EXPERIMENTAL STUDY OF DYNAMIC THERMAL BEHAVIOUR OF AN 11 KV DISTRIBUTION TRANSFORMER

Similar documents
New fem model for thermal analysis of medium voltage fuses

DYNAMIC BEHAVIOUR OF SINGLE-PHASE INDUCTION GENERATORS DURING DISCONNECTION AND RECONNECTION TO THE GRID

Impact Analysis of Fast Charging to Voltage Profile in PEA Distribution System by Monte Carlo Simulation

Overview about research project Energy handling capability

BEHAVIOUR OF ELECTRIC FUSES IN AUTOMOTIVE SYSTEMS UNDER INTERMITTENT FAULT

Torque-Vectoring Control for Fully Electric Vehicles: Model-Based Design, Simulation and Vehicle Testing

BALL BEARING TESTS TO EVALUATE DUROID REPLACEMENTS

INCREASING electrical network interconnection is

CFD Investigation of Influence of Tube Bundle Cross-Section over Pressure Drop and Heat Transfer Rate

SPEED AND TORQUE CONTROL OF AN INDUCTION MOTOR WITH ANN BASED DTC

Improvements to the Hybrid2 Battery Model

Marcel Fortin ing. Hydro Québec Distribution 1

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 04, 2016 ISSN (online):

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

Electric Vehicle Grid Integration Research Analyzing PHEV Impacts on Distribution Transformers in Hawaii

Integrated Simulation Technologies Pvt Ltd

SLIM Transformer. Compact transformer solutions for new applications. Your partner in energy solutions

Encapsulated Piezo Actuators for Use at High Power Levels and / or within Harsh Environmental Conditions.

APPLICATION OF VARIABLE FREQUENCY TRANSFORMER (VFT) FOR INTEGRATION OF WIND ENERGY SYSTEM

e t Performance of Extended Inlet and Extended Outlet Tube on Single Expansion Chamber for Noise Reduction

Investigation of Radiators Size, Orientation of Sub Cooled Section and Fan Position on Twin Fan Cooling Packby 1D Simulation

CHAPTER 1 INTRODUCTION

Analysis and evaluation of a tyre model through test data obtained using the IMMa tyre test bench

Electric Vehicles Coordinated vs Uncoordinated Charging Impacts on Distribution Systems Performance

Distribution of Electric Field Analysis in 36 kv Roof Top Bushing by using FEM Techniques

Hardware Testing of Photovoltaic Inverter Loss of Mains Protection Performance

FLUID DYNAMICS TRANSIENT RESPONSE SIMULATION OF A VEHICLE EQUIPPED WITH A TURBOCHARGED DIESEL ENGINE USING GT-POWER

Performance Analysis of Medium Voltage Induction Motor Using Stator Current Profile

Verifying the accuracy of involute gear measuring machines R.C. Frazer and J. Hu Design Unit, Stephenson Building, University ofnewcastle upon Tyne,

4th European PV-Hybrid and Mini-Grid Conference, Glyfada, Greece, May 2008

Modeling of Lead-Acid Battery Bank in the Energy Storage Systems

Optimizing Energy Consumption in Caltrain s Electric Distribution System Nick Tang

Simulated Switching Transients in the External Grid of Walney Offshore Wind Farm

Development of Emission Control Technology to Reduce Levels of NO x and Fuel Consumption in Marine Diesel Engines

International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014 ISSN

EXPERIMENTAL INVESTIGATIONS OF DOUBLE PIPE HEAT EXCHANGER WITH TRIANGULAR BAFFLES

Impact Analysis of Electric Vehicle Charging on Distribution System

EPE97 OPTIMIZED DESIGN OF VARIABLE-SPEED DRIVES BASED ON NUMERICAL SIMULATION

J.-J.Simond*, A.Sapin**, B.Kawkabani*, D.Schafer***, M.Tu Xuan*, B.Willy***

Research of Driving Performance for Heavy Duty Vehicle Running on Long Downhill Road Based on Engine Brake

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C

Chapter 7: Thermal Study of Transmission Gearbox

Use of Flow Network Modeling for the Design of an Intricate Cooling Manifold

GENERATOR SEAL OIL SYSTEM

POWER DISTRIBUTION SYSTEM ANALYSIS OF URBAN ELECTRIFIED RAILWAYS

Transient analysis of a new outer-rotor permanent-magnet brushless DC drive using circuit-field-torque coupled timestepping finite-element method

RESPONSE OF A MEDIUM VOLTAGE CURRENT LIMITING FUSE OF SMALL SIZE TESTED AS GENERAL PURPOSE AND FULL- RANGE TYPE.

