Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

Similar documents
INSTALLATION PRODUCTION TESTS

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50

600 A 25 kv class BT-TAP deadbreak connector

copper stud. If a 900 A rating is desired, specify a C as the 8th digit when determining your part number (See Table 3, page 3.)

600 A 15 kv class T-OP II deadbreak connector

600 A 35 kv class BT-TAP deadbreak connector

600 A 35 kv class separable splices

600 A 15 and 25 kv class deadbreak accessories, tools, and replacement parts

600 A 35 kv class deadbreak accessories, tools, and replacement parts

Loadbreak Apparatus Connectors

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

600 A 15 kv class Cleer loadbreak connector system

600 A 28 kv class Cleer loadbreak connector system

25 kv class fused loadbreak elbow connector

IEC Separable Connectors 17.5 kv/24 kv, 630A

1500 kva Padmount Transformer delta Primary Voltage 208Y/120 Secondary Voltage

Eaton s Cooper Power Systems

IEC Separable Connectors 36 kv and 42 kv, 630A and 1250A Front T-Body / Coupling (Rear) T-Body Connector

15 kv Class Fused Loadbreak Elbow Connector with Interchangeable Fuse Capability

Specifier's Guide COOPER POWER. Line installation and protective equipment master catalog 5 kv - 35 kv electrical distribution systems SERIES

200 A and 600 A, 15, 25, and 35 kv junction bars for separable connectors

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

600A Deadbreak Elbow. K656LR Elbow Connector (with Test Point) Features:

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

Edison modular fuse, vault application products

A 1.2 kv class externally removable secondary bushing

ELASTIMOLD UNDERGROUND CABLE ACCESSORIES


600 A 15 and 25 kv class Cleer grounding elbow

Grounding equipment COOPER POWER SERIES. Temporary Connections CA325004EN. Contents

600 A Deadbreak Connectors

100 A externally operated one-, twoand three-phase tap-changer switch

Quick Splice II 5451R. 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet. 1. Product Description. 2. Applications

GROUP C. Apparatus Bushing.

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Two-position sidewall (horizontal) and cover (vertical) mounted loadbreak switches

Quick Splice II. 35 kv Molded Rubber Inline Splicing Kit Data Sheet. 2. Applications. 1. Product Description

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

Branch Splice QS-2001B

Surge Arresters. UltraSIL Polymer-Housed VariSTAR Surge Arresters: Normal-Duty (5 ka), Heavy-Duty (10 ka), and Heavy-Duty Riser Pole (10 ka)

Effective March 2015 Supersedes S August 2012

Product Description: Objective and Certification: Test Samples and Test Cable:

ELB ELB

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

Surge arresters. UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters. General. COnSTrUCTIOn

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

Surge Arresters. UltraSIL Polymer-Housed Evolution (10 ka) Surge Arresters. General. Construction. features

25 kv Apparatus Bushings

CERTIFIED TEST REPORT. Cooper Power Systems. 25 kv Class 200 Amp 15.2/26.3 kv SEPARABLE CONNECTOR SYSTEM

M-Force three-phase switch

Jumpering and grounding equipment and assemblies

High-voltage primary bushings installation instructions

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

High Voltage Joints and Terminations up to 72,5 kv 145 kv

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

Molded Current-Limiting Fuse

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.

X-Limiter full-range current-limiting fuse

Elastimold & Hi-Tech Fuse Products

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

15 kv and 25 kv Thru-Bushings

Surge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable

FEBRUARY 14, 2017 Elastimold Solid dielectric switchgear customer presentation

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv

Easy-On II Terminations

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

M-Force three-phase switch

PRODUCT BROCHURE. Elastimold ComboT integral separable connectors

ELB ES. Product Installation Instructions

K-Limiter high ampere Companion II fuse

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

Portable High-Voltage Cable Couplers 415, 515

High Voltage Copper, Smooth Aluminum Shield/Sheath

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description

Medium Voltage. Joints & Terminations

your Green Power WIND POWER SOLUTIONS only Greener

CATALOG. Hi-Tech Fuse Products

High Voltage Aluminum, Smooth Aluminum Shield/Sheath

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

Installation Instructions LINK---C

I Surge Arresters. UltraSIL Polymer-Housed VariSTAR Type U3 Surge Arrester for Systems through 275 kv IEC 10 ka; Line Discharge Class 3 GENERAL

