The Magiflex Level Control System Installation and Setting up Instructions

Similar documents
TUNING FORK LEVEL WORKING PRINCIPLE APPLICATION. Solid Level Detection FEATURE. For Liquid: * Water & Solutions * General Purpose Solvent * Petroleum

P U L S A R point 210

STOCKTROL-H VIBRATING LEVEL SWITCH. Instruction Manual June 2002

The Mobrey product range provides reliable point level detection in a variety of dry solid applications

ROTARY PADDLE LEVEL SWITCHES

Vibrating Level Switches for Liquids & Solids HYC-VLS02 Elect. Iss. 02 SIL 2 APPROVED VIBRATING LEVEL SWITCHES FOR LIQUIDS AND SOLIDS

Excellence in Level Measurement

P17 Tempra Pro plugs, mobile sockets, fixed sockets, surface mounting sockets and appliance inlets - IP 66/67-63 A A

Mobrey dry products level measurement and control

Just Level. Table of Contents. Model CPH Capacitive Proximity Switch TECHNICAL INFORMATION. Principle of Operation 2. Applications 3.

AA4006 Speed Sensitive Trip Unit. User Manual

VLS SERIES Vibration Type Level Sensor

GCU-10. Automatic Engine Control Unit Operators Manual

702 AUTOMATIC START MODULE OPERATING INSTRUCTIONS

Contents R4 1. Capacitive Proximity Sensors

Industry Product Siloheight Status Chemical ABS pellet 3m good Chemical ABS Powder, PP & PE Pellet etc good Chemical Activated carbon 3m watch out

PRO REMOTE Series CAPACITANCE PROBE

LED AC DRIVERLESS FLOODLIGHTS WITH PIR FOR MODEL: FLAC10BPIR, FLAC20BPIR, FLAC30BPIR & FLAC50BPIR

CX-SERIES ADVANCED BATTERY CHARGER

EA07. Generator Automatic Voltage Regulator Operation Manual

Security alarms, warning systems.

for free flowing solids NIVOROTA ROTARY PADDLE LEVEL SWITCHES LEVEL SWITCHES

NIVOCONT R VIBRATING ROD LEVEL SWITCHES

M-Series 415 & in 1 Elevator Light Curtain. Installation Manual

Rotary Paddle Bin Monitor MODEL KA & KAX

Defining a timer in simple terms. Which actions are executed? Which market are they used frequently? Benefits and Advantages

Honeyville Cyclones. Sizes Ranging from 575 CFM to 57,000 CFM

SAFEDGE INSTALLATION & USER MANUAL PRESSURE SENSITIVE SAFETY EDGE SYSTEM READ THIS MANUAL IN FULL BEFORE INSTALLATION

PSU EN54-4 Power Supplies

Vertical Screw Elevator

PRO REMOTE 25 LV CAPACITANCE PROBE

PROCAP Capacitance Level Sensors

PSM72H Push-Button Start Module

Table 3:List of Mandatory Omani Standards

DEEP SEA ELECTRONICS PLC

MODEL 422 Submersible Pump Controller

process measurement solutions The dry products level control catalogue

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (0-10VDC Input Version)

Continuous level sensor NSK

PROCAP Capacitance Level Sensors

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2

Elmdene International Ltd

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS PLC

Continuous level sensor NSK

Level Devices. Rotary Level Indicators Roto-Bin-Dicator

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

CONDUCTIVITY LEVEL LIMIT SWITCH User s Manual

PHOTOSWITCH Liquid Level and Resistance Sensing Control Bulletin 13DJ3-3000

PRODUCT / TEST MANUAL 2L9K2 BATTERY EARTH FAULT RELAY

VRF II Series SURPASSING SENSITIVITY FOR THE TOUGHEST APPLICATIONS FEATURES AND BENEFITS STANDARD VS. ADVANCED UNITS

Advanced Battery Charger. 3 - stage charging capability (IUOU) 4.1 A / 100VAC 1.8A / 240VAC

GP Rev a ( ) DCN0533

HYPRA Prisinter 16/32/63 A

Soliswitch FTE30. Technical Information

Your Guide to the Installation, Care and maintenance of PERFORMA. Electronic Self Closing Fittings - Mains Powered 886V (343029) 885V (343027)

