Laboratory Evaluation Report for: Backflow Preventer for Beverage Dispensing Equipment

Similar documents
Laboratory Evaluation Report for: Laboratory Faucet Backflow Preventer

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM

DCAP Series 40-4 X X - X X X. Dual Check w/ Atmospheric Port Backflow Preventers

Summary of Substantive Changes between the 2008 and the 2017 edition of ASSE 1001, Performance Requirements for Atmospheric Type Vacuum Breakers

Net Metering Program

Installation, Operation & Maintenance Manual

City of Storm Lake Fire Department Heavy Rescue Specifications

LEAD FREE * PVS-7000 Engineered Flood Protection Valve Station with SentryPlus Alert

A. This Section includes natural gas piping, specialties, and accessories within the building.

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

INSTALLATION & MAINTENANCE MODEL mm

Report Issued: October 19, 2014 Project No.: 23942

Awide choice of devices

540 CMR: REGISTRY OF MOTOR VEHICLES 540 CMR 22.00: MISCELLANEOUS MOTOR VEHICLE AND TRAILER EQUIPMENT AND OPERATIONS REQUIREMENTS

Addendum No. 1 ADDENDUM # 1

SFI SPECIFICATION 28.1 EFFECTIVE: AUGUST 25, 2017 *

DC-501 Double Check Backflow Preventer OPERATIONS, MAINTENANCE AND TROUBLESHOOTING GUIDE

DEPARTMENT OF TRANSPORTATION. National Highway Traffic Safety Administration. [Docket No. NHTSA ; Notice 2]

Example Notification of Compliance Status Report a

NEW JERSEY S ALTERNATIVE FUEL VEHICLE REBATE PROGRAM

INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY

SECTION METERS AND GAGES FOR HVAC PIPING

SECTION METERS AND GAUGES

UNITED STATES DEPARTMENT OF AGRICULTURE FOREST SERVICE STANDARD FOR SPARK ARRESTERS FOR INTERNAL COMBUSTION ENGINES

This is a new permit condition titled, "2D.1111 Subpart ZZZZ, Part 63 (Existing Non-Emergency nonblack start CI > 500 brake HP)"

Regulation of Commercial Waste Originators, Pumpers, Transporters, Processors, and Disposal Facilities

Installation Instructions

AST REGISTRATION PIPE INSPECTION PE REQUIREMENTS. David D. Bradeson, P.E. Chemung Contracting Corporation

Solutions beyond products...

EU Mutual Recognition Technical Requirements

SAN ANTONIO WATER SYSTEM SPECIFICATIONS FOR RUBBER-SEATED BUTTERFLY VALVES 3 INCHES THROUGH 72 INCHES ANSI/AWWA C504 Class 150/250 December 2012

Installation Instructions

State of California AIR RESOURCES BOARD EXECUTIVE ORDER DE

E/ECE/324/Rev.2/Add.102/Rev.1 E/ECE/TRANS/505/Rev.2/Add.102/Rev.1

DISCUSSION DOCUMENT. New standards for off-road small spark-ignition engines under consideration

PBV s Engineering Excellence At Work

RM-1200 Slim Round Control Damper

Installation Instructions

COMMERCIAL DRIVER APPLICATION

5.1 Design and Install Dispenser Transfer Systems Performance Based Skill Assessments 2019

Series 867 Reduced Pressure Zone Assemblies

08.08 Vic-Check Valves

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

BMW of North America, LLC, Grant of Petition for Decision of. AGENCY: National Highway Traffic Safety Administration (NHTSA),

SECTION GENERAL-DUTY VALVES FOR PLUMBING PIPING

C h e c k M a t e I n l i n e C h e c k V a l v e

How to Replace the Lubricating Oil and Oil Filter October How to Replace the Lubricating Oil and Oil Filter

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

Maximum Motor Power 0.25 hp 0.19 kw Torque Range ft. lbs Nm. Torque Range ft. lbs Nm Non-Reversible

Underground Tank Applications Installation Guide

Proposal for amendments to UN Regulation No. 110 CNG/LNG vehicles

CHAPTER 403. HAZARDOUS MATERIAL TRANSPORTATION

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

AS/NZS :2010. Water supply Backflow prevention devices AS/NZS :2010. Part 1: Materials, design and performance requirements

SGS North America, Inc.: Grant of Expansion of Recognition. AGENCY: Occupational Safety and Health Administration (OSHA), Labor.

