DIAC DIFC DSFC Digital Self Powered Overcurrent Protection

Similar documents
ADDITIONAL INFORMATION. BE1-50/51B SELF POWERED TIME OVERCURRENT RELAY and RETROFIT KITS. FEATURES and APPLICATION Page 2

BE1-50/51B with S1 Case or FT-11 sized Case and Cover For non-retrofit applications, see Product Bulletin UHD.

GEK41931B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAYS TYPE HFA73K. GE Protection and Control 205 Great Valley Parkway Malvern, PA

COM Overcurrent Relay

INSTRUCTIONS HAA 15A / 15B / 15C / 15D / 15E / 15F / 15G / 15H AUXILIARY CURRENT RELAYS

SURE-TRIP OEM RELACEMENT TRIP UNIT

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

INSTRUCTIONS. GEI-38974A Supersedes GEI INSTANTANEOUS CURRENT RELAY TYPE PJC2OA GENERALS ELECTRIC

SURE TRIP RETRO KITS

GEK 45484B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAY HFA151 TYPE. GE Protection and Control 205 Great Valley Parkway Malvern, PA

University of Houston Master Construction Specifications Insert Project Name

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

GE CONSUMER & INDUSTRIAL

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

Type SOQ Negative Sequence Time Overcurrent Relay

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA GEK-49826D INSTANTANEOUS OVERCURRENT RELAYS TYPES:

SecoVac * Ground & Test Device

INSTRUCTIONS GEI-98305C UNDERVOLTAGE RELAY D-C. Type NGV18A GENERAL ELECTRIC

PRODUCT/TEST MANUAL 2C58K37 INSTANTANEOUS OVERCURRENT RELAY

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

B CW POWER RELAY

PRODUCT / TEST MANUAL 2C58K2 INSTANTANEOUS OVERCURRENT

4.0 OPERATION Type ITH-T Relay

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

5. OVERCURRENT RELEASE (OCR)

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

INSTRUCTIONS SYNCHRONISM-CHECK RELAYS. GE Meter and Control. 205 Great Valley Parkway Malvern, PA Types IJS51A.

5. OVERCURRENT RELEASE (OCR)

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

Electropneumatic Timing Relays Series 7000 Industrial

Type CRN-1 Reverse Power Relay 50 and 60 Hertz

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

SECTION MOTOR CONTROL

Inverse-Time Overcurrent & E/F Relays. Type ICM 21, ICM 21B. Station Automation & Protection. ABB Substation Automation Products

PORTABLE CURRENT SOURCE FOR CIRCUIT BREAKER AND MOTOR OVERLOAD TESTING INSTRUCTION MANUAL PI-250B. Release 1.0 April 5, 2013

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

P. Sub 4 184A404. Sub 3 876A220

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

A21M. Introduction: Functional Overview: Key Protection & Control Functions:

Operation and Maintenance Manual

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

Modular Metering - Trip Unit for >1200A Mains DEH41187 Application Guide

BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION! FOLLOW NATIONAL, STATE, AND LOCAL CODES! READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number:

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Low Voltage WavePro TM and EntelliGuard TM Circuit Breakers Remote Racking Operator

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

SURE TRIP SLT-201 SECONDARY TEST SET

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

ELECTRIC ACTUATOR HVAC/BAC ELECTRIC IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

MODEL 422 Submersible Pump Controller

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

Memshield - ACB Ratings & Specifications

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

White Paper. Ground Fault Application Guide. WL Low Voltage Power Circuit Breakers

PRODUCT / TEST MANUAL 2L9K2 BATTERY EARTH FAULT RELAY

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

MF /MS Series

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

Model HEA Multicontact Auxiliary

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Advanced Test Equipment Rentals ATEC (2832)

Electric Actuator Instructions

7. SERVICES OVER 600 VOLTS

Table of Contents. For latest version, visit:

ELECTRIC ACTUATOR 94OE IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

N-frame Circuit Breaker

Installation and Operations Manual

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

KD LV Motor Protection Relay

Jun06 Rev D

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA UNDERVOL TAGE RELAYS TYPES: IAV54E IAV55C IAV54F IAV55F

GENSET CONTROL MODULE A121A / A241A

GE Consumer & Industrial Electrical Distribution. Power Break II. Insulated Case Circuit Breakers

RVS-DX Digital Reduced Voltage Motor Starter

0.5 s to 30 h (30 s, 3 min, 30 min, 3 h, 30 h)

DETAIL SPECIFICATION SHEET

Vacuum Circuit Breaker (Vehicle)

K-Line Plus Types KP-32, KPE-32, KP-40 and KPE-40

Transcription:

GEK 070B GE Power Management DIAC DIFC DSFC Digital Self Powered Overcurrent Protection *(RZHU0DQDJHPHQW $QGHUVRQ$YHQXH 0DUNKDPQWDULR &DQDGD/% ZZZJHFRPLQGV\VSP