Simulation of dynamic torque ripple in an auxiliary power unit for a range extended electric vehicle

Effects of Traffic Emission Resolution on NOx Concentration Obtained by CFD-RANS Modelling Over a Real Urban Area in Madrid (Spain)

CLUTCH TRANSIENT HEAT TRANSFER SIMULATION FOR HILL START VEHICLE TEST CONDITION

Electromagnetic Fully Flexible Valve Actuator

DEVELOPING A REDOX FLOW BATTERY WITH SPANISH TECHNOLOGY. PROJECT REDOX2015

EFFECT OF UNCONSTANT OVERALL HEAT TRANSFER COEFFICIENT ON THERMAL PERFORMANCES OF MULTIPLE ASSEMBLIES OF AUTOMOBILE RADIATORS

Modelling and Control of Ultracapacitor based Bidirectional DC-DC converter systems PhD Scholar : Saichand K

Analyses of the grid resistance measurement of an operating transformer station

Aggregation of plug-in electric vehicles in electric power systems for primary frequency control

Performance of DC Motor Supplied From Single Phase AC-DC Rectifier

A manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

Chapter 5 ESTIMATION OF MAINTENANCE COST PER HOUR USING AGE REPLACEMENT COST MODEL

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

Modelling and Analysis of Crash Densities for Karangahake Gorge, New Zealand

Investigation & Analysis of Three Phase Induction Motor Using Finite Element Method for Power Quality Improvement

Perodua Myvi engine fuel consumption map and fuel economy vehicle simulation on the drive cycles based on Malaysian roads

Acceleration Behavior of Drivers in a Platoon

Development of a Multibody Systems Model for Investigation of the Effects of Hybrid Electric Vehicle Powertrains on Vehicle Dynamics.

SINGLE-PHASE LINE START PERMANENT MAGNET SYNCHRONOUS MOTOR WITH SKEWED STATOR*

GT-POWER/SIMULINK SIMULATION AS A TOOL TO IMPROVE INDIVIDUAL CYLINDER AFR CONTROL IN A MULTICYLINDER S.I. ENGINE

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

STUDY OF FEASIBILITY OF PLASTIC GEAR TO REDUCE NOISE IN A GEAR PUMP

Test requirements for Rotating Machines

Research Brief. Simulation and verification of results from 125mph current collection modelling for two pantographs. T841 - January 2011.

A LES/RANS HYBRID SIMULATION OF CANOPY FLOWS

Application of Distribution Transformer Thermal Life Models to Electrified Vehicle Charging Loads Using Monte-Carlo Method

Aerodynamically induced power loss in hard disk drives

LIFE CYCLE COSTING FOR BATTERIES IN STANDBY APPLICATIONS

Effect of Stator Shape on the Performance of Torque Converter

Comparison Between Different Arrangements of Bypass Valves in Scroll Compressors

Numerical Investigation of Diesel Engine Characteristics During Control System Development

Optimization of Seat Displacement and Settling Time of Quarter Car Model Vehicle Dynamic System Subjected to Speed Bump

Rotor Design & Performance for a BDFM

A STUDY ON ENERGY MANAGEMENT SYSTEM FOR STABLE OPERATION OF ISOLATED MICROGRID

tests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed.

Shock tube based dynamic calibration of pressure sensors

Tire Test for Drifting Dynamics of a Scaled Vehicle

Enhanced Heat Transfer Surface Development for Exterior Tube Surfaces

Enhancing Wheelchair Mobility Through Dynamics Mimicking

The Modeling and Simulation of DC Traction Power Supply Network for Urban Rail Transit Based on Simulink

Modeling and Vibration Analysis of a Drum type Washing Machine

GT-Suite Users Conference

MORSE: MOdel-based Real-time Systems Engineering. Reducing physical testing in the calibration of diagnostic and driveabilty features

Engine Power and Fueling Comparison Between Vessels with Conventional Transmissions and Controllable Speed Propeller Transmissions During Dynamic

United Power Flow Algorithm for Transmission-Distribution joint system with Distributed Generations

Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st Dry-type transformers Innovative Technology