APCO SLANTING DISC CHECK VALVES

Installation Manual DIAPHRAGM WELL TANK

VSI, LLC SERIES 2100 RESILIENT SEATED BUTTERFLY VALVES INSTALLATION, OPERATION AND MAINTENANCE MANUAL

SPECIFICATION: OPERATION: (Dimensional drawing on following page)

Henderson Engineers, Inc. SECTION GENERAL DUTY VALVES FOR PLUMBING PIPING PART 1 - GENERAL REQUIREMENTS

CDL TESTING AND REGULATIONS

IBV Series C-LF2 Carbon Steel Inverted Bucket Vertical Steam Trap

Department of Transportation. National Highway Traffic Safety Administration. [Docket No. NHTSA ; Notice 2]

VALVCHEQ BACKFLOW PREVENTERS FIGURE DC03

Hedge trimmers (combustion engine powered)

S19214 Series. Pedestal-Mount Halo Eyewash or Eye/Face Wash. Recommended Option:

GENERAL PLAN APPROVAL AND GENERAL OPERATING PERMIT BAQ-GPA/GP 2 STORAGE TANKS FOR VOLATILE ORGANIC LIQUIDS

DEPARTMENT OF TRANSPORTATION. National Highway Traffic Safety Administration. [Docket No. NHTSA ; Notice 2]

SECTION GENERAL-DUTY VALVES FOR PLUMBING PIPING

Chain-saws (combustion engine powered)

High Pressure 2-way 2 1/2-6 Globe Valves

A. This Section includes general duty valves common to several HVAC piping systems.

DRAFT AUTHORITY TO CONSTRUCT

PLS Boiler Inspection Standard Introduction

C.A.S.E. AIR CARRIER SECTION POLICIES AND PROCEDURES

Department of Transportation. National Highway Traffic Safety Administration. [Docket No. NHTSA ; Notice 2]

AUTOGAS 150 SERIES PUMPS INSTALLATION GUIDELINES FOR UNDERGROUND TANK APPLICATIONS

Dual Port Manifold Water Filtration Systems Instruction Manual

ENGINEERING MANUAL PRESSURE STEAM HUMIDIFIERS

SECTION VALVES

TRANSMITTER ATTACHES TO THIS SURFACE

E/ECE/324/Rev.1/Add.53/Rev.3/Amend.3 E/ECE/TRANS/505/Rev.1/Add.53/Rev.3/Amend.3

ISO :2015/DAM 1

Executive Order VR-205-B VST Phase II EVR System with Hirt Thermal Oxidizer. Exhibit 2 System Specifications

COMMERCIAL ITEM DESCRIPTION HOSE AND HOSE ASSEMBLIES, NONMETALLIC SPRAY

Section 08: Controlled Substances and Alcohol Testing Requirements

These regulations are created pursuant to and of the Colorado Revised Statutes.

THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT.

NMSU FIRE DEPARTMENT FIRE PUMP ACCEPTANCE TEST

City of Hammond Purchasing Department RFP # General Maintenance and Repair Service Contract City Generators

LOADING OF ORGANIC LIQUID CARGO VESSELS. (Adopted 10/13/1992, revised 1/18/2001)

Re: Online Reporting of Backflow Assembly Tests and Updates to Backflow Tester Records

DIVISION 311 MISCELLANEOUS ELECTRICAL RULES

1) Activity Description: Management of Petroleum Storage Tanks and Containers

SECTION GENERAL-DUTY VALVES FOR PLUMBING PIPING

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x in. W x 120 in. H (3658mm x 3048mm) 5 in.

