Modular Metering Stock Selection Guide. Meter Mod * III and Mini Mod * III Product Families

Similar documents
Modular Metering Application Guide

Modular Metering Application Guide. Meter Mod * III Product Family

Modular Metering Construction Details

Tenant Main Circuit Breakers. for GE Meter Mod * III Modular Metering

Modular Metering. Canadian Version

Modular Metering Section 2

MP Meter-Pak Meter Centers Product Description PRODUCT DESCRIPTION. MP Meter-Pak Meter Centers

MP Meter-Pak Meter Centers Product Description PRODUCT DESCRIPTION. MP Meter-Pak Meter Centers

Equipment. Metering. Metering Equipment 1. Contents

Equipment. Metering. Metering Equipment 1. Contents

MP Meter-Pak Meter Centers

Meter Centers & Loadcenters Group Metering

5.11. Metering Products 3 MTB 400 R C. Group Metering. Catalog Number Selection

New York City Apartment Metering Meter Sockets / Load Centers

Power Mod. Introduction.

5.11. Metering Products. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents

Single Socket and Horizontal Metering

1 Installation of accessories in molded case switches requires dummy trip; see page. Breaker/Switch Type TQD/TJD

Introduction. Upon completion of Basics of Meter Mounting Equipment

Loadcenters and Circuit Breakers. Contents. Overview. Three-phase, four-wire, 208Y/120 Vac Three-phase, three-wire, 240 Vac delta

Accessories. Accessories. Meter Mounting Equipment

THQL1120AF2 THQL1120AF2 Arc Fault BRKR

Single Socket and Horizontal Metering

Single Socket and Horizontal Metering

10 Commercial, Industrial, Agricultural Services

GE Energy. GE Panelboards. The right panelboard for any application. imagination at work

Metering Products. 4.1 Meter Sockets. 4.2 Meter Breakers. 4.3 Group Metering

1 Installation of accessories in molded case switches requires dummy trip; see page. Breaker/Switch Type TQD/TJD

POWER PRODUCT Meter Centres Contents

Safety Switches Section 4 Accessories: NEMA Type 1 and 3R Enclosures

4.10. Metering Products. Contents Description Systems for Residential and Commercial. Main Service Modules. Group Metering

Small Project Product Selection Guide

For Options, Modifications and Accessories, see pages Discount Schedule A6

Laser Service Factory-assembled Panelboards

Section 1. Load Centers and Circuit Breakers. Section Updated 11 / 2014

Power Mod. Type WC House Power Module. Revised 06/01/13. WC Series House Power Module

Group Meter Main - Without Bypass

1.2. Loadcenters and Circuit Breakers. Contents. Overview. Type BR Loadcenters and Circuit Breakers. Product Selection Guide.

5.2. Power Pedestals. Contents Description

Meter Mounting Equipment Wisconsin Area

New England. Area Catalog. Milbank Manufacturing 4801 Deramus Ave., Kansas City, MO milbankworks.com

Typical AD Panelboard

5.11. Metering Products. Contents Description Systems for Residential and Commercial


Contents. Power Outlet. Don t Give Up! If you don t find the product you want in this catalog, try the Flex Center at

REC Municipal Meter Mounting Equipment

Contents. Volume 1 Residential and Light Commercial CA E December

Technical catalog February 2017 Low Voltage Switchboards and Panelboards UL/CSA

SAFETY SOCKET BOX. Note 8 3" MIN. 3" Max. (200 A)

Typical ADP Panelboard

Typical AE Panelboard

Typical AQ/AL Panelboard

AMENDMENT ELECTRIC SERVICE MANUAL 2014

6.2. Power Pedestals. Contents

SERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

Evolution Series Switchboards

PowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ)

Typical AE Panelboard

Typical AEP Panelboard

Midwest Electric Products. Safety Switches Rugged, reliable and easy to install

Metering NEED. Meter Sockets. Product Description

4.5. Switchboards. Contents Description Instant Service Switchboards Product Selection...

FACTORY SEALED CIRCUIT BREAKER PANELBOARDS

Indianapolis Power & Light Company

Wisconsin Area Catalog

Section 6 Electric Metering: Residential

Indiana Meter Mounting Equipment

D2LC Series. Circuit Breaker Panelboards for Harsh and Hazardous Environments

GE Energy Industrial Solutions. EV Charging Station. Application Guide. imagination at work

GE Industrial Solutions. EntellEon * Low-Voltage Power Panel. Simple. Responsive. Revolutionary.

MEG Approval Meter Equipment Group

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

GE Consumer & Industrial

CT Metering. CT Metering. Meter Mounting Equipment

Approved Contractor Construction e-guide Residential Commercial

PANELBOARDS SECTION 1

Duke/MEG Approval Meter Equipment Group


Application guide. Tmax Link OEM UL 891 Switchboard Program

T H QL Recommendations based on standard conditions. Installation must conform to all local and national codes.

fastfax Rock Solid TM Load Centers General Information

American Electric Supply, Inc.

Design Standard. Purpose: Design Standard:

EZ Meter-Pak Meter Centers

Lighting Panelboards. P2 Panelboards

10. METERING General Requirements

T H QL Recommendations based on standard conditions. Installation must conform to all local and national codes.

Power Mod. Type WMM Residential Meter Stacks. Revised 06/01/13. Residential Meter Stacks

Selection and application guide

SECTION VII METERING INSTALLATIONS

Proline Panelboard and breakers

SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS

Meter Centers Meter Mounting Devices

XP Series Pre-Wired Factory Sealed Circuit Breaker Panelboards Explosionproof, Dust-Ignitionproof System

Selection and Application Guide For use in Alabama, Georgia, Mississippi and the Florida Panhandle. meter mounting

Standard switch modules (type WS) are designed for flexibility, space savings, & durability.

