Onix Structure Private Limited Solar PV Power Generation System Detailed Project Report 1
Main Features of the Project Project promoter:- Onix Solar Project location:- Village - Rojasar, Tehsil - Limbdi State :- Gujarat Proposed technology:- Si-Poly Technology Technology Supplier (PV Modules):- Goldigreen / Vikram Si-Poly Module Technology Supplier (Power Condition units) :- Power Electronics Design consultant:- enincon LLP Plant capacity:- 1 MW PV Module Type- Si Poly modules PV Modules Required (area):- 7179 m² Total Area Required: - 20235 m² Annual global solar radiation : 1976 kwh/m² Annual average temperature : 25.18 C Annual Gross Output :- 1579300 kwh Miscellaneous PV array losses :- 1 % Miscellaneous power conditioning losses :- 1 % Expected CUF :- 19 % Project implementation period:- 8 months Estimated project cost :- Rs 650 lakhs Design Optimization Software used:- RETScreen, METEONORM, PVSYST V5.72 Site selection:- Site identified and suitability confirmed Table of Contents Sr. No. Content Section No. 1 ABOUT SOLAR POWER SYSTEM Section 1 2 BILL OF MATERIALS Section 2 3 SOLAR PHOTVOLTAIC EQUIPMENT DETAILS Section 3 4 INSTALLATION & OTHER DRAWINGS Section 4 5 CONTACT DETAILS Section 5 2
SECTION 01 ABOUT SOLAR POWER SYSTEM 1.1 SYSTEM OVERVIEW A. About the system The solar PV Power generation system supplied by Onix Structure Pvt. Ltd. is a high efficient, modular, extendable and cost effective power generation solution. The system is designed to International Standards to ensure that you have years of trouble-free operations. As a result of proven technology, the system is highly efficient and maintenance free. With one-time investment, the Solar provides the prudent way of managing the energy costs in an eco-friendly way. The savings made on energy costs will help the companies to directly benefit and contributing to their growth. The List of major components used in this system are listed below. Solar PV Modules: The sun light (solar radiation) falling on the modules is converted in to DC energy by photovoltaic principle. The generated by solar modules can either be used to supply the power to the connected load or to charge the battery bank. PV Inverter (PCU): PCU is a common terminology used to the system consisting of Inverter and AC synchronization functionality. PCU does the function of controlling grid power by leading PF and prefer the solar energy to the load. The system also contains the Charge Controller as part of the same system or as an independent unit. Module mounting structure (MMS): MMS is the structure to mount the solar PV modules with specified angle depending on the location when the system to be mounted. The tilting will vary depending on the longitude and latitude of the location. B. Salient Features and Benefits of System C. Applications A clean, silent and eco-friendly source of power Solar modules convert sunlight into electricity without pollution Negligible maintenance as there are no moving parts and maximum reliability Long life span of solar modules Modular design and easily expandable Simple installation: can be mounted on roof top or ground Can be installed at point-of use to avoid transmission losses Energy Independence Protection against future escalation of energy costs Available throughout the year The system is ideal for industries and institutions where the energy usage is maximum during the sunlight hours. These include manufacturing companies, Software development Centres, Hospitals, Hotels, Schools, Colleges, Fuel Pump stations, R&D Centres, Transmission, Railways and Communication towers and many more applications. 3
1.2 SYSTEM WORKING PRINCIPLE Solar photovoltaic (PV) system is like any other electrical power generation systems in terms of the output except for the source of the power is solar radiation. The conversion of solar radiation to the electrical power is based on the photovoltaic principles. However, the principles of operation of the connected load and interfacing with other electrical systems remain the same. Though solar PV array produces power when exposed to sunlight, a number of other components are required to properly conduct, control, convert, distribute, and transform the energy produced by the array. Solar power generating system