I-VICFLEX.AB11. Victaulic VicFlex Style AB11 Low-Profile Sprinkler Fitting for Suspended Ceiling Systems WARNING INSTALLATION INSTRUCTIONS

Similar documents
I-VICFLEX.AB5. Victaulic VicFlex Style AB5 Sprinkler Fitting for Wood or Metal Joists/Studs and CD Profile (60 mm) Channel Ceiling Systems WARNING

I-VICFLEX.AB1/AB2/AB10

I-VICFLEX.AB7 VicFlex Sprinkler Fittings for Ceiling Suspension Systems STYLE AB7

I-795/906. Series 795 and 906 Installation-Ready Knife Gate Valves WARNING INSTALLATION AND MAINTENANCE INSTRUCTIONS

Data Sheet 3.11 Issue F

Data Sheet 3.03 Issue D

Data Sheet 3.01 Issue C

I-731-D/W731-D. Suction Diffuser. Important Installation Information. series 731-D and W731-D

I-317. AWWA Check Valves WARNING INSTALLATION AND MAINTENANCE INSTRUCTIONS SERIES 317 WARNING

Easy Riser swing check valve Models E-1 & F-1

I-799/79V Coil Components

I-234. Victaulic Styles 234/234S Restrained, Flexible Single-Gasket Couplings WARNING IMPORTANT INFORMATION ITEMS PROVIDED WITH SHIPMENT:

Model VKFD28 Flexible Sprinkler Drops (LPCB Approved) Installation Manual. January 2016 Form No. F_ Rev 16.1

I-232.T3S2 Victaulic Style 232 Restrained, Flexible High-Pressure Coupling

TECHNICAL DATA OBSOLETE

FRAME STYLE SPRAY NOZZLES TECHNICAL DATA

GROOVED COUPLINGS - STANDARD FLEXIBLE Model 101

I-231.T2S1/CLAD. Victaulic Style 231 Non-Restrained, Flexible Expansion Coupling with Cladding on Expansion Side of Pipe WARNING IMPORTANT INFORMATION

TECHNICAL DATA OBSOLETE

TECHNICAL DATA. Table 1: Model F1 Dry Valve Part Numbers and Specifications

TECHNICAL DATA. Q= C v P Cv = Flow Factor (GPM/1 PSI P)

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE 6 (DN150)

TECHNICAL DATA. Q= C v P S

Q= C. v P S Refer to Table 1 for part numbers and shipping weights. Accessories: Table 1: Valve Part Numbers and Specifications

Flexible Sprinkler Connector Braided & Unbraided

Instructions for Installation, Operation, Care and Maintenance

mirage standard and Qr concealed pendent sprinkler vk462 and hp sprinkler vk463 (K5.6)

model E Spray nozzles vk810 - vk817

Fire Protection Systems

TECHNICAL DATA 1-1/2 (dn40)

Flexible Sprinkler Connections

I-VIC300MS. Vic -300 MasterSeal Butterfly Valves WARNING SERIES 761

Instructions for Installation, Operation, Care and Maintenance

Grooved Piping System for Fire Protection Services

Fisher 657 Diaphragm Actuator Sizes and 87

I-VIC300MS. Series 761 Vic-300 MasterSeal Carbon Steel Butterfly Valve Series 461 Vic-300 MasterSeal Stainless Steel Butterfly Valve WARNING

30.85 FireLock NXT Actuated Valve with LPCB Approved Preaction Trim

TECHNICAL DATA. model f-1 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA. Page 1 of 11

Rosemount 485 Annubar Flanged Assembly

Document: 3 inch Vane Pump System-in-a-Box Assembly Instructions SPS100370

B21 Series BASOTROL Gas Valve

Listings and Approvals. G5 QR Gasket culus QR G5 SR Gasket culus, FM SR G5

REQUEST PUBLICATION 18.11

Speed Controller with One-touch Fitting

Series 758 FireLock Actuated System Valve

Model CV-1FR Grooved-End Riser Check Valves 2 Inch to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data

AK Application. Features. Applicable Literature. Positive Positioner Pneumatic Relay General Instructions

RG2100 Roll Grooving Tool

Size Inches UL ULC FM. Pipe Sch.

Rosemount 485 Annubar Threaded Flo-Tap Assembly

Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation

I-NXT.RBKIT 5-Year Rebuild Kit Instructions for FireLock NXT Valves

FireLock NXT Deluge Valve. With Deluge Trim Grooved x Grooved. System No. Submitted By Spec Sect Para Location Date Approved Date

Technical Data. Sizes 2 in. to 24 in. (DN50 to DN600) Approvals UL and ULC Listed FM Approved

Rosemount 285 Annubar Pak-Lok Assembly

EC4 SERIES CRYOGENIC VALVES 1/4 2 Sizes

Baumann Series Flexsleev Control Valve Instructions

2013 IMPCO Technologies, Inc. Page 1 of 20 EPR Repair Kit Instructions (PPI-122, Rev-B)

INSTALLATION/OPERATION/MAINTENANCE INSTRUCTIONS FOR ARCHON MODELS WD2010L, WD2010, WD2010H WASHDOWN STATIONS. ARCHON Industries, Inc.

TECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet)

Series 756 FireLock Dry System Check Valve

Victaulic Fittings, Couplings, Valves & Sprinkler Heads for the Fire Sprinkler Market Keeping the art of distribution simple

Scope. Applicability. Caution. I & M CV3000 Series. Storage. Installation & Maintenance Instructions for Marwin CV3000 Series Three Piece Ball Valves

TECHNICAL DATA VK810 (65 ) VK811 (80 ) VK812 (95 ) VK813 (110 )

Herpteraium SECTION VALVES GENERAL

2001 SERIES CRYOGENIC BAR STOCK BODY VALVES

I-BFV.KIT Butterfly Valve Gear Operator Replacement

MAINTENANCE GUIDELINES FOR NIBCO ¼ THROUGH 3 CLASS 125, 150, 200 & 300 BRONZE SWING CHECK VALVES FIGURE NUMBERS

ALARM CHECK VALVE 3", 4" & 6" MODEL H-1 FLANGE/FLANGE 3" & 4" MODEL H-2 GROOVE/GROOVE 3", 4" & 6" MODEL H-3 FLANGE/GROOVE

TECHNICAL DATA CAUTION

Series 751 FireLock European Alarm Check Valve Stations

Model DF233 Control Valve

Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description

Escape Cylinder and Valve

Grinnell Grooved Fire Protection Products Grooved Fittings

VALVE AND PLUMBING KIT 2409 LOADER CUB CADET & KIOTI TRACTORS

DEFENDER SERIES. 5 Gallon, Double Walled, Field Replaceable Spill Container Model Series INSTALLATION, OPERATION, & MAINTENANCE

Instructions for Installation, Operation, Care and Maintenance

Model RM-1 Riser Manifold Commercial and Residential General Description

Railroad Ball Valves Series 5REB3

Installation, Operation and Maintenance Manual

FIG Gruvlok Flanges

B U I L D I N G C O N N E C T I O N S T H AT L A S T

DeZURIK " BAW AWWA BUTTERFLY VALVES WITH EPOXY-RETAINED SEAT

Baumann Way Control Valve

Page 1 of 26 Oteco Inc. Houston, Texas

INSTALLATION INSTRUCTIONS 88029

Speed Controller with One-touch Fitting

4410 TwinHydrostatic Gas Seal

GBV-G Balancing Valves

K81-D FIRE HYDRANT GUARDIAN AWWA C502 NSF YEARS. For Generations CERTIFICATIONS ISO 9001 ISO BS OHSAS

Signet 2517 Brass Paddlewheel Flow Sensor * *

SERVICE INSTRUCTIONS ASSEMBLY & DISASSEMBLY T50X DOUBLE ACTING HYDRAULIC SERIES ACTUATORS

Bettis M11 Manual Hydraulic Override System Operating Instructions for HD, T, and G Series Pneumatic and Hydraulic Actuators

SITRANS F. Ultrasonic Flowmeters. Hi-Precision Mounts. Operating Instructions. Answers for industry.

SD Bendix E-10PR Retarder Control Brake Valve DESCRIPTION. OPERATION - Refer to Figure 2

Model DF269 Control Valve

DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Wet Pilot Actuation General Description

Baumann Mikroseal Control Valve

45 VALVE SERIES. 2-Position 4-Way 5-Ports, Installation & Service Instructions. Valve with Stem Operator, Installation & Service Instructions

Transcription:

