MOTORTRONICS Solid State AC Motor Control

Similar documents
WARRANTY INFORMATION...

DNH INDUSTRIES ***** COMPACT ***** EASY TO INSTALL ***** STATUS INDICATORS ***** DUAL LINE FUSING ***** INSULATED FRONT COVER ***** ADJUSTABLE OUTPUT

APPENDIX A: TECHNICAL SPECIFICATIONS WARRANTY INFORMATION...

Softstarters. Softstarters Power electronic brakes Type PEB

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

Pressure Makeup Jockey Pump Controller

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

Power electronic brakes

SECTION DC POWER SUPPLY/BATTERY CHARGER

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation

FAN-STOP INSTRUCTION MANUAL

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

High Frequency SineWave Guardian TM

SALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

CONTROL FEATURES AVAILABLE OPTIONS

Maintenance Manual 13 AMPERE POWER SUPPLY 19A704647P1-P3. Mobile Communications LBI-31801C

CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls

SECTION MOTOR CONTROL

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

A6Z OPERATING MANUAL

300% Motor full load amps at 80 seconds, 400% Motor full load amps at 35 seconds

Filtered PWM Speed Control for Permanent Magnet DC Motors

300% Motor full load amps at 80 seconds, 400% Motor full load amps at 35 seconds

PBA Series Prelube Controls

Noran Tel. a subsidiary of Westell Inc. Fuse Panel Technical Practice NPGMT /10 GMT NEBS Level 3 Verified

A3Z OPERATING MANUAL

CTi Automation - Phone: Fax: Web:

Valcom Failsafe Unit. 1620ESv2 SERIES. Operation and Maintenance Manual

Presented to the IAPMO Standards Review Committee on December 9, 2013

Owner's/Installation Manual

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

MAXIGARD A2000 SPEED SWITCH. Introduction

CBC-300 & CBC Series Dual Channel Adjust Clutch/Brake Controls

1900 William Street. Racine, WI (262) Transformer Application Notes

Models DP10 & DP20 Series Low Voltage Disconnects User s Manual Rev. 1.1 October 31, 2007

Exercise 1-5. Current Protection Devices EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Circuit breakers

Controls and Instruments

RCP200 Series Motor Controls. Instruction Manual Model RCP Model RCP Model RCP202-BC1 Model RCP202-BC2 Model RCP205-BC2

Application Description

AIR COOLED RECTIFIER SPECIFICATION S-50-A

331-SV. User Manual THREE PHASE DUPLEX LIFT STATION CONTROL PANEL WITH STATIONVIEW CONTROLLER. Ashland, OH

Softstarters. Softstarters Type SSM Medium voltage ,800V 1

SPC-PANEL Simplex, Single Phase Pump Control Panel

MODEL 422 Submersible Pump Controller

2122H. Arm Field Arm Field 1/8-1/ / /8-1/ / / /

The Da-Lite Difference.

A1P OPERATING MANUAL

FUSE PANEL Technical Practice FDP /10 GMT NEBS Level 3 Certified

PHASETRONICS SCR Power Control Specialists

Thyristor Power Controllers for Resistive and Inductive loads (Product Code 21.3)

NoMAX 900 SERIES. Instruction SWITCHED CAPACITOR CONTROLS

WINDGUARD BELT DRIVE (BD) INDUSTRIAL SERIES

PHANTOM (PH10 and PH12) COMMERCIAL AND INDUSTRIAL SERIES

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

WIND STOPPING 14 (WMI) AND WIND STOPPING 16 (WMH) INDUSTRIAL SERIES

HYGRODYNAMICS DIGITAL DEW POINT MONITOR PC BOARD MODEL 6392N & 6392N2 TABLE OF CONTENTS

MaxPak Plus Analog DC V S Drive

Surepowr Series 100 Installation Manual

Noran Tel. Fuse Panel Technical Practice N NCY 4/4TPA & 6/6 GMT NEBS Level 3 Certified

Noran Tel. FUSE PANEL Technical Practice N21C110-NCY 5/5 GMT (20Amp GMT) NEBS Level 3 Certified

The Z Series. SCR Power controllers for resistance heating applications. Zero-Fired SCR Power Controllers AMPS VAC

Temperature Controllers

Fincor DC Drives. Flexible & Powerful TYPICAL APPLICATIONS. Conveyor Rugged. Extruder Reliable. Conveyor Simple. Mixer Flexible

TPAK Series COOLANT PUMP

MODEL SPC-PANEL. Pump Controls for 2 HP Grinder Pumps

Installation, Operation & Maintenance Manual Control Panels for Automatic Self-Cleaning Strainers Model 596 and Model 2596

Auto-Trol Limited 1660 SW 196th Avenue * Aloha, OR 97003

Temperature Controllers

Centrifugal Constant Pressure Control

Control Power V AC, 50/60 Hz 150-C30NBD 150-C30FHD

CTFRP Series Power Supplies

Series 5 Inverter OPEN CHASSIS MOUNT - SINGLE PHASE INPUT. For Catalog Nos. ID56F50-CO, ID5601-CO & ID5602-CO