Recreational Vehicle Park Electrical Products & Accessories

Introduction. P1 Panelboards. P1 Feature Overview. Contents. Siemens Panelboards Introduction to P1 Panelboards 1. General Specifications 3

Eylander Electric Inc

Transcription:

Modular Metering Stock Selection Guide Meter Mod * III and Mini Mod * III Product Families

Table of Contents Page No. Nomenclature 3 Main Breaker Module, Single-Phase, 3 Wire, 0/40 Vac 4 Main Breaker Module, Single-Phase, 3 Wire, 0/40 Vac with Arc Reduction Means 4 Main Breaker Module, Three-Phase, 4 Wire, 08Y/0 Vac or Three-Phase, 4 Wire, 0/40V Delta Hi-Leg 5 Main Breaker Module, Three-Phase, 4 Wire, 08Y/0 Vac or Three-Phase, 4 Wire, 0/40V Delta Hi-Leg with Arc Reduction Means 5 Main Breaker Module Accessories: Alternate Rating Plugs and Shunt Trips 6 Main Fusible Switch Module, Single-Phase, 3 Wire 0/40 Vac 7 Main Fusible Switch Module, Three-Phase, 4 Wire 08Y/0 Vac 7 Main Fusible Switch Modules - Fuses and Compression Lugs 8 Main Lug Module Single-Phase, 3 Wire 0/40 Vac 9 Main Lug Module Three-Phase, 4 Wire 08Y/0 Vac 9 Meter Stack Modules, Residential, Single-Phase, 800 Amp Horizontal Bussing, 5 & 00A Sockets 0 Meter Stack Modules, Residential, Single-Phase, 800 Amp Horizontal Bussing, 5 & 00A Sockets - MEG Approved Meter Stack Modules, Residential, Single-Phase, 00 Amp Horizontal Bussing, 5 & 00A Sockets Meter Stack Modules, Residential, Single-Phase, 00 Amp Horizontal Bussing, 5 & 00A Sockets - MEG Approved Tenant Main Breakers for PH Residential Meter Modules (800A & 00A Horizontal Bussing) 3 Meter Mod III - Residential Meter Stacks - Field Installed Accessories 4 Meter Stack Modules, Commercial, Single-Phase, 5A/400A Ringless Sockets w/lever Bypass 5 Tenant Main Breakers for PH Commercial Meter Stack Modules (00A Horizontal Bussing) 6 Meter Stack Modules, Commercial, Three-Phase, 5A/400A Ringless Sockets w/ Lever Bypass 7 Tenant Main Breakers for 3PH Commercial Meter Stack Modules (00A Horizontal Bussing) 8 Meter Mod III - Commercial Meter Stacks - Field Installed Accessories 9 Mini Mod III Ring -Type and Ringless 9 Mini Mod III Ring -Type and Ringless - MEG Approved 5A & 00A Sockets 0 Tenant Main Breakers for Mini Mod Product Family Mini Mod III Field Installed Accessories Other Publications and References 4

Mini Mod III Nomenclature T MM 6 6 0 R F GE Identification Type MM = Mini Mod Ring Type MMR = Mini Mod Ringless Socket Rating Horizontal Bus Rating = 5A = 00A 0 = 00A 4 = 400A 6 = 600A Socket Positions -6 Additional Features F = MEG Approved Enclosures R = Type 3R Rainproof Meter Mod III - Main Nomenclature T MP 3 SB 8 R AR GE Identification Type MP = Meter Mod III Insert for 3-Phase Type SB = Main Breaker, Top/Bottom Feed (400-00A) SHB = Main Breaker, High Interrupting, Top/Bottom Feed (400-00A) BB = Main Breaker, Bottom Feed (400-000A) BT = Main Breaker, Top Feed (400-000A) BU = Main Breaker with Integral Pull Box - EUSERC FT = Main Switch, Top Feed FB = Main Switch, Bottom Feed L = Main Lug U = Main Pull Box Additional Features AR = Arc Reduction CRIS = Copper, Riser Enclosures R = Type 3R Rainproof CLL = Compression Lug Landing Kit Included ST = Shunt Trip, Factory Installed Maximum Ampere Rating 4 = 400A 6 = 600A 8 = 800A 0 = 000A = 00A 4 = 400A 6 = 600A 0 = 000A Meter Stack Nomenclature GE Identification Type MP = Meter Mod Ring Type MPR = Meter Mod Ringless MPK = Meter Mod K-Base Socket Insert for 3-Phase Horizontal Bus Rating 8 = 800A = 00A T MP 3 8 6 0 T R F Socket Rating = 5A 0 = 00A = 5A 40 = 400A Socket Positions -6 Special MEG Approved Enclosures R = Type 3R Rainproof Insert for Tenant Breakers 3

Main Breaker Module, Single-Phase, 3 Wire 0/40 Vac Breaker included. 80% Rated MCB Single-phase mains have a neutral, A-phase, B-phase and ground and may be connected to three-phase horizontal bus stacks. However, output is only single-phase. All mains are required to be center feed only when main breaker is greater than horizontal bus amps Catalog Number Main Ampere Rating IC Rating Max kaic TMPSB4R 65 400 TMPSHB4R 00 TMPSB6R 65 600 TMPSHB6R 00 Feed Location 0-40Vac Shunt Trip Main Breaker Frame Bottom No SGH400 Bottom No SGH600 AWG/kcmil Cu/Al - Phase Al: () /0-500 or () 6-600 Cu: /0-400 or () 6-600 Al: () /0-500 or () 6-600 Cu: /0-400 or () 6-600 AWG/kcmil Cu/Al - Neutral () -600 () -600 TMPSB8R 800 65 Bottom No SKH800 Al/Cu (3) 3/0-500 (4) 50-500 TMPSB0R 000 65 Bottom No SKH00 Al: (4) 50-500 Cu: (4) 50/350 (4) 50-500 TMPSBR 4 00 65 Bottom No SKH00 Al: (4) 50-500 Cu: (4) 50/350 (4) 50-500 TMPBB4R 3 Bottom RG (4) 500-000 kcmil (4) 50-500 400 00 No TMPBT4R 3 Top RG (4) 500-000 kcmil Al/Cu (4) 500-000 TMPBB6R 3 Bottom TMPBB6RST 3 Bottom Yes 600 00 TMPBT6R 3 Top No TMPBT6RST 3 Top Yes TMPBT0R 3 000 00 TMPBB0R 3 Top Bottom No RG Al/Cu (4) 500-000 kcmil Al/Cu (4) 500-000 No RG (6) # 600 kcmil (6) # 600 kcmil Optional lug TCAL4 field installed wire range (3) 300-750 kcmil. Optional neutral lug field installed wire range (3) /0-750 kcmil. Lug kit part number TMPL750. 3 Fixed Rating Plug not Field adjustable. 4 To meet NEC 04 Arc Energy Reduction (Section 40.87), please use a 75A rating plug. Product number SPRK00A75, order separately Main Breaker Module, Single-Phase, 3 Wire 0/40 Vac with Arc Reduction Means Breaker included. 80% Rated MCB Single-phase mains have a neutral, A-phase, B-phase and ground and may be connected to three-phase horizontal bus stacks. However, output is only single-phase. All mains are required to be center feed only when main breaker is greater than horizontal bus amps The main breaker in this section has an arc reduction means that satisfies the requirement of NEC 04 Section 40.87 Amperage Phase IC Rating Max kaic Feed Catalog Number Description AWG/kcmil Cu/Al - Phase AWG/kcmil Cu/Al - Neutral 400A to Less Than 00A Top or Bottom Use Standard Part #. Code effects only 00A and greater 00A Top or Bottom Use 400 or 600A and advise GE sales rep to make trip unit 00A 400A 00 Bottom TMPBB4RAR 400A Ph Main Breaker Bottom Feed - Arc Reduction (4) 500-000 (4) 50-500 600A 00 Bottom Top TMPBB6RAR TMPBT6RAR 400A Ph Main Breaker Bottom Feed - Arc Reduction 600A Ph Main Breaker Top Feed - Arc Reduction (4) 500-000 (4) 500-000 000A 00 Bottom TMPBB0RAR 000A Ph Main Breaker Bottom Feed - Arc Reduction (6) #-600 (6) #-600 NOTE: These main sections use type RG Breakers. These breakers no longer have rating plugs but have factory installed trip units. If you need a trip setting that is different than the frame, please your GE sales rep at time of order entry and they will work with the factory to manually change this. For example, if you want a TMP3BB6RAR (600A frame) with 00A trip. 4