SECTION FACILITY FUEL OIL PIPING

SECTION FACILITY FUEL - NATURAL GAS PIPING AND SYSTEMS

Toyota Motor North America, Inc. Grant of Petition for Temporary Exemption from an Electrical Safety Requirement of FMVSS No. 305

Transcription:

American Society of Sanitary Engineering Seal (Certification) Program Laboratory Evaluation Report for: Backflow Preventer for Beverage Dispensing Equipment Tested under ASSE Standard 1022 ASSE: 2003 ANSI: 2003 Laboratory File Number Manufacturer Model. Address Serial. Other Identification Markings Size Connections (screwed, flanged, etc.) General information and instructions for the testing engineer: Within the text there may be items which are only advisory to conditions which experience indicates could be troublesome. It is not for evaluation related to acceptance of the product. There may be other items for which the judgment of the test engineer will be involved. Should there be a question of compliance with that provision of the standard, a conference with the manufacturer should be arranged to enable a satisfactory solution of the question. Should disagreement persist and compliance remain in question by the test agency, the agency shall, if the product is in compliance with all other requirements of the standard, file a complete report on the questionable items together with the test report, for evaluation by the ASSE Seal Control Board. The Seal Control Board will then review and rule on the question of compliance with the intent of the standard item involved. Documentation of material compliance must be furnished by the manufacturer. He shall furnish to the testing agency, a bill of material which clearly identifies the material of each part included in the product construction. This identification must include any standards which relate thereto. Page 1 of 9 pages (2003)

Product Name Model Number Size(s) Date Submitted for Review Date Review Complete Section I 1.0 General 1.1 Application. Does this device, as stated by the manufacturer, comply with this section? 1.2.1 Description. Does the device conform to the product classified as a backflow preventer? 1.2.2 Minimum Flow. What is the minimum flow rate of the device at a maximum pressure of 15 p.s.i. (103.4 kpa)? gpm ( L/min.) 1.2.3 Inlet and Outlet Connections. What is the inlet connection? in. ( mm) What is the outlet connection? in. ( mm) 1.2.4 Pressure Range. What is the maximum working pressure? p.s.i. ( kpa) What is the minimum working pressure? p.s.i. ( kpa) 1.2.5 Temperature Range. o F to o F ( o C to o C) Page 2 of 9 pages (2003)

Section II 2.0 Test Specimens 2.1 How many devices of each size and model were submitted? 2.2 How many devices were utilized during the laboratory evaluation? If more than one (1) device was used, state why an additional device was utilized? 2.3 Were assembly drawings and other data provided? Were these reviewed by the laboratory personnel? Section III 3.0 Performance Requirements and Compliance Testing 3.1 Hydrostatic Pressure What was the supply pressure at the inlet? p.s.i. ( kpa) The test period was for minutes. Were there any external leaks or damage to the device? 3.2 Hydrostatic Tests of Check Valves What was the pressure applied to the downstream side of each check valve individually? p.s.i. ( kpa) The test period was for minutes. Were there any leaks or rise in the water level of the sight glass? Page 3 of 9 pages (2003)

3.3 Atmospheric Port Leakage Low Pressure: What was the pressure shown on gauge #2? p.s.i. ( kpa) What was the flow rate? gpm ( L/s) The test period was minutes High Pressure: What was the pressure shown on gauge #2? p.s.i. ( kpa) What was the flow rate? gpm ( L/s) The test period was minutes Was there any leakage from the atmospheric port? 3.4 Water Flow Test What was the rated flow? gpm ( L/s) What was the pressure drop? p.s.i. ( kpa) 3.5 Deterioration at Extremes of Manufacturer s Rated Temperature and Pressure Ranges Hot water tested at o F ( o C). How long was the test period? hours. What was the rated flow? gpm ( L/s) Supply Pressure: p.s.i. ( kpa) Cold water tested at o F ( o C). How long was the test period? hours. What was the rated flow? gpm ( L/s) Supply Pressure: p.s.i. ( kpa) Page 4 of 9 pages (2003)