TABLE OF CONTENTS INTRODUCTION... PRODUCT DESCRIPTION... GENERAL... APPLICATION... FUNCTIONS... CALCULATION OF SETTINGS... HARDWARE DESCRIPTION... CASE... ADJUSTMENTS... TARGETS AND INDICATORS... RESET AND MANUAL TRIP... TRIP CIRCUIT TEST... TRIP CIRCUIT... COVER INSTALLATION DIAC AND DSFC... RECEIVING, HANDLING AND STORAGE... INSTALLATION... 7 ENVIRONMENT... 7 MOUNTING... 7 SURGE GROUND... 7 ACCEPTANCE TESTS... VISUAL INSPECTION... MECHANICAL INSPECTION... ELECTRICAL TESTS... PERIODIC TESTS... 0 SERVICING... 0 SPECIFICATIONS... RATINGS... BURDENS... CONTACT RATINGS... ENVIRONMENTAL... Cover Photo: 89970

LIST OF FIGURES FIGURE IAC TOC CURVES... 7 FIGURE IAC TOC CURVES... 8 FIGURE SHORT TIME TOC CURVES... 9 FIGURE 7 MEDIUM TIME TOC CURVES... 0 FIGURE LONG TIME TOC CURVES... FIGURE 7 IAC77 TOC CURVES... FIGURE 8 9 SHORT TIME TOC CURVES... FIGURE 9 IEC INVERSE TOC CURVES... FIGURE 0 IEC VERY INVERSE TOC CURVES... FIGURE IEC EXTREMELY INVERSE TOC CURVES... 7 FIGURE IEEE INVERSE TOC CURVES... 8 FIGURE IEEE VERY INVERSE TOC CURVES... 9 FIGURE IEEE EXTREMELY INVERSE TOC CURVES... 0 FIGURE DEFINITE TIME... FIGURE I T TIME CURVE... FIGURE A IOC CURVE... FIGURE 8 DIAC AND DSFC EXTERNAL / INTERNAL CONNECTIONS... 8 FIGURE 9 DIFC EXTERNAL / INTERNAL CONNECTIONS... 9 FIGURE 0 DIAC PANEL MOUNTING AND DRILLING... 0 FIGURE DIFC PANEL MOUNTING AND DRILLING... FIGURE A SURFACE MOUNTING DIFC... FIGURE DSFC PANEL MOUNTING AND DRILLING... FIGURE 7 DIAC FRONT AND REAR VIEWS... FIGURE 8 DIFC FRONT AND REAR VIEWS... FIGURE 9 DSFC FRONT AND REAR VIEWS... FIGURE 0 BURDEN CURVE... These Instructions do not purport to cover all details or variations in equipment nor provide for every possible contingency to be met in connection with the installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s purpose, the matter should be referred to the GENERAL ELECTRIC COMPANY. To the extent required the product described herein meets applicable ANSI, IEEE, NEMA, and IEC standards; but no assurances are given with respect to local codes and ordinances because they vary greatly

INTRODUCTION Front View DIFC (899) Features Digital single Phase overcurrent protection General purpose feeder protection 0 / applications Self powered Selectable curves Reset curve enable/disable Low Burden Fully Retrofitable * Functional separate TOC & IOC operations. Wide settings range. Drawout case construction Main To Load 0 * When replacing unit and case (see instruction manual INSTALLATION section for details).

PRODUCT DESCRIPTION General The DIAC, DIFC and DSFC are a family of self-powered, single-phase, digital overcurrent relays. The DIAC is packaged in a GE S style case, the DIFC is packaged in a GE C style case and the DSFC is packaged in a GE V style case. See the HARDWARE DESCRIPTION section for mounting dimensions. The table below gives the model number breakdown. D CA B Revision Amp Nominal Current Amp Nominal Current IF C case IA S case SF V case These relays use waveform sampling of the current input together with appropriate algorithms to provide a time overcurrent (TOC) and an instantaneous overcurrent (IOC) function. Application Time and instantaneous overcurrent functions are widely used in many applications throughout the power system. Typical examples are protection of utility and industrial feeders and short circuit and overload protection for transformers, and motors. For feeder protection, the usual application requires one relay per phase and a fourth relay connected in the residual circuit of three wye connected current transformers (CTs). A typical external connection diagram for this application is shown in Figure 8 OR 9. Use of a separate ground relay provides more sensitive protection for ground faults. The TOC reset characteristics can be set to emulate those of an induction disk or set for fast reset with no intentional delay. Functions The TOC function operates on an RMS current calculated from the sampled values. The IOC function operates on the sampled values, and the algorithm virtually eliminates the decaying DC offset component to achieve low transient overreach of less than 7%. The relays contain two independent settings, one for TOC and one for IOC. TOC The TOC function provides selectable time current curves. IAC IAC -SHORT TIME 7-MEDIUM TIME -LONG TIME 7-SHORT TIME IAC77 9-SHORT TIME IEC Inverse IEC Very Inverse

