Quick Start Guide , Rev CB March Rosemount DP Level Transmitters and 1199 Diaphragm Seal Systems

Similar documents
, General Instructions for Handling and Installation of Rosemount 1199 Seal Systems

Rosemount 405 Compact Primary Element. Quick Start Guide , Rev HA June 2016

Rosemount Manifolds. Product Data Sheet April , Rev PC. Factory assembled, leak-tested, and calibrated

Quick Start Guide , Rev FB June Rosemount 485 Annubar Flanged Flo-Tap Assembly

Quick Start Guide , Rev AB June Rosemount 585 Annubar Flanged Assembly

Rosemount Smart Pressure Gauge

Rosemount 3095FC MultiVariable Mass Flow Transmitter

Rosemount DP Level Transmitters and Remote Seals

Rosemount Manifolds. Rosemount Manifolds. Product Data Sheet , Rev NB January Contents

Rosemount Manifolds. Product Data Sheet October , Rev PB. Factory assembled, leak-tested, and calibrated

Rosemount Manifolds. Product Data Sheet September , Rev PA. Factory assembled, leak-tested, and calibrated

Rosemount Manifolds. Rosemount Manifolds. Product Data Sheet , Rev MA August Contents

Installation/Start-up Manual CMB_MAN_ABR_CH88 September CH88 In-Situ Combustion O2. Analyzer System

Endurance TM Conductivity Sensors

Rosemount 228. Toroidal Conductivity Sensor. Product Data Sheet July Series LIQ-PDS-228

Selection and Types of 1199 Remote Mount Seal Systems

Rosemount 485 Annubar Threaded Flo-Tap Assembly

Rosemount 585 Annubar Flanged Flo-Tap Assembly

Triple offset technology for lower pressures.

Rosemount 485 Annubar Flanged Assembly

Sanitary Seals. Dimensional Drawing for VCS Sanitary In-Line Diaphragm Seal Process wetted surface finish max. Ra of 32 µ in. 1.

Rosemount 285 Annubar Pak-Lok Assembly

SHDP/GP Differential Pressure/Pressure Transmitter with Remote Diaphragm seals

Rosemount 485 Annubar Pak-Lok Assembly

Innovation in actuation.

Rosemount Manifolds. Rosemount Manifolds. Product Data Sheet , Rev LA Catalog Contents

Rosemount DP Level Transmitters and 1199 Seal Systems

Rosemount Pipe Clamp RTD Sensor

Rosemount DP Level Transmitters and 1199 Diaphragm Seal Systems

Rosemount 2160 Wireless Vibrating Fork Liquid Level Switch

Rosemount DP Level Transmitters and 1199 Remote Seals

Rosemount DP Level Transmitters and 1199 Diaphragm Seal Systems

Rosemount TM 222 Toroidal Flow-Through Conductivity Sensor. Instruction Manual LIQ-MAN-222 Rev.D June 2017

Rosemount Compact Vibrating Fork Liquid Level Switch. Product Data Sheet July , Rev EA

Rosemount 1810 Flush Mount Pressure Transmitter ROSEMOUNT 1810 FEATURES:

Rosemount 3051S Electronic Remote Sensor (ERS) System

Rosemount 285 Annubar Primary Element Series

DRAFT. Installation, Operation and Maintenance Instructions for Emerson KBG-V Series

Rosemount DP Level Transmitters and 1199 Seal Systems

Rosemount 402 and 402VP

Rosemount 9901 Chamber for Process Level Instrumentation

1495 Orifice Plate 1496 Flange Union 1497 Meter Section Installation & Operation Manual

Disassembly and Reassembly for WG Series Worm Gear Operator. User Instructions Part Number: XXXXXX, Rev. 0 Release: February 2017

Rosemount 9901 Chamber for Process Level Instrumentation

Rosemount Wireless Pressure Gauge

Technical Data Sheet PS , Rev C May Micro Motion R-Series Coriolis Flow and Density Meters

Type 289RC Exhaust Booster

Rosemount DP Level Transmitters and 1199 Seal Systems

Top Mount Installation for DP Flowmeters in Steam Service

Safety and Relief Valves for Industrial and Commercial Applications.