INSTALLATION INSTRUCTIONS I-VICFLEX.AB11 Victaulic VicFlex Style AB11 Low-Profile Sprinkler Fitting for Suspended Ceiling Systems Read and understand all instructions before attempting to install any Victaulic VicFlex products. Wear safety glasses, hardhat, and foot protection. These installation instructions are intended for an experienced, trained installer. The user shall understand the purpose of these products, c ommon industry standards for safety, and the potential consequences of improper product installation. It is the system designer s responsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the piping system and external environment. The effect of chemical composition, ph level, operating temperature, chloride level, oxygen level, and flow rate on the stainless steel flexible hose shall be evaluated by the material specifier to confirm system life will be acceptable for the intended service. Failure to follow these instructions could cause improper sprinkler operation and product failure, resulting in death or serious personal injury and property damage. Flexible Hose Listing and Approval Information Flexible Hose AH1-LP With AB11 With AB11 With AB11 AH1-CC-LP With AB11 With AB11 AH-LP With AB11 With AB11 With AB11 AH-CC-LP With AB11 With AB11 With AB11 AH-LP* With AB11 With AB11 * SERIES AH-LP REGIONAL AVAILABILITY ONLY NOTES: Victaulic VicFlex flexible hoses are City of Los Angeles (RR5659) Approved, accepted for use by the City of New York Department of Buildings (MEA 60-05-E), and have the OSHPD Pre-Approval (OPA-55-07). Flexible hoses are available in lengths from 1-7 inches/787-189 mm with either 1/-inch/DN15 or /-inch/dn0 NPT or BSPT threaded outlets. G10 Maximum Working Pressure Rating: 00 psi/1 Bar/179 kpa (FM) 175 psi/1 Bar/107 kpa (UL) 16 Bar/1600 kpa/ psi (VdS) Maximum Ambient Temperature Rating: 5 F/107 C Connection to Sprinkler Piping: 1 inch/dn5 NPT/BSPT 1 inch/dn5 IGS DN0// inch BSPT (VdS) of Flexible Hose: inch/76 mm (UL Series AH1-LP) inch/50 mm (UL Series AH-LP, AH-CC-LP) 7 inch/178 mm (FM) 76 mm/ inch (VdS) Maximum K-Factor of Sprinkler to be Connected to Sprinkler Reducing Nipple: K8.0 US/K115 metric for 1/ inch/dn15 K1.0 US/K00 metric for / inch/dn0 K115 metric/k8.0 US for / inch/dn0 (VdS) Maximum Number of 90 Bends Per Flexible Hose: Refer to the Friction Loss Data section Flexible Hose Bend Characteristics: NOTE: For out-of-plane (three-dimensional) bends, care shall be taken to avoid imparting torque on the flexible hose. X Bend Radius 90 OR X Bend Radius OR I-VICFLEX.AB11_1

INTRODUCTION Victaulic VicFlex Sprinkler Fittings connect the sprinkler piping directly to the sprinkler using a flexible hose and fittings and are designed for use in suspended ceiling applications. Each assembly comes with one flexible hose, one adapter nipple or captured coupling, one sprinkler reducing nipple, and the Style AB11 Bracket. IMPORTANT INSTALLATION INFORMATION Victaulic VicFlex products shall be installed according to current, applicable National Fire Protection Association (NFPA 1, 1D, 1R, etc.) standards or equivalent standards. Victaulic VicFlex products are intended to be installed in wet, dry, or preaction actuated systems. Deviations from these standards or alterations to Victaulic VicFlex products or sprinklers will void any Victaulic warranty and will impact system integrity. Installations shall meet the provisions of the local authority having jurisdiction and local codes, as applicable. Drop ceiling construction shall meet the requirements of ASTM C65 and shall be installed in accordance with ASTM C66. Victaulic VicFlex Sprinkler Fittings and Style AB11 Brackets shall not be intermixed with other manufacturer s flexible sprinkler products. SHORT 90 ELBOW REDUCERS ARE TYPICALLY USED WITH CONCEALED SPRINKLERS (FM AND VdS ONLY). Refer to the specific product submittal for applications and listing information. These submittals are located in Sections 10 and 0 of the Victaulic G-100 Catalog or on the Victaulic website at www.victaulic.com. In addition, when installing Victaulic FireLock Automatic Sprinklers with Victaulic VicFlex Sprinkler Fittings, refer to the I-0 Installation and Maintenance Instructions for details on sprinkler installation requirements. Size the piping system to provide at least the minimum required flow rate for the sprinkler system. Per NFPA requirements, flush the system to remove foreign material. Continue to flush the system until water runs clear. DO NOT install sprinkler system piping through heating ducts. DO NOT connect sprinkler system piping to domestic hot water systems. DO NOT install sprinklers and sprinkler fittings where they will be exposed to temperatures that exceed the maximum ambient temperature rating for the sprinkler and sprinkler fittings. The flexible hose shall not be bent or fluctuated up-and-down or side-to-side when it is pressurized. Flexible hose and fittings have limited flexibility* and are intended only to be installed with bends not less than their respective minimum bend radii. DO NOT install flexible hose in a straight configuration. Protect wet piping systems from freezing temperatures. If construction is altered, the building owner or their representative is responsible for referencing applicable standards to determine if additional sprinklers or other system adjustments are required. The owner is responsible for maintaining the fire protection system in proper operating condition. For minimum maintenance and inspection requirements, refer to NFPA 5 and any other applicable NFPA standards that describe the care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may have additional maintenance, testing, and inspection requirements that shall be followed. Relocation of Victaulic VicFlex products SHALL be performed by qualified personnel familiar with the system s original design criteria, sprinkler listings/ approvals, and state and local codes (including NFPA 1 standards). Failure to relocate this Victaulic VicFlex product properly could affect its performance during a fire, resulting in serious personal injury and property damage. * Reference UL : Section 5.1 STYLE AB11 BRACKET ASSEMBLY DRAWING Refer to pages 6 7 of this manual for bracket installation instructions. 5 Item Description 1 -inch/610-mm or 8-inch/119-mm Square Bar* Center Gate Assembly with Wing Nut Style AB11 End Bracket with Tapping Screw Relocation Warning Label 5 Wing Screw 1 * Reference submittal document 10.85 for listing information. Square bar length is in reference to nominal ceiling grid spacing. 5 I-VICFLEX.AB11_

