Requirements and Responsibilities for Fire Pump Packages

Similar documents
INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY

M.P.S.C. No. 2 Electric Third Revised Sheet No. 65 (Rate Case) Cancels Second Revised Sheet No. 65

Legal Considerations Related to Distributed Energy Resources

DEPARTMENT OF TRADE AND INDUSTRY NO APRIL 2016

COUNTY ROAD COMMISSION RULES FOR THE MOVEMENT OF OVERSIZE OR OVERWEIGHT VEHICLES AND LOADS

REPORT NO INSPECTION, TEST AND EVALUATION OF. Interlock Kits SUBMITTED TO MASTER ELECTRICAL SERVICES 3107 LANVALE AVENUE RICHMOND, VA 23230

SANTA CLARA CITY RENEWABLE NET METERING & INTERCONNECTION AGREEMENT

City of Storm Lake Fire Department Heavy Rescue Specifications

SFI SPECIFICATION 4.2 EFFECTIVE: OCTOBER 26, 1994*

RSPO PalmTrace - Book and Claim Terms and Conditions

SFI SPECIFICATION 35.1 EFFECTIVE: AUGUST 26, 2008 *

REBATE APPLICATION. 1. Rebate Applicant Information. 2. Dealer Information OKLAHOMA NATURAL GAS COMPRESSED NATURAL GAS (CNG)

Approval Standard for Centrifugal Fire Pumps Split-Case Type (Axial or Radial)

INCOMING INSPECTION DELEGATION GUIDELINES FOR ALENIA SUPPLIERS PROGRAM: ALL

AEROMOTIVE Part # INSTALLATION INSTRUCTIONS

SFI SPECIFICATION 15.2 EFFECTIVE: MAY 1, 2008 *

Microgeneration Installation Standard: MCS

Appendix C SIP Creditable Incentive-Based Emission Reductions Moderate Area Plan for the 2012 PM2.5 Standard

Newport News Shipbuilding Contractor Environmental, Health and Safety Resource Manual Cranes

QUALITY REQUIREMENTS FOR JUST IN TIME SERVICE PROVIDER (JIT S.P.) PROGRAM: ALL

LIIKENNEVIRTA LTD GENERAL TERMS AND CONDITIONS FOR THE CHARGING SERVICE

An Urgent Bulletin from CSA Group

Certification Scheme

Umatilla Electric Cooperative Net Metering Rules

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)

Hedge trimmers (combustion engine powered)

Implementation procedure for certification and continued airworthiness of Beriev Be-200E and Be-200ES-E

SFI SPECIFICATION 35.2 EFFECTIVE: DECEMBER 29, 2014 *

CHAPTER 25. SUBSTANTIVE RULES APPLICABLE TO ELECTRIC SERVICE PROVIDERS.

2014 Model Year Competitive Assistance Program

Louisville Gas and Electric Company

Chain-saws (combustion engine powered)

Diesel Exhaust Fluid Certification Program Overview FEBRUARY 2009 REVISION 01

Medium Voltage Drives. ABB Value Provider Program Partnership for growth and profit

(2) Scope. 220 CMR applies to all Distribution Companies subject to the jurisdiction of the Department.

SFI SPECIFICATION 34.1 EFFECTIVE: January 13, 2017*

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

MEMORANDUM OF UNDERSTANDING Between Colorado, Idaho, Montana, Nevada, New Mexico, Utah and Wyoming Regional Electric Vehicle Plan for the West

E/ECE/324/Rev.1/Add.78/Rev.2/Amend.3 E/ECE/TRANS/505/Rev.1/Add.78/Rev.2/Amend.3

Tillers Motor hoes (combustion engine powered)

Principle Decision by the Central Experience Exchange Circle of the Notified Bodies and the GS Bodies according to the Product Safety Act ZEK

ENERGY STAR Program Requirements for Single Voltage External Ac-Dc and Ac-Ac Power Supplies. Eligibility Criteria.

Net Metering Program

Abu Dhabi Conformity Assessment Scheme for Electric Vehicle Supply Equipment

Overview of ISO 9001 and ISO 14001

RSPO Supply Chain Certification Standard

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

ANNEX 9 RESOLUTION MEPC.258(67) Adopted on 17 October 2014

Rider 11 Partial Requirements Service (PRS)

D.P.U A Appendix B 220 CMR: DEPARTMENT OF PUBLIC UTILITIES

Schedule SP SOLAR PURCHASE (Experimental)

Instructions for Completing Oncor s Interconnection Application For Solar PV Projects

To complete the process for a net metering interconnection, please follow the steps below:

GRUNDFOS DATA BOOKLET. Fire NKF. Grundfos fire systems. Fire pump sets with electrically and diesel-powered pumps according to DBI 251/CEA4001

SFI SPECIFICATION 39.2 EFFECTIVE: August 25, 2017 *

PUBLIC SERVICE COMMISSION OF WEST VIRGINIA

Ride-on lawnmowers (combustion engine powered)