RTD and Thermocouple Assemblies Reference Manual

Rosemount 3095FC MultiVariable Mass Flow Transmitter with MODBUS Protocol

Baumann 24000F Wafer Control Valve

Rosemount Multipoint Thermocouple and RTD Profiling Sensors

Micro Motion F-Series Coriolis Flow and Density Sensors. Installation Manual , Rev CC December 2010

Rosemount 1195 Integral Orifice Primary Element

DIAPHRAGM SEALS Measuring your world since 1965

Rosemount 3095FT MultiVariable Flow Data Logger

Pressure Measurement Remote seals for transmitters and pressure gauges

Types 1808 and 1808A Pilot-Operated Relief Valves or Backpressure Regulators

Installation, Operation and Maintenance Manual DOC.IOM.MO.E October MO-Series Manual Override Gearboxes

289 Series Relief Valves

Rosemount Orifice Series Differential Pressure Flow

Bettis RGS Q-Series. Quarter-Turn Spring-Return (SR) and Double-Acting (DA) Pneumatic Actuators. Product Data Sheet April 2016 RGS Rev.

Fisher 644 and 645 Differential Pressure Pump Governors

Baumann Way Control Valve

Pressure control solutions for your industry. Aerospace & Defense

Electromagnetic Flow Meter Owner s Manual HARDWARE

Type 310A-32A Pressure Reducing Regulator

TYPE 2100 ELASTOMER BELLOWS UNITIZED SEAL Technical Specification

ES-665 Series Spring-Loaded Thief Hatch

type 122a three-way Switching Valve

Fisher CAV4 Control Valve

Y610A, Y611A, and Y612A Series Vacuum Service Equipment and Relief Valves

Railroad Ball Valves Series 5REB3

CombiTemp Temperature Measuring System

Fisher TBX Hydro Plug Fixture

CBA300 Series Pneumatic Actuators Improved Design - Compact, Lightweight To Suit All Applications And Environment

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

Rosemount 405 Compact Orifice Series

Micro Motion T-Series Straight-Tube Mass Flow and Density Meters. Product Data Sheet PS July 2001

Instrumentation Products Monoflanges & VariAS-Blocks

Fisher 9500 Butterfly Control Valve

Resistance Temperature Sensors for Hygienic and Sanitary Applications

Line Blank Specification

Type 289P Pilot-Operated Relief Valve

Fisher CAV4 Control Valve

Y690A Series Pressure Reducing Regulators

Rosemount Twisted Square Thermowells

Bettis GH-Series Pneumatic Spring-Return Actuator Torque Chart Imperial

Fisher CVX Hydro Plug Fixture

Process Industry. Diaphragm Seal Solutions

DIAPHRAGM SEALS. MHP SERIES MINI HIGH PRESSURE Mini diaphragm seal for pressures up to 6000 psi

Mobrey MLT100. Displacer Level Transmitter. Product Data Sheet February 2015 IP119, Rev CA. Level, contents or interface measurement transmitter

Model 3051 Sensor Module Replacement

Bettis TEC2 Electric Actuator with Model 500 Quick-Start Guide. Quick-Start Guide E2K Rev. 2 October 2017

Rosemount 1067 Compact Sensor and 1097 Thermowell

EIM TEC2 Electric Actuator with Model 500 Quick-Start Guide

Fisher RSS Lined Globe Valve

IMO-200EN 09/2010. Trunnion mounted forged ball valves Model FF and GG. Installation, Maintenance and Operating Instructions IMO-200EN 09/2010

Transcription:

Quick Start Guide 00825-0100-4016, Rev CB Rosemount DP Level Transmitters and 1199 Diaphragm Seal Systems

Quick Start Guide NOTICE This guide provides basic guidelines for the Rosemount DP Level Transmitters and 1199 Diaphragm Seal Systems Reference Manual. It does not provide instructions for configuration, diagnostics, maintenance, service, or troubleshooting. Refer to the appropriate reference manual for more instruction. This guide are also available electronically on Emerson.com/Rosemount. WARNING The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings. For information on Rosemount nuclear-qualified products, contact your local Emerson Sales Representative. Contents Introduction............................. 3 Preface.................................. 3 General handling overview................ 4 Mechanical installation.................... 4 Ranging the transmitter................... 9 Rosemount 1199 seal types................ 9 2