IEC Extremely Inverse IEEE Inverse IEEE Very Inverse IEEE Extremely Inverse Definite Time I T The IAC, IAC and IAC77 curves match the time current curve of the respective IAC model. This includes the. through 9.9 time dial setting and for both the and amp units. Numbered curves, 7,, 7, and 9 match the shape of the respective IAC model however the time dial positions are not one to one equivalents. The IEC, IEEE and I t curves are based on the following equations: Note IEC equations are defined by IEC - and IEEE equations are defined by IEEE PC7. M = multiple of pickup TD = time dial ( 0.,,, 9.9 ) t = time ( seconds ) IEC Inverse See Figure 9 for graph of equation Reset ì t = í î - time M. 97 ü ýtd -þ Pickup - time ì 0. 0 ü t = í ýtd 00. î -þ M IEC Very Inverse See Figure 0 for graph of equation Reset - time ì t = í î - Pickup - time ì t = í î. M. M - ü ýtd þ ü ýtd þ IEC Extremely Inverse See Figure for graph of equation Reset ì t = í î - time 8. ü ýtd -þ M Pickup - time ì 80. ü t = í ýtd î -þ M

IEEE Inverse See Figure for graph of equation IEEE Extremely Inverse See Figure for graph of equation Reset - time Reset - time t ì = í î M. 97 - ü ýtd þ t = ì í î 8. M - ü ýtd þ Pickup - time Pickup - time t ì = í î. 00 M 00. - + 008. ü ýtd þ t = ì í î. M - + 0. 0 ü ýtd þ IEEE Very Inverse See Figure for graph of equation I T See Figure for graph of equation Reset - time Reset - time t ì = í î. M - ü ýtd þ t = ì í î M ü ýtd þ Pickup - time Pickup - time t ì = í î 9. M - + 0098. ü ýtd þ t = ì í î 0 M ü ýtd þ

00 7 RESET OPERATE 0 7 Time in Seconds 7 9.9 9 8 7 Time Dial Settings. 0. 0. 7 0 00 Multiples of Pickup Setting IAC Inverse Standard OVERCURRENT RELAYS 08A0 DIAC, DIFC, & DSFC GES00 Frequency: 0/0 Hertz Time Dial Range: (0. - 9.9) Current Range: 0. -.9 ( Ampere Relays) 0. -.8 ( Ampere Relays) General Electric CO., 0 Great Valley Parkway, Malvern, PA 9 FIGURE IAC TOC Curve 7

00 RESET OPERATE 0 Time in Seconds 0. 9.9 9 7 8. Time Dial Settings 0.0 0. 7 0 00 Multiples of Pickup Setting IAC Very Inverse Standard OVERCURRENT RELAYS 08A0 DIAC, DIFC, & DSFC GES00 Frequency: 0/0 Hertz Time Dial Range: (0. - 9.9) Current Range: 0. -.9 ( Ampere Relays) 0. -.8 ( Ampere Relays) General Electric CO., 0 Great Valley Parkway, Malvern, PA 9 FIGURE IAC TOC Curves 8

0 7 RESET OPERATE 7 Time in Seconds 0. 7 9.9 9 8 7 Time Dial Settings. 0.0 0. 7 0 00 Multiples of Pickup Setting - ST Short Time OVERCURRENT RELAYS 08A0 DIAC, DIFC, & DSFC GES00 Frequency: 0/0 Hertz Time Dial Range: (0. - 9.9) Current Range: 0. -.9 ( Ampere Relays) 0. -.8 ( Ampere Relays) General Electric CO., 0 Great Valley Parkway, Malvern, PA 9 FIGURE Short Time TOC Curves 9

00 7 RESET OPERATE 0 7 Time in Seconds 7 9.9 9 8 7 Time Dial Settings. 0. 0. 7 0 00 Multiples of Pickup Setting 7 - MT Inverse Medium OVERCURRENT RELAYS 08A07 DIAC, DIFC, & DSFC GES00 Frequency: 0/0 Hertz Time Dial Range: (0. - 9.9) Current Range: 0. -.9 ( Ampere Relays) 0. -.8 ( Ampere Relays) General Electric CO., 0 Great Valley Parkway, Malvern, PA 9 FIGURE 7 Medium Time TOC Curves 0

000 RESET OPERATE 00 Time in Seconds 0 9 9.9 7 8. Time Dial Settings 0. 0. 7 0 00 Multiples of Pickup Setting - LT Inverse Long OVERCURRENT RELAYS 08A08 DIAC, DIFC, & DSFC GES007 Frequency: 0/0 Hertz Time Dial Range: (0. - 9.9) Current Range: 0. -.9 ( Ampere Relays) 0. -.8 ( Ampere Relays) General Electric CO., 0 Great Valley Parkway, Malvern, PA 9 FIGURE Long Time TOC Curves