LEM~flex RR3020 AC Current Probe Operating Instructions Mode d emploi Bedienungshandbuch Manuale Operativo Manual de uso

INDUCTIVE CONDUCTIVITY SENSOR. Instruction Manual. Bürkert 2001 Subject to technical change without notice

CAPACITANCE LEVEL SWITCH

DIAMOND POINT VIBRATING PROBES

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320

Screw Lift Conveyor for Efficient Elevation When Your Handling Problem Calls for Elevating Bulk Materials

TANK LINING RESISTANCE GUIDE I-19

User Manual. T6 Tachometer. Online: Telephone: P.O. Box St. Petersburg, Florida 33736

InteliCharger V 20A Intelligent Automatic Battery Charger

Standard Target for Inductive Proximity Sensors

Level Measurement. Point level measurement Capacitance switches. Pointek CLS200 Standard. icenta Controls Ltd

AVR Hybrid Universal Analog Digital Voltage Regulator Operation Manual

BOX A3 TEST REL. DATE R.T. Check and Approval

Operators Guide: RoboSign Stop/Go Traffic Control System

MAIN FUNCTION FEATURES. . D = v t /2

CD34CNFLFxxx. Capacitive sensor, Foreground Suppression. Main features. Main functions. Description

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD

Advanced Battery Charger 0 ~ 15A 0 ~ 25A 0 ~ 35A 0 ~ 50A 0 ~ 80A. 3 - stage charging capability (IUOU) 90 ~ 264VAC (refer to de-rating curve)

THERMAL DISPERSION / PADDLE TYPE LEVEL SWITCH

Mclennan Servo Supplies Ltd. Bipolar Stepper Motor Translator User Handbook PM546

PHASE CONVERTERS OPERATING & MAINTENANCE INSTRUCTIONS. MODEL NO: PC40 and PC60. PART Nos:

Contents. AQ Instruction Manual

MODEL No. BC 700. Par t No OPERATING & MAINTENANCE INSTRUCTIONS

Black Teknigas. Powerseat Eco Gas Safety Shut-Off Valve. Technical, Installation and Maintenance Details. WattsIndustries.co.uk

Level Measurement Point level measurement - RF Capacitance switches

Emergency lighting units EM converterled. EM converterled ST 90 V SELFTEST series

Level Measurement. Point level measurement Capacitance switches. Pointek CLS200 Standard. 4/18 Siemens FI Overview.

INSTALLATION & OPERATING MANUAL RW SERIES WALL-MOUNT RECTIFIERS

Control pressure switch series FF 4

RF Point Level Control with Sensor Monitor

The Powermatic User Guide Test Sieve Shaker

875 CP - NM 30 NP 34 - A2

OPERATION MANUAL Common for All models Bobbin Sensor (Weft End Detection) DP150 - L2 BP150 - L2-12V BP150 - L2-24V (PNP/NPN)

Operators Guide: RoboSign Stop/Go Traffic Control System

Advanced Battery Charger. 3 - stage charging capability (IUoU) 25A

ROTARY PADDLE LEVEL SWITCHES with 2 year warranty. Paddle switch catalogue HYC-PSC01

DKG-114 MANUAL AND REMOTE START UNIT

Inductive Proximity Sensor

Accessories Mounting Brackets, Sight Glass Style... page Sensor Wells... page 4--22

ECONOMISER SERIES E2T USER MANUAL

Product Information S/PA

ADVR-12. Hybrid Universal Analog Digital Voltage Regulator Operation Manual

SUBMERSIBLE WATER PUMP

2 WAY REMOTE STARTER & ALARM SYSTEM INSTALLATION GUIDE FCC ID NOTICE

Transcription:

