Reduction of Oil Discharge for Rolling Piston Compressor Using CO2 Refrigerant

Similar documents
Development of Scroll Compressor for 16HP VRF System

Development of High Performance 3D Scroll Compressor

CFD Analysis of Oil Discharge Rate in Rotary Compressor

Development of a Low Noise Rotary Compressor

Development of High Efficiency Swing Compressor for R32 Refrigerant

The Digital Simulation Of The Vibration Of Compressor And Pipe System

A Low Friction Thrust Bearing for Reciprocating Compressors

The Performance Optimization of Rolling Piston Compressors Based on CFD Simulation

Development of DC Inverter Scroll Compressor used for Marine Container Refrigeration Unit

Numerical Simulation and Performance Analysis of Rotary Vane Compressors for Automobile Air Conditioner

Development of Rotary Compressor for Highefficiency CO2 Heat-pump Hot-Water Supply System

Theoretical and Experimental Investigation of Compression Loads in Twin Screw Compressor

Small Oil Free Piston Type Compressor For CO2

Oil Circulation Rate in Rotary Compressor: Its Measurement and Factors Affecting the Rate

Discharge Characteristics of an Oil Feeder Pump Using Nozzle Type Fluidic Diodes for a Horizontal Compressor Depending onthe Driving Speed

Noise Reduction of Accumulators for R410A Rotary Compressors

CFD Analysis of Discharge Gas flow in Rotary Compressor for OCR reduction

A Two Stage-Double Acting Scroll Air Compressor

Twin-Screw Compressor Performance and Suitable Lubricants with HFC-134a

Experimental Study Of The Oil Injection Screw Air Compressor

An Experimental Analysis on the Flow Rate in Scroll Compressors

A Study On The Oil Supply System Of A Horizontal Rotary Compressor With Vane Utilized For Oil Feeding

Effects of Refrigerant Injection on the Scroll Compressor

Research And Development Of Variable-Speed Scroll Compressor

Scroll Expander for Carbon Dioxide Cycle

Investigation of Torque-Fluctuation Reducer Made of Permanent-Magnets for Screw Compressors

Structural Analysis Of Reciprocating Compressor Manifold

Availability Analysis For Optimizing A Vehicle A/C System

Evaluation of methods to decrease the discharge temperature of R32 scroll compressor

Research of the Effectiveness of Use of New Mechanism in Reciprocating Compressors

Extending the Operation Range of Dry Screw Compressors by Cooling Their Rotors

Developing a Compact Automotive Scroll Compressor

Influence of Cylinder Bore Volume on Pressure Pulsations in a Hermetic Reciprocating Compressor

Comparing FEM Transfer Matrix Simulated Compressor Plenum Pressure Pulsations to Measured Pressure Pulsations and to CFD Results

Development of Highly Efficient Compressor Series Driven by IPM Motors

Optimum Rotor Geometrical Parameters in Refrigeration Helical Twin Screw Compressors

The Reduction of the Noise/Vibration Generated by the Discharge Valve System in Hermetic Compressor for Refrigerator

CFD Simulation of a Scroll Compressor Oil Pumping System

Study of a Novel Compliant Suspension Mechanism in Low Side Type Scroll Compressor

Properties of Polyvinylether (PVE) as a Lubricant for Air Conditioning systems with HFC Refrigerants?Data Update?

A Study on the Starting Characteristics of a Reciprocating Compressor for a Household Refrigerator

A Prototype Oil-Less Compressor for the International Space Station Refrigerated Centrifuge

New Capacity Modulation Algorithm for Linear Compressor

Developments in Dry Running Seals for Reciprocating Compressors

Numerical and Experimental Research on Vibration Mechanism of Rotary Compressor

The Characteristics of LGE Linear Oscillating Motor

Performance Improvement of a Reciprocating Air Microcompressor

Compressor Noise Control

Reducing the Fuel Consumption by Speed Control of the Air Conditioning Compressor

The Design Aspects of Metal- Polymer Bushings in Compressor Applications

Lubrication Analysis of Journal Bearings in R410A Rotary Compressor

Twin Screw Compressor Performance and Its Relationship with Rotor Cutter Blade Shape and Manufacturing Cost

