25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

Similar documents
15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number:

Product Description: Objective and Certification: Test Samples and Test Cable:

CERTIFIED TEST REPORT. Cooper Power Systems. 25 kv Class 200 Amp 15.2/26.3 kv SEPARABLE CONNECTOR SYSTEM

Eaton s Cooper Power Systems

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

25 kv Apparatus Bushings

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Loadbreak Apparatus Connectors

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

Quick Splice II. 35 kv Molded Rubber Inline Splicing Kit Data Sheet. 2. Applications. 1. Product Description

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

Quick Splice II 5451R. 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet. 1. Product Description. 2. Applications

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL

High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide

TABLE OF CONTENTS Page

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

15 kv Class Fused Loadbreak Elbow Connector with Interchangeable Fuse Capability

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

600 A 15 kv class T-OP II deadbreak connector

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

15 kv and 25 kv Thru-Bushings

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

25 kv class fused loadbreak elbow connector

600 A 15 kv class Cleer loadbreak connector system

600 A 28 kv class Cleer loadbreak connector system

600 A 35 kv class BT-TAP deadbreak connector

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50

PRODUCT BROCHURE. Elastimold ComboT integral separable connectors

1500 kva Padmount Transformer delta Primary Voltage 208Y/120 Secondary Voltage

INSTALLATION PRODUCTION TESTS


600A Deadbreak Elbow. K656LR Elbow Connector (with Test Point) Features:

600 A 25 kv class BT-TAP deadbreak connector

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

REPORT OF TEST ON Elastimold Molded Vacuum Reclosers (MVRs)

IEC Separable Connectors 17.5 kv/24 kv, 630A

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

LV Bushing Oil to Air Dry Insulation PTAB-SLV832

Low voltage bushings for pad-mounted distribution transformers Technical information guide

200 A and 600 A, 15, 25, and 35 kv junction bars for separable connectors

IEC Separable Connectors 36 kv and 42 kv, 630A and 1250A Front T-Body / Coupling (Rear) T-Body Connector

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

TEMPERATURE RISE TESTS

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable

ELASTIMOLD UNDERGROUND CABLE ACCESSORIES

PSC Terminations. Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables.

8.3kV, 9.9kV, 15.5kV, 17.2kV and 23kV Cooper ELSP Backup Fuses Testing per C

600 A 15 and 25 kv class Cleer grounding elbow

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report

Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:

Installation Instructions LINK---C

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING

ANSI DESIGN TEST REPORT Report No. EU 1512-HR-00.5 Type PDV 100 Optima Heavy Duty Distribution Class Surge Arrester

CERTIFIED TEST REPORT

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.

600 A 15 and 25 kv class deadbreak accessories, tools, and replacement parts

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C

Molded Current-Limiting Fuse

A 1.2 kv class externally removable secondary bushing

copper stud. If a 900 A rating is desired, specify a C as the 8th digit when determining your part number (See Table 3, page 3.)

Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

Contents. Design Test Results for Specimen Design Test Results for Specimen Voltage Impulse Oscillograms...9

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

100 / 110 DRYWELL FUSE SPECIFICATION

Technical Specification For Outdoor Substation Harmonic Filter Banks

GROUP C. Apparatus Bushing.

Elastimold & Hi-Tech Fuse Products

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

600 A 35 kv class separable splices

600 A 35 kv class deadbreak accessories, tools, and replacement parts

ELB ES. Product Installation Instructions

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

GROUP D. Switch & Protective device.

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

Geometric vs. Capacitive Stress Control: choosing cable termination accessories to help reduce electrical stress.

Edison modular fuse, vault application products

35-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current-Limiting Fuses

CATALOG. Hi-Tech Fuse Products

Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles

Modification Record of Product Specification

ELB ELB

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

Surge Arresters. UltraSIL Polymer-Housed Evolution (10 ka) Surge Arresters. General. Construction. features

Technical Specification for Pole Mounted Capacitor Rack

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

Specifier's Guide COOPER POWER. Line installation and protective equipment master catalog 5 kv - 35 kv electrical distribution systems SERIES

Grounding equipment COOPER POWER SERIES. Temporary Connections CA325004EN. Contents

3M Connector System 0.050" x 0.100" Pitch. 3M Tripolarized Wiremount Socket - Series 820 3M 4-Wall, Tripolarized Header - Series 810

