V4043/V4044 Motorized Valves

Similar documents
V4043 and V4044 Motorized Valves

VC2, VC4, VC60, VC8 ON-OFF ACTUATOR FOR VC SERIES BALANCED HYDRONIC VALVES SPECIFICATIONS INSTALLATION INSTRUCTIONS

Zone Valves and Parts (Honeywell)

M436A/M836A,B Damper Motors

MS Application. Features. Proportional Valve Actuator General Instructions

V5197A Firing Rate Gas Valve

KVC7934, KVC7936. Modulating Actuators without and with Power Failure Reposition For KVC Series Cartridge Valve. Specifications 12.

Accessories. UP timer. Timer control. Approvals. UP Series

VE Series. Class "A" Gas Valves. Product handbook APPLICATION CONTENTS. General. Technical. Installation and operation. Various

2-Way & 3-Way Non Spring Return Characterized Ball Valves

Erie VM PopTop Series Modulating Valves

MC-351, 421, 431, MC-4311

Erie VT/VS PopTop Series Two Position Spring Return Valves

MA-5200 Series MA-5300 Series

599 Series Zone Valve Bodies:

V51E Butterfly Valve. The valve mechanism is equipped with strain release springs.

L404F,T,V PressureTrol Controllers

V5011N Two-Way Threaded Globe Valve

R EGI S TERED. Function

VC7936 Floating Cartridge/Cage Valve

CIRCLE SEAL CONTROLS

V9055A,D Modulating Fluid Power Gas Valve Actuator

AV-8020 Series Floating Control Actuated Valve

CALEFFI. zone valves. Z series 01115/14 NA. Replaces 01115/11 NA. Function

VE4000 & VE5000 SERIES

Powers TM Controls Three-way Electro-pneumatic (EP) Valve Model 2

Powers Controls Powermite Two-Way Flared Valves Normally Open/Normally Closed

V8043A,E,F 5000 Series

ML6420, ML7420 Non-Spring Return Electric Linear Valve Actuators

Pressure Control Valves. General Description. Specifications. Ordering Information

7 ZONE VALVES. Applications

ML7421A,B Electric Linear Valve Actuator

MF-22xx3. Application. Features. Floating Valve Actuator General Instructions

CIRCLE SEAL CONTROLS

Instructions for Installation, Operation, Care and Maintenance

SECTION E CONTENTS THREE WAY VALVES DESCRIPTION

Product Instructions. Diverting Valve. Valve Cross Section. Features. Specifications. Operations

Electromotoric Actuators. for zone valves VVI46.., VXI46.., VVS46.. and VXS46..

Series 41 and 81 Modutrol IV Motors

Powers TM Controls VP 656 Powermite Three-way Mixing Valves (Flared Type)

2-Port and 3-Port Zone Valves & Actuators, PN16

MP-5400 Series. Application. Features. Applicable Literature. Electronic Positive Positioning Hydraulic Actuator General Instructions

Selection Guide. Vx-2x13-5xx-9-xx Series Vx-2x13-8xx-9-xx Series VB-2x xx Series. Schneider Electric Ball Valve Assemblies

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

PNEUMATIC CONTROL SYSTEMS DESIGN AND CONSTRUCTION STANDARD PART 1 - GENERAL. A. Codes and Standards that are Standard at the University:

Fan-coil valves Series

Vacuum applications possible (up to 100kPa) Base mounted. Cylinder bore size (mm) Series CM2. Pressure: 0.5MPa Load ratio: 50% Cylinder stroke: 300mm

CALEFFI. Pre-assembled distribution manifolds for radiant panel systems. series 663 & /05 NA. Function

VB-9323 Series. Application. Features. Applicable Literature. 2-1/2" to 6" 125 Lb. Flanged Three-Way Diverting Valves General Instructions

VEP-11/12/21/22 Series

ACTIVAL Two-way Ball Valve with Threaded-end Connection

ML6425, ML7425 Spring Return Electric Linear Valve Actuators

Q5024A,B Globe Valve Linkages FOR DIRECT COUPLED ACTUATORS

Features Globe Valve 2-Way & 3-Way Assembly Features:

Series. Stainless Steel Ball Valve 1/4-1

V5011N Two-Way Threaded Globe Valve

Flowrite 599 Series Three-Way Valves 1/2 to 2-inch Bronze Body

V5055A-F Industrial Gas Valves

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

North American Automatic Manual Reset and Motorized Valves

TECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet)