Main Breaker Module, Three-Phase, 4 Wire 08Y/0 Vac or Three-Phase, 4 Wire, 0/40V Delta Hi-Leg Breaker included. 80% Rated MCB. All mains are required to be center feed only when main breaker is greater than horizontal bus amps Catalog Number TMP3SB4R Main Ampere Rating IC Rating Max kaic 65 Feed Location 0-40 Vac Shunt Trip Main Breaker Frame AWG/ kcmil Cu/Al -Phase Al: () /0-500 or () 6-600 Cu: /0-400 or () 6-600 AWG/kcmil Cu/Al - Neutral 400 Bottom No SGH400 () -600 TMP3SHB4R 00 TMP3SB6R 65 Al: () /0-500 or () 6-600 600 Bottom No SGH600 () -600 TMP3SHB6R 00 Cu: /0-400 or () 6-600 TMP3SB8R 800 65 Bottom No SGH800 Al/Cu (3) 3/0-500 (4) 50-500 TMP3SB0R 000 65 Bottom No SGH00 Al: (4) 50-500 Cu: (4) 50/350 (4) 50-500 TMP3SBR 4 00 65 Bottom No SKH00 Al: (4) 50-500 Cu: (4) 50/350 (4) 50-500 TMP3BB4R 3 Bottom 400 00 TMP3BT4R 3 Top No RG (4) 500-000 kcmil (4) 500-000 TMP3BB6R 3 No RG Al/Cu (4) 500-000 Al/Cu (4) 500-000 TMP3BB6RCLL 3 Bottom No RG Compression Lugs Compression Lugs TMP3BB6RST 3 600 00 Yes TMP3BT6R 3 No RG Al/Cu (4) 500-000 Al/Cu (4) 500-000 Top TMP3BT6RST 3 Yes TMP3BT0R 3 Top TMP3BB0R 3 Bottom No RG (6) # 600 kcmil (6) # 600 kcmil TMP3BB0RCLL 3 000 00 Bottom RG Compression Lugs Compression Lugs TMP3BT0RST 3 Top TMP3BB0RST 3 Bottom Yes RG (6) # 600 kcmil (6) # 600 kcmil Optional lug TCAL4 field installed wire range (3) 300-750 kcmil. Optional neutral lug field installed wire range (3) /0-750 kcmil. Lug kit part number TMPL750. 3 Fixed Rating Plug not Field adjustable. 4 To meet NEC 04 Arc Energy Reduction (Section 40.87), please use a 75A rating plug. Product number SPRK00A75, order separately Main Breaker Module, Three-Phase, 4 Wire 08Y/0 Vac or Three-Phase, 4 Wire, 0/40V Delta Hi-Leg with Arc Reduction Means Breaker included. 80% Rated MCB. All mains are required to be center feed only when main breaker is greater than horizontal bus amps The main breaker in this section has an arc reduction means that satisfies the requirement of NEC 04 Section 40.87 Amperage 400A to Less Than 00A Phase 3 00A 3 IC Rating Max kaic 400A 3 00 600A 3 00 000A 3 00 Feed Catalog Number Description Top or Bottom Top or Bottom Bottom Top Bottom Top Top Bottom Use Standard Part #. Code effects only 00A and greater Use 400 or 600A and advise GE sales rep to make trip unit 00A TMP3BB4RAR TMP3BT4RAR TMP3BB6RAR TMP3BT6RAR TMP3BT0RAR TMP3BB0RAR 400A 3Ph Main Breaker Bottom Feed - Arc Reduction 400A 3Ph Main Breaker Top Feed - Arc Reduction 600A 3Ph Main Breaker Bottom Feed - Arc Reduction 600A 3Ph Main Breaker Top Feed - Arc Reduction 000A 3Ph Main Breaker Top Feed - Arc Reduction 000A 3Ph Main Breaker Bottom Reed - Arc Reduction AWG/kcmil CU/AL - Phase AWG/kcmil CU/AL - Neutral (4) 500-000 (4) 500-000 (4) 500-000 (4) 500-000 (6) #-600 (6) #-600 NOTE: These main sections use type RG Breakers. These breakers no longer have rating plugs but have factory installed trip units. If you need a trip setting that is different than the frame, please contact your GE sales rep at time of order entry and they will work with the factory to manually change this. For example, if you want a TMP3BB6RAR (600A frame) with 00A trip 5

Main Breaker Module Accessories Main Breaker Modules Alternate Rating Plugs Field installed Breaker Frame Rating () Trip Rating () Rating Plug Part No. 5 SRPG400A5 400A 50 SRPG400A50 300 SRPG400A300 350 SRPG400A350 50 SRPG600A50 300 SRPG600A300 600A 350 SRPG600A350 400 SRPG600A400 450 SRPG600A450 500 SRPG600A500 300 SRPK800A300 400 SRPK800A400 800A 500 SRPK800A500 600 SRPK800A600 700 SRPK800A700 600 SRPK00A600 700 SRPK00A700 00A 800 SRPK00A800 900 SRPK00A900 000 SRPK00A000 75 SRPK00A75 Shunt Trip Field Installed For use on all Main Breaker Modules Shunt Trip Catalog Number 0 Vac SAST 40 Vac SAST 6

