Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Similar documents
Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Publication No.: PSG

Horizontal Circuit Switchers

Horizontal Circuit Switchers

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

CITY OF MARYVILLE ELECRIC DEPARTMENT Maryville, Tennessee SPECIFICATIONS FOR 15KV POWER CIRCUIT BREAKERS. September 2018

CENTER BREAK GROUP OPERATED AIR BREAK SWITCHES RATED 15.5kV THROUGH 170kV EFFECTIVE DATE: 10/25/16 REV B

Three-Phase Pole Mounted Recloser

Submersible Vacuum Fault Interrupters

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Technical Specification For Outdoor Substation Harmonic Filter Banks

43-SDMS-04 REV. 00 SPECIFICATIONS FOR

SDV7. Outdoor distribution circuit breaker family 15.5 kv to 38.0 kv. usa.siemens.com/sdv7

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

Type SDV7 distribution circuit breaker family

Typical Specification

43-SDMS-01 SPECIFICATIONS FOR

Descriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

Descriptive Bulletin. R-MAG magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

Type SDV7 distribution circuit breaker family Answers for energy.

SECTION III - VACUUM CIRCUIT BREAKER TECHNICAL SPECIFICATIONS TABLE OF CONTENTS 1. SCOPE PROJECT ENGINEER STANDARDS...

Product Specifications for Aluminum Vertical Break Switches

SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES

Cobra-S. Catalog Cobra-S

Solid Dielectric, Single Phase Recloser

S&C Series 2000 Circuit-Switchers Outdoor Transmission 69 kv through 230 kv

SECTION III SF6 GAS CIRCUIT BREAKER TECHNICAL SPECIFICATIONS TABLE OF CONTENTS

Outdoor vacuum breaker for railway applications - FSK II

C1000 Series Automatic Cap Bank

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

AIR CORE REACTORS. Phoenix Electric Corporation

Power IT MV Live Tank Vacuum Circuit Breaker Model VBF

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

Medium Voltage Metal-Enclosed Switches

Product Specifications for Phase Over Phase GOABS(r)

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

Power IT MV Live Tank Vacuum Circuit Breaker. Model OVB-SDB

شركة كهرباء محافظة القدس المساهمة المحدودة

Solid Dielectric, Independent Pole Operated Reclosers Catalog O-vst16

3TM Vacuum Contactors

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

B kv T&D GAS INSULATED SWITCHGEAR

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

Medium Voltage Metal-Enclosed Switches

100 / 110 DRYWELL FUSE SPECIFICATION

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

SECTION V - TECHNICAL SPECIFICATIONS TABLE OF CONTENTS

Westinghouse Electric Corporation Distribution and Control Business Unit Assemblies Division Bloomington, Indiana

Solid Dielectric, Triple Option Reclosers Catalog O-vst14

The vacuum circuit breaker for commercial buildings, industrial plants and utilities

Product Group Brochure. PS Range Capacitor Vacuum Switches

BUSWAY Low Voltage (Pow-R-Flex)

City of Jacksonville Beach

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

Acknowledge receipt of this addendum on page one of the Bid Form.

1VAL2401-SG Rev D. Spare parts list for Outdoor Products Reclosers, breakers, & padmount switches

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Solid Dielectric, Three Phase Reclosers CATALOG VS11

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

FEBRUARY 14, 2017 Joslyn Hi-Voltage Capacitor switches customer presentation

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

Outdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications

Underground Distribution Switchgear

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

SWITCHGEAR DIVISION PRODUCT PROFILES

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Extensible Unit - VCE2a

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

Solid Dielectric, Single Phase Reclosers

Switchgear Skid, C1192

AF series contactors (9 2650)

Special Specification 6058 Battery Back-Up System for Signal Cabinets

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

32-SDMS-02 SPECIFICATIONS FOR

Solid Dielectric, Three Phase Reclosers Catalog O-vs18

CP Automatic capacitor bank

Integrated Power Solutions

Change-over Disconnectors HUVS Range 36kV (630 to 6300Amp)

SD Series Non-Fused Load Switches

Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

Transcription:

TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads... 4 3.06 Operating Mechanism... 4 3.07 Ground Pads... 5 4.0 MANUFACTURING REQUIREMENTS... 6 4.01 Wiring... 6 4.02 Mechanism Frame... 6 4.03 Support Structure... 6 5.0 DESIGN TESTS... 7 6.0 PRODUCTION TESTS... 7 6.01 Mechanical Operation Tests... 7 6.02 Leak Test... 7 6.03 Resistance Tests... 7 6.04 Dielectric Tests... 7 7.0 SPARE PARTS... 8 8.0 DOCUMENTATION REQUIREMENTS... 8 8.01 Approval Drawings... 8 8.02 Final Drawings... 8 8.03 Instruction Books... 8 8.04 Additional Documentation... 8 9.0 SHIPPING and DELIVERY... 9 10.0 WARRANTY... 9 11.0 SPECIFIC QUOTE REQUIREMENTS... 9 12.0 ACCEPTABLE REACTOR SWITCHER... 9 Page 1 of 9 PSG-811-RLS362-R0 6/1/2012

1.0 SCOPE This specification covers the design, manufacture, and testing of a three pole, group operated outdoor reactor switcher with vertical interrupters. This switcher is to be rated for 72.5 kv 3 phase reactors of 67 MVAR (539 A) or less. 2.0 STANDARDS All outdoor reactor switchers shall be designed, manufactured, assembled, and tested in accordance with the latest applicable ANSI, NEMA, and ASTM standards and guidelines. If there are any conflicts between the ANSI, NEMA, or ASTM standards and this specification shall govern. 3.0 DESIGN REQUIREMENTS 3.01 Service Conditions The reactor switcher shall be suitable for outdoor installation in electric power substations under the following conditions: 3.01.01 Temperature The reactor switcher shall perform in an ambient temperature range of -30 o C through +50 o C. 3.01.02 Altitude The reactor switcher shall perform at elevations up to 3,300 feet. 3.01.03 Seismic The reactor switcher shall be capable of withstanding seismic loading categorized as (low, moderate, high) seismic per IEEE 693-2005 when installed on the manufacturer s furnished foundation and anchor bolts and with flexible connections to the terminal pads. The device shall perform its specified functions during and after the seismic event 3.01.04 Wind Loading The reactor switcher shall be capable of withstanding wind loads up to 90 mph without loss of function. 3.01.05 Additional Requirements If any site-specific service conditions not covered in sections 3.01.01 through 3.01.04 exist (e.g. extreme cold temperature installation, corrosive environment, high altitude installation, etc.) shall be defined in the quotation request. Page 2 of 9 PSG-811-RLS72-R0 5/13/2015

3.02 Ratings 3.02.01 General Specifications Rated Maximum Voltage Rated Power Frequency Rated Lightning Impulse Withstand Voltage (BIL) Rated Continuous Current Rated Short Circuit Interrupting Current Rated Short-Time Withstand Current Rated Short-Circuit Making Current Peak Withstand Current Interrupting Time Rated Duty Cycle Environmental Rating 72.5 kv 50/60 Hz 350 kv 539 A 40 ka RMS 40 ka RMS 3 sec 40 ka 104 ka Peak 3 cycles O-CO -30 C to +50 C REACTOR SWITCHING RATING Rated Reactor Switching Current 539 A 3.02.02 Additional The RLSwitcher switcher shall have an endurance life of 10,000 Operations. 3.02.03 Source Supply Voltages Purchaser will supply the following sources for the motor, auxiliary, and control circuits: 1. Motor Voltage: 48 VDC, 125 VDC, 230 VDC, 120 VAC 2. Control Voltage: 48 VDC, 125 VDC, 120 VAC 3. Auxiliary Voltage: 120 VAC, 240 VAC 3.03 Interrupter The reactor switcher shall use single gap SF6 interrupters. Each interrupter shall be housed in a porcelain insulator that is ANSI 70 gray. Each interrupter shall be provided with an overpressure relief device and shall be field refillable. Hermetically sealed interrupters are not acceptable. Page 3 of 9 PSG-811-RLS72-R0 5/13/2015

