Two-way cable interlock kit for Magnum drawout circuit breakers

Similar documents
Two-way cable interlock kit for Magnum fixed circuit breakers

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

3-way multi-family drawout cable interlock kit - type 32 - RF

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to:

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

Factory Authorized Mechanism Enhancement (FAME)

Instruction Booklet IB E. Contents

CM52 Network Protector with Arc Flash Reduction Module

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

O & M Manual for the EATON Generator Ready Loadcenter

Effective June 2016 New Issue

Digitrip Retrofit System for Allis-Chalmers LA-600 F Electrically Operated Fused Breakers

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

CCP2-FLR1-21_ flange-rod operating mechanism

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

Digitrip Retrofit System for Siemens-Allis RLX-1600 Breakers

Effective November 2016 Supersedes September 1998 (S )

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

Effective November 2016 Supersedes February 2012 (S )

Instructions for using Functional Test Kit on Digitrip 520 and 1150 family of Power Circuit Breaker Trip Units and Series G and FD MCCB Trip Units

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

Digitrip Retrofit System for BBC LKD 8 Breakers

Effective March 2015 Supersedes S August 2012

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

38 kv Type VCPW-HD Simple Electrical Ground & Test Device (SEG&TD) lower terminal instruction booklet

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

Magnum Breaker Remote Racking Device (MRR1000)

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

Digitrip Retrofit System for Allis-Chalmers G-25 Breakers

High-voltage primary bushings installation instructions

! WARNING I.L D WARNING GENERAL INFORMATION

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

Flush Mount AIN ALPHA Meters. General. Hardware Kit

TVSS Installation for RLCM/CHGENLC, RLCU, and CHGEN ATSs

COOPER POWER SERIES. Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions. Voltage Regulators MN225075EN

Effective May 2017 Supersedes December 2004 (S )

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN

Type NR oil switch installation and operation instructions

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

Advanced Test Equipment Rentals ATEC (2832)

COOPER POWER SERIES. Electronic control battery testing, charging, and replacement instructions. Reclosers MN280074EN

Effective May 2017 Supersedes January 2003 (S )

Instructions for installation, operation, and maintenance of medium voltage VC-W MR2 (integral racking)

Installation Instructions For Motor Control Center (MCC) Units

Digitrip Retrofit System for the General Electric AKR 6D/7D-30/50 and AKRT 6D/7D-50 Series Breakers

COOPER POWER SERIES. KA146W5 single pole-mounting hanger; KA146W2 tank lifting windlass assembly and installation instructions. Reclosers MN280039EN

www. ElectricalPartManuals. com Digitrip Retrofit System for BBC LKD 8 Breakers IL 33-LK8-2

Type DTU De-energized Tap Changer Application, Installation & Selection Guide. IL A Instruction Leaflet Page 1 September, 2003

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

RotoTract Remote Racking Operating Manual

DANGER. See Wiring Diagrams on page 7 for illustrations of both internal and connection wiring diagrams. WARNING

Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear rated up to 15kV, 25 and 40kA UPPER TERMINAL SET VERSION

Freedom FlashGard Aftermarket Kit Installation Manual

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Magnum breaker remote racking device (MRR1000)

Users Guide for Ac-sync

www. ElectricalPartManuals. com Digitrip Retrofit System for the Westinghouse DA-50 IL 33-DAC-2 WARNING

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

BC Brake Caliper. (i) MEX (55) QRO (442) MTY (81) DIST. AUTORIZADO

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

I.L. 29C121A WARNING 1. INTRODUCTION. Maximum Freq. Maximum Dielectric Voltage Current Withstand (V) (A) Voltage (V)

Installation Instructions for R-Frame Circuit Breakers and Molded Case Switches

www. ElectricalPartManuals. com Digitrip Retrofit System for Allis-Chalmers LA-4000 F Fused Breakers IL 33-A1K-1 WARNING

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

OPW Installation and Maintenance Instructions OPW Series Primary and Secondary Bucket Replacement Instructions

Installation Instructions for Type SM Safety Handle Mechanism for L-Frame Series C Circuit Breakers and Molded Case Switches