11. CABLE SPECIFICATIONS 5kV, 15kV, AND 35kV RUBBER OR PLASTIC INSULATED CABLE

GENERAL. CONSTRUCTION External

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified

Transcription:

Deadbreak Apparatus Connectors 600 A 15/25 kv Class BOL-T Deadbreak Connector Electrical Apparatus 600-30 GENERAL The Cooper Power Systems 600 A, 15/25 kv Class BOL-T Deadbreak Connector is used to terminate highvoltage underground cable on deadfront apparatus such as transformers, switches and switchgear. It is fully shielded, submersible and meets the requirements of IEEE Std 386 standard Separable Insulated Connector Systems. The capacitive test point on the insulating plug provides a means of testing the circuit without disturbing the bolted connection. In addition to the capacitive test point feature on the insulating plug, Cooper Power Systems offers an optional capacitive test point similar to the test points on Cooper 200 A Elbows. This allows the use of the Type TPR Series Fault Indicators, and provides a hotstick operable means of determining circuit condition when used with high impedance voltage sensing devices designed for test points. BOL-T Connectors are designed for use on solid dielectric cable (XLPE or EPR) with extruded semi-conductive shields and concentric neutral, with or without a jacket. Installation on jacketed concentric neutral cable may require additional sealing material. Cold shrinkable adapters are available for tape shield, linear corrugated and drain wire cable adaptation for use with deadbreak connectors. 900 Amp Rating The BOL-T Connector is rated for 900 A continuous when used with a coppertop compression connector, copper insulating plug, copper stud and copper bushing or junction. If a 900 A rating is desired, specify a C as the 9th digit when determining your part number. See Step 3, page 4. Interchangeability All Cooper Power Systems 600 A Deadbreak Connectors conform to the electrical, mechanical and dimensional requirements of IEEE Std 386 standard. The connectors can be used on any comparably rated bushing interface that also meets the requirements of this standard. In February 2010 Supersedes 2/03 Figure 1. 600 A Deadbreak Connector without test point; also available with test point. addition, all cable adapters, insulating plugs, compression connectors and other component parts are designed to be interchangeable with those currently available from all other manufacturers that also comply with IEEE Std 386 standard. INSTALLATION A torque wrench and one-inch socket are used to tighten the insulating plug through the compression connector within the T-body onto a de-energized 600 A bushing interface. Refer to Installation Instruction Sheet S600-10 2 for details. PRODUCTION TESTS Tests conducted in accordance with IEEE Std 386 standard: AC 60 Hz 1 Minute Withstand 40 kv Minimum Partial Discharge Extinction Voltage 19 kv Tests conducted in accordance with Cooper Power Systems requirements: Physical Inspection Periodic Dissection Periodic X-ray Analysis TABLE 1 Voltage Ratings and Characteristics Description kv Standard Voltage Class 25 Maximum Rating Phase-to-Ground 15.2 AC 60 Hz 1 Minute Withstand 40 DC 15 Minute Withstand 78 BIL and Full Wave Crest 125 Minimum Partial Discharge Extinction Voltage 19 Voltage ratings and characteristics are in accordance with IEEE Std 386 standard. TABLE 2 Current Ratings and Characteristics Description Amperes Continuous 600 A rms 24 Hour Overload 1,000 A rms Short Time 40,000 A rms symmetrical for 0.17 s 27,000 A rms symmetrical for 4.0 s Current ratings and characteristics are in ac cor dance with IEEE Std 386 standard. 1