IsoTherm FlowGuards Mini Ball Valves Gauges Aquastats Unions

Flare Valves 1/2 inch 2-Way and 3-Way

VA, VF, and VS Series Direct Mounted Globe Valve Assemblies. Application. Features

TK-6024, TK-6124, TK-8024, TK-8124

ROTARY MOTORIZED VALVES ROTARY MOTORIZED VALVES

Lesson 5: Directional Control Valves

AV-430. Application. Features. Applicable Literature. Valve Linkage for Pneumatic Actuators General Instructions

Series: ET. 4ET RPM - 60Hz. ET RPM - 60Hz. (See Indivdual curves for symbol number)

Mark 33 Series. Control Valves Mark 33/39 Electric Motor Control Valves. Electric Motor Control Valves. Features. CRN Registration Number Available

2-Port and 3-Port Zone Valves, PN16

2-Port and 3-Port Zone Valves, PN 16 / 20

Characterized Port -CP Three-Way Ball Valves

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE 6 (DN150)

Series: ET. 4ET RPM - 60Hz. ET RPM - 60Hz. (See Indivdual curves for symbol number)

V2880, Therafix Design Thera Design Edition - H-Block with TRV Insert WITH HIGH QUALITY SURFACE FOR DESIGN RADIATORS

ROTARY MOTORIZED VALVES ROTARY MOTORIZED VALVES

MF4E MF4E

PATENT PENDING. Phone: (877) Operation and Service Manual

V5000. Globe Valves Series for Terminal Units. Product Bulletin

MP-5200 Series. Application. Features. Applicable Literature. Electronic Hydraulic Actuator General Instructions

Flowrite 599 Series Three-Way Valves 1/2 to 2-inch Bronze Body

599 Series Zone Valve Bodies:

Q= C. v P S Refer to Table 1 for part numbers and shipping weights. Accessories: Table 1: Valve Part Numbers and Specifications

Installation Instructions

Honeywell VV, VP, VB & MS SERIES FOR VQ400M CLASS A VALVES PRODUCT HANDBOOK APPLICATION

ML6420, ML7420 Non-Spring Return Electric Linear Valve Actuators

R182J, R482J, R845A, R847A, R882J, RA89A, RA832A Switching Relays

Seven Features of the Koganei Vacuum Valve

J Flow Controls Model Numbering

VB-9313 Series. Application. Features. Applicable Literature

VE VVG Series Electronic Two-way Valves Normally Closed

BACnet MS/TP Networking Flow Balancing Control Valves

Power Train. Chapter 5

Honeywell MP516A UNIT VENTILATOR DAMPER OPERATOR GENERAL DESCRIPTION APPLICATION SPECIFICATIONS OPERATION

CALEFFI. Motorized ball valves with 3-wire control series ACCREDITED 01131/13 NA. Replaces 01131/07 NA

DWS 41. Installation Data 44 Performance Specs DWS & DW-PRV Series

Submittal 30 [762] 36 [914] 40 [1016] 50 [1270] 60 [1524] 70 [1778]

V5049A FLANGED LINEAR VALVE PN25/40

20 to 150 mm 2-Way Automatic Flow Balancing Control Ball Valves

Transcription:

V4043/V4044 Motorized Valves PRODUCT SPECIFICATION SHEET FEATURES V4043 provides 2-position, straight-through control of water. V4044 provides 2-position diverting control of water. Compact construction for easy installation. Manual opener for valve operation on power failure. Valve returns to automatic position when power is restored. Motor can be replaced by removing one screw, without disturbing the valve body or draining the system. Complete power-head may be removed or replaced without breaking the line connections or draining system. All models can be installed without disassembling the valve. SPECIFICATIONS Models: V4043: line voltage, straight-through valves. V4044: line voltage, 2-position diverting valves. APPLICATION These valves consist of an actuator motor and valve assembly for controlling the flow of hot or cold water. IMPORTANT These valves are not for use in systems containing dissolved oxygen. Static Pressure Rating: PN16 (232psi) Electrical Rating: 220V @ 0.042A, 120V @ 0.080A Timing: V4043: Open or close in 15 seconds maximum. V4044: Divert flow in 30 seconds maximum. Temperature ratings: Maximum Fluid Temperature: 116 Minimum Fluid Temperature: 5 Ambient Temperature: 50 Manual Opener: Manual opener (on all except the straight-through, normally open valves) allows opening the valve in case of power failure. Valve returns to automatic position when power is restored. Approvals: Underwriters Laboratories Inc. Listed Replacement Parts: Motor Part Numbers (use with V4043, V4044): 190620B 120Vac,60Hz, Class F, plated. 272868B 220Vac,50Hz, 240Vac,60Hz, Class F, plated. O-Ring Part Numbers: 272742A Includes replacement ball plug, large O-Ring and four screws. 272756A Package of five large O-Rings. 1 APEN0H-017CH33A1206