Straight-Bore Clutch LSCC-32, 44, 54

MOTORIZED FOLDING CAMPER WINCH

50 / 75 / 150 DHP [Cable or Hard Bus Application] Ground and Test Device

Instruction Sheet SRSR SERIES. Rotating Sliding Rail System

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

SPX9000 FR10 FR12 Adjustable Frequency Drives

CRD610 Automatic Fitting Inserter

STāSIS Engineering R8 Brake System

Transcription:

iwarning (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK ON THE EQUIPMENT. (2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A CIRCUIT BREAKER CANNOT BE REMOVED TO A SAFE WORK LOCATION. (3) DRAWOUT CIRCUIT BREAKERS SHOULD BE LEVERED (RACKED) OUT TO THE DISCONNECT POSITION. (4) ALL CIRCUIT BREAKERS SHOULD BE SWITCHED TO THE OFF POSITION AND MECHANISM SPRINGS DISCHARGED. FAILURE TO FOLLOW THESE STEPS FOR ALL PROCEDURES DESCRIBED IN THIS INSTRUCTION LEAFLET COULD RESULT IN DEATH, BODILY INJURY, OR PROPERTY DAMAGE. iwarning THE INSTRUCTIONS CONTAINED IN THIS IL AND ON PRODUCT LABELS HAVE TO BE FOLLOWED. OBSERVE THE FIVE SAFETY RULES: -DISCONNECTING -ENSURE THAT DEVICES CANNOT BE ACCIDENTALLY RESTARTED -VERIFY ISOLATION FROM THE SUPPLY -EARTHING AND SHORT-CIRCUITING -COVERING OR PROVIDING BARRIERS TO ADJACENT LIVE PARTS DISCONNECT THE EQUIPMENT FROM THE SUPPLY. USE ONLY AUTHORIZED SPARE PARTS IN THE REPAIR OF EQUIPMENT. THE SPECIFIED MAINTENANCE INTER- VALS AS WELL AS THE INSTRUCTIONS FOR REPAIR AND EXCHANGE MUST BE STRICTLY ADHERED TO IN ORDER TO PREVENT INJURY TO PERSONNEL AND DAMAGE TO THE SWITCHBOARD. Section 1: General information These instructions deal with the installation of the Magnum two-way mechanical interlock. The two-way mechanical interlock cable holds one circuit breaker in the open position and disables its closing mechanism when the other breaker is closed. A lever assembly is mounted on each breaker that interfaces with the pole shaft and the tripper bar. The lever assemblies are interconnected with cables. Cable can be used for any orientation of the breakers and are available in 5, 6, 8, and 10-foot lengths (1.5; 1.8; 2.4; and 3,0 m). Individual cable kits are ordered separately. Required tools 10 mm socket and 1/4-inch drive socket 10 mm open-end wrench 11/16-inch open-end wrench 3/8-inch open-end wrench (2) 0.5 mm feeler gauge 4 mm Allen wrench Drive extension Pliers Kit parts identification Refer to Figure 1 and Figure 2 for visual identification of the parts listed below. Kit 1 (2A11857G01, as shown in Figure 1): Interlock Assembly Kit. (A) M6 x 12 mm hex bolt (six) (B) M6 x 25 mm flat-head screw (two) (C) M6 lock washer (six) (D) M6 x 20 mm hex bolt (four) (E) Drive arm (two) (F) Interlock assembly (two) (G) Grease tube (one) Kit 2 (2A11858G01-G04, as shown in Figure 2): Interconnecting Kit (includes cables) (H) Cable bracket (two) (I) M6 x 10 mm thread-forming screws (four) (J) Cable assembly (two) in 5-, 6-, 8-, or 10-foot lengths (1,5; 1,8; 2,4; or 3,0 m) NNote: Parts (D) are not used for this installation

(A) (B) (C) (D) (G) (E) Figure 1. Contents of Kit 1 (F) Figure 3. Step 1 Label Bolt Step 2e: Remove the knockout (a U-shaped tab) from the right side of the front cover using pliers. Carefully file any excess material from broken edge. (H) (I) Remove Knockout Front Cover (J) Figure 2. Contents of Kit 2 Section 2: Installation of two-way cable interlock Proceed with the following 12 steps: Step 1e: Remove the front cover by unscrewing the hex-head captive bolts (four for three-pole, six for four-pole) that join the cover to the breaker housing using a 10 mm (1/4-inch) drive socket. Then hold the charge handle down approximately 45 degrees to pull off the cover. Figure 4. Step 2 Step 3e: Install the drive arm (E) to the right end of the pole shaft using an M6 x 25 mm flat-head screw (B) and 4 mm Allen wrench. The drive arm should be oriented as shown. Torque to 65-85 in-lbs (7,3-9,6 Nm). Bracket Trip Lever Pole Shaft M6 Screw (B) Drive Arm (E) End of Pole Shaft Figure 5. Step 3 2