00 RESET OPERATE 0 Time in Seconds 0. 9 9.9 7 8 Time Dial Settings. 0.0 0. 7 0 00 Multiples of Pickup Setting 7 - ST Inverse Medium Short OVERCURRENT RELAYS 08A09 DIAC, DIFC, & DSFC GES008 Frequency: 0/0 Hertz Time Dial Range: (0. - 9.9) Current Range: 0. -.9 ( Ampere Relays) 0. -.8 ( Ampere Relays) General Electric CO., 0 Great Valley Parkway, Malvern, PA 9 FIGURE 7 Short Time TOC Curves

00 RESET OPERATE 0 Time in Seconds 0. 9.9 9 8 7. Time Dial Settings 0.0 0. 7 0 00 Multiples of Pickup Setting OVERCURRENT RELAYS 08A0 DIAC, DIFC, & DSFC GES009 Frequency: 0/0 Hertz Time Dial Range: (0. - 9.9) IAC 77 Current Range: 0. -.9 ( Ampere Relays) Extremely Inverse Standard 0. -.8 ( Ampere Relays) General Electric CO., 0 Great Valley Parkway, Malvern, PA 9 FIGURE 7 IAC77 TOC Curves

00 RESET OPERATE 0 Time in Seconds 0. 9 9.9 7 8. Time Dial Settings 0.0 0. 7 0 00 Multiples of Pickup Setting 9 - ST Inverse Short OVERCURRENT RELAYS 08A DIAC, DIFC, & DSFC GES000 Frequency: 0/0 Hertz Time Dial Range: (0. - 9.9) Current Range: 0. -.9 ( Ampere Relays) 0. -.8 ( Ampere Relays) General Electric CO., 0 Great Valley Parkway, Malvern, PA 9 FIGURE 8 9 Short Time TOC Curves

00 RESET OPERATE 0 Time in Seconds 9 9.9 7 8 Time Dial Settings 0.. 0.0 0. 7 0 00 Multiples of Pickup Setting IEC Inverse OVERCURRENT RELAYS 08A DIAC, DIFC, & DSFC GES00 Frequency: 0/0 Hertz Time Dial Range: (0. - 9.9) Current Range: 0. -.9 ( Ampere Relays) 0. -.8 ( Ampere Relays) General Electric CO., 0 Great Valley Parkway, Malvern, PA 9 FIGURE 9 IEC Inverse TOC Curves

00 RESET OPERATE 0 Time in Seconds 0. 9.9 9 8 7 Time Dial Settings. 0.0 0. 7 0 00 Multiples of Pickup Setting IEC VERY INVERSE OVERCURRENT RELAYS 08A DIAC, DIFC, & DSFC GES00 General Electric CO., 0 Great Valley Parkway, Malvern, PA 9 Frequency: 0/0 Hertz Time Dial Range: (0. - 9.9) Current Range: 0. -.9 ( Ampere Relays) 0. -.8 ( Ampere Relays) FIGURE 0 IEC Very Inverse TOC Curves

00 RESET OPERATE 0 Time in Seconds 0. 0.0 0. 7 0 00 Multiples of Pickup Setting IEC Ext. Inv. Extremely Inverse OVERCURRENT RELAYS DIAC, DIFC, & DSFC General Electric CO., 0 Great Valley Parkway, Malvern, PA 9. 9.9 9 8 7 Frequency: 0/0 Hertz Time Dial Range: (0. - 9.9) Current Range: 0. -.9 ( Ampere Relays) 0. -.8 ( Ampere Relays) Time Dial Settings 08A GES00 FIGURE IEC Extremely Inverse TOC Curves 7

00 RESET OPERATE 0 Time in Seconds 9 9.9 7 8 Time Dial Settings 0.. 0.0 0. 7 0 00 Multiples of Pickup Setting IEEE Inverse OVERCURRENT RELAYS 08A DIAC, DIFC, & DSFC GES00 Frequency: 0/0 Hertz Time Dial Range: (0. - 9.9) Current Range: 0. -.9 ( Ampere Relays) 0. -.8 ( Ampere Relays) General Electric CO., 0 Great Valley Parkway, Malvern, PA 9 FIGURE IEEE Inverse TOC Curves 8

00 RESET OPERATE 0 Time in Seconds 0. 9 9.9 7 8 Time Dial Settings. 0.0 0. 7 0 00 Multiples of Pickup Setting IEEE Very Inv. Very Inverse OVERCURRENT RELAYS 08A DIAC, DIFC, & DSFC GES00 Frequency: 0/0 Hertz Time Dial Range: (0. - 9.9) Current Range: 0. -.9 ( Ampere Relays) 0. -.8 ( Ampere Relays) General Electric CO., 0 Great Valley Parkway, Malvern, PA 9 FIGURE IEEE Very Inverse TOC Curves 9