Reduction Of Noise And Over-Compression Loss By Scroll Compressor With Modified Discharge Check Valve

Elimination of Instability in Modulating Capacity Reciprocating Compressor

Practical Stability Performance of Polyvinylether (PVE) With HFC Refrigerants

Design Parameters to Determine Tangential Vibration of Rotary Compressor

Critical Solution Temperatures for Ten Different Non-CFC Refrigerants with Fourteen Different Lubricants

Design and Test of Transonic Compressor Rotor with Tandem Cascade

Development of a New Type Cylinder Head for Piston Compressors

Transmission Error in Screw Compressor Rotors

Scroll Compressor Oil Pump Analysis

Forces Analysis of Rotary Vane Compressor for Automobile Air Conditioning System

The Effects of the Tribo-Conditions and Antiwear Additives on the Degradation of an Ester Oil and Analyses of Degradation Products

A Novel Automotive Two-Stage A/C Compressor

Infinitely Variable Capacity Control

Development of TPL and TPS Series Marine Turbocharger

A Study on the Optimum Shape of Automobile Air Cleaner Diffuser

COMPRESSIBLE FLOW ANALYSIS IN A CLUTCH PISTON CHAMBER

ABSTRACT 1. INTRODUCTION

The Influence of Discharge Ports on Rotor Contact in Screw Compressors

Application of Trunk Piston Labyrinth Compressors in Refrigeration and Heat Pump Cycles

Comparison Between Different Arrangements of Bypass Valves in Scroll Compressors

Optimization of Suction Muffler Using Taguchi s DOE Method

Experimental Investigation of Sound Pressure Levels Variation During Modulation of a Compressor in a Unit Case Study

A Large Modern High Speed Reciprocating Compressor

STUDY ON COMPACT HEAT EXCHANGER FOR VEHICULAR GAS TURBINE ENGINE

Numerical Investigation of the Gas Leakage through the Piston-Cylinder Clearance of Reciprocating Compressors

Low Capacity Hermetic Type Compressor For Transcritical CO2 Applications

Two-Stage Rolling Piston Carbon Dioxide Compressor

Noise Reduction in Bus A/C Systems with Screw Compressors Part II

Study on Flow Fields in Variable Area Nozzles for Radial Turbines

Experimental Study on Inlet Structure of the Rod Pump with Down-hole Oil-water Hydrocyclone

Theoretical and Experimental Study of an Oil-Free Scroll Vapor Expander

Diesel-Driven Compressor Torque Pulse Measurement in a Transport Refrigeration Unit

Theoretical and Experimental Evaluation of the Friction Torque in Compressors with Straddle Bearings

High Efficiency Development of a Rotary Compressor by Clarification of its Shaft Dynamic Motion

Storage, Bulk Transfer, and In-Plant Handling of Zeotropic Refrigerant Blends

Energy Saving Technologies for Elevators

Transient Modeling of Vapor Compression Refrigeration Systems Using Measured Compressor COP

Application Technology regarding High-Powered Electric Power Steering System*

Reciprocating Air Microcompressor

Spool Seal Design and Testing for the Spool Compressor

Effect of Stator Shape on the Performance of Torque Converter

Performance Analysis of a Sliding -Vane Rotary Compressor for a Household Refrigerator/Freezer

Lower-Loss Technology

HCFC-22 Retrofits. There has been increased emphasis on retrofitting R-22

Development and Application of a Software Package for the Design of Twin Screw Compressors

On the Classification of Compressor,Pump or Engine Designs Using Generalized Linkages

Experimental Investigation of Damping Coefficient for Compressor Reed Valves

A magnetic fluid seal for rotary blood pumps: Long-term performance in liquid

Transcription:

Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2006 Reduction of Oil Discharge for Rolling Piston Compressor Using CO2 Refrigerant Takeshi Ogata Matsushita Electric Industrial Co. Hiroshi Hasegawa Matsushita Electric Industrial Co. Atsuo Okaichi Matsushita Electric Industrial Co. Fumitoshi Nishiwaki Matsushita Electric Industrial Co. Follow this and additional works at: http://docs.lib.purdue.edu/icec Ogata, Takeshi; Hasegawa, Hiroshi; Okaichi, Atsuo; and Nishiwaki, Fumitoshi, "Reduction of Oil Discharge for Rolling Piston Compressor Using CO2 Refrigerant" (2006). International Compressor Engineering Conference. Paper 1757. http://docs.lib.purdue.edu/icec/1757 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

C095, Page 1 Reduction of Oil Discharge for Rolling Piston Compressor Using CO 2 Refrigerant Takeshi Ogata 1, Hiroshi Hasegawa 1, Atsuo Okaichi 1, Fumitoshi Nishiwaki 1 1 Living Environment Development Center, Matsushita Electric Industrial Co., Ltd., 3-1-1 Yakumo-naka-machi, Moriguchi City, Osaka, 570-8501, Japan (Tel: +81-6-6906-0477, Fax: +81-6-6904-5163, E-Mail: ogata.t@jp.panasonic.com) ABSTRACT In this paper, two approaches are presented to decrease the oil discharge ratio from the CO 2 rolling piston compressor. The first approach is a numerical analysis on the oil inflow into the compression chamber. Optimizing the radial sealing line of the rolling piston and the vane groove sealing line decrease the oil discharge ratio from compression chamber to the high-pressure shell. The second approach is a numerical analysis on the mixing flow of CO 2 refrigerant and oil in the high-pressure shell. The numerical analysis revealed that there are circling flows of CO 2 refrigerant with oil mist in the high-pressure shell and that circling flows are greatly related to the oil discharge ratio from the CO 2 rolling piston compressor. According to the above-mentioned analysis, optimized dimensions of the piston and vane can be determined, and a plate to prevent circling flows of CO 2 refrigerant and a cover to separate the oil from circling flows is designed. The decrease of the oil discharge ratio from the CO 2 compressor is confirmed by the experiment. As a result, a compact highly efficient CO 2 rolling piston compressor with oil discharge ratio less than 0.1wt% has been successfully developed. 1. INTRODUCTION In recent years, regulations against Freon-based refrigerants such as hydro-chlorofluorocarbons (HCFCs) and hydrofluorocarbons (HFCs), which have high global-warming potential (GWP), have been tightened from the viewpoint of global warming. Consequently, much attention has been given to the development of a high-efficiency heat pump that uses CO 2, which has a low GWP and exists ubiquitously in nature. CO 2 heat pump has excellent performance in heating application. Furthermore, its coefficient of performance (COP) is 3 or more. The key device of a CO 2 heat pump is a compressor using CO 2 refrigerant. This device must be compact, efficient, and reliable. The oil used for lubrication and cooling in the sealing and sliding portions of the compression chamber greatly influences the efficiency and reliability of the device. Consequently, it is important to maintain the oil in a stable condition in the compressor. When excessive oil is discharged from the shell with the flow of refrigerant, the oil in the compressor decreases to an unacceptably low level, which degrades the compressor's reliability. In addition, the performance of a CO 2 heat pump system generally deteriorates with an increased oil circulation ratio (OCR). This is because heat transfer is hindered when a portion of the circulating oil attaches to the wall of the tube in the heat exchanger. The heat transfer coefficient begins to decrease when OCR exceeds about 1 wt% (1). Accordingly, it is important to reduce the oil discharge ratio from the compressor. In this study, countermeasures were devised to achieve reduced the oil discharge ratio based on numerical analysis. The effect of our approach was confirmed by experimental examination. This report also describes the development of a rolling piston compressor with CO 2 refrigerant that largely reduces the oil discharge ratio.