FLEXIBLE HOSE ASSEMBLY DRAWINGS Refer to pages 9 11 of this manual for flexible hose technical data. Example Series AH-LPSE (Low-Profile Short Elbow) Shown Below Example Series AH-CC-LPSE (Low-Profile Short Elbow) Shown Below 1 1 5 Item Example Series AH Description Example Series AH-CC-LP Description 1 Flexible Hose Assembly Flexible Hose Assembly Adapter Nipple Coupling Assembly Low-Profile Elbow Reducer (Flexible Hose to Sprinkler) Low-Profile Elbow Reducer (Flexible Hose to Sprinkler) Shipping Cap Identification Sleeve 5 Identification Sleeve Product Marking Information UL Model Designation Outlet Fitting Mark Description AH1-XX-LPSE LPSE AH1 with Low-Profile Short Elbow Reducer Outlet AH1-XX-LPLE LPLE AH1 with Low-Profile Long Elbow Reducer Outlet AH1-CC-XX-LPSE LPSE AH1-CC-LP with Low-Profile Short Elbow Reducer Outlet AH1-CC-XX-LPLE LPLE AH1-CC-LP with Low-Profile Long Elbow Reducer Outlet AH-XX-LPSE LPSE AH with Low-Profile Short Elbow Reducer Outlet AH-XX-LPLE LPLE AH with Low-Profile Long Elbow Reducer Outlet AH-CC-XX-LPSE LPSE AH-CC-LP with Low-Profile Short Elbow Reducer Outlet AH-CC-XX-LPLE LPLE AH-CC-LP with Low-Profile Long Elbow Reducer Outlet NOTE: Flexible hoses are marked with all UL model designations. In addition, the outlet fitting of the flexible hose is marked with the model s corresponding suffix designation, if applicable. Refer to the chart above to correlate the markings with the UL Listing. I-VICFLEX.AB11_

1-INCH/DN5 IGS CONNECTION TO THE SPRINKLER PIPING USING A SERIES AH1-CC-LP OR AH-CC-LP FLEXIBLE HOSE CORRECT - IGS Groove Profile INCORRECT - Orignal Groove System (OGS) Groove Profile The Style 108 Coupling assembly of the Series AH1-CC-LP and AH-CC-LP shall be used ONLY with sprinkler piping connections that are prepared to Victaulic IGS proprietary groove specifications. DO NOT attempt to install the coupling on sprinkler piping connections that are prepared to any other groove specification. Refer to Victaulic publication 5.1 for the IGS groove specification, which can be downloaded at victaulic.com. The flexible hose shall not be bent or fluctuated up-and-down or side-to-side when it is pressurized for test. Failure to follow this instruction could cause improper sprinkler operation, serious personal injury, and/or property damage. DO NOT REMOVE NUT/BOLT FOR INITIAL INSTALLATION. CHECK GASKET: Check the gasket to ensure that it is suitable for the intended service. The color code identifies the gasket grade. Refer to Victaulic publication 05.01 for the color code chart, which can be downloaded at victaulic.com. a. REFER TO THE NOTICE BELOW FOR IMPORTANT GASKET INFORMATION. NOTICE Series AH1-CC-LP and AH-CC-LP flexible hoses are designed for use ONLY in fire protection systems (temperatures greater than 0 F/ 0 C). Style 108 Coupling assemblies of Series AH1-CC-LP and AH-CC-LP flexible hoses are provided with the Vic-Plus gasket system. Additional lubrication is not required for the initial installation of wet pipe systems that are installed at or continuously operating above 0 F/ 18 C. Refer to Victaulic publication 05.0 for the Vic-Plus Material Safety Data Sheet (MSDS), which can be downloaded at victaulic.com. Supplemental lubrication is required for Vic-Plus gaskets only if any of the following conditions exist. If any of these conditions exist, apply a thin coat of Victaulic lubricant or silicone lubricant to the sealing lips of the gasket interior only. DO NOT over-lubricate the gasket. If the continuous operating temperature is below 0 F/ 18 C If the gasket has been exposed to fluids prior to installation If the surface of the gasket does not have a hazy appearance If the gasket is being installed into a dry pipe system If the system will be subjected to air tests prior to being filled with water If the gasket was involved in a previous installation If the gasket sealing surface of the pipe contains raised or undercut weld seams, or cracks or voids at the weld seams. Lubricated gaskets will not enhance sealing capabilities on adverse pipe conditions. Pipe condition and pipe preparation shall conform to the requirements listed in product installation instructions. 1. DO NOT DISASSEMBLE THE COUPLING: The Style 108 Coupling assembly of the Series AH1-CC-LP and AH-CC-LP is designed so that the installer does not need to remove the bolt and nut for installation. This design facilitates installation by allowing the installer to directly insert the sprinkler piping s grooved end into the coupling.. CHECK GROOVED END OF SPRINKLER PIPING: The outside surface of the sprinkler piping, between the groove and the end of the sprinkler piping, shall be smooth and free from indentations, projections, weld seams, and roll marks to ensure a leak-tight seal. All oil, grease, loose paint, dirt, and cutting particles shall be removed. The sprinkler piping s outside diameter ( OD ), groove dimensions, and maximum allowable flare diameter shall be within the tolerances published in current Victaulic IGS specifications, publication 5.1, which can be downloaded at victaulic.com. Never leave a Style 108 Coupling assembly of a Series AH1-CC-LP or AH-CC-LP partially assembled. A partially assembled coupling poses a drop or burst hazard during testing. Keep hands away from the opening of the coupling when attempting to insert the grooved sprinkler piping into the coupling. Failure to follow these instructions could result in serious personal injury and property damage. I-VICFLEX.AB11_