00 RESET OPERATE 0 Time in Seconds 0. 9 9.9 7 8 Time Dial Settings. 0.0 0. 7 0 00 Multiples of Pickup Setting IEEE Ext. Inv. Extremely Inverse OVERCURRENT RELAYS 08A7 DIAC, DIFC, & DSFC GES00 Frequency: 0/0 Hertz Time Dial Range: (0. - 9.9) Current Range: 0. -.9 ( Ampere Relays) 0. -.8 ( Ampere Relays) General Electric CO., 0 Great Valley Parkway, Malvern, PA 9 FIGURE IEEE Extremely Inverse TOC Curves 0

00 7 OPERATE Time in Seconds 0 7 9 9.9 8 7 Time Dial Settings 7. 0. 7 RESET 0. 7 0 00 Multiples of Pickup Setting Definite Time OVERCURRENT RELAYS 0A70 DIAC, DIFC, & DSFC GES008 Frequency: 0/0 Hertz Time Dial Range: (0. - 9.9) Current Range: 0. -.9 ( Ampere Relays) 0. -.8 ( Ampere Relays) General Electric CO., 0 Great Valley Parkway, Malvern, PA 9 Figure Definite Time

000 RESET OPERATE 00 Time in Seconds 0 0. 9 9.9 7 8. Time Dial Settings 0. 7 0 00 Multiples of Pickup Setting IT OVERCURRENT RELAYS 08A9 DIAC, DIFC, & DSFC GES007 Frequency: 0/0 Hertz Time Dial Range: (0. - 9.9) Current Range: 0. -.9 ( Ampere Relays) 0. -.8 ( Ampere Relays) General Electric CO., 0 Great Valley Parkway, Malvern, PA 9 FIGURE I t Time Curve

The I T curve has a K value equal to the time dial times 0. The minimum value of K is (0. times 0) and the maximum value is 7 (9.9 times 0). 90 80 70 0 Time in Milliseconds 0 0 0 00 9 8 7 0.. 7 8 9 0 Multples of Pickup Setting Instantaneous OVERCURRENT RELAYS 0A70 DIAC, DIFC, & DSFC GES009 Frequency: 0/0 Hertz Current Range: 0. -.9 ( Ampere Relays) 0. -.8 ( Ampere Relays) General Electric CO., 0 Great Valley Parkway, Malvern, PA 9 Figure A IOC Curve

CALCULATION OF SETTINGS When replacing IAC, IFC or SFC relays, review the time current curves of the digital relays to verify that they conform to the relays being replaced. In some cases it may be necessary to redo the coordination study to assure coordination with other devices. The base time of the Definite Time Curve is second. The base time is multiplied by the time dial to provide the actual operating time. The default or lowest time dial setting for the Definite Time Curve is 0.. The formula; IOC delay in milliseconds = DS x +, where DS is setting on IOC delay dial. The TOC reset characteristic can be controlled from the front panel. The TOC reset can be set to timed reset which emulates the characteristic of an induction disk relay, or instantaneous reset where the reset is fixed at 0 to 0 milliseconds. The system frequency can be set for 0 or 0 Hz controlled from the front panel. The I T curve has a K value of 0 @ time dial of. The range is from to 7 in steps of set by the time dial. The default or lowest time dial setting for the I T curve is 0.. TOC pickup is settable from 0. to.9 amps in 0. amp increments for the amp model, and 0. to.8 amps in 0.0 amp increments for the amp model, a setting of 0 disables the TOC element. The time dial can be set from 0. to 9.9 in 0. increments on both the amp model and the amp model. The only exception is for the Definite Time and I T curves where 0. is the minimum value. The IOC function is settable from to 9 amps in amp increments for the amp model, and 0. to.8 amps in increments of 0. amps for the amp model. Setting the pickup to 0 disables the IOC element. Both models have an IOC delay adjustment from 0 to 00 milliseconds in millisecond steps.

HARDWARE DESCRIPTION Case DIAC and DSFC The DIAC and DSFC relays consist of a case, cover, support structure, and a connection plug to make up the electrical connection. The case is shown in figures 0 and. The external connections are shown in figure 8. It has 0 connection points and a CT shorting bar. As the connection plug is withdrawn the trip circuit is broken prior to the current shorting bar engagement. The window provides visual indication of the CT shorting. DIFC The DIFC relays consist of a molded case, cover, support structure, and a connection plug to make up the electrical connection. The case is shown in figures 0 and 0A. The external connections are shown in figure 9. It has connection points and a visible CT shorting bar. As the connection plug is withdrawn the trip circuit is broken prior to the current shorting bar engagement. The window provides visual indication of the CT shorting. Adjustments All customer settings for the relay are accessible from the front of the relay. The relay cover must be removed to gain access to the settings. The cover has provisions for a sealing wire. The settings are left to right, pickup current level for the time element, time dial, curve selection, frequency/reset time, pickup current level for the instantaneous element, and the instantaneous element time delay. The settings are all calibrated and are set by turning the rotary switch to the desired value. The switches are recessed, a small screw driver is required to make the adjustment. The relay may be supplied with one of three pointer styles as shown. The color is the color of the indicator, note the arrow location, all switches are shown in the 9 :00 position. RLQWHU VW\OHV <HOORZ UDQJH :KLWH The TOC pickup current is set directly in Amps with two rotary switches. An arrow is used to indicate setting position. Setting the TOC or the IOC pickup current between, but not including 0 and a value less than minimum 0. (amp) or 0. (Amp) will result in the relay defaulting to its minimum setting. Setting the TOC or IOC pickup current to 0 will disable their respective elements. Although the time dial can be set to a value less than minimum the relay will use the minimum setting. The relay also provides a front panel trip circuit test. A actuating lever that must be pulled and then lifted is provided to trip the device connected to the relay. The level directly operates the trip contacts.