Main Fusible Switch Module, Single-Phase, 3 Wire 0/40 Vac Single-phase mains have a neutral, A-phase, B-phase group and may be connected to three-phase horizontal bus stacks. However, output is only single-phase All mains are required to be center feed only when the main fusible switch rating is greater than the horizontal bus amperage rating Catalog Number Main Ampere Rating TMPFT4R 400 IC Rating (Max) kaic Wire Entry AWG/kcmil Cu/Al -Phase () /0-750 or () /0-300 AWG/kcmil Cu/Al - Neutral () /0-750 or () /0-300 TMPFT6R 600 () -600 () -600 TMPFT8R 800 00 Top (4) 3/0-750 (4) 3/0-750 TMPFTR TMPFTRST 5 00 (4) -500 (4) -500 () /0-750 or () /0-750 or TMPFB4R 400 () /0-300 () /0-300 00 Bottom TMPFB6R 600 () -600 () -600 TMPFB8R 800 (4) 3/0-750 (4) 3/0-750 TMPFBRT 00 00 Bottom (4) -500 (4) -500 Stud Sets per Phase and Neutral Fuse Not Included. Order Separately. Compression Lug Landing Kit Class T only Order Separately Class L only. Bolted Pressure Switch Class T only Order Separately see footnote TMPFBR see footnote TMPFBRST 5 TMPFBRT is a standard fusible switch that uses only Class T fuses. This unit is less robust and smaller than the TMPFBR, but is significantly less expensive. TMPFBR is a bolted pressure switch that uses only Class L fuses. This unit is larger and more robust than the TMPFBRT, but more expensive. Main Fusible Switch Module, Three-Phase, 4 Wire 08Y/0 Vac Fuses not included. All mains are required to be center feed only when the main fusible switch rating is greater than the horizontal bus amperage rating Catalog Number Main Ampere Rating TMP3FT4R 400 IC Rating (Max) kaic Wire Entry AWG/kcmil Cu/Al -Phase () /0-750 or () /0-300 AWG/kcmil Cu/Al - Neutral () /0-750 or () /0-300 TMP3FT6R 600 () -600 () -600 TMP3FT8R 800 (4) 3/0-750 (4) 3/0-750 TMP3FTR TMP3FTRST 5 TMP3FT6R TMP3FT6RST 5 TMP3FT0R TMP3FT0RST 5 TMP3FB4R 400 00 00 Top (4) 4-600 (4) 4-600 600 (6) 4-600 (6) 4-600 000 (8) 4-600 (8) 4-600 () /0-750 or () /0-300 () /0-750 or () /0-300 TMP3FB6R 600 () -600 () -600 TMP3FB8R 800 (4) 3/0-750 (4) 3/0-750 Stud Sets per Phase and Neutral Fuse Not Included. Order Separately. Class T only Class L only. Bolted Pressure Switch Class T only TMP3FBR 4 00 (4) 4-600 (4) 4-600 See footnote 4 TMP3FBRT 3 00 00 Bottom (4) -600 (4) -600 See footnote 3 TMP3FBRST 5 00 (4) 4-600 (4) 4-600 TMP3FB6R 600 (6) 4-600 (6) 4-600 TMP3FB6RST 5 600 (6) 4-600 (6) 4-600 TMP3FB0R 000 (8) 4-600 (8) 4-600 TMP3FB0RST 5 000 (8) 4-600 (8) 4-600 Class L only. Bolted Pressure Switch Compression Lug Landing Kit TMP3F8CLL Order Separately TMP3F8CLL Order Separately 3 TMP3FBRT is a standard fusible switch that uses only Class T fuses. This unit is less robust and smaller than the TMP3FBR, but is significantly less expensive. 4 TMP3FBR is a bolted pressure switch that uses only Class L fuses. This unit is larger and more robust than the TMP3FBRT, but more expensive. 5 Product numbers ending in ST have shunt tripping style bolted pressure switch. 7

Main Fusible Switch Modules Fuses and Compression Lugs Class T Fuses Rated at 00K @ 40V Class L Fuses Rated at 00K @ 40V Frame Size Ampere Rating Catalog Number 50 TFUSE50 300 TFUSE300 400 50 TFUSE350 400 TFUSE400 500 TFUSE500 600 600 TFUSE600 800 800 TFUSE800 00 00 A3T00 Ampere Rating Catalog Number 600 A4BY600 650 A4BY650 700 A4BY700 750 A4BY750 800 A4BY800 900 A4BY900 000 A4BY000 00 A4BY00 Ampere Rating Catalog Number 00 A4BY00 350 A4BY350 400 A4BY400 500 A4BY500 600 A4BY600 800 A4BY800 000 A4BY000 Compression Lugs The following UL listed crimp connectors may be used Wire size (CU only) Mac T & B Burndy Panduit 50 kcmil 300 kcmil 350 kcmil 400 kcmil 500 kcmil 600 kcmil MSB50-8N MRB50-8N MSB300-8N MRB300-8N MSB350-8N MRB350-8N MSB400-8N MRB400-8N MSB500-8N MRB500-8N MSB600-8N MRB600-8N 5475 54868BE 5480 54870BE 548 5487BE 54874BE 5486 54876BE 5489 54878BE 700 kcmil 549 750 kcmil Wire size (AL/CU) 50 kcmil 300 kcmil 350 kcmil 400 kcmil 500 kcmil 600 kcmil MSB750-8N MRB750-8N MLB50-8N MULB50-8N MLB300-8N MULB300-8N MLB350-8N MULB350-8N MLB400-8N MULB400-8N MLB500-8N MULB500-8N MLB600-8N MULB600-8N 543 54880BE 6056 606 6067 6069 6073 6075 700 kcmil 6077 YA9-LN YA9-LN YA30-LN YA30-LN YA3-LN YA3-LN YA3-LN YA3-LN YA34-LN YA34-LN YA36-LN YA36-LN YA39-LN YA39-LN YA9A3 YA9AY-N YA30A3 YA30AY-N YA3A3 YA3AY-N YA3A3 YA3AY-N YA34A3 YA34AY-N YA36A3 YA36AY-N LCC50- LCC300- LCC350- LCC400- LCC500- LCC750- LAB50- LAB300- LAB350- LAB400- LAB500- LAB600-750 kcmil YA39A5 LAB750- Note: torque / nuts which attach crimp connectors to 45 ft.-lb. (6 N-m) 8

