Technical Specification for 12kV and 24kV Powder Filled Fuse-Links and Fuse Holders

Similar documents
Technical Specification for 12kV and 24kV Current Limiting Fuse- Links for Overhead Applications

Technical Specification for 12kV Powder Filled Current Limiting Fuse-Links for Use in Switchgear (In Oil)

Technical Specification for 12kV and 24kV Powder Filled Current Limiting Fuse Links for Use in Switchgear (In Air)

Technical Specification for 12kV, 24kV and 36kV Drop-Out Disconnector

34-SDMS-02 SPECIFICATIONS FOR

045 : 2000 CEB STANDARD

Section ( VI ) TECHNICAL SPECIFICATIONS AND SCHEDULES

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

شركة كهرباء محافظة القدس المساهمة المحدودة

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

NPS/001/017 Technical Specification for Low Voltage and High Voltage Current Limiting Fuse Links

TABLE OF CONTENTS FOREWORD... 2 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS... 3

TGK Prefabricated Substation Technical Data

34-SDMS-01 SPECIFICATIONS FOR

Technical Specification

High-voltage high-breaking capacity VV fuse-links

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators:

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA

026-2 : 1996 CEB STANDARD

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

DIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV.

TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES :

FUSES. Safety through quality

MEDIUM VOLTAGE DIN Fuse-Links

Company Directive STANDARD TECHNIQUE : TP4B/2. Relating to 11kV and 6.6kV Transformer Protection

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA

TITLE: SPECIFICATION FOR BENCH VICE & BENCH GRINDER TABLE OF CONTENTS. 0.1 Circulation List. 0.2 Amendment Record

Medium Voltage current limiting Fuse links

Guideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society

MEDIUM VOLTAGE DIN Fuse-Links

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society

Applications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS

High voltage high-breaking capacity VV fuse-links

Medium Voltage current limiting Fuse links

Guideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society

TECHNICAL SPECIFICATION FOR 11 KV AIR BREAK (A.B.) SWITCHES:

3 Pin Schuko Converter Plug Technical Data & Fitting Instructions

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

Paramount HRC Cartridge

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:-

TABLE OF CONTENTS FOREWORD...3 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS REQUIREMENTS...

NPS/003/019 Technical Specification for Electrical Insulating Fluids for use in Plant & Switchgear.

Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

MAINTENANCE AND TESTING OF PORTABLE ELECTRICAL EQUIPMENT, RCDS AND TOOLS CS-OHS-33

NPS/003/002 Technical Specification for 30V Distribution Tripping Battery and Charger Systems

NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

SPECIFICATION FOR REWIRABLE FUSES (KITKAT FUSES) 100A & 200A SPECIFICATION NO.: DIST/ A- KIT /

High-voltage high-breaking capacity VV fuse-links

Technical Specification of GECOL. Packaged Transformers

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.

Bussmann series NH catalogue. Leadership in circuit protection

LG HRC Power Fuses ISO 9001 ISO 14001

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail

Medium voltage products. Fuses

Certificate of Acceptance

Phase + Neutral, neutral on left side

SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED)

EU RO Mutual Recognition Technical Requirements

HHD. High Voltage Fuses German DIN Standard. The temperature limiting function of the fuse striker pin. Design and construction.

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

HHD HIGH VOLTAGE FUSES GERMAN DIN STANDARD. The temperature limiting function of the fuse striker pin. Design and construction.

Menu. Home About this portal Latest updates. Print Save Resource detail Citations. Table of Contents

Low Voltage Industrial Type T Fuse Links

Phase + Neutral, neutral on right side

ANNEX B TECHNICAL SPECIFICATIONS PORTABLE SOLAR-POWERED LIGHTS

MESP TECHNICAL SPECIFICATION FOR A STATIONARY CONTROL BATTERY AND CHARGER SET FOR USE IN A SUBSTATION

31-SDMS-02 REV. 01 SPECIFICATIONS FOR

Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A

STR-1415 SPECIFICATION FOR BATTERY CHARGERS 220V, 30A FOR SUBSTATIONS ANNEXURES B

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report

31-SDMS-01 REV. 03 SPECIFICATIONS FOR

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.

