S&C Circuit-Switcher Mark VI Outdoor Transmission (69 kv through 138 kv)

Similar documents
S&C Series 2000 Circuit Switchers Outdoor Transmission (69 kv through 230 kv)

S&C Trans-Rupter II Transformer Protector Outdoor Transmission (69 kv through 138 kv)

Specifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv)

Specifications. S&C Omni-Rupter Switches Outdoor Distribution (14.4 kv and 25 kv) Conditions of Sale

www. ElectricalPartManuals. com SPECIFICATIONS Page 1 of 24 March 24, 2003

Specifications. S&C Power Fuses Types SM- 4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through 34.5 kv)

Specifications. S&C Alduti-Rupter Switchesa Indoor Distribution (4.8 kv through 34.5 kv) Conditions of Sale SPECIAL TO THIS PRODUCT: How to Order

INSTRUCTIONS For Field Assembly and Installation

SPECIFICATIONS. S&C Alduti-Rupter Switches with Power Fusesa SPECIFICATION BULLETIN Indoor Distribution (4.8 kv and 13.

Publication No.: PSG

SPECIFICATION BULLETIN

Specifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34.

Product Specifications for Aluminum Vertical Break Switches

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

S&C Circuit-Switchers Mark VI Installed on S&C Mounting Pedestals 84- through 102-inch Phase Spacing Outdoor Transmission (69 kv through 138 kv)

INSTRUCTIONS Ç CAUTION. S&C Power Fuses Types SMD-1A, SMD-2B, SMD-2C, and SMD-3. For Field Assembly and Installation NOTE INSTRUCTION SHEET

S&C Mini-Rupter Switches Application The Standard Mounting Arrangement Scheme for S&C Mini-Rupter Switches Typical ED, reduced from full 11 size.

Specifications. S&C Switch Operators Types AS-1A and AS-10a. Conditions of Sale

Horizontal Circuit Switchers

Horizontal Circuit Switchers

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING

7. Residential Single-Family and Duplex Buildings (Dwellings)

Instructions for Installation

A 1.2 kv class externally removable secondary bushing

CENTER BREAK GROUP OPERATED AIR BREAK SWITCHES RATED 15.5kV THROUGH 170kV EFFECTIVE DATE: 10/25/16 REV B

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Product Specifications for Phase Over Phase GOABS(r)

INSTRUCTIONS For Field Assembly and Installation

Cleaning Flooded Gear

AMENDMENT ELECTRIC SERVICE MANUAL 2014

The Standard Mounting Arrangements for S&C Omni-Rupter Switches

Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings

CLEAVELAND / PRICE INC. Type RL-C Side Break Switch kv A. Bulletin DB-104E12

S&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv)

Installation. S&C Circuit-Switchers Mark VI 69-kV 51-inch Phase Spacing Single Pedestal Design Outdoor Transmission.

Volt Instrument Transformers

Kuhlman Electric Corporation Volt Instrument Transformers

Fuse & Switch. BUCHANAN Terminal Blocks. Product Facts High Density Blocks. Fuse Blocks. Switch Blocks. Common Features of 300 & 0300 Series

S&C Switch Operators Types AS-1A and AS-10

IB-FAS3 Mar Type FAS THRU 115Kv Amp 61 KA Momentary. Vertical-Break, Gang-Operated Outdoor Air Disconnect Switch.

Design Guide for Integration of Fixed-Mount Circuit Breakers

Kuhlman Electric Corporation Volt Instrument Transformers

Chapter 8 Interior Wiring and Lighting

Installation And Operation

PSC Terminations. Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables.