1.0 Introduction Quick Start Guide A remote seal system consists of a pressure transmitter, a remote seal, and either a direct mount or capillary style connection filled with a secondary fill fluid. During operation, the thin, flexible diaphragm and fill fluid separate the pressure sensor of the transmitter from the process medium. The capillary tubing or direct mount flange connects the diaphragm to the transmitter. When process pressure is applied, the diaphragm is displaced, transferring the measured pressure through the filled system, by way of the capillary tubing, to the transmitter. This transferred pressure displaces the sensing diaphragm in the pressure sensor of the transmitter. This displacement is proportional to the process pressure and is converted electronically to an appropriate output current and/or digital protocol. Figure 1. Path of Pressure in a Standard DP Level Seal System E C A B D A A. Pressure B. Process isolating diaphragm C. Transmitter diaphragm D. Fill fluid E. Transmitter pressure sensor 2.0 Preface This guide is designed to assist with general handling and installation instructions for the Rosemount DP Level Transmitters and 1199 Diaphragm Seal Systems. The Rosemount DP Level Transmitters and 1199 Diaphragm Seal Systems Reference Manual contains supplemental information about the seal system assemblies that are not covered in the corresponding transmitter manuals. 3

Quick Start Guide 3.0 General handling overview Check if equipment received conforms to the order. If any issues, contact your local Emerson sales representative immediately. When unpacking or handling seal system assemblies, do not lift the seal or transmitter by gripping the capillaries, doing so could result in disconnecting the seal and/or capillary from the transmitter, which will void the warranty. The material of a remote seal is designed to withstand pressure and wear from process material, but outside of process connection conditions, remote seals are delicate and should be handled with care. The protective cover should remain on the seal until the moment before installation. Try to avoid touching the diaphragm with fingers or objects and refrain from setting the diaphragm side of the seal down on a hard surface. Even minor dents or scratches in the diaphragm material may impair the performance of the seal system assembly. Avoid sharply bending or crimping the capillary tubing. The minimum bending radius of the capillary tubing is 3-in. (8 cm). When using heat or steam tracing, exercise caution if PVC coating is added onto capillary. The PVC coating on the armor will break down at temperatures around 212 F (100 C). Best practice for heat and steam tracing is to regulate the temperature above the maximum ambient temperature for a consistent result. To avoid accuracy effects and thermal stress, the capillary should not be partially heated. 4.0 Mechanical installation NOTICE Never attempt to disconnect the seals or capillaries from the transmitter or loosen bolts. Doing so will result in loss of fill fluid and will void the product warranty. 4.1 Mounting the seal system in vacuum applications Mounting the pressure transmitter at or below the bottom vessel tap is an important factor to ensure a stable measurement with vacuum applications. The static pressure limit for a differential pressure transmitter is 0.5 psia (25 mmhga), which ensures the transmitter sensor module fill fluid remains within the liquid phase of the vapor pressure curve. If the vessel static limit is below 0.5 psia, mounting the transmitter below the bottom tap provides a capillary fill fluid head pressure on the module. A general rule in vacuum applications is to mount the transmitter approximately 3 ft. (1 m) below the bottom tap of the vessel. Capillaries are to be securely fastened in order to avoid false readings. 4

Quick Start Guide 4.2 Insulation considerations with a Thermal Range Expander seal system The Thermal Range Expander System uses the heat from the process in order to keep both fluids within the system functioning properly, therefore insulation is not always required. However, it is always best practice to insulate systems to keep them functioning with optimum performance. The Thermal Range Expander should never be insulated above the line marked on the seal itself, see the figure below for reference. Figure 2. Thermal Range Expander System Insulation Considerations 4.3 Flanged type seals Gaskets When installing remote seal systems which employ a gasket or a gasket and flushing connection ring, make sure the gasket is aligned properly on the gasket sealing surface. Failure to properly install the gasket may cause process leaks, which can result in death or serious injury. In addition, make sure the gasket does not press down upon the diaphragm face. Anything pressing on the diaphragm will be read by the transmitter as pressure. A misaligned gasket may cause a false reading or damage the diaphragm. The diaphragm gasket is supplied when a lower housing or flushing connection is provided. The default gaskets are listed below, based on seal type. The process gasket must be supplied by the end user. Tantalum diaphragms are not supplied with default gasket, so a gasket option must be selected when applicable. 5

