Holder Construction Company 230 Peachtree Street NW, Suite 1250 Atlanta, GA 30303 Submittal Project Telephone #404.688.6233 Project Name: Submittal Number: Submittal Description: Submittal Review Date: Submittal Reviewed By: 230 Peachtree Hotel Conversion 260-23 60 00-2.7 Bulletin #4 - Fan Coil Units 05/05/15 Allie Creach acreach@holder.com Reviewed Reviewed as Noted Rejected The review of shop drawings does not relieve the Subcontractor/ Vendor from the requirements of the Contract Documents. Subcontractors/Vendors are hereby notified that any cost/schedule impacts caused by changes to a submittal must be reported to Holder Construction within (5) days as stated in Section 8 of Holder's subcontract. Subcontractors/Vendors failing to report, in writing, cost/schedule impacts within this time frame are fully responsible for such impacts. All changes or variations to the Contract Documents must be flagged and noted. Failure to do so leaves the responsibility for coordination any cost impacts caused from changes with that Subcontractor/Vendor. Holder Comments: 1. Updates per Bulletin #4 A/E Comments:
4/29/2015 Page 1 of 13 230 Peachtree Street Hotel 4/29/2015 Fan Coil Units - Bulletin 4 1 JCI/York See attached performance. 236000.2.7 FWC and FHP fan coil units See attached electrical characteristic details. See attached for accessories details. See attached for options details. None.
4/29/2015 Page 2 of 13 EQUIPMENT SUBMITTAL FOR APPROVAL PROJECT: 230 Peachtree Street Hotel LOCATION: Atlanta GA York Solution Indoor Air Handling Unit EQUIPMENT FWC & FHP Fan Coil Unit UNIT TAGS FCU B1-7 ~ FCU B1-17 & 2-16 QUANTITY (5) & 7 existing SOLD TO: Batchelor & Kimball Inc. 6700 Tribble Street Lithonia, GA 30058 CONSULTING ENGINEER: PerryCrabb 2987 Clairmont Road NE Suite 400 Atlanta, GA 30329 PREPARED BY: Allen J. Sirek Project Engineer 1350 Northmeadow Parkway Suite 100 Roswell, GA 30076 DATE: April 29, 2015 REVISION: 0
4/29/2015 Page 3 of 13 Bulletin 4 changes FCUs B1-14 ~ FCU B1-17 will be ordered also FCU 2-16 FCUs deleted - but can be re-used as FCUs FCU B1-7 ~ FCU B1-13
4/29/2015 Page 4 of 13 230 Peachtree Bulletin 4 FCU 4/27/15 Unit Electric Heat Chilled Water Coil Tag Airflow Qty ESP Model V/P/Hz EAT DB LAT DB Capacity Heating FLA V/P/Hz Steps 1 EAT DB/WB LAT DB/WB Total Capacity Sensible Capacity EWT/LWT Fluid Flow FCU 2 16 241 1 0.15 FHP 277/1/60 70 96.2 2 7.22 277/1/60 1 75/63 54.6/52.9 7110 5450 45/53.8 1.6 GPM FCU B1 7 566 1 0.2 FWC C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPM FCU B1 8 566 1 0.2 FWC C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPM FCU B1 9 566 1 0.2 FWC C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPM FCU B1 10 566 1 0.2 FWC C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPM FCU B1 11 566 1 0.2 FWC C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPM FCU B1 12 566 1 0.2 FWC C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPM FCU B1 13 566 1 0.2 FWC C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPM FCU B1 14 566 1 0.2 FWC C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPM FCU B1 15 566 1 0.2 FWC C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPM FCU B1 16 566 1 0.2 FWC C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPM FCU B1 17 566 1 0.2 FWC C 277/1/60 70 92.3 4 14.44 277/1/60 1 75/63 52.3/51.4 18790 14210 45/54.8 3.8 GPM Notes and clarifications: 1) Selections were based on mechanical drawings page M6 02 (bulletin 4) and are dated 4/6/15. 2) Bulletin 4 (4/6/15) deleted previous FCU 1 1 through FCU 1 7 fan coil units, and added the 12 new units however these deleted 7 units still meet the performance for the new B1 units and have been rerated. As a result only 5 additional terminal units will be required to be ordered (4 FWC C and 1 FHP). Note: Only FCU B1-14 ~ FCU B1-17 and FCU 2-16 will be ordered.