2. Structure of Rolling Piston Compressor Using CO 2 Refrigerant and Procedure for Reducing Oil Discharge Ratio C095, Page 2 2.1 Basic Structure of CO 2 Rolling Piston Compressor Figure 1 shows a cross-section of the CO 2 rolling piston compressor. The motor assembly is at the center of a shell, and the compression mechanism, a one-cylinder rolling piston, is at the bottom. The major specifications of the compressor are shown in Table 1. The refrigerant is compressed in the compression chamber and then discharged through the discharge port to the area under the rotor in a shell. After that, the refrigerant is transferred to the upper part of the shell through the gap between the rotor and stator or between the stator and shell, and then it is discharged through a discharge pipe installed in the upper part of the sell. The inside of the shell is filled with compressed high-pressure CO 2 refrigerant. There is an oil sump at the bottom, and a portion of the accumulated oil lubricates the journal bearing, flows out from the upper part of the bearing, and returns along the upper surface of the bearing to the sump. Since the inside pressure of the compression chamber during suction and compression is lower than that of the shell, oil in the sump is supplied to the compression chamber through a sliding gap, thus lubricating, sealing, and cooling the sliding portion of the compression chamber. Oil supplied to the compression chamber is mixed with CO 2 refrigerant and discharged to the interior of the shell, and then most of the oil is separated from the CO 2 refrigerant and returned to the oil sump. A part of the oil, however, is not separated but flows out along with the CO 2 refrigerant flow to the heat pump system through an discharge pipe in the upper part of the shell. Discharge pipe Rotor Shaft Shell Refrigerant flow Oil flow Discharge Port Stator Piston Journal bearing Cylinder Compression chamber Muffler Suction Port Oil sump Vane Figure 1: Cross-section of CO 2 rolling piston compressor Table 1: Compressor major specification of CO 2 compressor Shell diameter Shell height Suction volume Motor 88 mm 180 mm 1.3 cm 3 DC brushless Refrigerant CO 2

C095, Page 3 2.2 Procedure for Reducing Oil Discharge Ratio The compression performance of a prototype was evaluated, and consequently a good result was achieved with a target efficiency of 55%. However, the quantity of oil discharge was as much as 3.60 wt% for mass flow rate of refrigerant circulation. To prevent a large decrease in system performance, it is necessary to reduce the oil discharge ratio from the shell of the compressor to 1 wt% or less (1). To overcome this problem, we have devised the following two countermeasures to reduce oil discharge ratio: (1) Reduce the oil discharge ratio from the compression chamber to the shell by preventing the flow of excessive oil into the compression chamber. (2) Reduce the oil discharge ratio from the shell to the heat pump system by separating the oil from the CO 2 refrigerant in the shell. By taking these countermeasures, the oil discharge ratio was reduced (OCR target: 0.1 wt% or less). Details of these countermeasures are described below. 3. Reduction of Oil Inflow to Compression Chamber In a CO 2 heat pump system, the highest pressure is 10 MPa or more and the lowest pressure is 4 MPa or less. It is assumed that this pressure difference, which is larger than that using conventional refrigerant, causes excess oil supply in the compression chamber and thus increases the oil discharge from the compression chamber to the shell. Figure 2 shows the oil flow path to the compression chamber. The oil flows into the compression chamber mainly along the upper and lower end surfaces of the piston and the vane-sliding surface. High-pressure oil present on the inner surface of the piston and on the back surface of the vane causes the oil to flow into the compression chamber during suction and compression. Although this excess oil flow into the compression chamber can be prevented by designing each surface sufficiently wide, when the diameter of the shell is not changed the vane seal length L V becomes shorter with an increase in the piston seal length L P. Accordingly, the oil flow into the compression chamber was calculated with the variable of piston seal length, and the results shown in Fig. 3 were obtained. As the figure shows, although the oil flow from the upper and lower surfaces of the piston into the compression chamber decreases with the increase in L P, the oil flow from the vane groove surface increases, since L V decreases with the increase in L P. From these relations, it can be concluded that the total oil inflow is the least when it proceeds from the upper and lower surfaces of piston L P = L P opt and from the vane groove surface L V = L V opt. Oil inflow Suction port Suction pressure High pressure oil Lp Lv Figure 2: Oil inflow path to compression chamber Oil inflow [wt%] Vane seal length L V [mm] L V Max 0 50 40 30 20 Total oil inflow Oil inflow from vane Oil inflow from piston L P opt 10 L V opt 0 0 L P Max Piston seal length L P [mm] Figure 3: Relationship between each seal length and oil inflow