3.04 SF6 Gas System The gas system shall include the insulators, connecting tubing, and color-coded, temperature compensated gas density gauges that are visible from the ground and have low-pressure alarm and lockout contacts. The density switch must be at ground potential. Battery powered gas density monitors are not acceptable. The system shall be constructed such that the density gauge can be isolated from the interrupters to allow the low-pressure alarm and lockout contact set points to be verified. A means for refilling the system in the field without disassembling the reactor switcher must be provided. The reactor switcher shall have a leak rate of less than 0.5% per year. 3.05 Terminal Pads Terminal pads shall be unplated aluminum with 4 hole NEMA drilling pattern for use with purchaser furnished terminal connectors. 3.06 Operating Mechanism 3.06.01 Spring Operating Mechanism Each reactor switcher shall be provided with a spring open-spring close mechanisms with a rated duty cycle of CO 5 min CO 5 min CO capable of operating all three poles. The springs shall be charged via an electric motor in 15 seconds or less. Pneumatic, hydraulic, or combination pneumatic/hydraulic mechanisms are not acceptable. Page 4 of 9 PSG-811-RLS72-R0 5/13/2015

3.06.02 Mechanism Housing and Control Components The mechanism housing shall be painted ANSI 70 gray and shall be furnished with the following accessories: 1. Electric spring charging motor 2. Color coded, temperature compensated gas density gauge with low-pressure alarm contact and low-pressure lockout contact. (Gauge is located in baseframe but is accessible from mechanism Cabinet) 3. Trip-close pistol grip switch 4. Close coil 5. Trip coil 6. Anti-pump relay 7. Time delay relay 8. Local-remote selector switch 9. 12 spare non-adjustable auxiliary switch contacts factory set as 6 normally open (NO) and 6 normally closed (NC) contacts 10. Thermostatically controlled cabinet heater 11. Circuit breakers for protection of motor circuit, control circuit, and heater circuit 12. Spring charged-discharged indicator 13. Manual closing spring charging handle 14. Open-Close position indicator 15. Manual trip and close lever 16. Operations counter 17. 120 VAC cabinet light with door actuated switch 18. 120 VAC duplex receptacle with GFCI 19. View window in cabinet door 20. Hinged cabinet door with 3 point latch, open position door stop, and padlocking provisions 3.07 Ground Pads Two galvanized steel NEMA 2 hole ground pads shall be supplied for grounding the structure to the station ground grid. Page 5 of 9 PSG-811-RLS72-R0 5/13/2015

4.0 MANUFACTURING REQUIREMENTS 4.01 Wiring and Control System Wiring shall be: 1. Point-to-point without splices or tee connections. 2. Bundled using cable ties or inside wiring duct. 3. Clearly identified with permanently affixed markers. 4. SIS wire No. 14 AWG minimum. 5. Crimped with calibrated crimpers and tested with a 100% pull test. 6. Dielectric test will be performed on the control circuits per ANSI C07.016-2006 section 7.1 4.02 Mechanism Frame Each reactor switcher shall be provided with a manufacturer furnished base frame which houses the gas piping and gauge that forms the gas system while also housing the linkage that connects the interrupter to the spring operating mechanism. The base frame shall be ANSI 70 gray painted steel. Phase spacing is 48 inches when applied at 72.5 kv or lower. 4.03 Support Structure Each 72.5 kv capacitor switcher shall be provided with a manufacturer supplied support structure consisting of one hot dipped galvanized tubular steel 12 x 8 vertical column (mounting pedestal) 46-¾ tall with a 1 thick base plate measuring 24 x 24 with a 4 hole bolt pattern on 20 x 20 centers and furnished for use with 1 x 2-9 J type anchor bolts. Unless otherwise specified in the quotation request anchor bolts will be provided by the purchaser. All anchor bolts shall be sized as required for the operational loads generated by the reactor switcher. The manufacturer shall determine anchor bolt sizing and anchor bolt plan details when providing the anchor bolts. Page 6 of 9 PSG-811-RLS72-R0 5/13/2015