Main Lug Module, Single-Phase, 3 Wire 0/40 Vac Lugs included. Catalog Number Main Ampere Rating Use 3-Phase 400 Use 3-Phase 600 TMPL8R 800 TMPLR 00 IC Rating (Max) kaic 00 Wire Entry Bottom/ Top Mounting End or Center AWG/ kcmil Cu/Al - Phase () /0-750 or (4) /0-300 (3) /0-750 or (6) /0-300 AWG/kcmil Cu/Al - Neutral () /0-750 or (4) /0-300 (3) /0-750 or (6) /0-300 Stud Sets per Phase and Neutral TMPL6R 600 (6) 50-500 (6) 50-500 3 Limited to the lowest marked short circuit rating of the main and meter modules used. 3 Compression Lug Landing Kit Order Separately Main Lug Module, Three-Phase, 4 Wire 08Y/0 Vac Lugs included. Catalog Number TMP3L4R TMP3L4RCU TMP3L6R TMP3L6RCU TMP3L8R TMP3L8RCU Main Ampere Rating 400 IC Rating (Max) kaic 00 Wire Entry Bottom/ Top Mounting End or Center AWG/ kcmil Cu/Al - Phase () 6-600 or () /0-50 AWG/kcmil Cu/Al - Neutral () 6-600 or () /0-50 Stud Sets per Phase and Neutral 600 () 50-500 () 50-500 800 TMP3LR 00 () /0-750 or (4) /0-300 (3) /0-750 or (6) /0-300 () /0-750 or (4) /0-300 (3) /0-750 or (6) /0-300 TMP3L6R 600 (6) 50-500 (6) 50-500 3 TMP3L0R 000 (8) /0-750 (8) /0-750 Limited to the lowest marked short circuit rating of the main and meter modules used. Copper bused. Compression Lug Landing Kit Order Separately Main Lug with Feed Through, Three Phase, 4 Wire / Single Phase, 3 Wire 0/40 Vac, 08Y/0 Vac Catalog Number Main Amperage KAIC Incoming Line Outgoing Load Stud Sets per Phase and Neutral Compression Lug Landing Kit TMP3LRCRIS 00A (5) Up to 750 MCM per Phase/Neutral (AL/CU) (5) Up to 750 MCM per Phase/Neutral (AL/CU) TMP3L6RCRIS 600A 00 TMP3L0RCRIS 000A (8) /0-750 MCM per Phase/Neutral (AL/CU) (8) /0-750 MCM per Phase/Neutral (AL/CU) 9

Meter Stack Modules Residential Single Phase 800A Horizontal Bussing 5 & 00A Sockets 800 amp, 4 Wire Crossbus (Aluminum) UL Listed Front Accessible Field Phase Balancing by Meter Stack () 4-4 Equipment Ground per Socket, Factory Installed Socket 5 00 No. of Sockets Ring Type Socket Catalog Number Ringless Type Socket (4 Jaw Socket Standard) Ringless Type Socket (4 Jaw Socket Standard) Horned Bypass Factory Installed TMP8R TMPR8R TMPR8RHB 3 TMP83R TMPR83R TMPR83RHB 4 TMP84R TMPR84R TMPR84RHB 5 TMP85R TMPR85R TMPR85RHB 6 TMP86R TMP8R6R TMP8R6RHB TMP80R TMPR80R TMPR80RHB 3 TMP830R TMPR830R TMPR830RHB 4 TMP840R TMPR840R TMPR840RHB 5 TMP850R TMPR850R TMPR850RHB 5 TMP850RBUS, TMPR850RBUS TMPR850RHBBUS One snap-type, aluminum sealing ring (TSR5) per socket included BUS suffix indicates change to centerline of horizontal bussing from 8.88" to 4.0" from bottom of unit 800 amp, 4 Wire Cross bus (copper) - CON ED Approved UL Listed Front Accessible Field Phase Balancing by Meter Stack () 4-4 Equipment Ground per Socket, Factory Installed Catalog Number Socket 5 No. of Sockets 3 4 5 Factory Phase Balancing NEMA Indoor Enclosure Ring Type Socket Factory Phase Balanced with Copper Bus NEMA 3R Outdoor Enclosure AB TMP8AB TMP8RAB AC TMP8AC TMP8RAC BC TMP8BC TMP8RBC AB TMP83AB TMP83RAB AC TMP83AC TMP83RAC BC TMP83BC TMP83RBC AB TMP84AB TMP84RAB AC TMP84AC TMP84RAC BC TMP84BC TMP84RBC AB TMP85AB TMP85RAB AC TMP85AC TMP85RAC BC TMP85BC TMP85RBC 0

Meter Stack Modules Residential Single Phase MEG Approved 800A Horizontal Bussing 5 & 00A Sockets 800 amp, 4 Wire Crossbus (Aluminum) UL Listed Front Accessible Field Phase Balancing by Meter Stack () 4-4 Equipment Ground per Socket, Factory Installed Meter Equipment Group Approved These MEG approved units have an added cotter pin that eliminates failure of the metering stabs when the meter is plugged into the meter base. Socket 5 00 No. of Sockets Ring Type Socket Ringless Type Socket (4 Jaw Socket Standard) Ringless Type Socket (4 Jaw Socket Standard) Horned Bypass Factory Installed TMP8RF TMPR8RF TMPR8RHBF 3 TMP83RF TMPR83RF TMPR83RHBF 4 TMP84RF TMPR84RF TMPR84RHBF 5 TMP85RF TMPR85RF 6 TMP86RF TMPR86RF TMPR86RF TMPR80RF 3 TMP830RF TMPR830RF 4 TMP840RF TMPR840RF TMPR840RHBF 5 TMPR850RF One snap-type, aluminum sealing ring (TSR5) per socket included Meter Stack Modules Residential Single Phase 00A Horizontal Bussing 5 & 00A Sockets 00 amp, 4 Wire Crossbus (aluminum) UL Listed Front Accessible Field Phase Balancing by Meter Stack () 4-4 Equipment Ground per Socket, Factory Installed Socket 5 00 No. of Sockets Ring Type Socket Catalog Number Ringless Type Socket (4 Jaw Socket Standard) Ringless Type Socket (4 Jaw Socket Standard) Horned Bypass Factory Installed TMPR TMPRR TMPRRHB 3 TMP3R TMPR3R TMPR3RHB 4 TMP4R TMPR4R TMPR4RHB 5 TMP5R TMPR5R TMPR5RHB 6 TMP6R TMPR6R TMPR6RHB TMP0R TMPR0R TMPR0RHB 3 TMP30R TMPR30R TMPR30RHB 4 TMP40R TMPR40R TMPR40RHB 5 TMP50R TMPR50R TMPR50RHB 5 TMP50R, TMPR50RBUS TMPR50RHBBUS One snap-type, aluminum sealing ring (TSR5) per socket included BUS suffix indicates change to centerline of horizontal bussing from 8.88" to 4.0" from bottom of unit

Meter Stack Modules Residential Single Phase MEG Approved 00A Horizontal Bussing 5 & 00A Sockets 00 amp, 4 Wire Crossbus (Aluminum) UL Listed Front Accessible Field Phase Balancing by Meter Stack () 4-4 Equipment Ground per Socket, Factory Installed Meter Equipment Group Approved Socket 5 00 No. of Sockets Ring Type Socket Ringless Type Socket (4 Jaw Socket Standard) Ringless Type Socket (4 Jaw Socket Standard) Horned Bypass Factory Installed 4 TMPR4RF TMPR4RHBF 5 TMPR5RF TMPR5RHBF 6 TMPR6RF 4 TMP40RF TMPR40RF TMPR40RHBF 5 TMPR50RF One snap-type, aluminum sealing ring (TSR5) per socket included