600 A 15/25 kv Class BOL-T Deadbreak Connector SEMI-CONDUCTING SHIELD Precision molded peroxide-cured semi-conducting shield provides ground shield continuity and meets the requirements of IEEE Std 592 standard. COMPRESSION CONNECTOR Aluminum compression connector is sized to ensure a cool running connector with maximum current transfer. T-BODY Molded T-body adapts to all cable sizes and provides a deadfront shielded connection. EPDM INSULATION High quality peroxide-cured EPDM Insulation is mixed and formulated in-house for complete control of raw rubber characteristics. 12.5 " (318 mm) CABLE ADAPTER Molded cable adapter, sized to fit cable insulation diameters from 0.640 inch to 1.965 inches (16.3 to 49.9 mm), provides stress relief for the terminated cable. 9.6" (244 mm) HEX HEAD One-inch hex head is used to tighten the connection. Insulating plug CAP Semi-conducting rubber cap fits over insulating plug test point for waterproof seal and deadfront shielding. INSULATING PLUG Molded epoxy insulating plug provides excellent electrical, thermal and mechanical reliability. SEMI-CONDUCTING INSERT Molded semi-conducting peroxide-cured insert provides corona-free electrostatic shielding of the compression connector. CAPACITIVE TEST POINT Optional capacitive test point on molded T-body with snap-on cap provides a shielded, hotstick operable means to determine circuit condition when used with high impedance voltage sensing devices designed for capacitive test points, and a place to mount Cooper TPR Series Fault Indicators. DRAIN WIRE TAB Drain wire tab provides a convenient point to connect a drain wire to ensure grounding of the connector shield. Figure 2. BOL-T Cutaway illustrates design features. Note: Dimensions given are for reference only. OPTIONAL FEATURES Coppertop Compression Connectors Coppertop compression connectors (aluminum sleeve welded to a copper spade) provide a high conductivity material in a bolted connection and are compatible with aluminum or copper conductors. All Copper Current Path Full copper current carrying path and 900 A rating can be obtained by specifying a coppertop compression connector, copper stud and copper insulating plug. ORDERING INFORMATION Each BOL-T Connector kit contains: Molded Rubber T-body Insulating Plug Insulating Plug Cap Compression Connector Cable Adapter Silicone Lubricant Installation Instruction Sheet To order a 15/25 kv Class BOL-T Connector Kit, see following Steps 1-5 to build the catalog number. S2 S3 S4 S2 S3 S4 S5 S5 Figure 3. BOL-T stacking dimensions. 15/25 kv 0.5" (13 mm) 3.9" (98 mm) 1.5" (38 mm) 2.4" (61 mm) 2

600-30 BOL-T Connector Kit Catalog Numbering System Build the 11 digit catalog number for a BOL-T Kit by following the steps given below. The first 5 digits are BT625, so only digits 6 through 11 need to be selected. 1 2 3 4 5 6 7 8 9 10 11 12 B T 6 2 5 Catalog Number Digits: 1 & 2 = BT, BOL-T Connector System 3 = 6, 600 A System 4 & 5 = 25, 25 kv Class Bushing Interface Step 1 Select Digits 6 and 7 Cable Adapter Range Code Determine the cable s diameter over the electrical insulation as shown in Figure 4 (including tolerances). Then identify a cable range from Table 3 that covers the minimum and maximum insulation diameters. Select the correct CABLE RANGE CODE from Table 3. OUTER JACKET METAL NEUTRAL OR SHIELD INSULATION SHIELD DIAMETER OVER INSULATION CONDUCTOR INSULATION CONDUCTOR SHIELD Figure 4. Illustration showing typical construction of medium voltage underground cable. TABLE 3 Cable Diameter Range Cable Diameter Range Inches mm Code 0.610-0.970 15.5-24.6 AB 0.750-1.080 19.1-27.4 CC 0.970-1.310 24.6-33.3 DD 1.090-1.470 27.7-37.3 EE 1.260-1.640 32.0-41.7 FF 1.360-1.710 34.5-43.4 GG 1.510-1.850 38.4-47.0 HH 1.700-1.970 43.2-50.0 JJ 3