Principle of operation The Magiflex Level Control System Installation and Setting up Instructions The Magiflex probes are inserted into the vessel at the levels at which control or alarm is required. The sensitive tip of the plastic probe senses a change in capacitance when the material approaches or leaves the probe tip. This is amplified to activate the relay which has voltage free contacts, which may be used for alarm or control. Sensitivity The wide sensitivity range is set to suit the application, by means of a potentiometer & indicating LED situated in the termination head of the probe. When adjusting, avoid forcing the pot hard against the end stops. Fail Safe The fail safe switch is situated inside the control unit. In general FSH is used for filling applications, and FSL for emptying applications. Connection Details for Universal Controller UC1 : Wall mounted UC1 Point control or Alarm For Options see below ON DIP 1 2 3 4 5 6 Mains 24Vdc L N E or _ E SUPPLY AUX RELAY SENSORS 0V VE C N.O N.C 1 G 2 Power Relay 1 2 Screen 2 C NO NC - Point Detect Using MP1 UC1 Control between 2 Levels For Options see below ON DIP 1 2 3 4 5 6 1 C NO NC - SUPPLY AUX RELAY SENSORS 0V VE C N.O N.C 1 G 2 Power Relay 1 2 Screen 2 C NO NC - Control Using MP1 Pg 1

Dip itch Configuration for UC1 ON DIP 1 2 3 4 5 6 1. Failsafe L H L= Emptying / Low Alarm H= Filling / High Alarm 2. Mode 1 2 No of s fitted 3,4. Input on Delay 0S 5S 15S 120S 3 4 3 4 3 4 3 4 5,6. Input off Delay 0S 5S 15S 120S 5 6 5 6 5 6 5 6 Guide to setting up 1. H Fail Safe L Select L if the relay is to be energised when the probe is covered, contact is closed (if using a volt free contact input i.e. float switch) etc. Select H if the relay is to be de-energised when the probe is covered,contact is closed etc. 2. 1 Mode 2 Select how many input sensors are being used, mode 1 single input, mode 2 dual sensor input. Mode 1 Select when only using one input sensor. The input sensor should be connected to input 2. Both sensor on and off delays, if selected, apply to input 2 in this mode. Mode 2 Select when using two input sensors. 1 should be connected as the trigger, this is normally the higher sensing device in the vessel. Any on delay will act on this sensor. 2 should be connected as the latch, this is normally the lower sensing device in the vessel. Any off delay will act on this sensor. Any off delay if selected will only be acknowledged after the sensor 1 becoming active and then de-active. On power up if sensor 2 is not active and an off delay is selected the output relay state will be inverse for the delay period. 3, 4. Input on Delay Select the time delay before recognition of a covered probe, closed volt free contacts etc. 5, 6. Input off delay Select the time delay before recognition of an uncovered probe, open volt free contact etc. Dip itch Time Delay Settings On Delay (Dip itch 3 & 4) Selectable 0, 5, 15, 120 seconds (see dip switch instructions for configuration). Provides input sampling at approximately 500mS intervals, the input must be active throughout the period selected by the user. If at any time the input signal is invalid the timed period will be reset and no input acknowledged. Repeatability is 100% Off Delay (Dip itch 5 & 6) Selectable 0, 5, 15, 120, seconds (see dip switch instructions for configuration). Provides a delay on the output relay changing state after the input calling for it to do so. This is non resettable. repeatability is 100%. Setting the Fail Safe by Dip itch No 1 Pg 2

Connection Details for Panel Mounting Universal Controller Type UC1/P 11 Pin Base Connections for UC1/P Dip itch/timer Configurations for UC1/P 1 2 G If 2 s Used Aux 0v 4 5 3 6 7 8 9 2 10 1 11 ~L Supply ~ N Vdc 0Vdc Aux v 6 5 4 3 2 1 H Failsafe L 1 Mode 2 On Delay Off Delay 1 2 3 4 5 6 0s Fail to Safe Low or Fail to Safe High Single Operation or Dual Operation, for control On Delay 5s 15s 120s Off Delay Technical Data for Universal Controllers Supply: Consumption: Inputs: Max Input Resistance: Outputs: Operating Temp: Enclosure UC1/P: UC1: Weight UC1/P: UC1: Diagnostic: 230V/115V AC 50Hz 24V DC reverse polarity protected (selected at works) 0.35W @ 12V DC 1W @ 24V DC all with no aux load 5W @ 230V DC Single sensor Input 2 Trigger Twin sensor 2 latch, sensor 1 is trigger Normally 5V DC Active 0V DC 2,000 ohms Relay Volt Free SPCO contacts 5A @ 230v resistive LED'S Yellow = Power On Red = Relay Energised Green = 1 Active Green = 2 Active 0 0-10 C to 60 C 50W x 61H x 75D 11 Pin Plug in Base connector 11 Pin relay 130W x 170 H x 85D 215 gms 850 gms Flashing Input L.E.D.'s Mode 2 - Input 2 u/s, incorrect wiring/connection or probes reversed Mode 1 - Flashes if input is connected to input 1 & active Fast flash 3 sec no timer options selected Slow flash 1 sec in timing loop. 1 2 3 4 5 6 Power Relay Universal Controller HFailsafeL 1 Mode 2 On Delay Off Delay 1 2 Tel:44 (0)121 453 8911 Two Models Available UC1 Wall mounting, UC1/P Panel mounting Pg 3

