INSTALLATION AND OPERATING INSTRUCTIONS FOR FLOODED TUBULAR-HP AND TUBULAR-LM FAST CHARGE MOTIVE POWER BATTERIES

Similar documents
INSTALLATION AND OPERATING INSTRUCTIONS FOR FLOODED TUBULAR-HP MOTIVE POWER BATTERIES

Pallet Pro On-Board Power System and 6 Volt Group 27 Deep Cycle Bloc Batteries GB A Division of Exide Technologies

Deep Cycle Battery Safety. First. Battery Handling, Maintenance & Test Procedures

Long Duration MCT LEAD CALCIUM H1T LEAD CALCIUM SECTION

RAILROAD & DIESEL STARTER BATTERY USER MANUAL

SECTION

GNB Industrial Power EHF SERIES Family of Chargers

SPECIFICATIONS General Purpose/Long Duration Flooded Batteries TCXG LEAD CALCIUM. SECTION 33.40G A Division of Exide Technologies

SECTION A Division of Exide Technologies

Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries

Today, we re going to talk about battery safety. We ll discuss all the key issues associated with using batteries safely, including battery hazards,

Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service

EnergyCell FLA Series. Owner s Manual

SECTION 26.10C A Division of Exide Technologies

Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service

SECTION

SECTION 26.10C

SPECIFICATIONS. Top Terminal Batteries. SECTION A Division of Exide Technologies

Instructions for use. Hawker Premier

GNB Flooded. Long Duration MCT LEAD CALCIUM NAT LEAD ANTIMONY NCT LEAD CALCIUM HAT LEAD ANTIMONY HCT LEAD CALCIUM

Industrial Batteries Classic OCSM Energy delivery with high efficiency.

SECTION TECHNOLOGIES I NDUSTRIAL E NERGY

FLUSH EYES IMMEDIATELY WITH WATER. GET MEDICAL HELP FAST. SULFURIC ACID CAN CAUSE BLINDNESS OR SEVERE BURNS.

Basic Battery Safety. Lead Acid Storage Batteries

- Optional Audio warning when discharge test is complete or tester malfunction.

Pump Sentry. Models 812 PS & 1612 PS INSTALLATION INSTRUCTIONS

A+ Battery Backup Power Supply For use with Hydromatic model B-A1/BV-A1

VRLA Batteries. Battery Installation And Start up Guide

SECTION

Automatic Battery Charger Switching mode with Micro-controlled Input: Vac / Output: 12Volt DC

Automatic Battery Charger Switching mode with Micro-controlled Input: Vac / Output: 12Volt DC

Industrial Batteries Marathon T AGM long-term power on modular basis. Specifications

Proper Torque Values for Connection Hardware. 90 to 100 in-lbs

SOS SERIES SOS1 SOS2. Spares On Site Battery Cabinet Installation Guide rEV3

Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries

INSTALLATION AND OPERATION MANUAL

INSTRUCTIONS FOR CONTINUED AIRWORTHINESS COMPONENT MAINTENANCE MANUAL CONCORDE VALVE REGULATED LEAD-ACID RG-441 BATTERY AUTHORISED UNDER TSO-C173

Dual-Lite Trident TRF 40 Wide Battery Cabinet 20-40kVA Systems USER MANUAL

PALLET PRO ON-BOARD POWER SYSTEM AND 6 VOLT GROUP 27 DEEP CYCLE BLOC BATTERIES

Industrial Batteries Standby Power Marathon L Reliable and safe energy in long-term storage. Specifications

POWER FOR TOMORROW. Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service

Industrial Batteries Standby Power Classic Solar Powerful energy storage for photovoltaic systems. Specifications

BATTERY 8A - 1 BATTERY CONTENTS

TRICKLE CHARGER MODEL NO: ATC12VB OPERATION & MAINTENANCE INSTRUCTIONS PART NO: ORIGINAL INSTRUCTIONS LS0618 ISS 2

INSTALLATION AND OPERATION MANUAL

IEEE IAS Atlanta Chapter

NILFISK BA 500 Service Manual

TECHNICAL MANUAL RS02061

Vehicle battery BATTERY WARNING SYMBOLS BATTERY CARE

24 VOLT AUTOMATIC BATTERY CHARGER PART NO

Installation, Operation & Maintenance Manual

Automatic Battery Charger Switching mode with Micro-controlled Input: Vac / Output: 12Volt DC

Batteries and more. Powered by (CE, UL & ISO9001 APPROVAL)

INSTALLATION & OPERATING INSTRUCTIONS

Operator Manual. The most important component is you. This operator manual. has information for. all models of series. B plus some options and