Switchgear Type 8BT1, up to 24 kv, air-insulated. Medium Voltage Switchgear Catalog HA 26.

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation

EDS FUSE RATINGS AT DISTRIBUTION SUBSTATIONS

: DGVCL/11KV D.O.FUSE/SPECIFICATION : : 11KV DROP OUT FUSE CUTOUTS :

HIGH VOLTAGE CURRENT LIMITING FUSE-LINKS CAPABLE OF BREAKING ALL CURRENTS THAT CAUSE MELTING OF THE FUSE-ELEMENT. D. van der Scheer H.F.J.

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating

HV DIN FUSE-LINKS FOR TRANSFORMER PROTECTION. March 2017

DO-III Fuse Holder TPL , May 2000, Page 1 of 4. General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder. ABB Inc.

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance

RX 3 MCB 4500 A Phase + Neutral, neutral on left side

Current Limiting Fuses, CEF Motor Circuits Fuses, CMF. Catalogue 1YMB en. Industrial IT. enabled

Medium voltage products. Fuses

TECHNICAL SPECIFICATIONS FOR LT DISTRIBUTION BOX MADE FROM THERMOSETTING PLASTIC HAVING 200 /400 AMP CAPACITY.

REFERENCE REV CP_TSSPEC_016 1 TITLE SPECIFICATION FOR DATE: NOVEMBER 2010 LIGHTING TABLE OF CONTENTS Page FOREWORD INTRODUCTION

High voltage current limiting Fuse links type CEF

Use of switch-fuse combinations at the medium-voltage level for the protection of distribution transformers siemens.com/tip-cs

Medium voltage fuses - European Fuses

Transcription:

Ergon Energy Corporation Limited Technical Specification for 12kV and 24kV Powder Filled Fuse-Links and Fuse Holders ETS12-01-01 Specification ETS12-01-01 Ver 3

Contents 1. Purpose and Scope... 1 2. References... 1 2.1 Applicable Standards... 1 3. Drawings... 1 3.1 Drawings by the Purchaser... 1 4. Service Conditions... 1 5. Design and Construction... 2 5.1 Requirements... 2 5.2 Ratings... 2 5.3 Fuse-link Applications... 2 5.4 Fuse-Link Dimension Type II (Refer Figure D2 Appendix D of AS1033.2)... 3 5.5 Striker (refer Table 6.3 AS1033.2)... 3 5.6 Fuse Top and Base Attachment... 3 5.7 Vibration... 4 6. Performance and Testing... 4 6.1 Testing... 4 7. Risk Assessment... 4 8. Quality Assurance... 4 9. Samples... 5 9.1 Production Samples... 5 10. Packaging and Marking... 5 10.1 General... 5 10.2 Marking... 5 11. Service Performance... 5 12. Reliability... 5 12.1 Service Life... 5 12.2 Evidence in Support of Reliability... 5 13. Training... 5 14. Environmental Considerations... 6 i Specification ETS12-01-01 Ver 3

15. Information to be Provided... 6 15.1 Specific Technical Requirements... 6 15.2 Checklist of Supporting Documentation... 6 15.3 Documentation to be Supplied During the Course of the Contract... 6 16. Appendix A.1 Items List... 7 17. Attachment 1 Technical Details... 8 18. Attachment 2 Technical Document Checklist... 9 ii Specification ETS12-01-01 Ver 3