Quick Start Guide Table 1. Gasket Materials Seal type Gaskets Flanged seals assemblies FFW Thermo-Tork TN-9000 RFW Klinger C-4401 EFW PFW Thermo-Tork TN-9000 FCW RCW Klinger C-4401 FUW/FVW Threaded seal assemblies RTW Klinger C-4401 HTS Hygienic seal assemblies SCW (1) SSW STW EES VCS (1) SVS (1) SHP SLS (1) MLS (1) Specialty seals Ethylene propylene O-ring Ethylene propylene O-ring WSP Klinger C-4401 UCP Barium-Sulfate filled PTFE O-ring CTW TFW WFW Klinger C-4401 1. Ensure to use EHEDG approved gasket for EHEDG conformity. 6

Quick Start Guide Maximum working pressure (MWP) Verify the MWP as marked on the transmitter neck label meets or exceeds the expected maximum process pressure the transmitter/seal assembly could experience once installed. If a flushing ring is used, its MWP should also be verified. Bolt torquing When connecting the process and mating flange, the bolts should be torqued to the applicable flange requirements. Required torque is a function of the gasket material and surface treatment of the bolts and nuts which are customer supplied. 4.4 Pancake type seal options Capillary support tube A common option for the pancake type seal (PFW) is the capillary support tube. Due to the side capillary-to-seal connection, the support tube provides a handle for aligning the pancake seal during installation. The support tube should not be used for supporting any weight above that of the remote seal. Process flange Emerson offers the option of supplying the process flange, otherwise the process flange is furnished by the customer. For certain pancake seal assemblies, the Emerson supplied process flange has a machined hole through the center of the flange. This hole corresponds to a threaded connection in the back of the pancake seal upper housing. The flange can, therefore be connected to the seal prior to installation to make handling easier. 4.5 Threaded type seals Lower housing installation procedure The lower housing of the remote seal has either a male or female thread connection for attachment to a process pipe nipple. When threading the lower housing to the process pipe, care should be taken not to overtighten. The applied torque should comply to ANSI B1.20.1 for NPT connections or applicable torque requirements for pipe connections. Upper housing installation procedure The threaded seal is supplied with carbon steel, bolts, and nuts. 304 SST or 316 SST bolts and nuts can be ordered as options. The torque specifications for the RTW seal can be found in the table below. Gasket installation Threaded seals with flushing connection rings come with a sealing gasket. When connecting the remote seal, gasket, and flushing connection ring make sure the gasket is properly aligned on the gasket sealing surface. 7

Quick Start Guide Table 2. Gasket Specifications PSIG rating Bolt material Torque specification 2500 CS or SST 23 ft-lbs 5000 CS 53 ft-lbs 5000 SST 50 ft-lbs 10000 CS (SST N/A) 105 ft-lbs Alternative system installation procedure An alternative to threading the entire seal system assembly to the process piping is to unbolt the seal upper and lower housing and thread the lower housing to the hard piping separately. Bolt the upper and lower housings together to the required torque specification. Note that gaskets need to be replaced once they have been torqued. Thus this alternative system installation procedure requires gasket replacement. 4.6 Hygienic type seals Hygienic approvals Supplied 3-A approved hygienic seals are marked with a 3-A symbol. Supplied EHEDG approved hygienic seals are marked with a EHEDG symbol. Clamp style tank spud For clamp style tank spud seals the procedures for welding the tank spud to the tank vessel are shipped with the tank spud. For the welding procedure refer to Rosemount DP Level Transmitters and 1199 Diaphragm Seal Systems Reference Manual for proper welding tank spud guidelines. The clamp and gasket are furnished by the user. Maximum pressure rating of the system is dependent upon the clamp device. The clamp and O-ring are provided with the tank spud seal. Attach the clamp and hand-tighten the connection. Flange style tank spud When connecting the process and mating flange, the bolts should be torqued to the specifications outlined by ANSI B16.5 or applicable flange requirements. 4.7 Saddle type seals Lower housing installation procedure For 4-in. line size, the lower housing is welded directly into the process pipe. For 2- and 3-in. line sizes, the lower housing is welded onto the process pipe. The upper housing must be removed from the system when welding the lower housing into the process pipe. Allow the pipe connection to cool before installing the seal upper housing. 8