Substation Design Volume III

BUSWAY Low Voltage (Pow-R-Flex)

TABLE OF CONTENTS. Important Notices Underground Plant Protection Information. Commercial/Industrial Information Sheet

Specifications. S&C Mini-Rupter Switches Indoor Distribution (4.16 kv through 25 kv) Manually Operated Styles

Busway Construction. Bus Bars

CABINET - CURRENT TRANSFORMER Indoor - Outdoor 240 Volts Amperes Maximum

7 Single Family Service

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

The Standard Mounting Arrangements for S&C Alduti-Rupter Switches

Product Data. Features/Benefits. 42BH System Fan Coil. 800 to 4000 Cfm

A. Submit manufacturer's literature and technical data before starting work.

ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE

Installation and Operation

IEC Separable Connectors 36 kv and 42 kv, 630A and 1250A Front T-Body / Coupling (Rear) T-Body Connector

200 A and 600 A, 15, 25, and 35 kv junction bars for separable connectors

Easy-On II Terminations

Catalog 14A January 2013

Customer:... Model Number:... Serial Number:... Factory Reference Number:... Rated Torque (lbf-in):... Torque Overload Capacity (lbf-in):...

600 A 35 kv class BT-TAP deadbreak connector

INSTRUCTIONS. 1 Schematic. I Device ' I. S8C Switch Operators - Type CS-24. For Operation

Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:

Arktite Heavy Duty Circuit Breaking Plugs and Receptacles

Customer Substation Manual

Specifications. S&C Type XS Fuse Cutouts. Outdoor Distribution (4.16 kv through 25 kv)

100-Ampere Busway. Effective November 2005 New Information. Elbow, Busway and Cable Tap Box. Technical Data TD E

M-Force three-phase switch

FIELD CONNECTIONS FOR YK CHILLER (STYLE G) OPTIVIEW CONTROL CENTER WITH REMOTE MEDIUM VOLTAGE SSS

Disconnect & ByPass Switches

Section 6 Electric Metering: Residential

TYPE V CENTER BREAK SWITCH

S&C Loadbuster Disconnects

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES

OTEC Transfer switch open transition

Arktite Heavy Duty Circuit Breaking Plugs and Connectors

EXPANSION JOINT SELECTION GUIDE

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Special Specification 6058 Battery Back-Up System for Signal Cabinets

Installation. S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

CABINET - CURRENT TRANSFORMER Indoor - Outdoor 240 Volts Amperes Maximum

Riverhawk Company 215 Clinton Road New Hartford NY (315) Free-Flex Flexural Pivot Engineering Data

M-Force three-phase switch

IEC Separable Connectors 17.5 kv/24 kv, 630A

SOLAR HEATING SYSTEM

EXBLI & EXBSPI Series. Circuit Breaker Panelboards for Harsh and Hazardous Environments

3.1 Overview of ATCO Electric s URD System Design

Indianapolis Power & Light Company

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Transmission Switching

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

Corp L3 Revised CB17/CBH17 SERIES UNITS SPECIFICATIONS CB17-95V CBH17-95V

SECTION MOTOR CONTROLLERS

Three-Phase Pole Mounted Recloser

Transcription:

Outdoor Transmission (69 kv through 138 kv) Construction Guide This publication sets forth the data required for the user to design a support structure or pedestals for a Mark VI Circuit-Switcher; the data required to properly construct foundations for a Mark VI Circuit-Switcher on S&C Mounting Pedestals; the maximum-continuous and permissible-peak terminal pad loading limits for a Mark VI Circuit-Switcher; pole-unit wiring requirements; and external wiring and battery requirements. Table of Contents Section Page Section Page Installation on a User-Furnished Support Structure Checklist for Required Installation Materials....2 Loadings for Support Structures....2 How to Determine Total Bending Moments and Total Forces............................ 3 Foundation Loading Data for S&C Mounting Pedestals... 5 Terminal-Pad Loading Limits... 7 Battery and Wiring Requirements... 8 July 21, 2008 S&C Electric Company Data Bulletin 712-60