1. Purpose and Scope This specification sets out the technical requirements for 12kV and 24kV powder filled fuses and fuse-end fittings suitable for use on overhead electricity distribution systems in a totally exposed environment. The fuses are primarily used for the protection of distribution transformers. The items covered by this specification are given in the Appendix A.1. 2. References 2.1 Applicable Standards The fuses and fuse-holders (end fittings) shall be designed, manufactured and tested in accordance with the relevant parts of the following standards and all amendments issued from time to time except where varied by this specification. Should inconsistencies be identified between standards and/or this specification, the Tenderer shall immediately refer such inconsistencies to the Purchaser for resolution. STANDARD TITLE AS 1033.1 High voltage fuses (for rated voltages exceeding 1000V) Part 1 Expulsion type AS1033.2 High voltage fuses (for rated voltages exceeding 1000V) Part 2 Current-limiting (Powder-filled) type DIN 43625 High-voltage fuses, rated voltages 3.6 to 36kV; fuse-links IEC60282 AS/NZS ISO: 9001 High voltage fuses Quality systems model for quality assurance in design, development, production, installation and servicing 3. Drawings 3.1 Drawings by the Purchaser No drawings are included in this specification. 4. Service Conditions The fuse-links and end fittings will be exposed to the following environmental conditions: Ambient Temperatures Solar Radiation Level Precipitation Humidity 45 o summer day time -5 o winter night time 1100 watts per square metre with high ultraviolet content Tropical summer storms with gust wind speeds above 160km/h, and an annual rainfall in excess of 1500 mm Extended periods of relative humidity in excess of 90% R.H. Page 1 of 9 Specification ETS12-01-01 Ver 3

Atmospheric Classifications Areas of coastal salt spray and/or industrial pollution with equivalent salt deposit densities in the range 2.0-3.0 g/m 2. 5. Design and Construction Design and construction performance parameters are detailed in this section. 5.1 Requirements The fuse-links and fuse-end fittings shall be of the following ratings and comply with the Australian Standard AS1033.2 or an equivalent international standard. The fuse-links shall be used primarily for protection of delta connected distribution transformer/cable circuits. 5.2 Ratings Rated voltage 12kV 24kV Rated current of fuse-holder 200A 200 amp Rated current of fuse-links 63 and 80A as required 10, 20 and 40 as required Rated breaking current & power frequency of fuse-holder 40kA(minimum) 20KA (minimum) Rated frequency Fuse classification Time/current characteristics 50Hz General Purpose ( Full range preferred) Refer clause 5.3 below Rated insulation level of fuse-holder 95kV BIL 125kV BIL 5.3 Fuse-link Applications The HV fuse sizes currently used by the Purchaser for the protection of distribution transformers are listed below. Transformer three phase kva Fuse Rating(A) for 12kV Transformers Fuse Rating(A) for 24kV Transformers Page 2 of 9 Specification ETS12-01-01 Ver 3 Typical Fuse Rating for LV. 100 10 160 200 16 355 & 2x200 315 16 500 & 2x200 500 20 710 750 63 31.5 1000 80 40 The fuse links offered shall be capable of withstanding magnetising inrush currents up to 12 times the transformer rated full load current for 0.1 seconds and 25 times the transformer rated full load current for 0.01 seconds and discriminate with the secondary fuse links specified. The fuse links shall be capable of withstanding 125% of the transformer rated full load current continuously and periodic over-loads up to 150% of the transformer rated full load current.

The fuse links shall be able to clear a phase to neutral fault on the secondary terminals of the transformer in less than 1.5 seconds, in order to limit damage to the transformer in the event of such fault. (The impedance voltage of the transformer at the rated current may be assumed as 4%) The current-time characteristics of the fuse-links offered shall be submitted with the tender. Fuse links shall be suitable for mounting in any orientation. 5.4 Fuse-Link Dimension Type II (Refer Figure D2 Appendix D of AS1033.2) Rated Rated Fuse -Link Dimensions (mm) Voltage(kV) Current(A) Overall Length End Cap (excluding striker) Diameter meter Length(min) 24 10 567.0 + 0, - 4.0 50.8 ±0.5 38.0 20 567.0 + 0, - 4.0 50.8 ±0.5 38.0 50 567.0 + 0, - 4.0 76.2 ±0.5 38.0 12 63 361.0 + 0, - 4.0 76.2 ±0.5 38.0 80 361.0 + 0, - 4.0 76.2 ±0.5 38.0 Fuses shall be ferrule ended type II suitable for outdoor use in air. The ferrule ends shall be suitable for the fitting of fuse top and base contact attachments which would allow the fuse link to be mounted on an EDO unit. Limitations on the tightening of the attachments to the ferrules shall be detailed. Drawings showing the critical dimensions of the fuse links offered shall be submitted with the tender 5.5 Striker (refer Table 6.3 AS1033.2) The fuse-links shall be fitted with a striker for indication purposes and to initiate three phase tripping of the circuit being protected. The mechanical characteristics of the striker shall be in accordance with the medium duty type in Table 6.3 of AS1003.2. The energy rating of the striker shall be 1J±0.5J 5.6 Fuse Top and Base Attachment The fuse link with the end fittings attached shall be suitable for use with the 12kV/24kV EDO fuse mounts complying with AS1033.1 as applicable. The attachments shall be easily fitted to the fuse ends and shall have stops that ensure the correct spacing between the top and base when fitted to the fuse ferrule ends. The top attachment shall be designed to latch into the fuse-holder and unlatch on operation of the fuse. The base attachment shall be provided with an actuator which causes fuse-link assembly to drop downward when the striker is released during the operation of the fuse link. The fuse shall pivot on the base hinge and shall not hit the pole during opening. Page 3 of 9 Specification ETS12-01-01 Ver 3