C095, Page 4 However, since the vane divides the compression chamber into a high-pressure space and a low-pressure space, there is always a differential pressure around the top of the vane. In the model shown in Figure 4, the differential pressure applied to the vane stress concentration at the area surrounded by the broken red line. Because this stress concentration increases when the vane groove L V is shortened, it is undesirable to design a short vane groove L V from the viewpoint of the groove's reliability. By considering reliability in design, it was found that the vane seal length L V should be slightly longer than L V opt. Therefore, we decided to employ this length as the optimum design value. An experimental examination using the above optimum design showed that the oil discharge ratio was reduced by 0.4 wt%. Low-pressure space Differential pressure Stress concentration High-pressure space Lv Figure 4: Model drawing of stress concentrated at vane groove 4. Acceleration of Oil Separation in Shell 4.1 Examination of Oil Separation Mechanism in Shell The CO 2 refrigerant discharged from the compression chamber to the area under the rotor in the shell passes mainly through a gap between the stator and the shell to an upper space in the shell, from where it flows out through the discharge pipe. To separate the oil efficiently in the shell and reduce the oil discharge, it is necessary to study the flow field inside the shell. Thus, we first analyzed this for the single phase of CO 2 refrigerant by using a fluid analysis tool, FLUENT 6.0, and the κ-ε model for turbulent flow. Figure 5 and Table 2 show the calculation region and the calculation conditions, respectively. Discharge Pipe Shell Rotor Stator Gap between the rotor and stator Gap between the stator and shell Bottom wall (Oil surface) Discharge Port Figure 5: Calculation region Table 2: Calculation conditions Inlet condition Pressure Temperature Density Viscosity Mass flow rate 10.4 MPa 88 217.9 kg/m 3 22.85 10-6 Pa s 46.0 kg/h Rotor frequency 120 Hz

C095, Page 5 The streamline analysis results of CO 2 refrigerant inside the shell is shown in Figure 6. These results revealed that the motor rotation stirs CO 2 refrigerant, forming a circling flow in the upper and lower spaces of the rotor. Shell Discharge Pipe Rotor Discharge Port Figure 6: Analysis results of CO 2 flow in shell The oil flow velocity distribution in the shell was analyzed next. The Dispersed Phase Model (DPM) was adopted as a multi-phase flow model so that in the calculation the oil would be regarded as a small particle mixed with CO 2 refrigerant. The calculation region is the same as shown in Figure 5, and the analysis tool is FLUENT6.0. To examine the relationship between the circling flow velocity and the oil flow, we compared two cases: when the rotor rotates at 120 Hz and when the bottom surface of the rotor is stopped (the upper surface and the side surface rotate at 120 Hz). The results are shown in Figure 7. When the rotor rotated at 120 Hz, the circling flow generated by the rotor was stronger and the influence of oil flow velocity was observed to be lager compared with the case when the bottom surface of the rotor was stopped. It was also observed that the oil streamlines were concentrated in the upper part of the space and moved toward the upper part of the shell. On the other hand, when the lower part of the rotor was stopped, the oil flow was slow and the oil streamlines were observed to spread over the entire space. This is because stopping the bottom surface of the rotor weakens the circling flow of the CO 2 refrigerant at the bottom of the rotor as well as the oil particle flow, and thus the oil particles tend more to move downward by the gravity spreading throughout the entire space, not limited to the upper part (the oil density is around five times larger than CO 2 refrigerant). This finding suggests that it is possible to adjust the separation efficiency of the CO 2 refrigerant and oil in the lower space of the shell by changing the intensity of the circling flow. 4.0 The rotor rotated at 120 Hz The lower part of the rotor was stopped Oil flow velocity [m/s] 0.0 Figure 7: Oil flow rate distribution and oil streamline in lower space of shell.