Pg 4

Setting-up Set the probes sensitivity for the material by the potentiometer (pot) & LED in the probe head 1. Single Probe covered by material applicable to all probes except MP7 & MP7/E 1.1 Ensure that the probe tip is in contact with the material. 1.2 Turn pot clockwise to max sensitivity (arrow opposite max) LED is off. 1.3 Turn pot anticlockwise LED will first glow & then come fully on when correct point is reached. 1.4 Turn pot back in clockwise direction until light goes out 1.5 Continue clockwise a futher 3mm on the scale (1/8 ) 1.6 The probe is now set to an acceptable sensitivity for the material covering it. Futher slight adjustment in either direction may be desirable in practise to optimise the setting. 2. Single Probe not covered by material 2.1 Ensure that the probe tip is not in close proximity to a metal or earthed surface so that it is sensing air to give it max sensitivty. 2.2 Turn pot to max sensitivity by turning clockwise (arrow opposite max) LED is off. 2.3 Turn pot slowly anticlockwise LED will first glow & then come fully on. 2.4 Continue turning pot anticlockwise a futher 3mm (1/8 ) on the scale. 2.5 The probe is now set for max sensitivity & will probably operate above the surface of the material. 2.6 If this is too high, the sensitivity may be reduced by continuing to turn the pot anticlockwise. 3. Dual probe system for control between two levels. ensure low level probe is connected to sensor 2 high level probe is connected to sensor 1. Set fail safe switch FSL for emptying, FSH for filling. 3.1 For an empty vessel insert the low level probe & connect it to sensor 2 & when the material reaches it set as 1. 3.2 Remove this probe and insert the high level probe at the same level. Connect it to sensor 2 set up as 1 & 3.1. 3.3 Refit the probes in their correct positions & connect as 3. 3.4 If 3.2 is inpractical it will be necessary to set the high & low level probes in their respective positions as the vessel is filled. 4. To set up a MP7 & MP7/E probe. 4.1 The MP7 is for free suspension & is supplied with straining wire. The MP7/E is for attaching to the end of a ¾ BSP pipe. Both are prewired at works. The connections being Signal = Green/Yellow, Aux 0V = Brown Aux V = Blue. When installing the MP7 ensure that the straining wire is shorter than the cable. It is generally not practical to set up these probes in their operating location or covered state. They may therefore be set up in the uncovered state, i.e. sensing air as in 2. 4.2 The probe is set at works with the pot fully anticlockwise & the LED illuminating. 4.3 With the probe held in free air with no object in close proximity to the tip, insert the trimmer tool supplied & turn the pot slowly clockwise until the LED is extinguished. 4.4 Turn the pot slowly anticlockwise untill LED illuminates. 4.5 Continue turning 2 turns anticlockwise. The probe is now set for its max sensitivity. 4.6 Replace screw & O ring & tighten. 4.7 If dust or material gradually builds up in the area of the probe tip it may be necessary to re-adjust the sensitivity so turning the pot anticlockwise until it ignores the build up. Don t forget to replace screws & O ring. Pg 5