QPET, QPETXU Battery Chargers

PHANTOM (PH10 and PH12) COMMERCIAL AND INDUSTRIAL SERIES

CIRCUIT-TEST OPERATION MANUAL. Switching Mode Power Supply with Remote Sensing PSC V 5A / 0-27V 3A / 0-36V 2.2A (80W)

Overload Relay Heater Tables

AUTO CHARGE DUAL MODEL #: AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL. Ph: Fax:

NorthStar. brand. Instruction Manual. SLIM Tach SL Thru-Shaft Diameter. Magnetoresistive Encoder Designed for GE Wind Energy

Instruction Manual. Q Series 2 Motor Control Modules - OEM

Direct Gas-Fired Heating

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:

SECTION ENCLOSED CONTROLLERS

Pump Installation and Service Manual HRS Hydromatic Retractable System

Owner's Manual. GenReady Load Center and Transfer Switch. This manual should remain with the unit. Model Numbers. GenReady Basic Panelboard

SECTION MOTORS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES AND ELECTRICAL WORK

Graham. Vari Speed S1000 Instruction Manual. TRANSMISSIONS, Inc. Installation, Operation and Maintenance Manual

2. AC SERVICE AND MOTOR REQUIRED 1. ENCLOSURE REQUIRED

1.0 RATINGS MAXIMUM HORSEPOWER NEMA SIZE MOTOR VOLTAGE CONTINUOUS AMPERE RATING

Open Chassis Star-Delta Starter User Guide

1 AMP CURRENT SOURCE

HPV 100 Hydraulic Elevator Soft-Starter Technical Manual

MVC4MEDIUM VOLTAGESOLIDSTATESOFTSTARTER

SB SWITCH CONTROL BOX

Centrifugal Constant Pressure Control

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

Transcription:

Solid State AC Motor Control MWH Series Solid State Motor Winding Heater 10 to 80 Amps INSTALLATION & START-UP MANUAL REV 4 6091101MN

Table of Contents Chapter 1: General Information... 1 1.1 Introduction 1.2 Features 1.3 Specifications 1.4 Recieving and Unpacking 1.5 Dimensions Chapter 2: Installation... 4 2.1 Wiring Chapter 3: Operation... 7 Chapter 4: Diagrams... 8 4.1 MWH 10 Amp Model 4.2 MWH 25 Amp Model 4.3 MWH 50 Amp Model 4.4 MWH 80 Amp Model

Chapter 1 - General Information 1.1 Description The Motortronics MWH Series Solid State Motor Winding Heater is designed to prevent condensation build-up by applying a low level current to the AC motor windings when the motor is in the off condition. Motor windings are susceptible to condensation formation each time the motor is stopped and the windings temperature drops below the dew point. Over a period of time this condensation buildup can degrade the insulation of the windings and cause a short circuit when the motor is started. The same problem can occur when motors are not operated for an extended period of time. This is especially true for damp and humid locations. 1.2 Features Fully Automatic Operation The Motortronics MWH Series is designed for fully automatic operation. It turns on approximately one minute after power is applied to the system. When the motor is started the MWH is instantly turned off. The MWH turns back on approximately one minute after the motor is turned off. Overload Sensings With the optional overload sensing, the MWH can be disabled automatically when a motor overload trip occurs. The heater will go back on-line automatically after the overload is reset. This prevents additional motor heating when a trip occurs providing faster motor cool down after a thermal overload trip condition. LED Status Display Indicator lights on the MWH inform the operator of the unit stats. The POWER ON indicator shows that the power is on and both of the MWH fuses are good. The ENABLE indicator shows that the motor - 1 -

is off and the MWH control interlock is closed. The OUTPUT ON indicator shows that the MWH is supplying power to the motor windings. Designed for Safety The MWH Series is supplied in a compact open chassis design. Optional NEMA 1 enclosures are also available. The front cover of the unit is fiberglass insulation material which shields against accidental contact with electrically live parts. 1.3 Specifications MAX MODEL AMP MOTOR HORSEPOWER RANGE RATING 208V 240V 480V 575V MWH-10 10 3-40 5-50 10-100 15-125 MWH-25 25 50-100 60-125 125-250 150-300 MWH-50 50 125-200 150-250 300-500 350-600 MWH-80 80 250-300 300-400 600-800 700-900 Adjustments: Output voltage is factory set to provide sufficient power to the motor to maintain a +5 to 10 C differential above ambient temperature which is suitable for most applications. This adjustment can be used to trim the control as required for each application. Fusing: Two fuses protect the MWH. Transient Protection: An RC snubber circuit across the SCR protects it from rapid rate of change in the system voltage. A metal oxide varistor (MOV) protects the unit against voltage spikes on the line. - 2 -

1.4 Receiving and Unpacking Unpacking - Carefully unpack the unit from the shipping carton and inspect it for shipping damages. Immediately report any damages to the carrier. Mounting - Select mounting location and make sure ambient temperature does not exceed operating range limits given in specifications. Allow for sufficient clearance on all sides of the unit. 1.5 Dimensions MODEL OPEN PANEL NEMA1 (N) H W D H W D MWH-10 6.2 4.5 6 11 7 7 MWH-25 8 6 6 11 7 7 MWH-50 10 8 7.9 15 10 8 MWH-80 10 8 8 20 10 10. - 3 -