Tenant Main Breakers for PH Residential Meter Modules (800A & 00A Horizontal Bussing) Tenant Main Breakers for 5A, Pole Sockets 0kAIC kaic Wire Size 60 THQL60 THHQL60 () #8-#3 CU; #8-#3AL 70 THQL70 THHQL70 80 THQL80 THHQL80 90 THQL90 THHQL90 () #6-/0 CU; #4-#/0 AL 00 THQL00 THHQL00 () #-/0 CU; #-/0 AL 0 THQL0 THHQL0 5 THQL5 THHQL5 () #-/0 CU; #-/0 AL 5 TMQL5SSF Sub-Feed lug. No overcurrent protection. Tenant Main Breakers for 5A, Pole Sockets QL 4 kaic 60 TMQL60 Wire Size QA 65 kaic TMQA60 70 TMQL70 TMQA70 80 TMQL80 #8-# (Cu) or TMQA80 90 TMQL90 #8-/0 (Al) TMQA90 00 TMQL00 TMQA00 0 TMQA0 5 TMQL5 /0 - #4 TMQA5 Wire Size #8-/0 Tenant Main Breakers for 00A, Pole Sockets 0kAIC kaic Wire Size 00 TQD00 THQD00 5 TQD5 THQD5 50 TQD50 THQD50 75 TQD75 THQD75 00 TQD00 THQD00 () #-300 CU; #-300 AL Tenant Main Circuit Breakers for 00A, Pole Sockets QC 4 kaic QF 65 kaic QV 00 kaic 60 TMQC060MM TMQF060MM TMQV060MM 70 TMQC070MM TMQF070MM TMQV070MM 80 TMQC080MM TMQF080MM TMQV080MM 90 TMQC090MM TMQF090MM TMQV090MM 00 TMQC00MM TMQF00MM TMQV00MM 0 TMQC0MM TMQF0MM TMQV0MM 5 TMQC5MM TMQF5MM TMQV5MM 50 TMQC50MM TMQF50MM TMQV50MM 75 TMQC75MM TMQF75MM TMQV75MM 00 TMQC00MM TMQF00MM TMQV00MM For 60A-00A P breakers use TMQV5L to get 300MCM terminals. Wire Size #6-4/0 3

Meter Mod III Residential Meter Stacks Field Installed Accessories Steel Meter Socket Covers Fifth Jaw Kits Description Catalog No. Description Catalog No. Blank (fits bottom position only) Ringless (Field -converts ring-type to ringless) 5 Amp TMCBB 00 Amp TMCB0B 5 amp top socket for and 3 gang TMCRT 5 amp for all other sockets TMCR 00 amp for all sockets TMCR0 Bused; 3, 6, or 9 o'clock mounting Order two for fifth and sixth jaw. Not suitable for -gang ring type Isolated; 3 or 9 o'clock mounting TM5JA TM5JUA By-pass Kits Sealing Rings Description Manual Slider-Type (Ring Type Only) Catalog No. 5 amp top socket for, 3, 5 and 6 gang TMBPMTA 5 amp for all other sockets TMBPMA 00 amp for all sockets TMBPM0A Jumper Straps Type (use with TMCA) TMBPJ0 3 Description Material Catalog No. Screw Type Aluminum TSR Snap Type Stainless Steel TSR3 Screw and Lock Type Aluminum TSR4 Snap Type Aluminum (Standard) TSR5 Cover Includes Jumper Strap Type-fits all (Ring Type Only) TMBPC0 Horn-Type-fits all (Ringless Only) TMBPH0A 3 Miscellaneous Description Lexan Meter socket Cover Plate (without tabs) Lexan Meter Socket Cover Plate Equipment Ground Bar, (6) 6-/0 Individual Meter Socket Barrier Kit (includes 6) Mounting Z-Rail, 4-foot Spacer, 4-inch, 4 cross bus rated 00A Catalog No. TMCA TMCP TMEG TMBR TMZR TMPS Elbow, 6-inch x 6-inch, 4 cross bus rated 00A TMPE 4 Elbow, -inch x -inch, 4 cross bus rated 00A TMPEA 4 Anti-Inversion Clip Endwall Endwall TQD Breaker Mounting Kit. This is a replacement part. Units come with this part factory installed. Not UL Listed. 00 amps continuous. 3 00 amps continuous. 4 Indoor Type. TMIC TM34BEW00 TM56BEW00 TMTQD3 4

Meter Stack Modules Commercial Single-Phase 5A/400A Ringless Sockets w/ Lever Bypass Single-Phase/3 Wire 0/40 Vac or Three-Phase, 4 Wire, Horizontal Bus, 08Y/0 Vac System Voltage 00 amp, 4 Wire cross bus (aluminum) UL Listed Front Accessible Field Phase Balancing by Meter Socket () 4- Equipment Ground Kit per Socket, Factory Installed Only 5A and 400A Ringless Type Meter Stacks contain Lever Bypass 5A and 00A Meter Sockets do not contain Lever Bypass Ringless Type Socket with Lever Bypass. All units are 7-terminal except TMPK. Socket 5 No. of Sockets Catalog Number TMPRR TMPRR 3 TMPR3R 4 TMPR4R TMPR40RB,3 Factory Installed Fifth Jaw (TM5JA Bused) Included 400 TMPR40RB,3 TMPK40RB TMPK40RBA One 400A tenant main breaker included. Two 400A tenant breakers included. 3 Main Breaker Modules Alternate Rating Plugs table for alternate 400A Rating Plugs 5