SCHEDULE NO. ACG33 NET METERING SERVICE

Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System

February 2017 FTA COMPLIANCE REVIEW MAPLE GROVE TRANSIT PROGRAM EVALUATION AND AUDIT

PROCEDURE Commissioning and Decommissioning of Fleet Vehicles and Parts. Number: G 2104 Date Published: 8 August 2013

NEW HAMPSHIRE ELECTRIC COOPERATIVE S (NHEC) ABOVE THE CAP NET METERING INTERCONNECTION APPLICATION INFORMATION

Solar Photovoltaic (PV) Installation - Updates

Buying and processing Sustainable Palm Oil

EXECUTIVE ORDER D Relating to Exemptions under Section and 38391

HydroGenerations PROGRAM HANDBOOK

SFI SPECIFICATION 7.2 EFFECTIVE: DECEMBER 15, 2006 *

the importance of its role in local economic business operations that these business operations pursuant

NON-ROAD DIESEL ENGINE EMISSION REGULATION BYLAW CONSOLIDATED

DEPARTMENT OF TRANSPORTATION. National Highway Traffic Safety Administration. [Docket No. NHTSA ; Notice 2]

Learning Legacy Document

Wolverhampton City Council

RSPO Standard for Group Certification. Final approved July 2010

Standards Are Fit For Use Standard must be free of leaks, dents and seals must be intact

2.0 Reference: None. Explain the cost/benefit of the privatization for BC Hydro and for the BC Hydro customer. RESPONSE:

New Ulm Public Utilities. Interconnection Process and Requirements For Qualifying Facilities (0-40 kw) New Ulm Public Utilities

57. Line Extensions Policy 1: Individual Residential Customers

Columbia Water & Light Interconnection & Net Metering Agreement Electrical Facility

New Hampshire Electric Cooperative (NHEC) Introduction to Net Metering

Electric Vehicle Charging Station Incentives PROGRAM HANDBOOK

Capacity Market Rules for Energy Storage Resources

SFI SPECIFICATION 27.1 EFFECTIVE: OCTOBER 11, 2006 *

MEMBER RELATIONS POLICY NO SUBJECT: INTERCONNECTION OF CUSTOMER GENERATION RESOURCES

Definitions. Scope. Customer Generation Interconnection Requirements

AS/NZS 1927:1998 AS/NZS

THE CORPORATON OF THE TOWN OF MIDLAND VEHICLE TOWING AND POUND SERVICES 2018/2019 TENDER L

INDUSTRIAL HAUL AGREEMENT

APPLICATION FOR PRODUCT / ECO-LABELLING CERTIFICATION. GPS Coordinates. GPS Coordinates. Fax No. H/P No.

AS Electric Fire Pumpset Check List Please answer YES or No as appropriate. (if the answer is "NOT SURE" then answer "NO!

Every Disclosure Document issued by a Franchisor Member pursuant to the Code shall comply with the following requirements: -

RSPO Standard for Group Certification [4 th Draft For Executive Board review]

Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT. Skylight. VELUX America LLC

MENARD ELECTRIC COOPERATIVE POLICY MANUAL. SECTION IV Operating Rules for Cooperative Members

Not to be distributed outside of FM Approvals and its affiliates except by Customer

HOUGHTON COUNTY ROAD COMMISSION GUIDELINES FOR THE MOVEMENT OF OVERSIZE OR OVERWEIGHT VEHICLES AND LOADS

Accessories for Wind Power Inverter WINDY BOY PROTECTION BOX 400 / 500 / 600

Construction and Connection of Street Light Assets

SAVIK ERG Owner s Guide

SFI SPECIFICATION 15.4 EFFECTIVE: JULY 20, 2010 * PRODUCT: Top Fuel and Funny Car Drag Race Drive Beadlock Wheels

Transcription:

Philosophy The performance and long term reliability of a fire pump is directly related to proper assembly and installation of the fire pump package components. For this reason FM Approvals requires that the assembly and installation of a complete fire pump package is the responsibility of the fire pump manufacturer. Only fire pumps that comply with all of the requirements defined in this document, the appropriate FM Approvals fire pump standards, and supplied as part of a complete pump package are FM Approved. Pump packages can only be supplied by one of the following entities, fully described in the sections below: Manufacturer Alternate Manufacturing Location Packager Manufacturer The manufacturer of the FM Approved fire pump, is also referred to as the Original Equipment Manufacturer (OEM) of the fire pump. 1. FM Approvals and the Manufacturer have jointly signed a Master Agreement for Approval Services, which defines the contractual relationship between the two entities. 2. The Manufacturer owns the FM Approvals certification of the fire pump as listed in the FM Approval Guide. This responsibility includes control for: design, component sourcing, manufacturing, certification testing, production testing, quality control, and assembly locations. 3. The Manufacturer must be capable of performing a flow test to the full flow capability of the pump including the pump maximum required power point. 4. The Manufacturer shall be able to provide the necessary pump accessories (See Appendix D of any FM Approvals