Instructional Leaflet IL2C12860H06 Step 4e: Reinstall front cover (removed in Step 1). Perform Steps 1 to 4 for each breaker. Step 5e: Fasten the interlock assembly (F) to the drawout cassette s right-side sheet as shown using three M6 x 12 mm hex bolts (A) and lock washers (C). Torque to 40 50 in-lbs (4,5 5,6 Nm). Cassette Right-Side Sheet Upper Lock Nut Compression Spring M6 Hex Bolts and Washers Interlock Assembly (F) Spacer Tube Threaded End Figure 6. Step 5 Lower Nuts (should be shouldered against end of thread) Step 6e: Fasten the cable bracket (H) to the drawout cassette s rightside sheet (below the interlock assembly mounted in Step 5) as shown, using two M6 x 10 mm thread-forming screws (I). Torque to 65 85 in-lbs (7,3 9,6 Nm). Perform Steps 5 and 6 for each breaker. Rubber Boot Outer Bulkhead Nut Bulkhead Nut M6 Thread-Forming Screws (I) Figure 8. Step 7 - Cable Assembly Cable Bracket (H) Figure 7. Step 6 Step 7e: Perform the three tasks below to prep the cables before they are attached to the interlock assemblies. Check to be sure that all cables move freely in their cable housing. Each cable should have a long rod end and a short rod end. To perform the cable prep: 1. Remove the upper lock nut and spacer tube from both rod ends. 2. Remove the compresion spring from the short rod. 3. Two loose nuts should be positioned on the threads of each rod. Shoulder the lower nut against the end of the rod s threads until the nut stops. Using two 3/8 in. wrenches, tighten the upper nut against the lower nut (See Figure 9). Repeat the above process on any given cable. When prep is complete, install the breakers into their cassettes in the CONNECTED position. Figure 9. Step 7 - Cable Prep Step 8e: This step describes how to route and install the cables. Ensure that the breakers are in the OPEN and DISCHARGED positions and adhere to the following recommendations during cable installation: 4 inch (102 mm) minimum allowable cable housing bend radius and minimal number of total bends Use plastic wire ties/clamps to attach cable housing to the structure after installation and adjustment Do not compress cable housing Recheck to ensure cables move freely 3

Figure 11. Step 9. Figure 10. Step 8 Step 9e: This step describes how to attach the cables to the interlock assemblies. Each breaker needs one long rod and one short rod attached. The long (driven) rod will be attached first. To do so: 1. Slide the rubber boot toward the tip of the rod. 2. Unthread the outer bulkhead nut and slide the nut and lock washer upwards. 3. Slide the smaller diameter portion of bulkhead fitting in to the slot on the cable bracket (See Figure 11). 4. Raise cable assembly until threads of the bulkhead fitting show above the slotted hole in the bracket (See Figure 11). 5. Insert threaded end of rod into its swivel fitting. 6. Bring the bulkhead washer and nut down to the threads and hand-tighten. 7. Adjust the two bulkhead nuts to approximately center the fitting on the slot and hand-tighten. 8. Replace the rubber boot over end of fitting. 9. Replace spacer tube on rod end. 10. Replace lock nut on rod end. Hold the lower nuts that were tightened in Step 7 with pliers and use a 3/8-inch socket or a 3/8-inch open-ended wrench to tighten the lock nut until it touches the spacer tube. Torque to 30-40 in-lbs (3,3-4,5 Nm) Next, the short (drive) rod will be attached. The short rod is attached in the same way as the long rod except that it requires a compression spring (see Figure 13). Replace the compression spring after replacing the spacer tube on the rod tip. Manually compress the spring and replace the lock nut on rod end. Release the spring. Hold the lower nuts that were tightened in Step 7 and use a 3/8-inch socket or a 3/8-inch open-ended wrench to tighten the lock nut until it touches the spacer tube. Torque to 30 40 in-lbs (3,3 4,5 Nm). At the end of cable installation, the breakers should still be in the OPEN position. Figure 12. Step 9 - Long Rod Assembly Figure 13. Step 9 - Short Rod Assembly Step 10e: This step describes how to adjust the cables. Adjustment should be performed with the large bulkhead nuts ONLY and with all breakers OPEN. Ensure bulkhead fittings are still approximately centered on their slot and secure cables by snugly tightening bulkhead nuts with an 11/16-inch wrench. 4