Tenant Main Breakers for PH Commercial Meter Stack Modules (00A Horizontal Bussing) Tenant Main Circuit Breakers for 5A, Pole Sockets 0kAIC Wire Size 5 TEB05 0 TEB00 5 TEB05 30 TEB030 35 TEB035 40 TEB040 45 TEB045 50 TEB050 60 TEB060 70 TEB070 80 TEB080 90 TEB090 00 TQD00 5 TQD5 50 TQD50 75 TQD75 00 TQD00 5 Use TMQV () #4-3 CU; #- AL () #6/0 CU; #4-/0 AL () #-300 CU; #-300 AL Tenant Main Circuit Breakers for 5A, Pole Sockets kaic Wire Size 00 THQD00 5 THQD5 50 THQD50 75 THQD75 00 THQD00 5 Use TMQV () #-300 CU; #-300 AL Tenant Main Circuit Breakers for 00A/5A, Pole Sockets QC 4 kaic QF 65 kaic QV 00 kaic 60 TMQC060MM TMQF060MM TMQV060MM 70 TMQC070MM TMQF070MM TMQV070MM 80 TMQC080MM TMQF080MM TMQV080MM 90 TMQC090MM TMQF090MM TMQV090MM 00 TMQC00MM TMQF00MM TMQV00MM 0 TMQC0MM TMQF0MM TMQV0MM 5 TMQC5MM TMQF5MM TMQV5MM 50 TMQC50MM TMQF50MM TMQV50MM 75 TMQC75MM TMQF75MM TMQV75MM 00 TMQC00MM TMQF00MM TMQV00MM 5 TMQC5MM TMQF5MM TMQV5MM For 60A-5A P breakers use TMQV5L to get 300MCM terminals. Wire Size #6-4/0 6

Meter Stack Modules Commercial Three-Phase, 5A/400A Ringless Sockets w/ Lever Bypass Three-Phase / 4 Wire, 40-0 Vac, Three-Phase / 4 Wire 08Y/0Vac 00 amp, 4 Wire cross bus (aluminum) UL Listed Front Accessible Field Phase Balancing by Meter Socket () 4- Equipment Ground Kit per Socket, Factory Installed Swingaway Mounting Feet Factory Installed Only 5A and 400A Ringless Type Meter Sockets contain Lever Bypass 5A and 00A Meter Sockets do not contain Lever Bypass Ringless Type Socket with Lever Bypass. All units are 7-terminal except TMPK. Socket No. of Sockets Catalog Number Factory Installed Seventh Jaw (7 Terminal) TMPR3R 5 TMPR3R 3 TMPR33R 4 TMPR34R Included TMPR340TR TMPR340RB 400 TMPR340RB TMPK340RB TMPK340RBA Shipped from the factory as 7-jaw units (7 terminal.) 400 Amp tenant breaker included, 65 kaic 7

Tenant Main Breakers for 3PH Commercial Meter Stack Modules (00A Horizontal Bussing) Tenant Main Circuit Breakers for 00A/5A, 3 Pole Sockets 0kAIC Wire Size 5 TEB305 0 TEB300 5 TEB305 30 TEB3030 35 TEB3035 40 TEB3040 45 TEB3045 50 TEB3050 60 TEB3060 70 TEB3070 80 TEB3080 90 TEB3090 () #4-3 CU; #- AL () #6/0 CU; #4-/0 AL 00 TEB300 () #3-3/0 CU; #-3/0 AL 5 TQD35 50 TQD350 75 TQD375 00 TQD300 () #-300 CU; #-300 AL 5 Use TMQC Tenant Main Circuit Breakers for 00A/5A, 3 Pole Sockets kaic Wire Size 00 THQD300 5 THQD35 50 THQD350 () #-300 CU; #-300 AL 75 THQD375 00 THQD300 5 Use TMQC Tenant Main Circuit Breakers for 00A/5A, 3 Pole Sockets QC 4 kaic QF 65 kaic QV 00 kaic 60 TMQC3060 TMQF3060 TMQV3060 70 TMQC3070 TMQF3070 TMQV3070 80 TMQC3080 TMQF3080 TMQV3080 90 TMQC3090 TMQF3090 TMQV3090 00 TMQC300 TMQF300 TMQV300 0 TMQC30 TMQF30 TMQV30 5 TMQC35 TMQF35 TMQV35 50 TMQC350 TMQF350 TMQV350 75 TMQC375 TMQF375 TMQV375 00 TMQC300 TMQF300 TMQV300 5 TMQC35 TMQF35 TMQV35 For 60A-5A 3P breakers use TMQV5L3 to get 300MCM terminals. Wire Size #6-4/0 8

Meter Mod III Commercial Meter Stacks Field Installed Accessories Description TEB Breaker Mounting Kit Catalog No. TMTEB Barrel Lock Bracket and Guard Kit TMBL Bypass Kit, Totalizing Jumper Type TMBPT30, Replacement Phase Balancing Jumper Kit TMPJ3 Blank Meter Socket Cover, fits all positions Individual Meter Socket Barrier Kit, includes 6 Insulator for Lever By-Pass Handle Mounting Z Rail, 4-foot Spacer, 4-inch, 4 cross bus rated 00A TMCB3A TMBR3 TMHN TMZR TMPS Elbow, 6-inch x 6-inch, 4 cross bus rated 00A TMPE 3 Elbow, -inch x -inch, 4 cross bus rated 00A TMPEA 3 Not UL Listed. 80 amps continuous. 3 Indoor, Type, for inside corners only. Mini Mod III Ring-Type and Ringless UL Listed (Panelboards No. 67) Indoor/Outdoor construction Ring-Type and Ringless Meter Sockets Bondable Neutral, Strap included -inch Mounting Z Rail included Swing Away Mounting Feet factory installed Underground, incoming feed only Socket No. of Sockets Main Ampere Rating Ring-Type Socket 4 Ring-Type Socket (5 Jaw Socket Standard) Horned Bypass Factory Installed Ringless Type Socket Ringless Type Socket (5 Jaw Socket Standard) Horned Bypass Factory Installed Main Wire Size AWG/kcmil Cu/Al - Phase Service Ground Equipment Ground 00 TMMR 5 TMMRHB 5 TMMRR 5 TMMRRHB 5 () 6-300 6-/0 5 3 400 TMM43R TMM43RHB TMMR43R TMMR43RHB 4 400 TMM44R TMM44RHB TMMR44R TMMR44RHB 5 600 TMM65R TMM65RHB TMMR65R TMMR65RHB 6 600 TMM66R TMM66RHB TMMR66R TMMR66RHB () 6-600 or () /0-50 () 50-500 4-300 4-4 400 TMM40R TMMR40R TMMR40RHB 6-/0 3 600 TMM630R TMM630RHB TMMR630R TMMR630RHB 00 4 600 TMM640R TMM640RHB TMMR640R TMMR640RHB () 50-500 4-300 4-4 5 600 TMM650R TMMR650R TMMR650RHB 6 600 TMM660R TMMR660R TMMR660RHB 4 One snap-type, aluminum sealing ring (TSR5) per socket included 5 May be fed from overhead. Use hub TC300. 9