Targets And Indicators The yellow pick-up LED, will come on solid for the TOC function when the input current to the relay is higher than the set point. The location of the LED is between the frequency/reset switch and the IOC pickup level switch. It may be desirable to know when the relay is powered up and operating. The relay must be energized at or above 9% of the minimum possible setting and below pick-up set point. To activate, turn the SELECT switch one step clockwise or one step counterclockwise. This will cause the pickup LED to blink at second intervals while current is below the pick-up set point. Minimum current is 9% of minimum TOC pickup setting for both the amp and amp models. A blinking LED indicates the microprocessor is executing code and outputting signals. The relay uses a target and seal-in unit as its tripping element. The relays have one TOC target and one IOC target. The targets are mechanically latched when the function trips. The trip contacts will remain closed until the trip circuit current drops below 0.9 Amps. Reset And Manual Trip Targets can be reset by depressing the front cover target reset button for the DIFC or lifting the target reset level at the lower left edge of the cover on the DIAC and DSFC. Trip Circuit Test The front panel contains two manual trip levers to test the trip circuit. The relay cover must be removed to access the lever. The lever must be pulled and then lifted which prevents unintentional uplifted to prevent unintentional operation. Trip Circuit CAUTION: The trip circuit is polarity sensitive. The trip circuit will not be damaged if connected in reverse. However, it will not trip the associated breaker. The trip circuit is configured to have the positive battery terminal connected to stud for the TOC and IOC trip circuit and the negative to stud (TOC) and stud (IOC). NOTE: Both trip circuits are suitable for use with Cap-Trip devices. Cover Installation DIAC and DSFC NOTE: When replacing the cover on the DIAC and DSFC relays the reset wire should be locked behind the nameplate by a slight left to right motion to place the reset wire in the correct position. Receiving, Handling And Storage Immediately upon receipt, the relay should be unpacked and examined for any damage sustained during shipment. If damage occurred during shipment a damage claim should be filed at once with the transportation company, and the nearest GE sales office should be notified. If the relay is not installed im-

mediately, it should be stored in its original carton in a location that is dry and protected from dust, metallic chips and severe atmospheric conditions. braided ground lead connected to Terminal when replacing IFC relays. The IFC relay and case must be removed and replaced with the DIFC relay and case. INSTALLATION Environment Installation of the relay should be in a clean dry location that is free from dust. Mounting The relay should be securely mounted on a vertical surface that provides accessibility to both the front and rear of the unit. The outline and panel drilling dimensions are provided in figures 0,, A and for each stile case. An additional surface mounting option is available for the DIFC relay. Surge Ground (DIAC & DSFC) The relay should be grounded to the station ground mat with a AWG braided ground lead connected to terminal. If the relay is to be retrofitted in a panel, terminal should be removed from the new case and installed into the old case. For the surge protection to function properly the relay must be grounded. Surge Ground & RFI Immunity (DIFC) The relay should be grounded to the station ground mat with a AWG 7