I-VICFLEX.AB11 / Victaulic VicFlex Low-Profile Sprinkler Fittings / Installation Instructions GOOD. ASSEMBLE JOINT: Assemble the joint by inserting the grooved end of the sprinkler piping into the opening of the coupling. The grooved sprinkler piping shall be inserted into the coupling until contact with the center leg of the gasket occurs. A visual check is required to ensure that the coupling keys align with the groove in the sprinkler piping. BAD The nut shall be tightened until metal-to-metal c ontact occurs at the bolt pads. Failure to follow this instruction could cause joint failure, resulting in death or serious personal injury and property damage. 6. INSPECT PADS: Visually inspect the bolt pads at each joint to ensure that metal-to-metal contact is achieved in accordance with step 5. NOTICE Refer to the instructions on page 8 for disassembly and reassembly requirements. 5. TIGHTEN NUT: Using an impact wrench or standard socket wrench with an 11/16-inch/17-mm deep well socket, tighten the nut until metal-to-metal contact occurs at the bolt pads. Verify that the housings keys engage the sprinkler piping s groove completely. I-VICFLEX.AB11_5

CONNECTION TO THE SPRINKLER PIPING USING AN ADAPTER NIPPLE AND A SERIES AH1-LP, AH-LP, OR AH-LP FLEXIBLE HOSE INSTALLATION OF THE SPRINKLER REDUCING NIPPLE ONTO THE FLEXIBLE HOSE The flexible hose shall not be bent or fluctuated up-and-down or side-to-side when it is pressurized for test. Failure to follow this instruction could cause improper sprinkler operation, serious personal injury, and/or property damage. 1. Apply pipe joint compound or PTFE thread sealant tape to the tapered threads of the adapter nipple, in accordance with the pipe joint compound or tape manufacturer s instructions. Using a pipe wrench, tighten the adapter nipple into the sprinkler piping.. Confirm that the seal inside the nut of the flexible hose is in place and is free from damage prior to installation. Connect the nut to the adapter nipple, as shown. DO NOT use pipe joint compound or PTFE thread sealant tape on the threads of the adapter nipple. The seal inside the nut of the flexible hose provides the leak-proof connection. Tighten the connection nut to a torque of 0 ft-lbs/5 N m (approximately 1/ to / of a turn past hand-tight). NOTE: To prevent damage to the seal, tighten the assembly by applying torque only to the connection nut and DO NOT exceed the specified torque. TURN CONNECTION NUT ONLY 1. Confirm that the seal inside the nut of the flexible hose is in place and is free from damage prior to installation. Connect the nut to the sprinkler reducing nipple. SHORT 90 ELBOW REDUCERS ARE TYPICALLY USED WITH CONCEALED SPRINKLERS. DO NOT use pipe joint compound or PTFE thread sealant tape on the fine threads of the sprinkler reducing nipple. The seal inside the nut of the flexible hose provides the leak-proof connection. Tighten the connection nut to a torque of 0 ft-lbs/5 N m (approximately 1/ to / of a turn past hand-tight). NOTE: To prevent damage to the seal, tighten the assembly by applying torque only to the connection nut and DO NOT exceed the specified torque. INSTALLATION OF STYLE AB11 BRACKETS FOR ASTM C65 CEILING SUSPENSION SYSTEMS INSTALLED IN ACCORDANCE WITH ASTM C66 OR ASTM C75 STANDARDS For adjustment purposes, the wing screw on top of the end bracket assembly can be loosened to allow the end bracket to slide on the square bar. Tighten the wing screw on top of the end bracket assembly to a torque of 6 inch-lbs/ N m (approximately 1/ to / of a turn past hand-tight) to secure the end bracket to the square bar. 1. Attach the end brackets of the Style AB11 Bracket to the T-bar rails of an ASTM C65 ceiling suspension system installed in accordance with ASTM C66 standards. Make sure the ends of the Style AB11 Bracket engage the rails. I-VICFLEX.AB11_6