Mini Mod III Ring-Type and Ringless - MEG Approved 5A & 00A Sockets UL Listed (Panelboards No. 67) Indoor/Outdoor construction Ring-Type and Ringless Meter Sockets Bondable Neutral, Strap included -inch Mounting Z Rail included Swing Away Mounting Feet factory installed Underground, incoming feed only These MEG approved units have an added cotter pin that eliminates failure of the metering stabs when the meter is plugged into the meter base. Socket No. of Sockets Main Ampere Rating Ring-Type Socket Ringless Socket (5th Jaw Socket Standard) AWG/kcmil Cu/Al - Phase Service Ground 00 TMMRF TMMRRF () 6-300 6-/0 Equipment Ground 5 00 3 400 TMM43RF TMMR43RF () 6-600 or 4 400 TMM44RF TMMR44RF () /0-50 5 600 TMM65RF TMMR65RF 6 600 TMM66RF TMMR66RF 400 Use TMM630R TMMR40RF 3 600 TMM630RF TMMR630RF 4 600 TMM640RF TMMR640RF 5 600 Use Ringless or Meter Mod III TMMR650RF 6 600 Use Ringless or Meter Mod III TMMR660RF One snap-type, aluminum sealing ring (TSR5) per socket included. May be fed from overhead. Use hub TC300. () 50-500 () 50-500 4-300 6-/0 4-300 4-4 4-4 0

Tenant Main Breakers for Mini Mod Product Family Tenant Main Breakers for 5A, Pole Sockets 0kAIC kaic Wire Size 60 THQL60 THHQL60 () #8-#3 CU; #8-#3AL 70 THQL70 THHQL70 80 THQL80 THHQL80 () #6-/0 CU; #4-#/0 AL 90 THQL90 THHQL90 00 THQL00 THHQL00 () #-/0 CU; #-/0 AL 0 THQL0 THHQL0 5 THQL5 THHQL5 () #-/0 CU; #-/0 AL 5 TMQL5SSF Sub-Feed lug. No overcurrent protection. Tenant Main Breakers for 5A, Pole Sockets QL 4 kaic 60 TMQL60 Wire Size QA 65 kaic TMQA60 70 TMQL70 TMQA70 80 TMQL80 #8-# (Cu) or TMQA80 90 TMQL90 #8-/0 (Al) TMQA90 00 TMQL00 TMQA00 0 TMQA0 5 TMQL5 /0 - #4 TMQA5 Wire Size #8-/0 Tenant Main Breakers for 00A, Pole Sockets 0kAIC kaic Wire Size 00 TQD00 THQD00 5 TQD5 THQD5 50 TQD50 THQD50 75 TQD75 THQD75 00 TQD00 THQD00 () #-300 CU; #-300 AL Tenant Main Circuit Breakers for 00A, Pole Sockets QC 4 kaic QF 65 kaic QV 00 kaic 60 TMQC060MM TMQF060MM TMQV060MM 70 TMQC070MM TMQF070MM TMQV070MM 80 TMQC080MM TMQF080MM TMQV080MM 90 TMQC090MM TMQF090MM TMQV090MM 00 TMQC00MM TMQF00MM TMQV00MM 0 TMQC0MM TMQF0MM TMQV0MM 5 TMQC5MM TMQF5MM TMQV5MM 50 TMQC50MM TMQF50MM TMQV50MM 75 TMQC75MM TMQF75MM TMQV75MM 00 TMQC00MM TMQF00MM TMQV00MM For 60A-00A P breakers use TMQV5L to get 300MCM terminals. Wire Size #6-4/0

Mini Mod III Field Installed Accessories By-pass Kits Semi-Flush Kits Description Manual Slider-Type (Ring Type Only) Catalog No. 5 amp top socket for, 3, 5 and 6 gang TMBPMTA 5 amp for all other sockets TMBPMA 00 amp for all sockets TMBPM0A Jumper Straps Type (use with TMCA) TMBPJ0 4 Cover Includes Jumper Strap Type-fits all (Ring Type Only) 3 TMBPC0 4 Horn-Type-fits all (Ringless Only) TMBPH0A Description 5A Sockets 00A Sockets Catalog No. gang TMMSF 3 and 4 gang TMMSF4 5 and 6 gang TMMSF6 gang TMM0SF 3 and 4 gang TMM0SF4 5 and 6 gang TMM0SF6 Compression Lug Landing Kit Description Catalog No. 600 amp TMM6CLL Includes 3 pads each with threaded stud connections (and hardware) for compression or mechanical lugs with NEMA -hole bolt configuration (lugs not furnished). Not suitable for -gang. Fifth Jaw Kits Description Bussed; 3, 6, or 9 o'clock mounting Order two for fifth and sixth jaw. Not suitable for -gang ring type Isolated; 3 or 9 o'clock mounting Catalog No. TM5JA TM5JUA Steel Meter Socket Covers Sealing Rings Description Blank (fits bottom position only) Ringless (Field -converts ring-type to ringless) Catalog No. 5 Amp TMCBB 00 Amp TMCB0B 5 amp top socket for and 3 gang TMCRT 5 amp for all other sockets TMCR 00 amp for all sockets TMCR0 Description Material Catalog No. Screw Type Aluminum TSR Snap Type Stainless Steel TSR3 Screw and Lock Type Aluminum TSR4 Snap Type Aluminum (Standard) TSR5 Miscellaneous Description Lexan Meter socket Cover Plate (without tabs) Lexan Meter Socket Cover Plate Equipment Ground Bar, (6) 6-/0 Individual Meter Socket Barrier Kit (includes 6) Mounting Z-Rail, 4-foot Lug Kit for (3) 4/0 cable 00 amps continuous. For top socket on TMM40R, order TMBPM0TA. 3 00 amps continuous. 4 Not UL Listed. Catalog No. TMCA TMCP TMEG TMBR TMZR TMPAL40

3

Other Publications and References Refer to these publications and resources for additional information about our products: Pub No. DET-008 DET-388 DET-395 DET-838 DET-843 DET-848 DET-860 Title UL Component Recognized Series-Connected Ratings Renewal Parts Construction and Details Residential Electronic Circuit Interrupters Houses to High Rises Modular Metering Application Guide Modular Metering Application Guide: Mini Mod III Product Family Visit our website: www.geindustrial.com/products/modular-metering for links to the above publications and additional information such as time current curves, outline and dimensional drawings, installation instructions, application and technical information. For questions about any of our modular metering products, please e-mail us at modular.metering@ge.com GE 4 Woodford Avenue Plainville, CT 0606-800-43-7867 www.geindustrial.com *Indicates a trademark of the General Electric Company and/or its affiliates. Information provided is subject to change without notice. Please verify all details with GE. All values are design or typical values when measured under laboratory conditions, and GE makes no warranty or guarantee, express or implied, that such performance will be obtained under end-use conditions. 08, General Electric Company and/or its affiliates. All rights reserved. 6.8 DET856E