V4043/V4044 MOTORIZED VALVES SELECTION OS# 2/3 way Voltage (Vac) Freq (Hz) Size (in.) Pipe Connection (Internal Thread) Flow Capacity Cv Max. Close-Off Pressure (psi) Valve Action V4043A1580B 2 220 60 3/4" BSPT 8.0 8 Normally Closed V4043A1598B 2 110 60 3/4" BSPT 8.0 8 Normally Closed V4043A1671B 2 220 50 3/4" BSPT 8.0 8 Normally Closed V4043C1347B 2 220 50 1/2" BSPT 3.5 20 Normally Closed V4043C1354B 2 220 50 1/2" Flare 3.5 20 Normally Closed V4043C1362B 2 220 50 3/4" BSPP 8.0 8 Normally Closed V4043A1720B 2 220 50 3/4" BSPP 3.5 20 Normally Closed V4044A1563B 3 110 60 3/4" BSPT 7.0 10 Port A normally closed V4044A1571B 3 220 60 3/4" BSPT 7.0 10 Port A normally closed V4044A1704B 3 220 50 3/4" BSPT 7.0 10 Port A normally closed V4044C1668B 3 220 50 1/2" BSPT 3.5 20 Port A normally closed V4044C1734B 3 220 50 3/4" BSPP 7.0 10 Port A normally closed V4044C1817B 3 220 50 1/2" Flare 4.0 20 Port A normally closed MOUNTING DIMENSIONS V4043 BSPP / BSPT MODELS V4043 FLARE-FITTING MODELS V4044 FLARE-FITTING MODELS Fig. 1. Mounting dimensions in in. (mm) of V4043 and V4044 Motorized Valves 2 APEN0H-017CH33A1206

How to Find Maximum Valve Operating Temperature The maximum operating temperature for motorized valves depends on the maximum ambient temperature at the valve location, and on the maximum fluid temperature. Using the graph in Fig. 2, find the maximum valve operating temperature as follows: 1. Measure the ambient temperature at the valve and locate that temperature on the ambient temperature scale on the graph. 2. Draw a line from the ambient temperature, parallel with the fluid temperature scale, to the maximum fluid temperature line. 3. Draw a line from that point down to the fluid temperature scale to find the maximum operating temperature. (Note the example shown by the dashed line in Fig. 2.) To find the maximum ambient temperature for a valve when the fluid temperature is known, reverse the procedure. How to Find Valve Pressure Drop The pressure drop in psi (kpa), equivalent ft (m) of pipe, or feet of water (kpa) can be calculated from Fig. 3 through 8 as follows: 1. Calculate the flow rate to heat the zone. 2. Determine the Cv (Kv) rating of the motorized valve. 3. Select the graph corresponding to the Cv (Kv) rating (Fig. 3 through 5). 4. Determine the pressure drop across the valve using the following procedures for calculating pressure drop. Pressure Drop in psi (kpa) 1. Locate the flow rate at the bottom of the graph. 2. Draw a line up from the flow rate to the intersection of the curve. 3. Draw a line from the intersection to the left edge of the graph to determine the pressure drop in psi (kpa). Pressure Drop in Equivalent ft (m) of Pipe NOTE: Both 1/2 and 3/4 in. pipe conversion scales are available for this determination. 1. Locate the flow rate at the bottom of the graph. 2. Draw a line vertically to the top of the graph. Determine the pressure drop for either the 1/2 or 3/4 in. pipe. Pressure Drop in ft of Water (kpa) 1. Locate the flow rate at the bottom of the graph. 2. Draw a line up from the flow rate to the intersection of the curve. 3. Draw a line from the intersection to the right edge of the graph to determine pressure drop in ft of water (kpa). Fig. 2. Maximum temperature characteristics of valves with Class F motors 3 APEN0H-017CH33A1206

V4043/V4044 MOTORIZED VALVES Fig. 3. Flow characteristics of 3.5 Cv (3.0 Kv) valve. Fig. 5. Flow characteristics of 8 Cv (6.9 Kv) valve. INSTALLATION When Installing this Product 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. 3. Installer must be a trained, experienced service technician. 4. After installation is complete, check out product operation as provided in these instructions. Fig. 4. Flow characteristics of 7 Cv (6.0 Kv) valve. 4 APEN0H-017CH33A1206