SERVICE INFORMATION BATTERY/CHARGING SYSTEM XL CHARGING SYSTEM INSPECTION 15-5 REGULATOR/RECTIFIER 15-6 ALTERNATOR 15-7

OPERATION & MAINTENANCE INSTRUCTIONS

LESTRONIC II BATTERY CHARGER MODEL 07210

TROJAN BATTERY USER S GUIDE

Installation & Maintenance Manual

Industrial Battery Care

DISCHARGER-ANALYZER BDX USER'S MANUAL

40 V LITHIUM-ION BATTERY ATTACH YOUR RECEIPT HERE AB13786C 1. kobalttools.com ITEM # /

Smart Charger 12-24V 60A, 1600W

Operator Manual. This operator manual has. information for all models. of series M plus some. options and accessories. Some of the illustrations

OPERATION & MAINTENANCE INSTRUCTIONS

400 Watt Backup Power System Owner s Manual

MXEM Manual Push/Electric Lift Stackers Service Manual

INSTALLATION & OPERATING INSTRUCTIONS

MAxxIMA SOLAR BATTERY USER MANUAL

STEP-BY-STEP INSTALLATION GUIDE

Operating conditions of VRLA batteries in HVCBS and LVDBS Systems

PAC 600 PAC 800 PAC 800 comfort

Light condition and operation Windshield glass condition Wiper blade condition Paint condition and corrosion Fluid leaks Door and hood lock condition

C&D Technologies, Inc. Dynasty Division 900 East Keefe Avenue Milwaukee, WI53212 Phone: Fax:

36 VOLT AUTOMATIC BATTERY CHARGER PART NO

OPERATION & MAINTENANCE INSTRUCTIONS

HIGH FREQUENCY AUTOMATIC BATTERY CHARGER

Battery. Student booklet

C3 Operating Instructions

5 IN 1 JUMP START OPERATION & MAINTENANCE INSTRUCTIONS MODEL NO: JS5IN1 PART NO: LS0810

4 in 1 POWER STATION Model: 7226

Matson Jump Starter Operator s Manual

Installation, Operation & Maintenance Manual. For Pro-Fill kits with part numbers beginning in BG

HAZE 6/12 Volt. STATIONARY 6/12 Volt BATTERIES. HAZE Battery Co. INSTALLATION and OPERATING INSTRUCTIONS. Supplied Worldwide by :

RECHARGEABLE SPOTLIGHT

Sentry Battery Charger. Installation and Operations Manual Section 75

PW Operator Manual PW This operator manual. has information for all. models of series PW plus some options. and accessories.

IMPORTANT SAFETY INSTRUCTIONS

SECTION 6 4 SERVICE PROCEDURES AND SPECIFICATIONS. Electrical components

BATTERY CHARGER-STARTER

MP V 8A Electronic Smart Charger. Instruction and Information Manual

JUMP STARTER OPERATOR S MANUAL RA1900

MULTIVOLTAGE PORTABLE BATTERY CHARGER MVM

INSTALLATION AND OPERATION INSTRUCTIONS

2603 Battery Pal 3 AMP, 1 2 VOLT BATTERY CHARGER

INSTRUCTION MANUAL. Maintenance-free Absorbent Glass Mat technology and valve-regulated batteries. (AGM / VRLA)

12 VDC Power Sources For Your RV

MB V 3-IN-1 JUMP STARTER WITH SPIRAL WOUND BATTERY

BATTERY 8A - 1 BATTERY CONTENTS

Transcription:

PLEASE READ THESE INSTRUCTIONS BEFORE PLACING BATTERIES INTO SERVICE. THESE INSTRUCTIONS MUST BE SHIPPED WITH THE BATTERY AND MUST BE DELIVERED TO THE USER. INSTALLATION AND OPERATING INSTRUCTIONS FOR FLOODED TUBULAR-HP AND TUBULAR-LM FAST CHARGE MOTIVE POWER BATTERIES 1. SAFETY 1.1 Follow your company s Safety Instructions when working with or near industrial truck batteries. Observe the caution label affixed to the battery. Thoroughly familiarize yourself with industry and government guidelines (OSHA, ANSI) for charging, handling, and maintaining industrial batteries. 1.2 Assign battery and charger care to properly trained personnel. 1.3 This battery contains sulfuric acid electrolyte. Avoid contact with skin, eyes, or clothing. Wear rubber apron, gloves, boots, and goggles or face shield when handling, checking, filling, charging or repairing batteries. 1.4 Keep water readily available for flushing spilled electrolyte from eyes or skin. Use plain water only and obtain medical attention immediately. Special deluge showers and eye wash basins are required. 1.5 Batteries produce hydrogen and oxygen gas during charge. Keep open flames away. Do not check electrolyte level with a cigarette lighter or match. Use a flashlight or permanent lights. Switch on/off away from the top of the battery. Do not smoke or create sparks. 1.6 Lift batteries with a certified/approved hoist, crane, lift truck, or similar equipment. Move batteries with trucks, conveyors, or rollers. Be sure to place a rubber mat or similar insulating material across the tops of coverless batteries when handling. Make sure equipment is of ample strength and properly installed. DO NOT USE CHAIN OR WIRE ROPE SLINGS. 1.7 Never lay metal tools, such as wrenches or screwdrivers, on top of a battery. Page 1