Standard) to supply a complete pump package. 5. The Manufacturer shall be accountable for the complete pump package (as detailed above and in Appendix D) and satisfactory performance of the Field Acceptance Test (i.e., commissioning) for fire pumps which they manufacture bearing the FM Approvals Certification Mark. This accountability includes proper operation and sizing of the fire pump and accessories listed in Appendix D. 6. The Manufacturer shall not sell or release an unpackaged ( bare shaft ) FM Approved fire pump unless it is for replacement purposes. The Manufacturer shall maintain design/documentation control, and manufacture FM Approved s only at the location(s) audited by FM Approvals and as specified in the FM Approval Report. Audits are conducted at a quarterly frequency for all locations producing FM Approved fire pumps in accordance with FM Approvals Surveillance Audit program. All FM Approved fire pumps shall have a permanently-marked, legible, corrosion-resistant nameplate securely attached to the pump or bedplate where it shall be easily visible. The nameplate shall include the following information: Manufacturer s name and address Country of Manufacture (if different than above) Model or type designation Rated capacity Rated total head Rated speed Maximum power required Impeller diameter(s) Number of stages Pump serial number Manufacturer and serial number of the driver Manufacturer and serial number of the controller FM Approval s Certification Mark The above required markings may be provided on two nameplates, at the discretion of the manufacturer. Page 2 of 5

Alternate Manufacturing Location A location that manufactures a complete pump to the design requirements of the Manufacturer (OEM) or modifies (i.e. trimming of a pump impeller) an OEM supplied fire pump. The Alternate Manufacturing Location may be an alternate facility owned and operated by the OEM or a facility owned by others that performs the complete, or partial, manufacturing of the complete fire pump and/or package under direct control of the OEM. 1. The Alternate Manufacturing Location must be capable of performing a flow test to the full flow capability of the pump including the pump maximum required power point. 2. The Alternate Manufactuing Location must conduct performance testing and supply certified pump curves for pumps modified or assembled by the Alternate Manufacturing Location. 3. The Alternate Manufacturing Location is responsible for the assembly of the complete fire pump using documents and instructions provided by the OEM. 4. The Alternate Manufacturing Location shall be able to provide the necessary pump accessories (See Appendix D of any FM Approvals Fire Pump Standard) to supply a complete pump package. 5. The Alternate Manufacturing Location shall not sell or release an unpackaged ( bare shaft ) FM Approved fire pump unless it is for replacement purposes. Identical auditing requirements to those discussed above under Manufacturer, apply to alternate manufacturing locations with the exception of design / documentation control (which are the sole responsibilities of the OEM). The OEM is responsible to rectify any non-conformances discovered at the Alternate Manufacturing Location to the satisfaction of FM Approvals. All of the required markings shown under the Manufacturer section are required. If the alternate manufacturing location is in a different country than the OEM, the additional requirement Assembled in xxxx (where xxxx is the country of final trimming or assembly) is also required. Page 3 of 5

Packager The Manufacturer can delegate, through a legal agreement, the function of assembling the fire pump package to a third party known as the fire pump packager. Alternatively or in addition to, a Packager may package or just distribute complete private labeled fire pump packages. The Packager may be a facility owned and operated by the Fire Pump Manufacturer or a facility owned by others that performs the assembly of the complete fire pump package under direct control of the OEM. Only Packagers recognized and audited by FM Approvals can undertake the assembly of, or distribute private labeled, fire pump packages utilizing FM Approved Pumps. 1. At a minimum, the Packager will receive a fully tested FM Approved bare-shaft pump, along with the performance curve, from the OEM. 2. The Packager shall assemble the complete fire pump package to the specifications supplied by the OEM. 3. The Packager is not allowed to trim impeller or otherwise modify the fire pump. 4. The responsibilities for Manufacturers to supply a complete pump package (as detailed above and in Appendix D) and ensure satisfactory performance of the Field Acceptance Test (i.e., commissioning) may be, at the OEMs discretion, delegated to a Fire Pump Packager. This delegation does not relieve the Manufacturer of their accountability and responsibility for the satisfactory performance of the complete fire pump package (as detailed in Appendix D). 5. The fire pumps being packaged by the Packager are listed in the FM Approval Guide, an online resource of FM Approvals, under the name of the Manufacturer or Private Labeler (if applicable). 6. The Packager shall not sell or release an FM Approved bare-shafted fire pump. Page 4 of 5

The Packager shall package or distribute pump packages only at location(s) audited by FM Approvals and as specified in the FM Approval Report. Audits are at a quarterly frequency for all locations packaging FM Approved fire pumps in accordance with FM Approvals Surveillance Audit program. The OEM is responsible to rectify any non-conformances discovered at the Packager facility to the satisfaction of FM Approvals. All of the required markings shown under Manufacturer are required. If the packaging location or private labeler address is a different country than the Manufacturer location, the additional requirement Assembled in xxxx (where xxxx is the country of assembly) is also required. Private Labeler A company, other than the Manufacturer (OEM), that has a legal agreement with the OEM whereby the pump is manufactured and labeled by the OEM in the name of the Private Labeler. In order to enter into a Private Label agreement, a Private Labeler must be one of the following entities: a Manufacturer a Alternate Manufacturer a Packager See the responsibilities of the specific entity referenced above. See the auditing requirements of the specific entity referenced above. See the marking requirements of the specific entity referenced above. Page 5 of 5