2.0 - Installation 2.1 Wiring Connection diagrams illustrate typical wiring connections. Use 75 C minimum wires. Note: All wiring must comply with local codes, regulations and ordinances. WARNING! Do not service equipment with voltage applied. Unit can be the source of fatal electrical shocks. 1. Mount the MWH on a vertical panel with the line connection (L1, L2) at the top. Proper orientation is required to achieve proper convention cooling of the solid state power device (SCR). 2. Remove the front cover of the winding heater for access to the power and control connections. 3. Recommended fuse and power wire sizes for MWH: MAXIMUM MWH AMP WIRE SIZE TYPE THHN REPLACEMENT FUSE F1 F2 10 14 Class T 600V 15 A Class CC 20A Time Delay 25 8 Class T 600V 30 A Class T 600V 70A 50 6 Class T 600V 60 A Class T 600V 100A 80 2 Class T 600V 100 A Class T 600V 150A TORQUE LB/IN MWH L1 L2 T1 T2 10 20 20 45 20 25 20 50 50 50 50 20 50 50 50 80 50 50 50 50-4 -

4. Connect L1 and L2 on the MWH to L1 and L2 on the magnetic contactor us ing the wire size recommended for your unit. (See Connection Diagram on right). 5. Connect T1 and T2 to the load side of the magnetic contactor before the over load relay heater elements. Do not connect to starter terminals T1 and T2. Use the wire size recommended for your unit. Wiring Diagram for units rated at 10, 50 and 80 Amps 6. If your system utilizes a heater off-on switch, connect it in series with normally closed auxiliary contact on the motor starter to the terminals labelled SW. Use AWG 16 wire for the circuit. 7. If your system does not utilize a heater off-on switch, connect the normally closed auxiliary contact directly to the terminals labeled SW (TB1). Note: The cover of the motor winding heater depicts the connection diagram (See page 5). 8. If required, connect the normally open contact from the motor overload to the overload connection as shown on the wiring diagram. 9. Replace the cover when all connections have been completed and checked. Wiring Diagram for units rated at 25 Amps - 5 -

10. Included with each unit are two self-adhesive warning labels. Attach one warning label in a conspicuous place on the motor junction box and the other on the outside of the starter enclosure. WARNING THIS MOTOR IS EQUIPPED WITH A MOTOR WINDING HEATER. VOLTAGE IS PRESENT AT MOTOR TERMINALS EVEN WHEN MOTOR STARTER IS OPEN. BEFORE SERVICING MOTOR OR MOTOR WIRING ALWAYS DISCONNECT MAIN POWER AHEAD OF MOTOR STARTER. Sample Warning Label 11. If the motor winding heater is to be parallelled with a soft start, the customer must provide an isolation contactor between the output of the MWH and the motor as shown in the figure below. Wiring Diagram to Parallel the MWH unit with a Soft Start - 6 -

3.0 - Operation 1. Apply line voltage to the system. The Power On LED on the MWH should light. If the Power On LED does not light, it is an indication of a blown fuse or improper connections. Do not proceed until this is corrected. 2. If the motor starter is off and the SW circuit is closed, then the Enable On LED will be on. The MWH will turn on automatically in approximately 1 minute. LED Placement 3. The Output On LED will turn on when the MWH begins to apply voltage to the motor. 4. The output voltage to the motor is factory set for 8% to 9% of the line voltage. (Measured with an RMS AC Voltmeter) Maximum range of this adjustment is approximately 15% of line voltage. Note: Caution must be used when adjusting the output. Too high a setting may cause excessive heating in the motor. 5. During initial start-up monitor the output current to the motor. Use a standard AC clamp-on ammeter. Output current must not exceed the rating of the motor winding heater unit. 6. When the motor is starter the MWH automatically shuts off. It will remain off until the motor is turned off. The MWH will then turn on after approximately 1 minute. - 7 -

4.0 - Diagrams 4.1 MWH 10A Model - 8 -

4.2 MWH 25A Model - 9 -

4.3 MWH 50A Model - 10 -

4.4 MWH 80A Model - 11 -

Warranty Motortronics warrants its products to be free from defects in material and/or workmanship for a period of one year from the date of installation of a maximum of 18 months from the date of shipment as indicated by the unit s date code. The company reserves the right to repair or replace any malfunctioning units under warranty at their option. All warranty repairs must be performed by the Company factory, or on site by factory authorized service firms or personnel approved by the Company. Solid state controls have different operating characteristics from those of electro-mechanical equipment. Because of these differences and the wide variety of applications for solid state controls, each application designer must verify that the solid state equipment is acceptable for his application. In no event will Motortronics be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The diagrams and illustrations in this document are included solely for illustrative purposes. Because of the number of different applications, Motortronics can not be responsible or liable for actual use based on the examples or diagrams. - 12 -