I-VICFLEX.AB11 / Victaulic VicFlex Low-Profile Sprinkler Fittings / Installation Instructions Side Facing the Opening of the Center Gate Assembly For center-of tile installations, position the center gate assembly between the two reference marks on the square bar, as shown above. 1a. For center-of-tile installations, align the end bracket with the center-of-tile slot of the T-bar rail (with the side facing the opening of the center gate assembly), as shown above.... Apply light downward pressure, as shown above, to maintain the position of the end bracket flat against the T-bar rail. To secure the end brackets to the T-bar rails, tighten the pre-installed sheet metal screws using a # recessed square drive bit. Penetrate through the T-bar rail until the end bracket is seated fully against the T-bar rail. DO NOT over-tighten the screws. Over-tightening will cause the screw to strip, resulting in an unsecured bracket connection. Close the center gate assembly around the sprinkler reducing nipple. Swing the pivot screw and washer into the slot on the gate, and tighten the wing nut to a torque of 50 inch-lbs/6 N m (approximately hand-tight, plus 1/ to / of a turn). NOTE: Make sure the washer is seated under the head of the wing nut. SPRINKLER INSTALLATION: Install the sprinkler by following the manufacturer s installation instructions. For Victaulic sprinklers, refer to the I-0 Victaulic FireLock Automatic Sprinklers Installation and Maintenance Instructions. Move the center gate assembly of the Style AB11 Bracket to the desired location. Loosen the wing nut to open the center gate assembly, then slide the sprinkler reducing nipple into the center gate assembly. NOTE: The pivot screw of the center gate assembly is staked to resist removal of the wing nut. I-VICFLEX.AB11_7

INSTRUCTIONS FOR REASSEMBLY OF A SERIES SERIES AH1-CC-LP OR AH-CC-LP FLEXIBLE HOSE Verify that the system is depressurized and drained completely before attempting to disassemble a Series AH1-CC-LP or AH-CC-LP Flexible Hose from the sprinkler piping. Failure to follow this instruction could result in death or serious personal injury and property damage. 1. Verify that the system is depressurized and drained completely before attempting to disassemble a Series AH1-CC-LP or AH-CC-LP Flexible Hose from the sprinkler piping.. Loosen the nut of the Style 108 Coupling assembly to permit removal from the sprinkler piping.. Remove the nut, bolt, gasket, and linkage from the Style 108 Coupling housings. Inspect all components for damage or wear. If any damage or wear is present, replace with new Victaulicsupplied components. NOTE: Replacement gaskets shall be of the same grade that is suitable for the intended service.. Verify that the outside surface of the sprinkler piping, between the groove and the end of the sprinkler piping, is smooth and free from indentations, projections, weld seams, and roll marks to ensure a leak-tight seal. All oil, grease, loose paint, dirt, and cutting particles shall be removed. The sprinkler piping s outside diameter ( OD ), groove dimensions, and maximum allowable flare diameter shall be within the tolerances published in current Victaulic IGS specifications, publication 5.1, which can be downloaded at victaulic.com. 7. REASSEMBLE COUPLING ONTO FLEXIBLE HOSE: Place the lubricated gasket onto the inlet end of the flexible hose, then place the Style 108 Coupling housings over the gasket. Verify that the gasket is seated in the gasket pocket of the housings and that the housings' keys engage with the spacer. 8. INSTALL LINKAGE: Install the linkage onto the housings, as shown above. Spacer 5. Verify that the spacer is oriented on the inlet end of the flexible hose, as shown above. CAUTION A thin coat of Victaulic Lubricant or silicone lubricant shall be used to prevent the gasket from pinching/tearing during reassembly. Failure to use a compatible lubricant will cause gasket damage, resulting in joint leakage and property damage. 9. INSTALL HARDWARE: Install the bolt through the housings. Thread the nut onto the bolt until the top of the nut is flush with the end of the bolt, as shown above. Verify that the gasket remains seated in the gasket pocket of the housings and that the housings' keys engage with the spacer. 10. Follow all steps on pages 5 of this instruction sheet to complete the assembly. 6. LUBRICATE GASKET: Apply a thin coat of Victaulic Lubricant or silicone lubricant to the gasket sealing lips and exterior. It is normal for the gasket surface to have a hazy white appearance after it has been in service. I-VICFLEX.AB11_8