FIGURE 8 DIAC and DSFC External / Internal Connections 8

FIGURE 9 DIFC External / Internal Connections 9

FIGURE 0 DIAC Panel Mounting and Drilling 0

FIGURE DIFC Panel Mounting and Drilling

FIGURE A SURFACE MOUNTING DIFC

FIGURE DSFC Panel Mounting and Drilling

ACCEPTANCE TESTS Immediately upon receipt of the relay, an inspection and acceptance test should be made to make sure that no damage has been sustained in shipment, and that the relay calibrations have not been disturbed. Visual Inspection Check the nameplate stamping to make sure that the model number and rating of the relay agree with the requisition. Remove the relay from its case and check that there are no broken or cracked molded parts or other signs of physical damage, and that all screws are tight. Mechanical Inspection. The target and seal-in unit, pull and lift the TOC lever to test the target, repeat the test for the IOC target. The Target flag should remain when the lever is released. Reset the target by pushing the reset bar.. Make sure that the fingers and shorting bars agree with the internal connections diagram. Caution Every circuit in the drawout case has an auxiliary brush. It is especially important on current circuits and other circuits with shorting bars that auxiliary brush be bent high enough to engage the connection plug or test plug before the main brushes do. This will prevent CT (current Transformer ) secondary circuits from being opened. Electrical Tests DRAWOUT RELAYS, GENERAL Since all drawout relays in service operate in their cases, it is recommended that they be tested in their cases or an equivalent case. A relay may be tested without removing it from the panel by using the appropriate test plug. For a C case use XCA. test plug and for a V or S case use the XLA series test plug refer to GE s product catalog GEZ- 77D section. Although the test plugs provide greater flexibility, it requires C.T. shorting jumpers and exercise of greater care since connections are made to both the relay and the external circuitry. INVERSE TIME UNIT Pickup Verification - Connect the relay as indicated in Figure or. In order to apply current to the relay, use a 0/0 Hz voltage source, with a variable resistor in series, or an electronic current source. - Set the relay at the desired pickup TOC and disable the instantaneous unit by setting the instantaneous current setting to zero (0). Apply current to the relay and verify that the Pickup LED on the front of the relay

lights between 98% and 0% of the pickup TOC setting. If the relay is set to blink between power up and pickup, look for the LED to be on most or all of the time to indicate pickup. Reduce the current applied, verifying that at a value between 9% and 00% of the pickup TOC, the relay Pickup LED turns off or blinks if set to blink. Verification of Operating Time Because the Digital self powered series of relays has many different curve characteristics, the basic test instruction will be given and the data for each of the curves can be found in Table. With the relay still connected as indicated in Figure or, set the time overcurrent unit to minimum pickup and set the corresponding time dial to. Successively apply currents of,, and 0 times pickup TOC, verifying that the operating times are within the margins indicated in Table. Note Time measured in seconds Table : Pickup Times for Varying Multiples of Pickup (MPU) MPU CURVE* 0 IAC. -.00.9 -.8.9 -. IAC. - 7.. -.7 0.87-0.79 -ST 0.98-0.0 0. - 0.7 0. - 0. 7-MT 0. -. 8.8-9.7.7 -. -LT.7-7. 7.8-9. 0.78 -.9 7-ST 0.78-0.87 0. - 0. 0. - 0.707 IAC 77.9-7.7 0.89-0.9 0. - 0.9 9-ST 0.89-0.99 0. - 0.9 0.7-0.0 IEEE Inverse.9 -.99.9 -.7. -. IEEE Very Inverse. - 7.. -. 0. - 0.7 IEEE Ext. Inverse 8.7-9.7.8 -. 0.7-0. IEC Inverse.7 -..0 -..9 -. IEC Very Inverse. - 7.0. -.7 0.9-0.78 IEC Ext. Inverse. -.7. -.7 0.9-0. Definite Time.7 -..7 -..7 -. T.7 -. 0.9-0. 0.0-0.0 * TD =

For the Definite Time Characteristics, based on any current input, the time should be half of the maximum value. Verification of Time Dial Set the relay at the minimum pickup TOC and verify that with an input current of five times (x) pickup TOC, the operating time is between the margins shown in Table. Table : Pickup Times for Varying Time Dials Time Dial CURVE* 0 7 IAC. -.0. -.9 0.99 -.0 0.7-0. IAC.7 -.0.78 -.98 0.7-0.8 0.0-0.08 -ST 0.9-0. 0. - 0. 0.0-0. 0.08-0.0 7-MT 7. - 9.. -..7 -.8.78 -.98 -LT.9-7.7. -.7 0. -.. -.88 7-ST 0.77-0. 0. - 0.7 0. - 0. 0.09-0. IAC77.8 -.0. -. 0. - 0.0 0.8-0. 9-ST 0.9-0.77 0.9-0. 0. - 0. 0.0-0. IEC Inverse.9 -.7.79 -.. -. 0. - 0.78 IEC Very Inverse.0 -.0.7 -. 0.9 -.0 0. - 0.9 IEC Ext. Inverse.9 -.8.09 -. 0.9 -.0 0.9-0. IEEE Inverse.08 -..0 -. 0.9 -.0 0. - 0.8 IEEE Very Inverse.9 -..9 -.88 0.7-0.88 0.7-0.0 IEEE Ext. Inverse. -.8. -.8 0.7-0.8 0. - 0.9 Definite Time 9. - 0.. - 7..8 -. 0.9 -.0 T 0. - 0.8 0. - 0.8 0. - 0.7 0.0-0.07 * MPU = X