IEEE Insulated Conductors Committee. Subcommittee B, Cable Accessories

Transcription:

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report Report Number: Date: RN-R7604 9/16/2013

Table of Contents I. OBJECTIVE... 2 II. SUMMARY... 2 III. CONCLUSION... 2 IV. CABLE DATA... 2 V. TEST SAMPLES... 2 VI. TESTING SEQUENCE... 2 VII. TESTING... 4 1. Sequence A Dielectric Tests Sequence... 4 1.1 Partial Discharge Test Bushing Insert... 4 1.2 Partial Discharge Test Elbow... 5 1.3 AC Withstand Voltage Test Bushing Insert... 7 1.4 AC Withstand Voltage Test - Elbow... 8 1.5 DC Withstand Voltage Test Bushing Inert and Elbow... 10 1.6 Impulse Withstand Voltage Test - Bushing Insert and Elbow... 12 1.7 Test Point Test... 15 2. Sequence B Accelerated Life Tests Sequence... 17 2.1 Accelerated Sealing Life Test Bushing Insert and Elbow... 17 3. Sequence C Switching and Fault-closure... 23 5. Individual Testing... 24 4.1 Short-time Current Test... 24 4.2 Current-cycling Test Elbow and Bushing Insert... 25 4.3 Elbow Cable Pull-Out Test... 29 4.4 Operating Force Test... 30 4.5 Elbow Operating Eye Test... 31 4.6 Test Point Cap Test... 33 4.7 Shielding Test... 34 APPENDIX -External Test Report Summary... 35 1

I. OBJECTIVE To evaluate the Chardon 25kV Loadbreak bushing insert and elbow to the 25kV class performance requirements of IEEE Std 386-2006. II. SUMMARY All samples are qualified to the full design testing sequence of IEEE 386-2006, including partial discharge test, AC withstand testing, DC withstand testing, impulse withstand testing, short time current test, cable pull out test, operating force test, elbow operating eye pulling test, test point cap test, test point test, shielding test, switching and fault closure. III. CONCLUSION By passing the above test requirements, it is concluded that 25kV series Loadbreak Bushing Insert and Elbow design is suitable for use as a fully shielded, fully separable submersible cable connections for 25kV class 1Φ and 3Φ 200A medium voltage circuits. IV. CABLE DATA Class: Conductor: Insulation: Jacket: 25kV 1/0 Str Al 220mils, TRXLP PVC V. TEST SAMPLES The required number of 25kV 200A Bushing Insert and Elbow samples, according to each specific test requirements, were mated with each other according to the installation instruction provided by Chardon. VI. TESTING SEQUENCE The samples were tested in accordance with IEEE 386-2006 Standard. Table 1 shows the different test sequence and sections the samples were subjected to. The section numbers refer to the corresponding sections in the standard. 2

Design test No. Samples Reference Sequence A B C Individual 10 4 30 Four each Thermal cycle withstand 7.20 N/A Partial discharge test 7.4 X X AC withstand voltage 7.5.1 X X DC withstand voltage 7.5.2 X Impulse withstand voltage 7.5.3 X X Short-time current 7.6 X Switching 7.7 X Fault-closure 7.8 X Current cycling 7.9 to 7.11 X Accelerated sealing life test 7.12 X Cable pull-out 7.13 X Operating force 7.14 X Operating eye 7.15 X Test point cap 7.16 X Test point 7.17 X X Shielding 7.18 X Bushing well stud torque 7.19 N/A Impulse withstand voltage 7.5.3 X Table 1 : Design test sequence Samples were tested according to the sequence and quantities shown in Table 1. 3

VII. TESTING 1. Sequence A Dielectric Tests Sequence 1.1 Partial Discharge Test Bushing Insert Object To verify the connectors that the parts meet the ANSI/IEEE Standard 386-2006 25kV partial discharge spec of 19kV/3pC. Testing Samples Bushing Insert 25-LBI200 10 PCS Mating Parts Bushing Well Insulating Cap Elliott 200 Amp Bushing Well #1101-225B Hubbell 25kV200A Loadbreak Insulating Cap(9U01BEW5000) Procedure and Testing Spec The test voltage shall be raised to 20% above the corona voltage level of 19kV. If corona exceeds 3pC, the test voltage shall be lowered the corona voltage level of 19kV and maintained at this level for at least 3 seconds but not more than 60 seconds. Corona readings taken during this period shall not exceed 3 pc. Results All samples passed. 4