TECHNICAL DATA FOR FLEXIBLE HOSES The following section provides friction loss information for flexible hoses that can be used with Style AB11 Brackets. It is the system designer s responsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the piping system and external environment. The effect of chemical composition, ph level, operating temperature, chloride level, oxygen level, and flow rate on the stainless steel flexible hose shall be evaluated by the material specifier to confirm system life will be acceptable for the intended service. Failure to follow these instructions could cause product failure, resulting in death or serious personal injury and property damage. I-VICFLEX.AB11_9

SERIES AH1-LP FLEXIBLE HOSE FRICTION LOSS DATA (FM AND UL) Model AH1-1-LP AH1-6-LP AH1-8-LP AH1-60-LP AH1-7-LP Length of Flexible Hose inches/mm 1 790 6 915 8 10 60 155 7 180 Equivalent Length of Outlet Size# 1-inch/DN5 Schedule 0 Pipe feet/meters Maximum Number of 90 Bends inches/metric FM* UL FM UL 1/ 9.0 6.0 DN15 1.9 19. / 7.9 65.0 DN0 1.6 19.8 1/ 58.5 76.0 DN15 17.8. / 58.0 76.0 DN0 17.7. 1/ 81.5 99.0 DN15.8 0. / 8. 98.0 DN0 5.1 9.9 1/ 10. 108.0 DN15 1.8.9 / 106. 10.0 DN0. 1.1 1/ 17. 1.0 DN15 8.8 7.8 / 10.8 1.0 DN0 9.9 0. 5 * 7-inch/178-mm minimum bend radius -inch/76-mm minimum bend radius # /-inch/dn0 outlet data shown with K1.0 - For other K-factor friction loss data, refer to Victaulic submittal 10.95 A higher number of bends may be permitted, provided the sum of degrees is equal to or less than the total maximum allowable degrees of bends (e.g. Two 90 bends equal 180. Three 90 bends equal 70 ). The minimum bend radius and maximum number of 90 offset (bends), stated in these installation instructions, refer to the final installed condition of the hose. NOTE: Differences in equivalent lengths are due to varying test methods, per UL and FM 167 standards. Refer to these standards for additional information regarding friction loss test methods. SERIES AH1-CC-LP FLEXIBLE HOSE FRICTION LOSS DATA (FM) Model AH1-CC-1-LP AH1-CC-6-LP AH1-CC-8-LP AH1-CC-60-LP AH1-CC-7-LP Length of Flexible Hose inches/mm 1 790 6 915 8 10 60 155 7 180 Outlet Size# inches/metric Equivalent Length of 1-inch/DN5 Schedule 0 Pipe feet/meters* 1/ 9.0 DN15 1.9 / 7.9 DN0 1.6 1/ 58.5 DN15 17.8 / 58.0 DN0 17.7 1/ 81.5 DN15.8 / 8. DN0 5.1 1/ 10. DN15 1.8 / 106. DN0. 1/ 17. DN15 8.8 / 10.8 DN0 9.9 Maximum Number of 90 Bends * 7-inch/178-mm minimum bend radius # /-inch/dn0 outlet data shown with K1.0 - For other K-factor friction loss data, refer to Victaulic submittal 10.95 A higher number of bends may be permitted, provided the sum of degrees is equal to or less than the total maximum allowable degrees of bends (e.g. Two 90 bends equal 180. Three 90 bends equal 70 ). The minimum bend radius and maximum number of 90 offset (bends), stated in these installation instructions, refer to the final installed condition of the hose. NOTE: Differences in equivalent lengths are due to varying test methods, per the FM 167 standard. Refer to this standard for additional information regarding friction loss test methods. I-VICFLEX.AB11_10