Filter and Particle Simulation for Hydraulic Systems

TRANSIENT PERFORMANCE OF THREE PHASE INDUCTION MACHINE USING SYNCHRONOUSLY ROTATING REFERENCE FRAME

Table 1. Sample Identification and Comparison Connectors Used in Experiments Sample Conductor Size

Heat transfer enhancement of a single row of tube

A NOVEL IN-FLIGHT SPACE BATTERY HEALTH ASSESSMENT SYSTEM Brandon Buergler (1), François Bausier (1)

Scroll Compressor Oil Pump Analysis

Transcription:

Paper 110 EXPERIMENTAL STUDY OF DYNAMIC THERMAL BEHAVIOUR OF AN 11 KV DISTRIBUTION TRANSFORMER Rafael VILLARROEL Qiang LIU Zhongdong WANG The University of Manchester - UK The University of Manchester - UK The University of Manchester - UK rafael.villarroelrodriguez@manchester.ac.uk qiang.liu@manchester.ac.uk zhongdong.wang@manchester.ac.uk ABSTRACT This paper investigates the dynamic thermal behaviour of a 00 kva, 11/0.433 kv mineral oil filled and oil natural air natural (ONAN) cooled distribution transformer manufactured with 16 fibre optic sensors inside the tank. The transformer was subjected to extended temperature rise tests under multiple levels of constant loadings, i.e. 0.7 pu, 1.0 pu and 1.5 pu to derive the thermal parameters required in the IEC thermal model for estimating the hotspot temperature (HST). Measured and estimated HSTs are compared through a validation test simulating a short period overloading up to 1.8 pu for hours. Based on the data availability, three scenarios or cases are proposed to derive thermal parameters. Thermal parameters derived based the internal fibre optic sensor measurements provide the best estimation of HST. INTRODUCTION Reliability of transformers is essential for the safe operation of distribution networks. One of the main failure mechanisms of distribution transformers is bubble formation under overheated conditions, which is predominately determined by the hot-spot temperature (HST) inside the transformer. In addition, HST is essential to estimate the life expectancy of transformer insulation system [1]. The dynamic thermal rating (DTR) of distribution transformers requires understanding the thermal behaviour of transformers under dynamic load scenarios. The key to DTR is to estimate the HST, based on which the rating of transformer can be optimised responsively and predictably. The HST is described as the sum of the ambient temperature, the top-oil temperature rise and the hot-spotto-top-oil gradient in IEEE C57.91 []. It should be referred to the adjacent top-oil temperature inside the winding [3], where the oil temperature increases linearly from bottom to top and the temperature of the winding rise is parallel to the oil temperature rise, with a constant difference g r between the two straight lines [3]. Fibre optic sensors have been widely used to measure temperature distribution and the HST for power transformers [4, 5]. In this work, the same technique is used to carry out a set of temperature rise tests for an 11 kv distribution transformer, where different cases of available information are proposed to analyse their effect on the HST derivation. Referring to the IEC thermal model [3], a set of new thermal parameters are then determined based on the experimental results. An additional test simulating a short period overloading is undertaken to verify the newly derived thermal parameters. TESTED TRANSFORMER The transformer used in this work is a 00 kva, 11/0.433 kv distribution transformer with ONAN cooling mode and filled with mineral oil. It has been specially manufactured with 16 fibre optic temperature sensors embedded into different locations carefully chosen in order to capture the HST and the top and bottom oil temperatures inside the tank. EXPERIMENTAL DESCRIPTION A set of extended temperature rise tests on the transformer were carried out according to IEC 60076- [6], where the short-circuit method was used. Experimental Setup The short-circuit method followed the procedure specified in IEC Standard 60076- [6]. During the test, the LV terminals of the transformer were short-circuited using a solid copper link, and the transformer is then subjected to a test current corresponding to the calculated total losses (load losses plus no-load losses) [7]. A schematic diagram of the experimental setup is shown in Figure 1. Figure 1. Experimental setup of temperature rise tests. Top oil temperatures were measured by thermocouples at the oil pocket on the top of the transformer and top of the radiator (upper tube to the radiator), whereas bottom oil temperature at the bottom of the radiator (lower tube to the radiator). CIRED 017 1/5