INSTANTANEOUS UNIT The Instantaneous unit is designed similarly to a hinged armature instantaneous unit. The instantaneous unit will react differently depending on how the signal is applied. If the signal is applied suddenly with no prefault current, the operating time will be longer. If a prefault current is applied prior to the fault the operating time will be shorter. The following test determines that the instantaneous unit is working correctly and confirms the operating time for faults applied with no prefault current. IOC delay setting. Apply Amps (Amp rated relay) or. Amps ( Amp rated relay) and measure the operating time. The operating time should be between ms and ms. This time is subject to dependent on the multiple of pickup current and the fault incidence angle. A graph of how the instantaneous unit varies as a function of input current is provided in this book for reference, figure A. Connect the relay as shown in figure or, Set the instantaneous unit pickup to Amps (Amp rated relay) or 0.Amps (Amp rated relay) with a zero 7

Start TIMER Stop Single Phase Current Source AUX TOC contact T I in T T T T Target & Seal-in T DIFC - Negative /00VDC Power Supply Current Limited to 00ma + Positive FIGURE DIFC Test Setup for Pickup and Operating Time Verification Start TIMER Stop Single Phase Current Source AUX TOC contact T7 I in T T T8 T Target & Seal-in T - Negative /00VDC Power Supply Current Limited to 00ma + Positive DIAC or DSFC FIGURE DIAC or DSFC Test Setup for Pickup and Operating Time Verification 8

Start TIMER Stop Single Phase Current Source AUX IOC contact T I in T T T T Target & Seal-in T DIFC - Negative /00VDC Power Supply Current Limited to 00ma + Positive FIGURE DIFC Test Setup for Instantaneous Unit Start TIMER Stop Single Phase Current Source AUX IOC contact T0 I in T T T9 T Target & Seal-in T DIAC or DSFC - Negative /00VDC Power Supply Current Limited to 00ma + Positive FIGURE DIAC or DSFC Test Setup for Instantaneous Unit 9

PERIODIC TESTS It is recommended that the user perform a periodic test to verify that the relay is operating properly. It is recommended that a portion of the acceptance tests be performed to verify the relay. An inspection of the seal-in contacts can be performed by removing the relay from its case and visually inspecting the contacts for corrosion. SERVICING If the relay fails to perform as specified in this instruction manual consult the factory or call your local GE sales office. Before returning the relay consult with the factory s technical support. It is not recommended that the relay be serviced to the component level. This requires substantial investment in repair/test equipment and in technical expertise, and usually results in a longer down time than if a spare relay were used in its place, while the unit is shipped back to the factory. 0

FIGURE 7 (9897/8998) DIAC Front and Rear Views

FIGURE 8 (899/899) DIFC Front and Rear Views

FIGURE 9 (899/899) DSFC Front and Rear Views

SPECIFICATIONS Burdens Burdens for the over-current units are listed in Table. Burdens decrease with increasing current above minimum setting, due to the power supply shunting in the power supply circuit. Since the power supply is the major portion of the burden, the burden for a given input current will be constant, irrespective of pick-up settings on both TOC and IOC units. Table Burden Settings Burden @ Minimum Setting Burden in ohms (Z) at multiples of minimum pickup unit range Hz R jx Z Ð X 0X 0X 00X A. /.8 0 8.8 9.. 9....78 A. /.9 0.8...7.9.09.0.0 00 Burden in VA 0 AMP Model AMP Model 7 8 7 0 00 0. 7 8 7 0 Input Current OVERCURRENT RELAYS DIAC, DIFC, & DSFC Power Management Frequency: 0/0 Hertz Burden General Electric CO., 0 Great Valley Parkway, Malvern, PA 0A70 GES000 Current Range: 0. -.9 ( Ampere Relays) 0. -.8 ( Ampere Relays) FIGURE 0 Burden curve

SPECIFICATIONS Ratings Frequency 0 / 0 Hz Current A or A Models Maximum Permissible Current A Model / A Model Continuous A A Second 0 A 0 A Second 00 A 00 A Operating Current Range A Model / A Model minimum.09 A.7 A I T (constant) 0 8000 Maximum Transient Overreach 7% Burdens AC Current Circuit: A / A Unit Burden 0. / 0.A 0.VA.0 / A.VA See Figure 0 for curve and Table. Contact Ratings Output Contacts DC Resistive DC Inductive L/R=0ms Voltage Cont. Make & carry sec. V 0V V 0V 70V Break 0A 0A.A.A 0A 0A.A.A.0A Max load 0W 0VA Environmental Ambient Temperature: Storage: -0 to +8 o C Operation: -0 to +70 o C Humidity: Up to 9% without condensing. Insulation Withstand Tests: Impulse Voltage: KVpeak,./0ms, 0. Joules. Per: IEC-, Class III Surge Withstand Capability: Fast Transient: Per: ANSI C7.90. Per: IEC -- Class IV Oscillatory: Per: ANSI C7.90. Per: IEC --, Class IV Radio Frequency Withstand: MHZ-GHZ Keyed every MHZ for seconds. Per: ANSI C7.90. Per: IEC -- Electrostatic Discharge: Per: IEC -- NOTE: Suitable for Cap-Trip devices.