3.6 Check Valve Sealing Pressure Upstream Check Valve: The test period was minutes Water column level? In compliance in. ( mm) Downstream Check Valve: The test period was minutes Water column level? in. ( mm) If questionable, explain: 3.7 Endurance and Cycle Testing What was the pre-conditioning temperature? F ( C) Submerged time was minutes. (a) What was the temperature for this portion of the test? F ( C) What was the supply pressure? p.s.i. ( kpa). (b) What was the back pressure for this portion of the test? p.s.i. ( kpa) At a two (2) seconds per cycle, what was the total cycles completed? Cycles Was there any leakage from the atmospheric port opening during the test? Did the device comply with these sections? 3.8 Atmospheric Port-Opening Pressure Low Pressure: What was the inlet pressure? What was outlet pressure? p.s.i. ( kpa) p.s.i. ( kpa) Page 5 of 9 pages (2003)

At what differential pressure did the atmospheric port open? p.s.i. ( kpa) Intermediate Pressure: What was the inlet pressure? What was outlet pressure? p.s.i. ( kpa) p.s.i. ( kpa) At what differential pressure did the atmospheric port open? p.s.i. ( kpa) High Pressure: What was the inlet pressure? p.s.i. ( kpa) What was outlet pressure? p.s.i. ( kpa) At what differential pressure did the atmospheric port open? p.s.i. ( kpa) 3.9 Check Valve Leakage Downstream Check Valves: Low Pressure What pressure was applied to the outlet? p.s.i. ( kpa) The test period was for minutes. Downstream Check Valves: Intermediate Pressure What pressure was applied to the outlet? p.s.i. ( kpa) The test period was for minutes. Downstream Check Valves: High Pressure What pressure was applied to the outlet? p.s.i. ( kpa) The test period was for minutes. Upstream Check Valves: Low Pressure What pressure was applied to the outlet? p.s.i. ( kpa) The test period was for minutes. Upstream Check Valves: Intermediate Pressure What pressure was applied to the outlet? p.s.i. ( kpa) The test period was for minutes. Page 6 of 9 pages (2003)

Upstream Check Valves: High Pressure What pressure was applied to the outlet? p.s.i. ( kpa) The test period was for minutes. Were there any leaks? If questionable, explain: Section IV 4.0 Detailed Requirements 4.1 Materials and Toxicity Do the polymers and elastomers that come in contact with potable water comply with any of the following: a) US Code of Federal Regulations (CFR) b) NSF Standard 61 c) Certified as non-toxic materials by independent approved testing agency. 4.2.1 Metal to Metal Seating. 4.2.2 Atmospheric Vent Port(s). 4.2.3.1 Pipe Threads. Page 7 of 9 pages (2003)

4.2.33 Female Pipe Threaded Connections. Is the construction of the device such that it is impossible to run a pipe into the connections far enough to restrict the flow through the device or interfere with the working parts? 4.3 Markings. Identify the following markings on the device: (a) Name of manufacturer of trademark (b) Type and model number (c) Maximum rated working pressure p.s.i. ( kpa) (d) Maximum rated water temperature o F ( o C) (e) The direction of flow Would these markings be visible in the installed position? How were the markings shown on the assembly? 4.4 Instructions. Were instructions furnished with the assembly that included illustrations, installation, operations and maintenance? Page 8 of 9 pages (2003)

TESTING AGENCY ADDRESS PHONE: FAX: TEST ENGINEER(S) We certify that the evaluations are based on our best judgments and that the test data recorded is an accurate record of the performance of the device on test. Signature of the official of the agency: Title of the official: Date: Signature and seal of the Registered Professional Engineer supervising the laboratory evaluation: Signature Seal Page 9 of 9 pages (2003)