1.2 Partial Discharge Test Elbow Object 19kV/3pC To verify the connectors that the parts meet ANSI/IEEE Standard 386-2006 25kV partial discharge requirement of 19kV/3pC. Testing Samples Elbow 25-LE200TB 10 PCS Mating Parts Bushing Insert Bushing Well Copper Test Rod Elbow Test Rod 25-LBI200 Elliott 200 Amp Bushing Well #1101-225B 25kV 25kV#B Testing Rod Φ22.20mm Procedure and Testing Spec The test voltage shall be raised to 20% above the corona voltage level of 19kV. If corona exceeds 3pC, the test voltage shall be lowered the corona voltage level of 19kV and maintained at this level for at least 3 seconds but not more than 60 seconds. Corona readings taken during this period shall not exceed 3 pc. Results All samples passed. 5

Fig 7-1 Partial Discharge Testing Setup 6

1.3 AC Withstand Voltage Test Bushing Insert Object To verify the connectors that the parts meet ANSI/IEEE Standard 386-2006 25kV AC withstand voltage testing requirements 40kV/1 min. Testing Samples Bushing Insert 25-LBI200 10 PCS Mating Parts Bushing Well Insulation Cap Elliott 200 Amp Bushing Well #1101-225B Hubbell 25kV200A Loadbreak Insulating Cap(9U01BEW5000) Procedure and Testing Spec The test voltage shall be raised to the value of 40kV in 30 seconds. The test sample shall withstand the specified test voltage for 1 minute without flashover or puncture. Results All samples passed. 7

1.4 AC Withstand Voltage Test - Elbow Object To verify the connectors that the parts meet ANSI/IEEE standard 386-2006 25kV AC withstand requirement of 40kV/ 1 min. Testing Samples Elbow 25-LE200TB 10 PCS Mating Parts Bushing Insert Bushing Well Copper Testing Rod Elbow Testing Rod 25-LBI200 Elliott 200 Amp Bushing Well #1101-225B 25kV 25kV#B Testing Rod Φ22.20mm Procedure and Testing Spec The test voltage shall be raised to the value of 40kV in 30 seconds. The test sample shall withstand the specified test voltage for 1 minute without flashover or puncture. Results All samples passed. 8

Fig 7-2 Testing in Progress Fig 7-3 Test Fixture Setup 9

1.5 DC Withstand Voltage Test Bushing Inert and Elbow Object To verify the connectors that the parts meet the ANSI/IEEE Standard 386-2006 25kV DC withstand voltage testing spec of 78kV/15 min. Testing Samples Elbow 25-LE200TB 10 PCS Bushing Insert 25-LBI200 10 PCS Mating Parts Bushing Well Elbow Test Rod Elliott 200 Amp Bushing Well #1101-225B 25kV#B Testing Rod Φ22.20mm Procedure and Testing Spec The test voltage shall have a negative polarity and shall be raised to the value of 78kV. The connector shall withstand the specified test voltage for 15 minutes without flashover or puncture. Results All samples passed. 10

Fig 7-4 DC Withstand Testing Fixture Setup 11

1.6 Impulse Withstand Voltage Test - Bushing Insert and Elbow Object To verify the connectors that the parts meet ANSI/IEEE Standard 386-2006 25kV impulse withstand testing requirements of 1.2 50μs ±125kV wave., 3 positive and 3 negative full-wave impulses. Testing Samples Elbow 25-LE200TB 10 PCS Bushing Insert 25-LBI200 10 PCS Mating Parts Bushing Well Elbow Testing Rod Elliott 200 Amp Bushing Well #1101-225B 25kV#B Testing Rod Φ22.20mm Procedure and Testing Spec The test voltage shall be 1.2/50µs wave having the crest value (BIL) of 125kV. The connector shall withstand 3 positive and 3 negative full-wave impulses without flashover or puncture. Results All samples passed. 12

Elbow and Bushing Insert, 4 sets Fig 7-5 Positive Wave (Data Amplification: 5,000). Elbow and Bushing Insert, 4 sets Fig 7-6 Negative Wave (Data Amplification: 5,000) 13