Paper 110 In addition to the thermocouples placed outside of the tank, temperatures inside the transformer were measured by fibre optic sensors installed at the top of the LV and HV windings to register the HST as well as sensors installed in a Bakelite frame next to the inlet and outlet of the radiator to measure the top and bottom temperatures. Ambient temperature around the transformer was also measured by four thermocouples immersed in small oilfilled containers at 1 m high from ground and at a distance of m from each side of the transformer according to [6], and the average of their readings is used for the evaluation of the ambient temperature. Extended Temperature Rise Tests The steady state oil temperature rise at top and bottom of the transformer as well as the average winding temperatures are measured at constant load profiles of 0.7 pu, 1.0 pu and 1.5 pu according to IEC 60076- [6]. At the beginning of the test, the transformer is subjected to a test current corresponding to the total losses (load losses plus no-load losses) at the 1.0 pu, until reaching the steady state, where the rate of change of top-oil temperature rise had fallen below 1 K/h and remained there for a period of 3 hours. In the second step, the test current is reduced to the current corresponding to the load losses for a duration of 1 hour. In the final step, the load supply is disconnected, and the average winding resistance measurement starts. The average winding temperatures are determined from the continuous resistance measurements. Due to the Winding resistance value decreases with time, measurements must be extrapolated backwards in time to the instant of shutdown to obtain the winding resistance value at that time. The duration of the winding resistance cooling down curve should be at least two times the thermal time constant of the winding [6], then the total duration of the measurements was 30 minutes, according to the characteristics of the transformer used, and measurements were taken in intervals of 15 seconds. The procedure applied to 1.0 pu load profile was repeated to 0.7 pu and 1.5 pu load profiles to complete the extended temperature rise tests. EXPERIMENTAL RESULTS The hottest temperature was always measured at the top of the LV winding in phase A, furthest away from the radiator, from a total of eight sensors distributed at the top of HV and LV windings. The dynamic profiles of HST recorded during the extended temperature rise tests at 0.7 pu, 1.0 pu and 1.5 pu are shown in Figure. Top-oil temperatures were measured at different locations inside and outside the transformer tank. Measurements at internal top oil give the highest values followed by oil pocket and then external top oil. Bottom-oil temperatures were also recorded at internal and external locations, where measurements at internal bottom oil give higher values than those at external bottom oil. Figure. Hotspot temperature in low voltage windings (phase A) at different constant load profiles. Table 1 summarises the measured temperatures at the oil pocket, internal top oil and bottom oil, external top oil and bottom oil, hotspot at the LV winding in phase A and ambient, which are used in this work to derive the thermal parameters. Table 1. Absolute temperatures in C from temperature rise tests. Temperature 0.7 pu 1.0 pu 1.5 pu Average ambient 18.8 17.6 18.3 HST (LV phase A) 56.9 80.6 10.0 Internal top oil 44.4 60.3 76.5 Internal bottom oil 35.9 50.4 65.0 Oil pocket 40.9 55. 69.8 External top oil 37.8 51.0 63.9 External bottom oil 33.3 46. 59.7 IEC THERMAL MODEL The thermal model in standard IEC 60076-7 [3] was adopted to estimate the HST. It considers the HST as a function of time, for varying load current and ambient temperature. Therefore, a HST corresponding to a load factor of K is given by Equation 1 [3]. x 1RK h() t ao() i or o() i f1() t A 1 R Where: Equation 1 A Hg K f t y () h( i) r h( i) 11 w t/ k () 1 o f1 t e t / k t / o/ k 1 1 11 1 f t k e k e CIRED 017 /5