C095, Page 6 4.2 Restraining Circling Flow From the results of the above flow analysis, we devised a structure that employs a circling-flow-prevention wall at the bottom end of the rotor and examined its effect. Figure 8 shows the analysis results of oil concentration distribution when the rotor rotates at 120 Hz and when the bottom surface of the rotor is stopped (the latter case is the model in which a circling-flow-prevention wall is installed at the bottom of the motor). The calculation region and conditions are the same as those for the analysis shown in Fig. 7. The oil flow moving through the stator gap to the upper space of the shell was 74.3% when the rotor turns at 120 Hz and 42.7% when the bottom end of the rotor is stopped. Consequently, we analytically confirmed that the circling-flow-prevention wall is effective in reducing the amount of oil discharge to the upper part of the shell. The lower part of the rotor was stopped High The rotor rotated at 120 Hz To the upper space oil concentration [%] Low 74.3 % 25.7 % To the oil sump 100 % 42.7 % 57.3 % 100 % Figure 8: Influence of oil concentration distribution by circling flow In an experiment to confirm the effect of the circling-flow-prevention wall, the oil discharge ratio was reduced to 0.12 wt%. Therefore, by separating the refrigerant and oil, the oil discharge ratio could be successfully reduced. 4.3 Journal Bearing Cover Another method of refrigerant/oil separation is to prevent the oil around the upper surface of the journal bearing from being lifted by the circling flow. Figure 9 illustrates the lubrication oil discharge from the journal bearing. As shown in the figure, the oil used for journal bearing lubrication flows through the gap between the bearing and shaft and then flows out from the upper part of the bearing. The oil makes contact with the flow of CO 2 refrigerant at the lower part of the rotor, being lifted by the circling flow. This can be a cause of increased oil discharge. Therefore, a cover was installed on the journal bearing as shown in Figure 10 to prevent the oil after lubrication from making contact with the circling flow. This accelerates the oil separation. An experimental examination achieved oil discharge ratio of 0.08 wt%. Circling flow Oil flow Journal bearing cover Overflowing oil Journal bearing Figure 9: Flow of journal bearing lubrication oil Figure 10: Cross-section of CO 2 rolling piston compressor with journal bearing cover

5. Performance Evaluation of Oil Discharge Ratio Reduction Specifications C095, Page 7 We made a prototype compressor with optimized piston seal length and a CO 2 refrigerant/oil separation mechanism for restraining the circling flow by the rotor, and we evaluated the performance. The evaluation results are shown in Table 3. This approach not only sufficiently reduced the oil discharge ratio but also improved the compressor efficiency. The reasons for improved compressor efficiency are considered as follows: (1) reduced heat loss due to the oil by optimizing the oil quantity flowing into the compressor chamber, (2) improved volume efficiency by reducing the excessive oil in the compressor chamber, and (3) reduced oil film on the wall of the discharge port's flow path achieved by reducing excessive oil, thus reducing the pressure loss. Table 3: Performance evaluation results Compression efficiency Oil Circulation Ratio Before measures 55.0 % 3.60 wt% After measures 60.0 % 0.08 wt% 6. CONCLUSIONS The oil discharged ratio from a compact rolling piston compressor using CO 2 refrigerant was reduced by taking the following two measures. (1) Oil discharge ratio from the compressor was reduced to 0.4 wt% by targeting the reduction of oil flowing into the compression chamber and using the optimum design of the seal length on the upper and lower surfaces of the piston as well as the seal length of the vane groove. (2) Oil discharge ratio was reduced to 0.08 wt% by installing a circling-flow-prevention plate to improve the separation of CO 2 refrigerant and oil due to the circling flow in the shell and by installing a journal bearing cover to separate the refrigerant flow and journal bearing lubrication oil. By taking these measures, we have succeeded in reducing the discharged oil ratio from the compressor and, consequently, developed the prototype of a compact rolling piston CO 2 compressor with oil discharge ratio of 0.1 wt% or less. REFERENCES (1) C. Dang, K. Iino, K. Fukuoka, E. Hihara, 2006, Effect of Lubricating Oil on Boiling Heat Transfer of Carbon Dioxide, 7th IIR Gustav Lorentzen Conference on Natural Working Fluids, (to be published)