Fig 7-7 Impulse Withstand Testing Fixture Setup 14

1.7 Test Point Test Object To verify the elbow test point meeting the ANSI/IEEE Standard 386-2006 testing requirement. Testing Samples Elbow 25-LE200TB 10 PCS Mating Parts LCR Meter Testing Fixture CHENHWA 1012F Procedure and Testing Spec The purpose of this test is to verify that the capacitance values of the test point meet the requirements of 6.5.1. of IEEE 386. The connector shall be installed on a cable of the type for which it is designed to operate, and the shielding shall be grounded in the normal manner. The capacitances from test point to cable and test point to ground shall be measured with suitable instruments and proper shielding techniques. The measured values shall be within the tolerances specified in 6.5.1. of IEEE 386. Results All samples passed. 15

Fig 7-8 Capacitance Test Setup 16

2. Sequence B Accelerated Life Tests Sequence 2.1 Accelerated Sealing Life Test Bushing Insert and Elbow Object To verify the connector can maintain a long-tern seal at all interfaces to prevent the entrance of moisture. Testing Samples and Mating Parts Elbow 25-LE200TB 4 PCS Bushing Insert 25-LBI200 4 PCS Mating Parts Bushing Well Cable Conductor Type Cable Insulation Thickness Elliott 200 A Bushing Well #1101-225 1/0 AWG Aluminum Cable 260 mil 4 PCS Conductor Equalizers Bushing Bus 1/0 Bi-metal Lug Aluminum Equalizers Size:106mm(L)20mm(OD)10.1mm(ID) 356mm(L), 102mm(W),10mm(T) Testing Spec 1. The four connector assemblies shall be placed in an oven having 121 C temperature and remain there for three weeks. (July-30~Aug-20 of 2013) 2. After the time has elapsed, the four samples shall be subjected to 50 cycles of the following sequence of operations: The assemblies shall be heated in air using sufficient current to raise the temperature of the connector of the control cable to 90 C ± 5 C for 1 hour. 3. The assemblies shall be de-energized and within 3 min, submerged in 25 C ± 10 C conductive water (5000 Ω-cm maximum) to a depth of 30 cm (1 ft) for 1 hour. 4. After 50 th cycle, the connector and cable assembly shall withstand a design impulse test of IEEE 7.5.3(1.2*50µS impulse wave of 125kV, 3 positive and 3 negative) and test point voltage test.( During the impulse test, the bushing well and bushing bus were soaked into the silicone oil.) Results All samples passed. 17

Fig 7-9 : Testing Setup of Accelerated Life Sealing Test 18

Fig 7-10 Partial Discharge Test - Fig 7-11: Impulse Test Setup 19

Fig 7-12: Testing Samples Assembly Fig 7-13: Testing Samples in the Chamber 20

Fig 7-14: Current On Testing Loop Fig 7-15: Current Off Testing Loop 21

Fig 7-16: Impulse test after accelerated sealing life test I. Fig 7-17: Impulse test after accelerated sealing life test II. 22

Description 3. Sequence C Switching and Fault-closure The purpose of these tests is to verify that the Loadbreak Bushing Insert and Elbow are capable of closing and interrupting the rated switching current of 200A rms. Additionally, these tests will verify the parts are capable of closing on a 10,000A rms fault current for 0.17 sec. Requirement The Loadbreak Bushing Insert shall withstand 10 complete switching operations without arcing to ground or impairing its ability to meet the spec of IEE Std 386-2006. The Loadbreak Elbow shall also withstand 10 complete switching without arcing to ground or impairing its ability to meet the spec of IEE Std 386-2006. Failures are permitted; however, none of the failures are permitted in 10 consecutive samples of a maximum lot size of 30. Procedures 1. Assemble 30 Bushing Inserts and Elbows assemblies on cable. 2 Test all samples in accordance with IEEE Standard 386-2006 sections 7.7 Switching Test under the conditions described in Tables 7 and 8, Figure 19(a) of the standard. Each sample is subjected to 10 complete switching operations at 15.2/26.3 kv, 200A using a mechanical fixture. 3. Test all samples that successfully passed 10 switching operations in accordance with IEEE Standard 386-2006 sections 7.8 Fault-closure Test under the conditions described in Table 8 and 9, Figure 20(a) of the standard. Each sample is subjected to 1 fault-close operation. 4. The procedure above was repeated with elbow samples from Elastimold and Cooper Industries, in compliance with IEEE 386-2006 standard section 6.4.1 Complete Interchangeability Results Switching passed; Fault-closure passed. Testing performed at Powertech Labs Inc, Surrey BC Canada. Chardon Powertech Report 20328-C-26 Elastimold Interchangeability Powertech Test Report 80020959-B Cooper Interchangeability Powertech Test Report 20770-B-26 23