Quick Start Guide Upper housing installation procedure The torque specifications for the saddle seal upper housings is 180 in-lb. (20 N-m) for all bolting material. As it is necessary for the customer to torque the upper housing bolts during installation, each saddle seal includes a torque label with the specified torque. Gasket installation The saddle type seal comes standard with a sealing gasket. When connecting the upper and lower housings make sure the gasket is aligned properly on the gasket sealing surface. 4.8 TFS wafer style in-line seal Connection styles The in-line flow-through seal is attached to the process piping by flange, clamp, or male threaded connections. Flanged type connection The flow-through seal comes between the two process flanges due to the flanged process connection. The bolts should be torqued to the specifications outlined by ANSI B16.5 or EN 1092-1, JIS B 2210 flange torque requirements. Required torque is a function of the gasket material and surface treatment of the bolts and nuts, which are customer supplied. 5.0 Ranging the transmitter Rosemount DP Level Transmitters and 1199 Diaphragm Seal Systems Reference Manual for proper ranging guidelines for open tank-single seal and pressurized tank-two seals. 6.0 Rosemount 1199 seal types 6.1 Flanged seal assemblies FFW Flush Flanged Seal RFW Flanged Seal EFW Extended Flanged Seal PFW Pancake Seal FCW Flush Flanged Seal - Ring Type Joint (RTJ) Gasket Surface RCW Ring Type Joint (RTJ) Flanged Seal FUW and FVW Flush Flanged Type Seals 6.2 Threaded seal assemblies RTW Threaded Seal HTS Male Threaded Seal 9

Quick Start Guide 6.3 Hygienic seal assemblies SCW Hygienic Tri-Clover Style Tri Clamp Seal SSW Hygienic Tank Spud Seal STW Hygienic Thin Wall Tank Spud Seal EES Hygienic Flanged Tank Spud Extension Seal VCS Tri Clamp In-Line Seal SVS VARIVENT Compatible Hygienic Connection Seal SHP Hygienic Cherry-Burrell I Line Seal SLS Dairy Process Connection - Female Thread Seal per DIN 11851 6.4 Specialty seal assemblies WSP Saddle Seal UCP Male Threaded Pipe Mount Seals and PMW Paper Mill Sleeve Seals CTW Chemical Tee Seal TFS Wafer Style In-Line Seal WFW Flow-Thru Flanged Seal 10

Quick Start Guide 11

*00825-0100-4016* Quick Start Guide 00825-0100-4016, Rev DA Global Headquarters Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com North America Regional Office Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com Latin America Regional Office Emerson Automation Solutions 1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA +1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com Europe Regional Office Emerson Automation Solutions Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland +41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com Asia Pacific Regional Office Emerson Automation Solutions 1 Pandan Crescent Singapore 128461 +65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com Middle East and Africa Regional Office Emerson Automation Solutions Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates +971 4 8118100 +971 4 8865465 RFQ.RMTMEA@Emerson.com Linkedin.com/company/Emerson-Automation-Solutions Twitter.com/Rosemount_News Facebook.com/Rosemount Youtube.com/user/RosemountMeasurement Google.com/+RosemountMeasurement Standard Terms and Conditions of Sale can be found on the Terms and Conditions of Sale page. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and Rosemount logotype are trademarks of Emerson. VARIVENT is a registered trademark of GEA Process Engineering Limited. Thermo-Tork is a registered trademark of Armstrong World Industries, Inc. All other marks are the property of their respective owners. 2017 Emerson. All rights reserved.