Installation on a User-Furnished Support Structure Checklist for Required Installation Materials The following items are included with the Mark VI Circuit- Switcher: Three interrupters Three interrupter charging motors Three vertical-break disconnectsa Hardware to attach the interrupters to the disconnects Hardware to attach the charging motors to the interrupters One drive-train gearbox (double offset) Interphase operating shaft sections, cut to lengtha Vertical operating shaft sections, cut to lengtha Drive-train couplings and associated hardware Mark VI CS-1A Switch Operator. The following items are not included and must be furnished by the user: Mounting brackets and hardware to attach the Mark VI CS-1A Switch Operator to the structure Mounting brackets and hardware to attach the powertrain gearbox to the structure Hardware to attach the conduit to the structure Conduit and wiring to electrically connect pole-units to operator. All of the above items are included when S&C Mounting Pedestals are furnished. Loadings for Support Structures The high operating speed of the vertical-break disconnect (1.5-second total travel time on closing) brings about high acceleration and deceleration rates, which result in high dynamic forces transferred to the support structure and the adjoining bus. The support structure must be designed to withstand apparatus loads, dead-weight loads, wind loads, and ice loads. Structures should be designed to limit deflections as follows: Horizontal deflections of the structural section to which a pole-unit is attached should not exceed C \, inch in any direction. Horizontal deflections of the structural section under static wind load should not exceed one inch. The total of the rotational deflections of the switch operator and the gearbox support in resisting the switch operator locked-rotor torque of 21,500 inch-pounds (2429 Newton-meters) should not exceed 5. Pole-units must be mounted vertically upright, at 90 ±15. For purposes of supporting-structure design, it is assumed that dynamic forces and static wind loads do not occur simultaneously. Generally, the bending moments produced by dynamic forces will dictate the design of the structure and the foundation. Forces produced by wind loads must be considered in the case of high structures, as these static bending moments may exceed the dynamic moments. In these loading diagrams, no attempt has been made to indicate a specific arrangement of the supporting structure, since there are many ways in which it can be executed. However, the values shown provide complete loading data. (Steel pedestals are available from S&C which meet the requirements outlined herein.) For further information on the arrangement of the components for a specific installation, refer to the catalog drawing supplied by S&C. a A drawing or specification detailing the configuration of the userfurnished structure must be made available to S&C Electric Company at the time of order. Vertical and interphase pipe is cut to length and mounting holes on the pole-unit base may need to be customized to the userfurnished structure. 2 S&C Data Bulletin 712-60

How to Determine Total Bending Moments and Total Forces M wt and M wl are the wind moments in the transverse and longitudinal directions, respectively, at each Circuit-Switcher pole-unit. F wt and F wl are the wind forces in the transverse and longitudinal directions, respectively, at each Circuit-Switcher pole-unit. For individual pole-units mounted on independent structures of height B, the maximum bending moment at the foundation may be found as follows: Transverse: M wt + (F wt 3 B)+ (Bending moment from wind acting on structure) Longitudinal: M wl + (F wl 3 B) + (Bending moment from wind acting on structure) F c and F o appear as forces at the Circuit-Switcher terminal pads accompanying closing and opening operations. F c is a direct compression force resulting from closing of the Circuit-Switcher. F o is a shear force parallel to the pole-unit base. M o is a turning moment tending to rotate the pole-unit in a counterclockwise direction as viewed in the elevation drawings. Limiting deflections of the Circuit-Switcher supporting members to recommended values will ensure that these forces will be absorbed by the structures and not transferred to adjoining bus or other apparatus (e.g., bushings). Use of expansion joints at Circuit-Switcher terminal pads will compensate for inherent insulator-column deflection. LEGEND: A = Moment arm of force F o B = Height of pedestal or supporting structure F c = Dynamic force accompanying closing operation F o = Dynamic force accompanying opening operation F wl = Static wind force, longitudinal F wt = Static wind force, transverse M o = Dynamic bending moment (= F o 3 A) M wl = Static wind bending moment, longitudinal M wt = Static wind bending moment, transverse T 1 = Switch operator locked-rotor torque T 2 = Torque delivered to interphase shaft W 1 = Weight of one Circuit-Switcher pole-unit W 2 = Weight of switch operator X = Horizontal distance from the centerline of rotating insulator stack to center of gravity Y = Vertical distance from center of gravity to bottom of base F c CENTER OF GRAVITY Y W 1 X F o F wl A F wl M wl Dimensions in Inches F o F wl M o M wl 34 (864) 3 (76) 9 (229) 15 (381) Switch operator mounting-hole spacing, inches W 2 S&C Data Bulletin 712-60 3