5. Individual Testing 4.1 Short-time Current Test Object To verify the connectors that the parts meet ANSI/IEEE Standard 386-2006 200A short-time current test requirements. Testing Samples Elbow 25-LE200TB 4 PCS Bushing Insert 25-LBI200 4 PCS Mating Parts Bushing Well Bushing Extender Cable Conductor Type Elliott 200 Amp Bushing Well #1101-225B Hubbell 625BE #1 AWG 2 PCS Procedure and Testing Spec The rms value of the first major loop of a current wave shall be not less than the value specified in Table 2 multiplied by 1.3 (X/R=6) for 200 A connectors The magnitude shall be measured in accordance with ANSI/IEEE C37.09. Connectors shall withstand the current without separation of interfaces or impairing the ability to meet the other requirements of the standard. Results All samples passed. 24

4.2 Current-cycling Test Elbow and Bushing Insert Object The purpose of this accelerated test is to demonstrate that 200 A insulated connectors can carry rated current under usual service conditions. Successful completion of the test shall be considered as evidence that the connector meets its rating. Testing Samples Elbow 25-LE200TB 4 PCS Bushing Insert 25-LBI200 4 PCS Mating Parts Bushing Well Elliott 200 A Bushing Well #1101-225B 4 PCS Cable Conductor Type Cable Insulation Thickness 1/0 AWG Aluminum Cable 260 mil Conductor 2761035020 Equalizers Bushing Bus Aluminum Equalizers Size:106mm(L), 20mm(OD), 10.1mm(ID) 356mm(L),102mm(W),10mm(T) Testing Spec A control cable, used for the purpose of obtaining conductor temperature, shall be installed in the heat cycle loop between two equalizers. Its length shall be 183 cm (72 in). The control cable shall be the same type and size as the cable used to join the connectors under test. Four connectors shall be assembled in series on AWG No 1/0 insulated aluminum conductors having a length of 91 cm (36 in). The cable insulation thickness shall be selected according to its voltage class (see Table 10 of IEEE 386).Equalizers used shall be in accordance with ANSI C119.4.The bushing bus shall be a flat, rectangular, bus bar 356 mm (14 in) long, 102 mm (4 in) wide, and 10 mm (3/8 in) thick. The bushing wells 25

shall be mounted 31 cm (12 in) apart centered along the midline of the bus bar. The bushing well studs shall be tightened to the bus bar using an installation torque of 9 N m ± 1 N m (80 lbf in ± 10 lbf in). Unless otherwise specified by the manufacturers, the elbow male contact probe shall be threaded into the elbow compression lug using an installation torque of 9 N m ± 1 N m (80 lbf in ± 10 lbf in). Current-cycling tests shall be conducted at an ambient temperature of 15 C to 35 C in a space free of drafts. The current-cycle amperes shall be adjusted during the current-on period of the first five cycles to result in a steady-state temperature rise of 100 C to 105 C on the control conductor. This current shall then be used during the remainder of the test current-on periods, regardless of the temperature of the control conductor. The test shall consist of 50 current cycles, with the current on 4 h and off 2 h for each cycle. At the end of each current-on cycle, the assembly shall be de-energized and within 3 min be submerged in water at 5 C ± 5 C for the remainder of the current-off cycle. At the end of the 10th, 25th and 40th cycles (± 2 cycles), after the samples have returned to room temperature, a short time ac current of 3500 A ± 300 A rms shall be applied to each sample for a minimum of 3 s. The temperature of at least the following current transfer points shall be measured at the end of each cycle with the current on: a) Probe to compression lug b) Probe to female contact c) Female contact structure to metallic housing (piston contact) d) Between bushing insert and bushing well. These temperatures shall not exceed the temperature of the control conductor. The temperature differences between the control conductor and the connector shall show a condition of stability from the fifth cycle to the end of the test. Stability is indicated when the change in the individual differences is not more than 10 C from the average of the measured differences in this interval for this connector. The dc resistance of the connector system shall be measured at the end of cycles 10, 20, 30, 40, and 50 (± 2 cycles). The dc resistance measurements shall be made between the elbow cable equalizer and the bushing stud after the connector system has stabilized at ambient temperature. Ambient temperature shall be measured by devices located within 61 cm (2 ft.) of the test loop but in a location that minimizes the effect of thermal convection. The ambient temperature shall be recorded at the same time as each set of resistance measurements, and the resistance shall be corrected to 20 C. The dc resistance shall be stable over the period of measurement. 26