Paper 110 Function f 1 () t describes the increase of the top-oil temperature rise according to the unit of the steady-state value, while f () t describes the relative increase of the hot-spot-to-top-oil gradient. Parameters required to implement Equation 1 are: thermal model constants k 11, k 1 and k which are given in [3]; θ h is the HST, θ a is the ambient temperature, Δθ o and Δθ or are the top-oil temperature rise in steady state at the load considered and at rated losses, respectively, Δθ h is the hot-spot-to-top-oil gradient at the load considered, K is the load factor used during the tests, R is the ratio of load losses at rated current to no-load losses obtained from routine tests, H is the hotspot factor, and g r is the average-winding-to-average-oil temperature gradient at rated current. Oil exponent (x), winding exponent (y), oil time constant (τ o ) and winding time constant ( τ w ) are thermal parameters to be determined by implementation of the differential equations solution method proposed in [3]. Oïl time constant (τ o ) As it is mentioned in [8], the oil time constant can be derived by curve fitting of the top oil temperature rise. Figure 3 shows the top oil temperature rise and exponential fitting curves for cases and 3 proposed in this work, to determine the oil time constant at 1.0 pu load profile. Oil time constant for case 1 is taken from IEC 60076-7 [3]. Oil time constant values obtained are: case 1 =180 min (taken from [3]), case =16 min and case 3=44 min. DERIVATION OF THERMAL PARAMETERS To study the effect of the locations of the sensors on the estimation of the HST, three different scenarios/cases are proposed to derive thermal parameters. Cases proposed and studied in this work are given as follows: Case 1 is based on the estimation of the HST using thermal parameters proposed in the standard IEC 60076-7 [3]. This case represents the scenario that temperature rise test results are not available. Therefore it uses conservative values, i.e. the temperature rise limit required in IEC 60076- [6], top-oil temperature rise of 60 K over ambient temperature and HST rise of 18 K over top oil temperature. Case estimates the HST using derived thermal parameters from temperature rise tests based on external temperature measurements, therefore values at the top and bottom of the radiator pipe and oil pocket are used to estimate the top oil temperature and the average oil temperature. HST is not directly measured in this case, so it is then derived from the hot-spot-factor (HSF) of 1.1 suggested for distribution transformers [3]. This case is commonly used in factory when internal fibre optic sensors are not available. Case 3 estimates the HST using derived thermal parameters from measured temperatures inside the transformer based on fibre optic sensors. HST is directly measured by fibre optic sensors inside the winding. This case is not frequently used in factory due to the complexity and cost of the fibre optic sensors installation. However, it seems necessary in terms of understanding a specific thermal design and corresponding thermal parameters. Figure 3. Fitting top oil temperature rise from internal fibre optic sensor and oil pocket at 1.0 load factor. Winding time constant (τ w ) A numerical extrapolation method of cooling down curve proposed in [6] was used to determine the winding time constant. This method can be used to fit an analytical function to a set of timewise equidistant temperature readings. The winding time constants (τ w ) were then calculated for both cases and 3 based on the average oil temperature from thermocouples/fibre optic sensors placed at the aforementioned locations as well as the average winding resistance measurements. Winding time constant values obtained are: case 1=4 min (taken from [3]), case =9.6 min and case 3=9.4 min. Oil exponent (x): According to IEC 60076-7 [3] when the transformer reaches the steady state, the top-oil temperature rise can be determined by the Equation [3]: 1RK o or 1 R Equation R and Δθ o are obtained from routine test and extended temperature rise tests respectively, then the oil exponent (x) can be obtained by plotting the ratio of Δθ o /Δθ or against the value of 1R K in a log-log plot. Derivation of (x) 1 R x CIRED 017 3/5

Paper 110 is shown in Figure 4, where values correspond to the slope of the straight line that best fits all points. Oil exponent values are: case 1=0.80 (taken from [3]), case =0.8 and case 3=0.79. Winding exponent (y): The winding exponent (y) can be also derived from steady state conditions by plotting the ratio of the average winding resistance under a load factor (K) and the average winding resistance at rated load factor against the load factor in a log-log plot according to the Equation 3 [3]. g g K r Equation 3 In the same way, derivation of (y) is shown in Figure 5, where values correspond to the slope of the straight line that best fits all points. Oil exponent values are: case 1=1.6 (taken from [3]), case =1.4 and case 3=1.5. y As results of this section, Table summarises all thermal parameters derived from the extended temperature rise tests and proposed in IEC 60076-7 [3] for the three cases proposed in this work. Key parameters such as Δθ or, the hot-spot-to-top-oil gradient at rated current (Δθ hr ) and g r are obtained from the temperature rise tests for both case and case 3. H is taken as the ratio of the Δθ hr to g r for case 3, which is 1.5. While HST measurements are not available for case 1 and case, H of 1.1 is used according to IEC 60076-7 [3]. Table. Summary of thermal parameters for three case studies. Parameters Case 1 Case Case 3 Δθ or (K) 60.0 37.6 4.7 Δθ hr (K) 18.0 17.7 0.3 x 0.80 0.8 0.79 y 1.6 1.4 1.5 τo (min) 180 16 44 τw (min) 4.0 9.6 9.4 g r 16.4 16.1 13.6 H 1.1 1.1 1.5 Figure 4. Derivation of the oil exponent (x) for cases and 3. EXPERIMENTAL VALIDATION Thermal parameters derived in this work (Table ) were validated by comparing the measured HST with the estimated one in a validation test which represents a short period overloading scenario. It is based on a two-step load profile where the transformer was subjected to 0.7 pu for 17 hours, 1.8 pu for hours and 0.7 pu for 4 hours. Figure 6 shows a comparison of three estimated HSTs from the proposed cases and the measured HST using fibre optic sensors. Root-mean-square-deviation (rmsd) To quantify the difference between the experimental HST curve and the estimated curve, the calculation of the rootmean-square-deviation (rmsd) was done according to Equation 4, which has been used in previous works [9]. Where n is the number of readings, HS( estimated) and HS (exp erimental ) are the estimated HST and the measured HST, respectively. 1 n HS ( estimated ) i HS (exp erimental ) i n i1 Equation 4 rmsd t t Figure 5. Derivation of the winding exponent (y) for cases and 3. Values obtained for the three cases are: case 1=1.4, case =6. and case 3=., which indicates case 3 provides the best estimation of HST. CIRED 017 4/5