Instructional Leaflet IL2C12860H06 Perform initial adjustments on the driven (long rod) end of cable. There should be a small (0.0 0.5 mm) clearance between the rod lock nut and the face of the swivel on which it pulls. Too much clearancee: adjust both bulkhead nuts to retract cable housing No clearancee: advance cable housing in a similar manner For additional adjustment lengthe: use bulkhead nuts on other end of cable When the proper clearance is attained on the driven end, tighten the cable bulkhead nuts on both ends to a torque of 100 120 in-lbs (11 13 Nm). With the breaker CLOSED, grasp and slowly rotate the driven lever counterclockwise. After about 30 degrees of rotation (lever approximately horizontal), the breaker should trip. If the breaker does not trip before the upper right-hand corner of the driven lever is within 3 mm of the interlock assembly flange (see Figure 15 Breaker TRIPPED), the driven lever and/or inner trip arm are out of specification. DO NOT CONTINUE THE INSTALLATION. Consult Eaton for additional instructions. To reach an EatonCare representative, call (877) 386-2273. Perform this check for each breaker. Drive Lever 0-4 mm Breaker Open Figure 14. Step 10. Section 3: Functional Tests of Interlock Assembly Step 1e: Perform the Checks below to test funtionality of the lever assembly. Check 1e: With the breaker OPEN and CONNECTED, observe the position of the drive (lower) lever. The gap between the lower right-hand corner of the drive lever and the interlock assembly flange should be 0 4 mm (see Figure 15 Breaker OPEN). Now CHARGE and CLOSE the breaker, and the drive lever should rotate approximately 60 degrees counterclockwise. The gap between the lower left-hand corner of the lever and the interlock assembly flange should be 1 7 mm (see Figure 15 Breaker CLOSED). If either of these gaps is out of specification, DO NOT CONTINUE THE INSTALLATION. Consult Eaton for additional instructions. To reach an EatonCare representative, call (877) 386-2273. Perform this check for each breaker. Check 2e: Now check the function of the driven (upper) lever and inner trip arm. With the breaker OPEN, the upper left-hand corner of the driven lever should be held in contact with the interlock assembly flange by the return spring, and the inner trip arm that operates the tripper bar should protrude a few millimeters beyond the right edge of the interlock assembly. Drive Lever Driven Lever Figure 15. Step 1. 1-7 mm 3 mm minimum Breaker Closed Breaker Tripped 5

Step 2e: The final step is to test the interlock. 1. CHARGE and CLOSE Breaker A. Breaker B should be held in the open condition. Inspect the driven lever on Breaker B. There should be less than a 5 millimeter gap between the upper right-hand corner of the driven lever and its stop (the interlock assembly flange). CHARGE and attempt to CLOSE Breaker B. It should not respond to the CLOSE attempt (no noise, no spring discharge, no contact motion). If the breaker does not respond as described, review Steps 6 through 10. Additional adjustment may be required at the cable bracket. 2. OPEN Breaker A. The interlock should release. CLOSE Breaker B. Verify that it closes with the OPEN/CLOSED indicator. Breaker A should now be held in the OPEN condition. Inspect the driven lever on Breaker A. There should be less than a 5 millimeter gap between the upper right hand corner of the driven lever and its stop (the interlock assembly flange). CHARGE and attempt to CLOSE Breaker A. It should not respond to the CLOSE attempt (no noise, no spring discharge, no contact motion). If the breaker does not respond as described, review Steps 6 through 10. Additional adjustment may be required at the cable bracket. Breaker A Breaker B Figure 16. Step 2 The mechanical interlock is now properly installed and adjusted. If some interlock parts are sticky, use a light amount of the lubricant grease (G) to reduce the friction. This is ONLY recommended if needed. 6

Instructional Leaflet IL2C12860H06 7

Disclaimer of warranties and limitation of liability The information, recommendations, descriptions, and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment, and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability, or otherwise for any special, indirect, incidental, or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations, and descriptions contained herein. The information contained in this manual is subject to change without notice. Eaton Corporation Electrical Sector 1000 Cherrington Parkway Moon Township, PA 15108 United States 877-ETN-CARE (877-386-2273) Eaton.com 2010 Eaton Corporation All Rights Reserved Printed in USA Publication No. IL2C12860H06 / Z8848 March 2012 PowerChain Management is a registered trademark of Eaton Corporation. All other trademarks are property of their respective owners.