F wt T 2 F wt M wt T 1 B Gearbox support may be installed as indicated, at the end of the phases or at opposite side To base of mounting structure MAXIMUM LOADING DATA Per pole-unit1 Rating, kv 69 F c, lbs. 2 225 (1001) F o, lbs. 2 200 (890) F wl, lbs. 2 410 (1824) F wt, lbs. 2 425 (1890) M o, (Newtonmeters)2 17,400 (1966) M wl, (Newtonmeters)2 7,500 (847) M wt, (Newtonmeters)2 9,000 (1017) T 1, (Newtonmeters) 21,500 (2429) T 2, (Newtonmeters) 20,000 (2260) W 1, lbs. (kg)23 730 (329) W 2, lbs. (kg) (158) A, in. 87 (2210) X, in. 5.5 (140) Y, in. 22 (559) 115 (1557) 275 (1223) 530 (2358) 580 (2580) 31,400 (3548) 16,500 (1864) 18,200 (2056) 21,500 (2429) 20,000 (2260) 1040 (468) (158) 114 (2896) 15 (381) 30 (762) 138 450 (2002) (1557) 560 (2491) 625 (2780) 45,200 (5107) 20,500 (2316) 22,000 (2486) 21,500 (2429) 20,000 (2260) 1120 (504) (158) 129 (3277) 19 (483) 34.5 (876) 1 Values shown assume 100-mph (160-kmph) wind velocity. 2 Per Circuit-Switcher pole-unit. 3 For Pre-insertion Inductors Option -P6, add 240 lbs. (109 kg) per pole-unit (W1 ). For Pre-insertion Inductors Option -P61, add 215 lbs. (97 kg) per pole-unit. 4 S&C Data Bulletin 712-60

Foundation Loading Data for S&C Mounting Pedestals The following tables provide the loading data necessary to properly construct foundations for Mark VI Circuit-Switcher pole-units installed on S&C Mounting Pedestals. This loading data is based on the most-adverse combination of maximum terminal-pad loading limits and accounts for the dead-weight contribution of the Mark VI Circuit-Switcher, Mark VI CS-1A Switch Operator, and S&C Mounting Pedestal(s), along with wind loading of 100 miles (160 kilometers) per hour. Mark VI Circuit-Switcher, when installed with the recommended S&C anchor bolts and with flexible-conductor connections at all six terminal pads, is capable of withstanding seismic loading of 0.2 g ground acceleration in any direction, as well as performing as intended during such loading and afterward. Dimensions in Inches 4 3 [ 1Z\v (32) FOR TWO-PEDESTAL SWITCHES 4 3 [ 1Z\x (38) FOR SINGLE-PEDESTAL SWITCHES 20 24 (508) (610) 12 (305) 12 (305) 20 (508) 24 (610) S M S MOUNTING PEDESTAL BASE DETAIL T S&C Data Bulletin 712-60 5