1.8 Disconnect the battery from the truck when performing maintenance and repair on motor or electrical system. 1.9 Open or break the battery circuit before attempting repairs to the charging plug or receptacles. 1.10 Apply a strong neutralizer, such as baking soda or soda ash, when electrolyte is spilled on the floor. Check local regulations regarding the disposal of neutralized waste. 2. RECEIVING BATTERIES Immediately upon receipt of shipment, examine the outside of the packing for signs of rough handling before accepting the battery from the carrier. Wet spots on the shipping pallet may be an indication of leaking jars broken in shipment. If there is evidence of damage, the receipt should be signed and both copies (carrier s and receiving copies) marked Shipment Received Damaged. The carrier should be called immediately and asked to make a Carrier s Inspection for Damage Report. If concealed damage is later detected, the carrier should be called immediately and requested to make a Carrier s Inspection for Concealed Damage Report. After inspection by the carrier, arrangements should be made with the local GNB Industrial Power representative to have the battery repaired before placing it in service. BEFORE PLACING BATTERIES IN SERVICE, REVIEW AND FOLLOW THE SAFETY GUIDELINES LISTED IN ITEM 1. SAFETY. 3. PLACING IN SERVICE Verify that the battery weight meets or exceeds the minimum truck weight requirements. Allow the battery to cool or warm to room temperature before charging or adding water. Make sure the battery charger is properly matched to the battery and GNB-approved for use with Tubular-HP or Tubular-LM Fast Charge batteries. Use a charger with automatic charger termination controls. Remove the vent caps from each cell and check to see that the electrolyte level is above the top of the separators. If it is obvious that the electrolyte has spilled out of any cells, replace it with electrolyte of the same specific gravity as found in the other cells of the battery. Insert the vent caps and give the battery a freshening charge until there is no increase in specific gravity for three hydrometer readings taken at one hour intervals. During shipment of the battery, low temperatures and/or normal shock and vibration often results in a drop in the electrolyte level. If the level is below the top of the separators, recheck it after 3 hours of charging. If the level remains below the top of the separators, add water or electrolyte to the proper level at the end of charging. Page 2

Following the first month of service, the battery should reach its normal operating specific gravity of 1.305 +/- 0.005 at 77 F. IF BATTERIES ARE NOT IN USE, KEEP THEM CHARGED. CHECK THE SPECIFIC GRAVITIES MONTHLY AND GIVE A FRESHENING CHARGE (3 OR 4 HOURS AT THE FINISH RATE) IF THE GRAVITIES HAVE FALLEN 0.030 OR MORE; OTHERWISE GIVE A FRESHENING CHARGE EVERY THREE MONTHS. 4. OPERATION Batteries are rated in ampere-hours (Ah) and are selected to perform a specific workload within an established period of time. Because fast charge systems are designed to return a significant amount of ampere-hours in short periods of time, fast charge batteries are capable of delivering up to 160% of their rated capacity within a 24-hour period. To achieve such high levels of usage, operators must be diligent to "plug in" at all opportunities throughout the day, including breaks, meals, and shift changes. Care must be taken to ensure specific gravity readings in the battery cells do not go below 1.160 at any time. A Tubular-HP or Tubular-LM Fast Charge Battery is designed for fast charging during breaks, meal times, and shift changes. When not being used, the battery should always be connected to the charger. The battery must be limited to no more than twenty (20) hours of use per day, six days per week, and 50 weeks per calendar year. A battery should always be recharged immediately following a complete discharge. Never allow it to remain in a discharged condition; otherwise, permanent damage may result. Flooded tubular-plate motive power batteries are designed and built to deliver 80% of their rated capacity at 77 F. 5. TEMPERATURE In the operation of fast charge lead-acid batteries, the electrolyte temperature must never exceed 140 F or a 7-day average temperature of 125 F. Following the end of the day full charge, the battery should be allowed to cool to ambient temperature prior to the next discharge. The average electrolyte temperature of the battery shall not drop below 60 F (15 C). If a battery consistently operates at temperatures close to the allowable maximums, contact your local GNB representative for service. Page 3