supplied for this project shall be utilized for powering various office loads like Computer, Lighting loads, fans etc. for specified hours of sun shine operation. This system is designed to generate the energy in an eco-friendly manner with the source from solar radiation which is available in abundance. The system designed is for 1 MW Solar Power Generation Grid Connecting System. The system does not have any storage for standby power. The solar PV array will have 3125 no s of 320Wp crystalline solar modules. These modules will be connected in series / parallel combination through Optimizers to the desired string configuration as per the design parameters of the PCU. The PCU is of 1.2 MVA capacity with three phase AC Output. Grid power supply is provided to support the loads and to reduce the Grid power consumption when solar power is available. The power generated from solar array is fed into the PCU through Optimizer and being inverted by the PCU (Vac). This voltage is being combined with standard grid supply to the phases (R/Y/B) and will lead the power 4
factor of the inverter supply by comparing the grid power factor. So the solar generated power will always be preferred by the leading power factor and rest of the power will be used from the grid as required by the load. If the load demand is lesser than the solar power generated, the balance power may be exported to grid and customer may get feed-in benefit as per the policies of the local electricity board. This system is working in the principal of power factor comparison and the system will feed the power either to load or grid through grid power supply. That means loads will be indirectly connected with the solar system. So, if the grid supply is not available at any moment the solar system will shut OFF immediately. We can only use sunlight directly to the load whenever the grid power is available. The system will shuts OFF at the time of low intensity or no sun light and restarts automatically when the sunlight is available. The proposed system does not required any dedicated loads or separate wiring to work on. At the time of power failure if the customer turns ON the DG supply again the solar system will run and pushes the energy back to the DG. To avoid this reverse current situation, the DG rating should be at least be 4 to 5 times higher rating than the proposed solar power plant rating. System Details: 1. Solar PV Modules: 320 Wp Polycrystalline Quantity: 3125 Nos. (320 x 3125 = 1000kWp). - Solar PV Module exposed to the sunlight converts it into DC energy. 2. Optimizer: Power Optimizer 3125 Nos. - The power optimizer is a DC/DC converter connected to Solar PV modules to increase the energy output from PV systems by constantly tracking the maximum power point (MPPT) for one or more modules individually 3. PCU / Inverter: Grid connected system, 3 Phase AC Output - 1 No - The inverter responsible for DC to AC inversion 4. The output of the inverter is connected to the AC Panel through a proper AC Protection. 5. Inter connecting cables are used to interconnect solar PV components like Solar Modules, Junction Boxes, & Inverter. 5
SECTION 2 BILL OF MATERIALS Sr. No. Description Quantity 1 Polycrystalline Solar PV Modules 320 Wp PV 3125 Nos. 2 Power Optimizers 3125 Nos. 3 Solar PV Inverter 50 KVA 3 Phase 20 No. 4 Data Logging for monitoring Available as part of the PCU 5 DC Cable 6 Sq.mm (Module to Optimizer and Optimizer to As per required PCU) 6 AC Cable - 6 Sq.mm /10 Sq.mm Inverter to ADCB As per required 7 Earthing Kit 1 Set 8 Module Mounting Structure 1 Set 9 Installation Kit (Cable tie & tray, Nuts, bolts, lugs, etc) 1 Set 10 66KV line and substation As per required 11 11KV line As per required 6