MOUNTING-PEDESTAL FOUNDATION LOADING DATA Mark VI Circuit-Switcher12 Rating, kv 69 115 138 Phase Spacing, inches 51 (1295) 84 (2134) 84 (2134) 96 (2438) 102 (2591) 84 (2134) 96 (2438) 102 (2591) Pedestal Height, inches Mounting Pedestal Suffix Bending Moment, M, ft.-lbs. (Newton-meters) Shear Load, S, lbs. Thrust Load, T, lbs. Static Dynamic Total 96 (2438) -E84 28,000 (37963) 3,200 (14234) 3,800 (16903) 3,000 (13345) 6,800 (30248) 120 (3048) -E104 34,000 (46098) 3,300 (14679) 3,900 (17348) 3,000 (13345) 6,900 (30693) 144 (3658) -E124 40,500 (54911) 3,400 (15124) 4,000 (17793) 3,000 (13345) 7,000 (31138) 96 (2438) -E88 20,000 (27116) 2,100 (9341) 2,600 (11565) 1,500 (6672) 4,100 (18238) 120 (3048) -E108 24,000 (32540) 2,200 (9786) 2,700 (12010) 1,500 (6672) 4,200 (18683) 144 (3658) -E128 28,000 (37963) 2,300 (10231) 2,800 (12455) 1,500 (6672) 4,300 (19127) 96 (2438) -E88 27,500 (37285) 2,300 (10231) 3,000 (13345) 1,500 (6672) 4,500 (20017) 120 (3048) -E108 32,000 (43386) 2,400 (10676) 3,100 (13789) 1,500 (6672) 4,600 (20462) 144 (3658) -E128 36,500 (49487) 2,500 (11121) 3,200 (14234) 1,500 (6672) 4,700 (20907) 96 (2438) -E89 27,500 (37285) 2,400 (10676) 3,100 (13789) 1,500 (6672) 4,600 (20462) 120 (3048) -E109 32,000 (43386) 2,500 (11121) 3,200 (14234) 1,500 (6672) 4,700 (20907) 144 (3658) -E129 36,500 (49487) 2,500 (11121) 3,300 (14679) 1,500 (6672) 4,800 (21351) 96 (2438) -E81 27,500 (37285) 2,400 (10676) 3,100 (13789) 1,500 (6672) 4,600 (20462) 120 (3048) -E101 32,000 (43386) 2,500 (11121) 3,200 (14234) 1,500 (6672) 4,700 (20907) 144 (3658) -E121 36,500 (49487) 2,600 (11565) 3,300 (14679) 1,500 (6672) 4,800 (21351) 96 (2438) -E88 31,500 (42708) 2,500 (11121) 3,100 (13789) 1,500 (6672) 4,600 (20462) 120 (3048) -E108 36,500 (49487) 2,600 (11565) 3,200 (14234) 1,500 (6672) 4,700 (20907) 144 (3658) -E128 41,500 (56267) 2,700 (12010) 3,300 (14679) 1,500 (6672) 4,800 (21351) 96 (2438) -E89 32,000 (43386) 2,500 (11121) 3,200 (14234) 1,500 (6672) 4,700 (20907) 120 (3048) -E109 36,500 (49487) 2,600 (11565) 3,300 (14679) 1,500 (6672) 4,800 (21351) 144 (3658) -E129 41,500 (56267) 2,700 (12010) 3,400 (15124) 1,500 (6672) 4,900 (21796) 96 (2438) -E81 32,000 (43386) 2,500 (11121) 3,200 (14234) 1,500 (6672) 4,700 (20907) 120 (3048) -E101 36,500 (49487) 2,600 (11565) 3,300 (14679) 1,500 (6672) 4,800 (21351) 144 (3658) -E121 41,500 (56267) 2,700 (12010) 3,400 (15124) 1,500 (6672) 4,900 (21796) 1 A single column is used for 69-kV Mark VI Circuit-Switchers with 51-inch phase spacing. All other models use two columns. 2 Values for Pre-insertion Inductors are included in the foundation loading data. 6 S&C Data Bulletin 712-60

