickness code 16 (16 gage). Material Code SS (316 stainless steel) only available with inish code 90 (polished). If Material Code SS (Stainless Steel) is selected, the Duct Cover and Installation Base, if selected will be Stainless Steel. *** inish code 90 (polished) not available with Material Code GS (steel). SMPLE CONIGURTION: - 16x47 - STD - 10 - GS - 20 - WHT - DP - 120.250 - B4-44