SECTION 03 SOLAR PHOTOVOLTAIC EQUIPMENT DETAILS 3.1 SOLAR POWER GENERATING SYSTEM DETAILS The solar PV Power generation system supplied by Onix Structure Pvt. Ltd. is a high efficient, modular, extendable and cost effective power generation solution. The system is designed to International Standards to ensure that you have years of trouble-free operations. Technical data of the solar power pack supplied is given below. 1. System Type Solar PV Grid Connect System 2. System Solar Array Capacity - Nominal @ standard test condition 3. System Output AC voltage - Nominal 400Vac (line to line), 50 Hz (230V - Line to Neutral) 4. Inverter Output Rating - Nominal 1200KVA 3.2 SOLAR PV MODULE The PV Goldigreen photovoltaic module provides superior value and performance. They may be used in single-module and multiple module systems to meet the current or voltage requirements of a wide range of applications with its nominal power; it s well-suited to utility grid systems and traditional applications. The high efficiency Solar PV Modules are: Made from imported Poly-Crystalline solar cells to exacting International Standards Modules comply with the International standards IEC 61215, IEC 61730 and IEC 61701 product certification Standard 10 year manufacturing warranty 10 years/25 years limited power guarantee for 90% & 80% power respectively Cells are encapsulated with premium EVA from USA, with good light transmission resistance to degradation over a long period of time Back sheet is from Japan with extra white surface for light reflection and high strength Junction box has six bypass diodes for extra protection and standard MC4 compatible connectors for easy installation. IP65 compliant for all weather usage Structural integrity offered by a robust double wall screw less, snap fit aluminium frame that is anodized for safety against corrosion *String: - A number of modules or panels interconnected electrically in series to produce the required operating voltage. **Array: - Number of modules or panel strings connected in parallel at one common place. 3.3 SOLAR MODULE MOUNTING STRUCTURE 7
To use the fixed module mounting structure made of mild steel with hot dipped galvanization/ pregalvanized structure for mounting the solar PV modules on the canopy of the main entrance. Power Generation 3.4 INVERTER Inverter is designed for years of trouble-free use. The Inverter is a Grid connected sine wave to serve the loads. It is rated for 1200KVA at 400Vac, 50Hz and designed to operate with DC input only. Inverter required grid supply mandatorily to synchronize the source. Without grid the system, the inverter will go OFF. Solar Inverters (Three Phase) with Optimizers a. Inverters specifically designed to work with power optimizers b. Superior efficiency (>97%) c. Excellent reliability with standard 12 year warranty against manufacturing defects d. Small, lightweight and easy to install e. Built-in module-level monitoring receiver f. IP65 / NEMA 3R Outdoor and indoor installation 8
SECTION 04 INSTALLATION & OTHER DRAWINGS Line diagram for Grid Connected SPV System 9
10
PROTECTION AND SAFETY MEASUREMENTS A SCHEMATIC OF THE PROTECTION SYSTEM 11
Investment Model for 1 MW Solar Power Plant We see a huge demand for information for investment models for setting up a 1 MW Solar Plant. We have decided to create a 1MW 10 MW estimate series. Below is the investment model for 1 MW Solar Plant All over India Capacity of Power Plant : 1 MW Generation Expected per year: 17.50 Lakhs Units/MW Degradation till 1st 10 years: 0.05% Degradation from 11 to 25 years: 0.67% Debt Percentage: 70% Equity Percentage: 30% Rate of Interest of Indian Bank Loan: 13.0% Rate of Interest of Foreign Bank Loan: 10% Repayment Period of Indian Loan: 11 years Repayment Period of Foreign Loan: 15 years Percentage of Indian Loan: 70% Average Cost of Sale of Electricity: 6.49 Rs/unit Cost of Project per MW: 650 Lakhs/MW O&M Cost per MW for 1st year: 8.0 Lakhs/MW Depreciation: 5.28% Corporate Tax: 30.28% Minimum Alternate Tax: 18.38% Project Cost: 650 Lakhs Debt: 455 Lakhs Equity: 195 Lakhs 12
SECTION 05 CONTACT DETAILS Head Office : ONIX STRUCTURE PVT. LTD. Shop. : 2,alax Shopping Center, Galaxy Chowk, Dhoraji 3604110. Dist. : Rajkot, State : Gujarat, India, Phone : 02824 225007 Mobile : +91 9998571647 Branch Office (Rajkot) : ONIX STRUCTURE PVT. LTD. 202 - Classica, Near Jaddu s Food Filed, Kalawad Road, Rajkot 360004 Dist. : Rajkot,State : Gujarat, India Mobile : +91 98254 31761 / +91 9737636169 Branch Office (Surat) : ONIX STRUCTURE PVT. LTD. 9-10, Bhavani Nagar, Dharam Nagar Road, Hirabag, Varachha, Surat- 395008. Dist : Surat, State : Gujarat, India Mobile : +91 97141 68531 Wesite : www.onixstructure.in Email : info@onixstructure.in project@onixstructure.in purchase@onixstructure.in account@onixstructure.in 13