4/29/2015 Page 5 of 13 Confirmations for Release FCU 2-16 1) Confirm 277/1/60 2) Confirm cooling coil left or right hand connection FCU B1-14 3) Confirm 277/1/60 4) Confirm cooling coil left or right hand connection FCU B1-15 5) Confirm 277/1/60 6) Confirm cooling coil left or right hand connection FCU B1-16 7) Confirm 277/1/60 8) Confirm cooling coil left or right hand connection FCU B1-17 9) Confirm 277/1/60 10) Confirm cooling coil left or right hand connection
Performance Data Sheet Page 1 of 1 4/29/2015 Page 6 of 13 Project Name: 230 Peachtree Bulletin 4 FCU JCI Contract No: Contract # Location: Coil Version: 7.01d Consultant/Engineer: Printed Date: 4/29/2015 8:57:33 AM Contractor: Selection Date: 4/24/2015 11:44:14 AM Sold To: Last Revision Date: 4/24/2015 11:44:31 AM Performance Data Sheet P.O. No: PO Unit Tag Qty Model Air Flow Total Duty Sensible Duty FCU-2-16 1 FHP25 241 CFM 7,110 Btuh 5,450 Btuh Unit Data Model : 25 Size No. Fans : 1 (Motor) HP : (1) 1/15 Motor FLA : 0.45 Type : Horizontal Low Profile Fan Speed : Medium Capacity : Std. Capacity Output Data Altitude [Ft.] 0 Air Flow Rate [CFM] 241 ESP [in.wg] 0.15 Cooling Data EAT DB/WB [ F] 75.0/ 63.0 LAT DB/WB [ F] 54.6/ 52.9 Total Capacity [Btuh] 7,110 Sensible Capacity [Btuh] 5,450 EWT/LWT [ F] 45.0/ 53.9 Fluid Flow [gpm] 1.60 Fluid P.D [ft.wg] 6.60 Fluid Velocity [fps] 2.80 Rows / FPI / Circuits : 3 Row / 10 FPI / 1 Ckt Coil Connection Size: [in.] 0.875 Heating Data EAT DB [ F] - LAT DB [ F] - Sensible Capacity [Btuh] - Rows / FPI / Circuits : - / - / - Electric Heat Data V/P/HZ : 277/1/60 KW : 2 Steps : 1-Stage Temp Rise [ F] 26.2 Amp Draw : 7.22 Special Quote (SQ)# SQ 1625 600 PSI Unions Special Quote (SQ)# SQ 2841 Y strainer on FH with cleanout Electrical Data V/P/HZ : 277/1/60 Total Full Load Amps : 7.67 MCA / MSCP : 9.59 / 15.00 Fan Power Input [Watts] 120 Sound power By Octave Band (db Re 10 12 Watts) Speed 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Medium 53 53 49 45 41 34 29 Filter : 1" Throwaway Filter (Qty) Size : 26x8.5x1 Filter Face Area [ft²] 1.54 Inlet Direction : Rear Coil Tube Dia. [in.] 1/2 Tube Wall [in.] 0.016 Coil Face Area [ft²] 1.35 Weight* [lb] 77 Options BC07 24V, Unit S/S & Fan Op. Relay, 3-Spd Fan Relay & Transformer OC011 Drain Pan Float Switch OC013 Non-Fused Door Interlocking Disconnect Switch - 40 Amps Stainless Steel Unit Drain Pan Cooling Coil: Piping Package Size - 1/2" Cooling Coil: 2-Way Control Valve Cooling Coil: Factory Provided (2-Position Close-Off, Normally Closed) Cooling Coil: Galvanized Casing Cooling Coil: Left Hand Connection Cooling Coil: Manual Air Vent Cooling Coil: P/T Ports Cooling Coil: Package Code- Code: 25 (Manual Ball Valve with Memory Stop, Fixed Flow Control) (2.00 GPM) Cooling Coil: Unions Special Quote (SQ)# Special Quote (SQ)# * Unit weight includes unit with wet coil(s) as selected. (Does not include accessories) Unit pressure drop and air flow based upon dry coil as required by AHRI- 440. Total sound power level data based on Horizontal Concealed Plenum Return Model with fan air flow at corresponding motor tap with 115/1/60 volt PSC motor, 4 row coil, 1" throwaway filter, 0.0" external static pressure and standard rated internal pressure losses. Sound data tested in accordance with AHRI-350-2000. Scheduled motor information is for Fan Input Power at High Speed. For 0' altitude the coil selection has been made at Standard Conditions. http://webselect.johnsoncontrols.com/submittals/perfreport/performancedatasheet.aspx?ch... 4/29/2015