5.0 DESIGN TESTS The RLSwitcher shall be design tested in accordance with ANSI C37.09-2001 or IEC 62271-100 unless otherwise specified. The testing shall include: Dielectric tests o 50/60 Hz power frequency: 72.5 kv o Lightning impulse withstand voltage: 350 kv Power test shall include o Short-circuit making current: 104 kv Peak (40 ka rms) o Short-time withstand current: 40 ka for 3 sec o Shunt reactor bank switching current: 539 A Continuous current test: 2500 A 6.0 PRODUCTION TESTS Each reactor switcher shall be fully assembled as a three-phase unit at the factory, adjusted, tested, and timed per ANSI C37.09 Section 5. The tests shall include: 6.01 Mechanical Operation Tests There shall be at least 50 mechanical operations performed at the factory. Timing tests, opening and closing operations at minimum and maximum operating voltage, and spring recharge time shall be recorded. 6.02 SF6 Tightness Test An SF6 leak test shall be performed to confirm the leak rate is less than 0.5% per year. 6.03 Resistance Tests 6.03.01 Current Path Resistance Tests A terminal-to-terminal micro-ohm resistance check shall be performed on each interrupter and each full two phase interrupter set using a 100 A DC source and the values shall be recorded. 6.03.02 Heater, Coil, and Relay Resistance Tests The resistance of each heater, coil, and relay shall be confirmed to be within specifications and the value(s) shall be recorded. 6.04 Dielectric Tests 6.04.01 Control Circuit Dielectric Test The completely assembled and wired operator control circuit shall pass a dielectric test of 1500 V for 1 minute. Page 7 of 9 PSG-811-RLS72-R0 5/13/2015

7.0 SPARE PARTS 6.04.02 Interrupter Dielectric Test Each phase shall pass a power frequency withstand test at 60 Hz for one minute. The required test value shall be at least 3 times rated lineground voltage. No spare parts shall be required to be purchased at the time of reactor switcher purchase. Stock shall be maintained at the manufacturer available for rush shipment in the event of an emergency need. 8.0 DOCUMENTATION REQUIREMENTS 8.01 Approval Drawings The manufacturer shall furnish approval drawings in AutoCAD.DWG format via e-mail. The purchase order will designate the name and e-mail address of the individual where the drawings should be forwarded. If there are no comments to the approval drawings purchaser will respond via e-mail that drawings are approved as submitted with no changes. If comments are required then one copy of the drawings will be returned to the manufacturer within 10 days from the date of transmittal marked approved with comments as noted. 8.02 Final Drawings The manufacturer shall furnish final drawings in AutoCAD.DWG format via e-mail. Unless otherwise specified in the purchase order, the final drawings will be forwarded to the same individual that the approval drawings were sent to. 8.03 Instruction Books The manufacturer shall furnish an electronic copy of each applicable instruction book in Adobe Acrobat.PDF format via e-mail. Unless otherwise specified in the purchase order, the instruction book(s) will be forwarded to the same individual that the approval drawings were sent to. 8.04 Additional Documentation One complete set of final drawings and one copy of each applicable instruction book shall be shipped in a weatherproof envelope with each reactor switcher. Page 8 of 9 PSG-811-RLS72-R0 5/13/2015

9.0 SHIPPING and DELIVERY The reactor switcher shall be match-marked and disassembled as necessary to accommodate shipping dimensional clearance restrictions. The interrupters shall be shipped with a positive pressure of 10 psi of SF6, eliminating the need to pull a vacuum on them in the field. An SF6 fill kit shall be provided to fill the common gas system to rated pressure during installation. 10.0 WARRANTY All reactor switchers and their accessories furnished under this specification shall be covered by a five year warranty from date of invoice or 2,000 operations; whichever comes first; against failure due to design or to defects in workmanship or material. 11.0 SPECIFIC QUOTE REQUIREMENTS Information furnished by purchaser at time of quote request will include: 1. Maximum Rated Voltage in kv 2. Motor / Control voltage (48 VDC; 125 VDC; 250 VDC; 120 VAC, 60 Hz, 1 ; or 240 VAC, 60 Hz, 1 ) 3. Heater voltage (120 VAC, 60 Hz, 1 or 240 VAC, 60 Hz, 1 ) 4. If manufacturer is to supply anchor bolts 5. Additional requirements, if applicable (see section 3.01.05) 6. Wind loading requirements 7. Seismic requirements per IEEE 693-2005 12.0 ACCEPTABLE REACTOR SWITCHER Supply Southern States type RLSwitcher or acceptable equal. Any equal proposed must meet or exceed this specification. RLSwitcher is a registered trademark of Southern States, LLC. Page 9 of 9 PSG-811-RLS72-R0 5/13/2015