Both attachments shall have lifting rings to enable the operations and removal of the fuselink. The top end lifting device shall be suitable for the opening of the fuse-link using a portable load breaking tool. All current carrying parts shall be of high electrical conductivity and corrosion resistant metal. The contact parts shall be electrolytically bright tin plated (or silver plated) to ensure long term durability of the contact surfaces. All nuts, bolts and washers shall be stainless steel in accordance with AS2837. The bolts and washers shall be grade 316 and to avoid binding, the nuts should be grade 304. 5.7 Vibration When the fuse link is intact and correctly assembled it shall latch securely when closed and shall not be dislodged from the EDO fuse contacts by vibration or wind pressure. The carrier shall not dislodge from the bottom hinge in the opening operation, or in the open position during wind or vibration conditions. The manufacturer shall state the design features and testing undertaken to meet these requirements. 6. Performance and Testing 6.1 Testing Test certificates of the type tests specified in the Section 4 of AS1033.2, and the weatherproof test (Section 5, AS1033.2) shall be provided with the tender. The routine and batch test certificates shall be submitted with each delivery. The test certificate for the time current characteristics provided with the tender shall include the minimum melting time characteristics and the total clearing time characteristics. A table of (current -time) data defining the above curves should also be included with the tender in (MS Office) Excel format. Current limiting data showing the extent of current limiting should be included. The testing shall have been carried out by a nationally accredited testing authority. 7. Risk Assessment There is no requirement for manufacturer provided safety risk assessments for the items covered in this specification. 8. Quality Assurance It is the Purchaser s policy to procure goods, equipment and services from sources that demonstrate the ability to supply quality products. Tenderers are required to documentary evidence of the Quality System Certification of BOTH the SUPPLIER and the MANUFACTURER (including Capability Statement) such that the design and manufacture of the fuses offered is in accordance with AS/NZS/ISO 9001. This documentation shall include the Capability Statement associated with the Quality System Certification. Page 4 of 9 Specification ETS12-01-01 Ver 3

9. Samples 9.1 Production Samples When requested, production samples of each item shall be submitted with the offer. 10. Packaging and Marking 10.1 General Tenderer's attention is specifically drawn to the requirements of the Logistic Specification with regard to the packaging, marking and delivery of palletised goods. 10.2 Marking Markings shall be provided on the fuse-links in accordance with Clause 6.9.3 of AS 1033.2 11. Service Performance Potential first time Suppliers to the Purchaser shall state: 12. Reliability a) The period of service achieved by items offered within Australian service conditions; b) Australian electricity supply authorities who have a service history of the items offered; c) Contact names and phone numbers of relevant employees of those supply authorities who can verify the service performance claimed. 12.1 Service Life Comments on the reliability and performance of the items offered, for a service life of 35 years under the specified system and environmental conditions, shall be submitted with the offer. 12.2 Evidence in Support of Reliability Such comments shall include evidence in support of the reliability and performance claimed including information of Failure Mode and Effect Analysis. 13. Training Training material in the form of drawings, instructions and/or audio visuals shall be provided for the items accepted under the offer. This material shall include but is not limited to the following topics: Handling Storage Fuse application Installation Maintenance Environmental performance Electrical performance Page 5 of 9 Specification ETS12-01-01 Ver 3