CAUTION 1. Disconnect power supply before connecting wiring to prevent electrical shock or equipment damage. 2. Normally it is not necessary to remove the powerhead from the valve body during installation. If the valve must be disassembled, be certain that it is reassembled with the water flow in the direction of the arrow. Reversal of the powerhead results in damage to the gear train. 3. On 24V systems, never jumper the valve coil terminals even temporarily. This can burn out the heat anticipator in the thermostat. IMPORTANT Use this valve in hydronic heating systems that do not contain dissolved oxygen in the system water. The dissolved oxygen, which is found in systems that have a frequent source of makeup water, causes the rubber plug inside the valve to deteriorate and eventually fail. Mounting See Fig. 9. If the valve is mounted horizontally; the powerhead must be even with or above the center line of the piping. Make sure to leave enough room above the powerhead to remove the cover for servicing. Fig. 6. Mounting positions. Mount the valve directly in the tube or pipe. Make sure that the flow through the valve is in the direction indicated by the arrow stamped on the valve body. On diverting valves, the three fittings or ports are labeled on the bottom of the valve body casting. Port AB is the inlet port and is open at all times. Port A is closed when the valve is de-energized; port B is open when the valve is de-energized. Refer to the equipment manufacturer instructions to determine which port (A or B) should be connected to the coil bypass. Flare Fitting Models Use new, properly reamed pipe, free from chips. The valve body is threaded for standard 5/8 in. OD copper, 45 degree SAE flare fitting nuts. These nuts are not furnished with the valve and must be obtained separately. OPERATION AND CHECKOUT CAUTION On 24V systems, never jumper the valve coil terminals even temporarily. This can burn out the heat anticipator in the thermostat. Operation Automatic Operation On a call for heat by the zone thermostat, the valve opens and its auxiliary switch contacts make, closing the circuit to the system circulator. In a multizone system with all the valve auxiliary switches wired in parallel, any zone calling for heat can operate the circulator. When the call for heat ends, the valve closes by integral spring return. The auxiliary switch contacts break the circulator circuit. Manual Operation The motorized valve can be opened manually by lifting the manual opening lever over the stop and pushing slowly and firmly to the MAN. OPEN position. The stop permits the valve to be locked in the open position. The valve returns to automatic position when the valve is energized. Normally Closed Models With the manual opener set to AUTO and the powerhead energized, the valve is opened as shown in Fig. 36A. When the powerhead is de-energized, a spring-return mechanism drives the valve to the closed position as shown in Fig. 36B. The valve can also be opened with no electrical power by moving the manual opening lever over the stop and pushing slowly and firmly to the MAN. OPEN position. The stop permits the valve to be locked in the open position. The valve returns to the automatic position when the valve is energized. Auxiliary switch is not energized when the valve is manually opened. Normally Open Models When the powerhead is de-energized, a spring-return mechanism drives the valve to the open position (Fig. 36A). When energized, the valve is closed as shown in Fig. 36B. A reverse-acting thermostat is required to control a normally open valve. NOTE: Inlet Port is stamped A and Outlet Port is stamped B on the valve body. 5 APEN0H-017CH33A1206

V4043/V4044 MOTORIZED VALVES Checkout 1. Raise the setpoint on the zone thermostat above the room temperature to initiate a call for heat. 2. Observe all control devices the valve should open and the auxiliary switch should make the circuit to the circulator or other valve at the end of the opening stroke. 3. Lower the setpoint on the zone thermostat below the room temperature. 4. Observe the control devices. The valve should close and the auxiliary equipment should stop. Service This valve should be serviced by a trained, experienced service technician. 1. If the valve is leaking, drain the system and check to see if the O-ring needs replacing. 2. If the gear train is damaged, replace the entire powerhead assembly. See the Installation section. If the motor is burned out, replace the motor. See Replacement Parts list in the TRADELINE Catalog. NOTE: Honeywell zone valves are designed and tested for silent operation in properly designed and installed systems; however, water noises can occur as a result of excessive water velocity or piping noises can occur in high temperature (higher than 212 F(100 C) systems with insufficient water pressure. Automation and Control Solutions Honeywell (Tianjin) Limited No. 66, BaiHe Road Tianjin Economic-Technological Development Area Tianjin, 300457, P.R.C. Phone: +86-22-2532 0745 Fax: +86-22-2532 5214 Subject to change without notice. 6 APEN0H-017CH33A1206