M 5. Checking the Correct Operation 5.1 Emptying 5.11 itch on 5.12 Level rises to lower probe 5.13 Level rises to upper probe 5.14 Level falls below upper probe 5.15 Level reaches lower probe Fail Safe itch Probe LED's Low Level High Level Motor/Pump Valve FSL On On Stopped Off On Stopped Off Off Starts Off On Running/Energised On On Stops 5.2 Filling 5.21 itch on 5.22 Level rises to lower probe 5.23 Level rises to upper probe 5.24 Level falls below upper probe 5.25 Level reaches lower probe FSH On On Running/Energised Off On Running/Energised Off Off Stops Off On Stopped/Energised On On Starts Typical Applications Alum Aggregates Alcohol Acetone Bone Meal Black Nickel Barley Bran Bitumen Bread Crumbs Benzene Coal Cat Litter Cocoa Beans Coffee Beans Cement Carbon Tetrachloride Creosote Chocolate Distilled Water Diesel Oil Edible Fats Food Products Foundry Sand Flour Fullers Earth Fertilizer Frozen Vegetables Glucose Glacial Acetic Acid Spent Grains Glycerine Gravel Ice Cream Powder Lime Molasses Methylated Spirits Maize Oats P.F. Ash Potato Chips Petrol Paraffin Perchlorethylene Peat Polypropylene & PVC Potatoes Peanuts Refractory Materials Starch Sugar Sawdust Soda Ash Dry Salt Sodium Carbonate Sulphur Sucrose Tea Toluene Turpentine Whiting Wood Shavings Wheat Washing Powders Whisky Xylene Ceramic Powders Clay Limestone Lubricating Oils Latex All Hawker products are covered by a 12 months guarantee against failure of components or faulty workmanship. The period of guarantee commences 7 days after date of despatch or by special agreement, from date of commissioning. Equipment returned for service under guarantee will be repaired by Hawker Electronics Limited free of labour and component charges, but subject to the following conditions:- 1. Equipment shall not have been tampered with in any way or subjected to misuse. 2. The guarantee does not cover pilot bulbs. 3. Postage and packing charges are applicable. Warning Before switching on mains supply to instrument & or control circuit, ensure that :- 1. Supply voltage corresponds to instrument voltage. 2.Control wiring is correct. Failure to observe these precautions may result in damage to printed circuit boards, so invalidating our terms of agreement. Before disconnecting mains leads or control wiring at the terminal block, ensure that:- 3. Mains supply to the controller is switched off. 4. Mains supply to the equipment being controlled is switched off. E.M.C. (Electromagnetic Compatibility) Due to the nature of the Magicap Probe sensing circuit, it is possible that electromagnetic radiation applied to the probe tip can affect the switching of the probe. This effect is negated when the probe is mounted in an earthed vessel, or the source of radiation is not immediately adjacent to the probe (e.g. a mobile phone has no effect when more than 1 metre from the probe tip). No operational problems of an E.M.C. nature have been experienced throughout the "Magicap`s & Magiflex's 25 year life. This product has been designed Because and of complies continuing to the developm relevant ent standards w e reserve as listed the in right its certificate to change of the conformity, specifica The tions installer/user w ithout notice. must ensure system compliance Fo rbecause a fulllistofh continuing AW KERdevelopm products entand we reserve applicathe tionright notes to change visitourw the specifications eb site atw wwithout w.hawnotice. ker-electronics.co.u k HAW H A WKER K ELECTRONICS N LTD.. 57,The Avenue, RuberyIndustrialEstate, IndustrialEstate, Birm ingham,b45 9AL,EN G LAND. Birm ingham B45 9AL, EN G LAN D Telephone :44(0)121-453-8911 Fax :44 (0)121-453-3777 Te lephone : 44 (0)121-453-8911 Fax : 44(0)121-453-3777 e m ail:info @ haw ker-electronics.co.uk W eb Site:w ww.haw ker-electronics.co.uk e.m ail:info@ haw ker-electronics.co.u k G E R I ST BSI E R E D F I R CERT No.FM 10,000 BRITISH M ADE FM 10000 HISU-52 June 01 Issue A HISU-52 Feb DOC 02 52 Issue B O&M 52 Issue C May 03 Pg 6 Pg 6