6. CHARGING The start rate of a fast charge battery can be as high as 40% of the batteries rated capacity at the 6 hour rate. During the end of the day full charge, the charge rate should taper down to the finish rate (approximately 5% of the rated capacity) by the time the battery is 85% charged and may be even lower when the battery is fully charged. Short running times and/or low end-of-charge specific gravities may indicate inadequate recharge. Consult your local GNB representative on specific charging problems. 7. MAINTENANCE KEEP RECORDS Showing specific gravities, equalizing, charging, temperature, cleaning and voltages on a monthly basis. These records are required to maintain your warranty. TEMPERATURE Under nor mal fast charge operating conditions, the electrolyte temperature shall be between 60-140 F. Operating temperature above 100 F will reduce the battery s service life. Operating temperature below 60 F results in less capacity and special charging is required. WATER ADDITIONS GNB-approved fast chargers have the capability for equalize charging at specific times and days of the week (e.g. Sunday 08:00). Water additions can be made the following day prior to use, provided an equalization charge is confirmed to have been performed. EQUALIZE Once a week. DEPTH OF DISCHARGE Do not discharge the battery below 80% of the rated capacity. Over discharging shortens the battery life and voids the warranty. CLEANING Keep the top of the battery clean and dry. See Item 8. PREVENTIVE MAINTENANCE SCHEDULE WEEKLY Check electrolyte levels (see water additions). Equalize charge. MONTHLY Record electrolyte specific gravities. Visual inspection and confirmation that the battery-mounted monitor is functioning properly. Inspect the cables and charging plugs. Clean the top of the cells. SEMI-ANNUAL Inspect the charger. Confirm proper output voltage and current. Check for external damage, frayed cables, or worn connectors. Clean the exterior of the battery. Page 4

TROUBLE SIGNS Battery temperature averages more than 125 F. Open circuit cell voltages vary by 0.15 volts or more and specific gravity varies by 0.020 or more during equalizing. The top of the battery is always wet or one cell requires excessive water. 8. MAINTENANCE CLEANING The top of the battery should be kept clean and dry. Keep the vent caps in place during use and charging. Remove the vent cap only to observe electrolyte levels, make water additions, take temperatures, or take specific gravity readings with a hydrometer. If the battery requires cleaning, contact your local GNB Industrial Power servicing representative. The solution used to clean and neutralize the outside of the batteries should be disposed of in an environmentally safe manner. 9. WATER ADDITIONS Maintain electrolyte levels above the top of the separators, but no higher than 1/8" from the bottom of the vent well. Check the electrolyte level weekly, or as necessary depending on battery use prior to charging. If the level is not visible (below the top of the separators), add just enough water to cover it and then proceed with charging the battery. Otherwise, defer watering the battery until the end of the charging period when the battery is fully charged and the charger has tapered to its finish rate. At that time, add enough water to bring the electrolyte level to 1.2-2.2 of the top of the cover. Always use distilled water or water that is known to be free of abnormally high amounts of impurities. Contact your local GNB Industrial Power representative if you are not sure of your water quality. BATTERIES MUST BE VISUALLY INSPECTED PER THE ABOVE SCHEDULE EVEN WITH THE USE OF A WATERING SYSTEM. COVER VENT WELL POST 1.25 HIGH WATERING LEVEL 2.0 JAR LOW WATERING LEVEL Page 5

10. SERVICE AND PARTS Your local GNB Industrial Power sales representative has more information regarding the full range of maintenance and repair service available. GNB Industrial Power can also supply all of your battery, charger, and accessory device replacement part needs. For more information in the U.S.A. and Canada, call 1-888-563-6300. All others, please contact your local GNB Industrial Power battery sales representative. 11. RECYCLING U.S. Federal and State Regulations require that lead acid batteries be handled and disposed of in compliance with strict guidelines. GNB Industrial Power offers disposal service for lead acid batteries. Call 1-888-438-5865 to arrange a pick-up or to get additional information. Page 6

This page left blank

GNB Industrial Power The Industry Leader. GNB Industrial Power, a division of Exide Technologies, is a global leader in motive power battery and charger systems for electric lift trucks and other material handling equipment. With a strong manufacturing base in both North America and Europe and a truly global reach (operations in more than 80 countries) in sales and service, GNB Industrial Power is best positioned to satisfy your power needs locally as well as all over the world. Based on over 100 years of technological innovation, the Motive Power group leads the industry with the most recognized global brands, such as GNB FLOODED CLASSIC, GNB FLOODED CLASSIC PLATINUM, TUBULAR-HP HIGH PERFORMANCE, TUBULAR-LM LOW MAINTE- NANCE, ELEMENT and GNB FUSION. They have come to symbolize quality, reliability, performance and excellence in all the markets served. GNB Industrial Power takes pride in its commitment to a better environment. Its Total Battery Management program, an integrated approach to manufacturing, distributing and recycling of lead acid batteries, has been developed to help ensure a safe and responsible life cycle for all of its products. For alternate language versions of this document, visit www.gnb.com GNB Industrial Power USA Tel: 877.462.4636 Canada Tel: 800.268.2698 www.gnb.com GB4146 2013-06 A Division of Exide Technologies