Stability is achieved when any resistance measurement, including allowance for instrument accuracy, does not vary more than ± 5% from the average of all the measurements in this interval. Results All samples passed. Fig 7-18: Testing Setup Diagram 27

Fig 7-19: Current On Cycle Fig 7-20: Current Off Cycle 28

4.3 Elbow Cable Pull-Out Test Object To verify the compression lug and cable assembly that the parts can meet ANSI/IEEE Standard 386-2006 Cable Pull-Out Test requirements. Testing Samples Elbow Compression Lug #1AWG(Cu) 4 PCS Mating Parts Cable #1AWG(Cu) Procedure and Testing Spec The purpose of this test is to determine if the connection between the cable conductor and compression lug of the connector is capable of withstanding a tensile force of 890 N (200 lbf). The compression lug shall be held in a manner that will not affect the strength of the connection. The tensile force shall be applied to the cable conductor. The connection shall withstand the applied force for 1 minute without impairing the connector's ability to meet the other requirements of this standard. Results All samples passed. 29

4.4 Operating Force Test Object To verify the force of the elbow connector operating force when mating with bushing insert that the force meets NSI/IEEE Standard 386-2006 operating force requirement. Testing Samples Elbow 25-LE200TB 4 PCS Mating Parts Bushing Insert 25-LBI200 4 PCS Elbow Test Rod 25kV#B Testing Rod Φ22.20mm Procedure The purpose of this test is to demonstrate that the force necessary to operate a connector meets the requirements of 6.2.( 222 N - 890 N (50 lbf - 200 lbf) for connectors without hold-down bails) The elbow shall be assembled with a probe and compression lug and the connector system shall be lubricated in accordance with the manufacturer's instructions. Results All samples passed. 30

4.5 Elbow Operating Eye Test Object To verify the elbow operating eye that the part meet ANSI/IEEE Standard 386-2006 requirements. Testing Samples Elbow 25-LE200TB 4 PCS Mating Parts Testing Fixture Procedure and Testing Spec The purpose of this test is to demonstrate that the operating eye meets the requirements of 6.2 at 25 C ±5 C. A tensile force shall be gradually applied to the operating eye in the direction of normal operation. The operating eye shall withstand the force for 1 minute. A rotational force shall be applied with a suitable live-line tool to the operating eye in a clockwise direction and in a counter-clockwise direction. Some distortion of the operating eye is acceptable provided the connector is serviceable after the test and meets the corona voltage-level requirement specified in Table 1 of IEEE standard 386-2006. Results All samples passed. 31

Fig 7-21 Torque Testing Setup 32

4.6 Test Point Cap Test Object To verify the test point cap of the elbow that the part meets ANSI/IEEE Standard 386-2006 requirement. Testing Samples Elbow 25-LE200TB 4 PCS Test Point Cap Testing Fixture Procedure and Testing Spec 4 PCS The purpose of this test is to demonstrate that the removal force of the test point cap meets the requirements of 6.5.2 and the cap operating eye is capable of withstanding the maximum operating force Results All samples passed. 33

4.7 Shielding Test Object To verify the outer conductive layer of the connector that the material meet ANSI/IEEE Standard 386-2006 requirement of shielding test Testing Samples Elbow 25-LE200TB 6 PCS Procedure 1. Shield Resistance. The shield resistance measured between the cable entrance and the farthest extremity of the shield from the cable entrance shall be 5000Ω or less. 2. Fault-Current Initiation. The semi-conducting shield shall be capable of initiating two consecutive fault-current arcs to ground specified in 4.3, IEEE 592. Results 1. Shield Resistance : 4 testing samples resistance measured are less than 5000Ω, all samples passed. 2. Fault-Current Initiation: 2 testing samples successfully initiate two consecutive fault-current arcs to ground in the test performed in Powertech Labs, Surrey, B.C., Canada. All 2 samples passed. Powertech Test Report PL-26015B. 34

APPENDIX -External Test Report Summary 35