Johnson Controls - Selection Summary Page 1 of 1 4/29/2015 Page 7 of 13 Project Name: 230 Peachtree Bulletin 4 FCU Line #: 4 Selection Method: Fixed ESP/Nominal Airflow Selection Date: 4/24/2015 11:44:15 AM Coil Version: 7.01d Mfg Model Unit Size * Weight does not include accessories. Unit Airflow Capacity (cfm) OA (cfm) Johnson Controls FHP 25 Standard 241 0 0.15 ESP Motor Motor (in.wc) (Hp) RPM (1) 1/15 General Fan Full Load Amps Ship Cycle: Standard Shipment Tag: FCU-2-16 Elevation: 0 ft. Printed Date: 4/29/2015 8:56:02 AM ET Notes: This field is for user purposes only and will not transfer to the order form. Total Full Load MCA MSCP Amps Fan Fan Watts Qty V/P/Hz Motor Speed Weight* (lb) 1450 0.45 7.67 9.59 15 120 1 277/1/60 Medium 77 Filter Type 1" Throwaway Fan selection and performance is shown at elevation of 0 ft. Electric Heat Coil EAT DB (deg.f) LAT DB (deg.f) Capacity (kw) Heating Full Load Amps Volts/Phase/Hz. Steps Air PD (in.wc) EAT DB/WB (deg.f) 70 96.2 2 7.22 277/1/60 1 0.01 LAT DB/WB (deg.f) Total Capacity (Btuh) Sensible Capacity (Btuh) EWT/LWT (deg.f) Chilled Water Coil Fluid Flow (gpm) Fluid PD (ft.) Fluid Velocity (fps) Air PD (in.wc) Coil Coil Rows FPI 75 / 63 54.6 / 52.9 7110 5450 45 / 53.8 1.60 6.6 2.8 0.05 3 10 1 No. Circuits Tube Wall 0.016 in. Sound Power By Octave Band (db Re 10-12 Watts) Band 2 3 4 5 6 7 8 Frequency 125 250 500 1000 2000 4000 8000 Total 53 53 49 45 41 34 29 Unit data is certified in accordance with AHRI-440. Sound data tested in accordance with AHRI-350-2000. Total sound power level data based on Horizontal Concealed Plenum Return Model with fan CFM at corresponding motor tap with 115/1/60 volt PSC motor, 4 row coil, 1" throwaway filter, 0.0" external static pressure and standard rated internal pressure losses. Unit pressure drop and CFM based upon dry coil as required by AHRI-440. Scheduled motor information is for Hi Speed. The coil selection has been made at Standard conditions. Outside Airflow is a user input value for scheduling purposes. http://webselect.johnsoncontrols.com/selection/fcu.asp?action=printallselections&projecti... 4/29/2015
4/29/2015 Page 8 of 13
Performance Data Sheet Page 1 of 11 FCU-B1-7 ~ FCU-B1-17 (11 total) Project Name: 230 Peachtree Bulletin 4 FCU JCI Contract No: Contract # Location: Coil Version: 4.28a Consultant/Engineer: Printed Date: 4/29/2015 9:02:05 AM Contractor: Selection Date: 4/24/2015 11:37:34 AM Sold To: Last Revision Date: 4/24/2015 11:38:02 AM Performance Data Sheet P.O. No: PO Unit Tag Qty Model Air Flow Total Duty Sensible Duty FCU-B1-7 1 FWC-C12 566 CFM 18,790 Btuh 14,210 Btuh Unit Data Model : 12 Size No. Fans : 4 (Motor) HP : (2) 1/20 Motor FLA : 0.84 Filter : 1" Throwaway Filter (Qty) Size : (3) 9.25 X 21.75 X 1 Filter Face Area [ft²] 4.19 Coil Tube Dia. [in.] 1/2 Tube Wall [in.] 0.016 Coil Face Area [ft²] 4.03 Weight* [lb] 166 Type : Vertical Floor - Series C Fan Speed : High Capacity : Std. Capacity Output Data Options Altitude [Ft.] 0 Auxiliary Drip Pan- Plastic, Double Wall Air Flow Rate [CFM] 566 BC03 24V, Unit S/S Relay / Fan Op. Relay & Transformer ESP [in.wg] 0.20 Coil Casing- Galvanized Casing Cooling Data OC011 Drain Pan Float Switch EAT DB/WB [ F] 75.0/ 63.0 OC013 Non-Fused Door