600 A 15/25 kv Class BOL-T Deadbreak Connector Step 2 Select Digits 8 and 9 Conductor Code Identify the conductor size and type in Table 4 and select the CONDUCTOR CODE from the far right column. TABLE 4 Conductor Size and Type Concentric or Compact or CONDUCTOR Compressed solid CODE AWG or kcmil mm 2 AWG or kcmil mm 2 No Connector 00 2 1 _ 11 1 1/0 12 1/0 50 2/0 70 13 2/0 70 3/0 14 3/0 4/0 95 15 4/0 95 250 120 16 250 120 300 17 300 350 18 350 400 185 19 400 185 450 20 450 500 a 240 21 500 240 600 300 22 600 300 700 23 650 b 750 c 24 750 d 900 25 900 1000 500 26 1000 500 27 a. Also accepts 550 kcmil compact conductor. b. Also accepts 700 kcmil compressed conductor. c. Also accepts 800 kcmil compact conductor. d. Also accepts 700 kcmil concentric conductor. Step 3 Select Digit 10 Determine whether Aluminum or Copper is required for the compression connector, stud, and deadbreak insulating plug. A = Aluminum C = Copper (Coppertop for the connector) Required to achieve 900 A rating. Step 4 Select Digit 11 Determine if a stud should be included in the kit. 1 = Stud Included 2 = Stud Not Included Step 5 Select Digit 12 Determine if the T-body should have a test point. T = Test Point on T-body If no test point is required, do not include an 11th digit. 4

600-30 EXAMPLE: Select a BOL-T Kit for 250 kcmil compressed cable with a nominal insulation diameter of 1.160" ± 0.030". The kit should have aluminum current-carrying parts and should have a stud included. The T-body should have a test point. Step 1 Select Digits 6 and 7 Nominal diameter over insulation is 1.160" ± 0.030". Minimum diameter = 1.160" - 0.030" = 1.130". Maximum diameter = 1.160" + 0.030" = 1.190". From Table 3, identify the cable range that covers 1.130" - 1.190" and select the EE cable range code. Step 2 Select Digits 8 and 9 The conductor size is 250 kcmil compressed. From Table 4, under the column Concentric or Compressed, identify 250 kcmil and select the 17 conductor code. Step 3 Select Digit 10 The kit should have aluminum current-carrying parts. Select an A for digit 9. Step 4 Select Digit 11 The kit should include a stud, so select 1 for digit 10. Step 5 Select Digit 12 A test point is needed, so use a T for digit 11. The complete catalog number is: BT625EE17A1T ACCESSORIES Cable adapters, compression connectors, and other accessories that can be used with Cooper Power Systems BOL-T Connectors are described in Section 600-46, Deadbreak Accessories, Tools, and Replacement Parts. TABLE 5 Replacement Parts Description Catalog Number T-body without Test Point DT625 T-body with Test Point DT625T T-body without Test Point With Aluminum Stud DT625SA T-body without Test Point With Copper Stud DT625SC T-body with Test Point With Aluminum Stud DT625TSA T-body with Test Point With Copper Stud DT625TSC Insulating Plug Cap DIPCAP Aluminum Insulating Plug with Cap (No Stud) DIP625A Copper Insulating Plug with Cap (No Stud) DIP625C Aluminum Insulating Plug with Cap and Aluminum Stud DIP625AS Copper Insulating Plug with Cap and Copper Stud DIP625CS 5 / 8" 11 UNC 2A Aluminum Threaded Stud STUD-A 5 / 8" 11 UNC 2A Copper Threaded Stud STUD-C 5

600 A 15/25 kv Class BOL-T Deadbreak Connector This page intentionally left blank. 6

600-30 This page intentionally left blank. 7

600 A 15/25 kv Class BOL-T Deadbreak Connector 2010 Cooper Industries. All Rights Reserved. Cooper Power Systems and BOL-T are valuable trademarks of Cooper industries in the U.S. and other countries. You are not permitted to use the Cooper Trademarks without the prior written consent of Cooper industries. IEEE Std 386 and IEEE Std 592 standards are trademarks of the Institute of Electrical and Electronics Engineers, Inc. This publication/product is not endorsed or approved by the IEEE. 2300 Badger Drive Waukesha, WI 53188 USA www.cooperpower.com 8