Mechanical performance Disposal 14. Environmental Considerations Suppliers are required to comment on the environmental soundness of the design and the materials used in the manufacture of the items offered. In particular, comments should address such issues as recyclability and disposal at end of service life and also disposal of packaging material. 15. Information to be Provided 15.1 Specific Technical Requirements Attachment 1 is a schedule of the technical details that suppliers are required to complete and return with their offer. 15.2 Checklist of Supporting Documentation Attachment 2 details a checklist of supporting technical documentation which is required to be submitted with the tender. 15.3 Documentation to be Supplied During the Course of the Contract Test certificates as required in Clause 6. Page 6 of 9 Specification ETS12-01-01 Ver 3

16. Appendix A.1 Items List Item No IINo Description 1 2404141 FUSE LINK, 24kV, HRC, 20 Amp, Barrel 565mm Long 50.8mm Diameter including End Caps 44mm Long 50.8 mm Diameter, with Striker Pin to DIN Standard 43625. 2 2404143 FUSE LINK, 24kV, HRC, 50 Amp, Barrel 565mm Long 76.2mm Diameter including End Caps 44mm Long 76.2mm Diameter, with Striker Pin to DIN Standard 43625. 3 2400622 FUSE LINK, 12kV, 63 A, HRC, Air Insulated, Barrel 359mm Long 76.2mm Diameter including End Caps 44mm Long 76.2mm Diameter, with Striker Pin, to DIN Standard 43625. 4 2400626 FUSE LINK, 12kV 80 Amp 12kV HRC, Air Insulated, Barrel 359mm Long, 76.2mm Diameter, including End Caps 44mm Long 76.2mm Diameter, with Striker. to DIN Standard 43625. 5 2400623 FUSE LINK, 12kV, 90 A, HRC, Air Insulated, Barrel 359mm Long 76.2mm Diameter including End Caps 44mm Long 76.2mm Diameter, with Striker Pin, to DIN Standard 43625. Page 7 of 9 Specification ETS12-01-01 Ver 3

17. Attachment 1 Technical Details The supplier shall complete this schedule for each item offered and shall guarantee the particulars as set out: Tender Item Number # Units II Number (Stock Code) Name of Manufacturer Address of Manufacturer Country of Manufacturer Manufacturer s Catalogue Number and Drawing Numbers Material of Fuse Weight of Fuse Weight per Crate (kg) (kg) Time-Current Characteristics of Fuse Attached? Cut-off current Characteristics of Fuse Attached? I 2 t Characteristics Attached? Dimensional details of the fuse Attached? YES/NO YES/NO YES/NO YES/NO Prospective Breaking Current Breaking Capacity Minimum Breaking Current Power dissipation at rated current Energy rating of the striker pin (ka) (ka) (A) (W) (J) Class of Fuse (Full Range or General Purpose) Fuse End Cap Details: Fuse End Cap Material Plating Material Thickness of plating Fuse End Fittings Details: Material of Castings Plating Material Thickness of Plating SIGNATURE OF TENDERER: Page 8 of 9 Specification ETS12-01-01 Ver 3

18. Attachment 2 Technical Document Checklist CLAUSE Ref. PARTICULARS UNITS Have full and comprehensive details been submitted WITH the tender documents associated with each of the following items? 5.3 Time-current characteristics Yes/No 5.4 Drawings and limitations on the tightening torque on end fittings/fuse-inks 5.7 Design features and testing undertaken to prove performance under vibration and wind conditions Yes/No 6 Test certificates included in tender documentation Yes/No 8 Documentary evidence of the Quality System Certification of BOTH the SUPPLIER and the MANUFACTURER (including Capability Statement) Yes/No 9 Availability of samples Yes/No 11 Service Performance Yes/No 12 Reliability Yes/No 13 Training Materials (availability) Yes/No 14 Environmental Considerations (availability) Yes/No 15 Completed Attachment 1 and fuse characteristics requested therein Yes/No NAME OF TENDERER: ADDRESS OF TENDERER: SIGNATURE: FOR AND ON BEHALF OF TENDERER DATE: Page 9 of 9 Specification ETS12-01-01 Ver 3