TERMINAL-PAD LOADING LIMITS TERMINAL-PAD LOADING LIMITS In-line loads in the same direction12 Rating, kv 69 115 138 In-Line with Terminal Pads Perpendicular to Terminal Pads4 Vertical to Terminal Pads Maximum Continuous Permissible Peak3 Maximum Continuous Permissible Peak3 Maximum Continuous Permissible Peak3 L U, lbs. 50 (224) 50 (224) 50 (224) L L, lbs. 150d 150d 150d L U, lbs. 65 (291) 65 (291) 65 (291) L L, lbs. 300f (1345) 300f (1345) 300f (1345) P U, lbs. 20 (90) 20 (90) 20 (90) P L, lbs. 75d (336) 75d (336) 75d (336) P U, lbs. 30 (134) 30 (134) 30 (134) P L, lbs. 150f 150f 150f V U, lbs. V L, lbs. V U, lbs. V L, lbs. 1 Higher terminal-pad loading combinations for the disconnect and interrupter terminal pads may be possible, depending on the loads each is required to carry. Contact the nearest S&C Sales Office for more information. 2 Terminal pad Z\x0330 #356-T6 aluminum alloy for lower terminal and Z\x0330 tin-plated copper on upper terminal. 3 Permissible-peak loads are calculated at wind loads of 100 miles (160 kilometers) per hour. For terminal-pad loading limits at higher wind loads, contact the nearest S&C Sales Office. 4 Perpendicular loads are calculated at a maximum pull-off angle of 30 from in-line. Contact the nearest S&C Sales Office if a more severe pulloff angle is required. d With Pre-insertion Inductor Option -P61 or -P6 terminal-pad load is limited to 50 lbs. (224 N) on the disconnect end. f With Pre-insertion Inductor Option -P61 or -P6 terminal-pad load is limited to 100 lbs. (449 N) on the disconnect end. P L P U L L L U TOP VIEW V U LEGEND: L U = Interrupter terminal pad, in-line loads L L = Disconnect terminal pad, in-line loads P U = Interrupter terminal pad, perpendicular loads P L = Disconnect terminal pad, perpendicular loads V U = Interrupter terminal pad, vertical loads V L = Disconnect terminal pad, vertical loads V L SIDE VIEW S&C Data Bulletin 712-60 7

Battery and Wiring Requirements Interrupters are shipped with 12 inches (305 mm) of 20-gauge wire running from the electrical junction boxes, with butt splices on the ends for connection to pole-unit wiring. S&C recommends use of 18-gauge tinned stranded wire to connect the interrupters and motor operators to the Mark VI CS-1A Switch Operator. Shielded wire is not required. S&C Mounting Pedestals include all necessary wiring and conduits to connect the interrupters to the Mark VI CS-1A Switch Operator. If the Mark VI Circuit-Switcher is to be installed on a user-furnished support structure or pedestals, the user must furnish the appropriate wiring and conduit. Optional quick-connect cable is available by specifying catalog number suffix -C2 or -C3. Amphenol Tri-Start connectors will be supplied in place of the interrupter electrical junction box and charging motor wiring.d d Amphenol is a trademark of Amphenol Aerospace Division of the Amphenol Corporation. MARK VI CIRCUIT-SWITCHER Mark VI CS-1A Switch Operator Control source (battery1 or transformer) Mark VI CS-1A Switch Operator L 1 Catalog Number Suffix Schematic Wiring Diagram Drawing Control Source Voltage Rating, Volts Motor Accelerating Current at Rated Voltage, Amperes Minimum Size of Control Wire for Line L1, A.W.G.2 Distance, Feet 100 200 300 400 500 1000 2000 -A CDR-6514 48 V dc 48 80 6 4 2 1 1/0 4/0 -B CDR-6515 125 V dc 125 30 12 10 8 8 6 4 1 -D CDR-6516 115 V 60 Hz 115 46 10 6 6 4 2 1/0 1 Recommended minimum battery rating for Mark VI Type CS-1A Switch Operator is: Volts, dc One-Minute Discharge Rate, Amperes 48 75 125 36 2 Where long distances and large wire sizes are encountered, comparative cost of relocating battery closer to switch operator should be considered. 8 S&C Data Bulletin 712-60