Interlocking Disconnect Switch - 40 Amps LAT DB/WB [ F] 52.3/ 51.5 Paint Options- Pearl White Satin Total Capacity [Btuh] 18,790 Remote Mounted Thermostat Sensible Capacity [Btuh] 14,210 Return Air Options- Return: Open Toe Space EWT/LWT [ F] 45.0/ 54.8 Stainless Steel Unit Drain Pan Fluid Flow [gpm] 3.80 Supply Air Options- Supply: Duct Collar Fluid P.D [ft.wg] 3.38 Cooling Coil: Piping Package Size - 1/2" Fluid Velocity [fps] 2.20 Cooling Coil: 2-Way Control Valve Rows / FPI / Circuits : 3 Row / 10 FPI / 3 Ckt Cooling Coil: Factory Mounted Piping Package Coil Connection Size: [in.] 0.625 Cooling Coil: Factory Provided (2-Position Close-Off, Normally Closed) Heating Data Cooling Coil: Left Hand Connection EAT DB [ F] - Cooling Coil: Manual Air Vent LAT DB [ F] - Cooling Coil: Manual Ball valve w/ Memory Stop, fixed flow control (4.00 GPM) Sensible Capacity [Btuh] - Cooling Coil: P/T Ports Rows / FPI / Circuits : - / - / - Cooling Coil: Unions Electric Heat Data Cooling Coil: Y-Strainer- Y-Strainer with Blowdown V/P/HZ : 277/1/60 KW : 4 Steps : 1-Stage Temp Rise [ F] 22.3 Amp Draw : 14.44 Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# SQ 1625 600 PSI Unions Electrical Data V/P/HZ : 277/1/60 Total Full Load Amps : 15.28 MCA / MSCP : 19.10 / 20.00 Fan Power Input [Watts] 154 Sound power By Octave Band (db Re 10 12 Watts) Speed 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz High 62 64 65 56 50 44 35 4/29/2015 Page 9 of 13 * Unit weight includes unit with wet coil(s) as selected. (Does not include accessories) Unit pressure drop and air flow based upon dry coil as required by AHRI- 440. Total sound power level data based on Vertical Floor Exposed Model with fan air flow at corresponding motor tap with 115/1/60 volt PSC motor, 4 row coil, 1" throwaway filter, 0.0" external static pressure and standard rated internal pressure losses. Sound data tested in accordance with AHRI-350-2000. Scheduled motor information is for Fan Input Power at High Speed. For 0' altitude the coil selection has been made at Standard Conditions. http://webselect.johnsoncontrols.com/submittals/perfreport/performancedatasheet.aspx?ch... 4/29/2015
Johnson Controls - Selection Summary Page 1 of 11 FCU-B1-7 ~ FCU-B1-17 (11 total) 4/29/2015 Page 10 of 13 Project Name: 230 Peachtree Bulletin 4 FCU Line #: 5 Selection Method: Fixed ESP/Nominal Airflow Selection Date: 4/24/2015 11:37:35 AM Coil Version: 4.28a Mfg Model Unit Size Unit Airflow Capacity (cfm) OA (cfm) FWC- Johnson Controls 12 Standard 566 0 0.2 C * Weight does not include accessories. ESP Motor Motor (in.wc) (Hp) RPM (2) 1/20 2 @ 1050 General Fan Full Load Amps Ship Cycle: Standard Shipment Tag: FCU-B1-7 Elevation: 0 ft. Printed Date: 4/29/2015 9:01:05 AM ET Notes: This field is for user purposes only and will not transfer to the order form. Total Full Load MCA MSCP Amps Fan Fan Watts Qty V/P/Hz Motor Weight* Filter Type Speed (lb) 0.84 15.28 19.1 20 154 4 277/1/60 High 166 1" Throwaway Fan selection and performance is shown at elevation of 0 ft. EAT DB/WB (deg.f) LAT DB/WB (deg.f) Total Capacity (Btuh) Sensible Capacity (Btuh) EWT/LWT (deg.f) Chilled Water Coil Fluid Flow (gpm) Fluid PD (ft.) Fluid Velocity (fps) Air PD (in.wc) Coil Coil No. Tube Rows FPI Circuits Wall 75 / 63 52.3 / 51.4 18790 14210 45 / 54.8 3.80 3.38 2.2 0.04 3 10 3 Electric Heat Coil EAT DB (deg.f) LAT DB (deg.f) Capacity (kw) Heating Full Load Amps Volts/Phase/Hz. Steps Air PD (in.wc) 70 92.3 4 14.44 277/1/60 1 0.01 0.016 in. Sound Power By Octave Band (db Re 10-12 Watts) Band 2 3 4 5 6 7 8 Frequency 125 250 500 1000 2000 4000 8000 Total 62 64 65 56 50 44 35 Unit data is certified in accordance with AHRI-440. Sound data tested in accordance with AHRI-350-2000. Total sound power level data based on Vertical Floor Exposed model with fan CFM at corresponding motor tap with 115/1/60 volt PSC motor, 4 row coil, 1" throwaway filter, 0.0" external static pressure and standard rated internal pressure losses. Unit pressure drop and CFM based upon dry coil as required by AHRI-440. Scheduled motor information is for Hi Speed. The coil selection has been made at Standard conditions. Outside Airflow is a user input value for scheduling purposes. http://webselect.johnsoncontrols.com/selection/fcu.asp?action=printallselections&projecti... 4/29/2015
4/29/2015 Page 11 of 13 Equipment Release Approval Form Product Type: Non-Stacker Fan Coil Units Unit Tags: Various The following table must be completed prior to releasing the equipment for fabrication. Please initial the column indicating the information contained in this submittal has been verified, or indicate to refer to a marked-up page. SUBMITTAL VERIFICATION Electrical voltage and electrical connections are compatible with jobsite requirements. Purchaser Initials Piping / Ductwork connections shown in this submittal are correct. Unit tag designations are correct. Equipment dimensions (length, width, and height) and weights have been verified to comply with jobsite conditions and rigging requirements. Please indicate approval by your initials on all included drawings. Project: 230 Peachtree Street Hotel 1 Submittal
4/29/2015 Page 12 of 13 Important Notes: 1) Actual fabrication release cannot commence until this form is signed by the customer and returned to JCI along with a release notification want date and ship to address. 2) Equipment "lead-time" does not start until confirmed release documentation is received, and the order is actually released to the factory. 3) Modifications to equipment configurations after fabrication release may impact cost and lead-time. 4) Attached configurations are as shown in the approved equipment submittals or as defined in superseding customer correspondence. 5) "Side" / "Hand" orientation is relative to a person with air hitting the back of your head. 6) Note that once this document is confirmed, the equipment configurations defined by this document take precedence over all other documents. 7) "Want date" and/or "ship to address" changes made after this document is confirmed may impact cost and lead-time. Project: 230 Peachtree Street Hotel 2 Submittal
4/29/2015 Page 13 of 13 Please fill out the following table and refer to the receiving/rigging instructions in this submittal to help ensure a smooth delivery and installation of the equipment. DELIVERY INFORMATION Contact name for coordinating delivery of equipment with transportation company Please fill out information below Contact phone number Advance notice required from transportation company prior to delivering equipment (typically 48 hours) Ship to address: Other special shipping instructions or requirements CUSTOMER APPROVAL: Customer Name: Signature (*) Date: Project: 230 Peachtree Street Hotel 3 Submittal