Paper 110 From Figure 6 it can be noticed that the estimation obtained using thermal parameters from case 1 is far from the experimental data, where the HST reached a peak value of 155.1 C, overestimated by 3.6 C compared to the measured value. On the other hand, although the estimated HST using thermal parameters from case fits better to the measured values than the one from case 1, it is underestimated by 10.3 C. The thermal parameters obtained from case 3 using internal fibre optic sensors provide the best estimation of HST with a maximum difference of 4 C. Acknowledgments This work was funded by the Engineering and Physical Sciences Research Council (EPSRC) through the Innovate UK consortium project Common Application Platform for Low Voltage Network Management, grant number EP/N50841/1. Special thanks to Innovate UK and the industry partners EA Technology and Nortech for their contributions to this project. The authors would also like to thank Winder Power for its valuable input on the construction of the transformer used in this work. REFERENCES Figure 6. Comparison of the estimated HST using parameters from cases 1, and 3 and the measured HST under a two-step overloading profile. CONCLUSION In this work a 00 kva, 11/0.433 kv distribution transformer with built-in fibre optic sensors has been tested under different load scenarios to study its dynamic thermal rating. Extended temperature rise tests under three constant load profiles have been carried out on the transformer to derive thermal parameters needed to estimate the HST by implementing the IEC thermal model. Based on the data measured from internal and external sensors as well as values taken from the IEC standard, three different cases or scenarios have been proposed to analyse the thermal behaviour of the transformer. The HST was estimated and compared with experimental data obtained from an additional validation test based on a twostep load profile, where the transformer was subjected to a load peak value of 1.8 pu for hours. The HST was overestimated when thermal parameters referred to the IEC standard (Case 1) were used. Thermal parameters derived from external sensors (Case ) underestimated the HST. The best estimation of the HST was achieved by implementing thermal parameters derived from internal sensors (Case 3). Comparing the three sets of thermal parameters, one of the key differences is oil time constant, which could be the major reason causing the different estimation of HST under short term overloading conditions. [1] CIGRE, 009, "Thermal performance of transformers," Working Group A.4. Technical Brochure 393, vol. 19. [] IEEE C57.91, 01, "Guide for Loading Mineral- Oil-Immersed Transformers and Step-Voltage Regulators," 1-13. [3] IEC 60076-7, 005, "Loading guide for oilimmersed power transformers," in Power transformers Part 7. [4] Z. Radakovic and K. Feser, 003, "A new method for the calculation of the hot-spot temperature in power transformers with ONAN cooling," Power Delivery, IEEE Transactions on, vol. 18, 184-19. [5] D. Susa and H. Nordman, 009, "A simple model for calculating transformer hot-spot temperature," IEEE transactions on power delivery, vol. 4, 157-165. [6] IEC 60076-, 011, "Temperature rise for liquidimmersed transformers" Power transformers Part. [7] IEC 60076-1, 011, "General" Power Transformers part 1". [8] Y. Gao, Z. Wang, and D. Jones, 014, "How to make use of transformer heat run test results? review on thermal parameter derivation methods," in International Conference on Condition Monitoring and Diagnosis (CMD), 383-387. [9] R. Villarroel, D. F. García, B. García, and J. C. Burgos, 015, "Moisture diffusion coefficients of transformer pressboard insulation impregnated with natural esters," IEEE Transactions on Dielectrics and Electrical Insulation, vol., 581-589. CIRED 017 5/5