SERIES AH-LP AND AH-CC-LP FLEXIBLE HOSE FRICTION LOSS DATA (FM AND UL) Model AH-1-LP AH-CC-1-LP AH-6-LP AH-CC-6-LP AH-8-LP AH-CC-8-LP AH-60-LP AH-CC-60-LP AH-7-LP AH-CC-7-LP Length of Flexible Hose inches/mm 1 790 6 915 8 10 60 155 7 180 Equivalent Length of Outlet Size# 1-inch/DN5 Schedule 0 Pipe feet/meters Maximum Number of 90 Bends inches/metric FM* UL FM UL 1/ 1.7.0 DN15. 7. / 1.5.0 DN0.1 7. 1/ 17.0 6.0 DN15 5. 7.9 / 16.8 8.0 DN0 5.1 8.5 1/ 5.0.0 DN15 7.6 1.1 /.7.0 DN0 7.5 1.8 1/.0 9.0 DN15 10.1 1.9 /.7 50.0 DN0 10.0 15. 1/ 1.1 65.0 DN15 1.5 19.8 / 0.7 6.0 DN0 1. 19. 5 8 10 1 * 7-inch/178-mm minimum bend radius -inch/50-mm minimum bend radius # /-inch/dn0 outlet data shown with K1.0 - For other K-factor friction loss data, refer to Victaulic submittal 10.85 A higher number of bends may be permitted, provided the sum of degrees is equal to or less than the total maximum allowable degrees of bends (e.g. Two 90 bends equal 180. Three 90 bends equal 70 ). The minimum bend radius and maximum number of 90 offset (bends), stated in these installation instructions, refer to the final installed condition of the hose. NOTE: Differences in equivalent lengths are due to varying test methods, per UL and FM 167 standards. Refer to these standards for additional information regarding friction loss test methods. SERIES AH-LP FLEXIBLE HOSE FRICTION LOSS DATA (FM) REGIONAL AVAILABILITY ONLY Model AH-1-LP AH-6-LP AH-8-LP AH-60-LP AH-7-LP Length of Flexible Hose inches/mm 1 790 6 915 8 10 60 155 7 180 Outlet Size# inches/metric Equivalent Length of 1-inch/DN5 Schedule 0 Pipe feet/meters* 1/ 5.8 DN15 16. / 69.8 DN0 1. 1/ 60.0 DN15 18. / 76.5 DN0. 1/ 75.0 DN15.8 / 9.5 DN0 8.1 1/ 90.0 DN15 7. / 108.6 DN0.1 1/ 105. DN15.0 / 1.9 DN0 8.0 Maximum Number of 90 Bends * 7-inch/178-mm minimum bend radius (tested with standard 5 /-inch/16-mm length straight reducer) # The /-inch/dn0 outlet data is shown with K11.. For other K-factor friction loss data, refer to Victaulic submittal 10.9. A higher number of bends may be permitted, provided the sum of degrees is equal to or less than the total maximum allowable degrees of bends (e.g. Two 90 bends equal 180. Three 90 bends equal 70 ). The minimum bend radius and maximum number of 90 offset (bends), stated in these installation instructions, refer to the final installed condition of the hose. For friction loss data for elbows, refer to Victaulic submittal 10.9. I-VICFLEX.AB11_11

INSTALLATION INSTRUCTIONS I-VICFLEX.AB11 Victaulic VicFlex Style AB11 Low-Profile Sprinkler Fitting for Suspended Ceiling Systems SERIES AH1-LP, AH1-CC-LP, AH-LP, AH-CC-LP, AND AH-LP* FLEXIBLE HOSE FRICTION LOSS DATA (VDS) Length of Flexible Hose mm/ inches 790 1 Outlet Size Metric/ inches DN15/1/ DN0// Maximum Number of 90 Bends at 76.-mm/-inch Series AH1-LP and AH1-CC-LP Series AH-LP and AH-CC-LP Series AH-LP* Equivalent Length of Steel Pipe in meters/feet According to EN 1055 DN 0 (6,9 x,65).0 1.9 Equivalent Length of Steel Pipe in meters/feet According to EN 1055 DN 5 (,7 x,5) 5.5 18.0 Equivalent Length of Steel Pipe in meters/feet According to EN 1055 DN 0 (6,9 x,65) 5.9 19. 915 6 DN15/1/ DN0//.6 15.0 6. 1.0 6.9.5 10 8 DN15/1/ DN0// 6.1 0.0 8.5 7.9 9. 0.0 155 60 DN15/1/ DN0// 7.6 5.0 10.7 5.1 11. 7.5 180 7 DN15/1/ DN0// 9. 0.0 1.8.0 1.7 5.0 * SERIES AH-LP REGIONAL AVAILABILITY ONLY Flexible Hoses are VdS Approved for use in wet systems only. Only VdS Approved pendent spray sprinklers of 10-mm, 15-mm, and 0-mm nominal diameters with K-factors of 57, 80, and 115 shall be used. The VdS Approval applies only for use with the following manufacturers suspended ceiling systems: AMF Armstrong Chicago Metallic Dipling Durlum Geipel Ceiling Suspension Systems for Style AB11 Brackets Gema-Armstrong Hilti Knauf Lafarge Lindner Odenwald Richter Rigips Rockfon Pagos Suckow & Fischer USG Donn Other manufacturers ceiling systems, with comparable or better performance, can be considered for approval. VdS standards for safety include, but are not limited to: pressure cycling, corrosion resistance, flow characteristics, vibration resistance, leakage, mechanical strength, and hydrostatic strength. Differences in equivalent lengths are due to varying test methods, per FM 167 and VdS standards. Refer to these standards for additional information regarding friction loss test methods. For complete contact information, visit victaulic.com I-VICFLEX.AB11 908 REV C UPDATED 10/017 Z00AB11000 VICTAULIC AND VICFLEX ARE REGISTERED TRADEMARKS OR TRADEMARKS OF VICTAULIC COMPANY AND/OR ITS AFFILIATED ENTITIES IN THE UNITED STATES AND/OR OTHER COUNTRIES. 017 VICTAULIC COMPANY. ALL RIGHTS RESERVED.