S&C Recloser Bypass Disconnects

Similar documents
S&C Loadbuster Disconnects

www. ElectricalPartManuals. com SPECIFICATIONS Page 1 of 24 March 24, 2003

SPECIFICATION BULLETIN

S&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv)

Specifications. S&C Power Fuses Types SM- 4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through 34.5 kv)

Specifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv)

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

Disconnect & ByPass Switches

Specifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34.

SPECIFICATIONS. S&C Alduti-Rupter Switches with Power Fusesa SPECIFICATION BULLETIN Indoor Distribution (4.8 kv and 13.

Specifications. S&C Alduti-Rupter Switchesa Indoor Distribution (4.8 kv through 34.5 kv) Conditions of Sale SPECIAL TO THIS PRODUCT: How to Order

T YPE MZ DISTRIBUTION S TANDARD CUTOUT

Specifications. S&C Type XS Fuse Cutouts. Outdoor Distribution (4.16 kv through 25 kv)

TYPE PSI/II PADMOUNT SWITCHGEAR 15KV 25KV

S&C Manual PME Pad-Mounted Gear

Figure 1. HX cutout fuseholders.

Specifications. S&C Mini-Rupter Switches Indoor Distribution (4.16 kv through 25 kv) Manually Operated Styles

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv)

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description

PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT

S&C Type XS Fuse Cutouts

TYPE BLT DISCONNECT SWITCHES

Figure 1. HX cutout fuseholders. Positive Interruption

S&C Type XS Fuse Cutouts

HUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter

PAD-MOUNT SWITCHGEAR 15kV 25kV 35kV

T HREE-SHOT TYPE MZR F USE CUTOUT

UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout

15 kv and 25 kv Thru-Bushings

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Specifications. S&C Manual PMH Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv)

CLEAVELAND / PRICE INC. Type RL-C Side Break Switch kv A. Bulletin DB-104E12

S&C Alduti-Rupter Switches. Outdoor Distribution, 14.4 kv through 69 kv

Copper Vertical Break Switch kv A.

Aluminum Vertical Break Switch kv A.

25 kv Apparatus Bushings

TYPE V CENTER BREAK SWITCH

S&C SMD -20 Power Fuses

D-73P disconnect and bypass switches

Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

TYPE BILT DISCONNECT SWITCHES

Specifications. S&C Omni-Rupter Switches Outdoor Distribution (14.4 kv and 25 kv) Conditions of Sale

INSTRUCTIONS Ç CAUTION. S&C Power Fuses Types SMD-1A, SMD-2B, SMD-2C, and SMD-3. For Field Assembly and Installation NOTE INSTRUCTION SHEET

STANDARD SPECIFICATION FOR TYPE PLD LIVE-FRONT/DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV A. General

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Specifications. S&C Source-Transfer PMH Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv) With Micro-AT Control. Conditions of Sale

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

STANDARD SPECIFICATION FOR LIVE-FRONT 15KV AND 25KV PSI/II PAD-MOUNTED SWITCHGEAR

Copper Double Break Switch

Catalog 14A January 2013

Typical Specification

Operators/Accessories. Type V2-CA Aluminum. Vertical Break Switch. Ordering Information Furnish: Available Accessories. Standard Operator Features

Westinghouse Electric Corporation Distribution Apparatus Division Bloomington, Indiana 47401

SWITCHGEAR DIVISION PRODUCT PROFILES

M-Force three-phase switch

SWITCHGEAR DIVISION PRODUCT PROFILES

M-Force three-phase switch

DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

Aluminum Vertical Break Switch 345 kv, 1300 kv BIL 2000 A A.

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

WARNING. TYPE PSI/II PAD-MOUNT SWITCHGEAR with Non-Loadbreak Fuse Mountings 15kV 25kV INSTRUCTIONS. Qualified Persons. For Installation and Operation

RBA Catalog Numbers and Information

A. The ratings for the integrated pad-mounted gear shall be as designated below:

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

Improving distribution systems reliability with Cutoutmounted single phase Reclosers

Type EB, EBB, EBF and VEB DOUBLE SIDE BREAK SWITCHES 38 kv through 362 kv 600 to 3000 Ampere

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10A January 2014

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

15-kV Live Terminal 200 Amp Mini-Switch Source-Isolated Pad-Mounted Switchgear 40 Amp (Max) Arc-Strangler NX Fuses

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10A October 2015

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required!

Jumpers & Load Pickup Tools

Electronic Resettable Sectionalizer

VersaRupter 5-38 kv Load Interrupter Switch. Technical Guide

Solid Dielectric, Single Phase Recloser

INSTRUCTIONS For Field Assembly, Installation, and Maintenance

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10AA March 2013

Cleaning Flooded Gear

Installation and Operation

Cobra-S. Catalog Cobra-S

Underground Distribution Switchgear

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Westinghouse Electric Corporation Distribution and Control Business Unit Assemblies Division Bloomington, Indiana

Transmission Switching

Instructions for Installation

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10AA August 2015

TYPE EE and EEB CENTER- SIDE-BREAK SWITCH TYPE VEE and CBV CENTER BREAK V SWITCH 1200, 1600, 2000 & 3000 Amperes 7.

Horizontal Circuit Switchers

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

C1000 Series Automatic Cap Bank

The Standard Mounting Arrangements for S&C Alduti-Rupter Switches

Joslyn Hi-Voltage. Overhead Reclosers & Switches. In this section...

35-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current-Limiting Fuses

Transcription:

S&C Recloser Bypass Disconnects Outdoor Distribution (14.4 kv through 34.5 kv)

Application S&C Recloser Bypass Disconnects are station-type devices used to bypass and isolate automatic circuit reclosers for repair or routine maintenance and are generally applied in combination with a separately mounted S&C Loadbuster Disconnect. They can also be applied to bypass and isolate other devices such as current transformers. S&C Recloser Bypass Disconnects consist of a fuse (which provides protection for the circuit during recloser downtime) in series with an integral S&C Loadbuster Disconnect. A choice of fuses, including S&C Power Fuses Type SMD-20, Type SMD-40, or Type SM-5, or an S&C Fuse Cutout Type XS, is offered to allow tailoring to the available fault and continuous current levels of a specific application. (S&C Recloser Bypass Disconnects are available with the power fuse mounted either on the right or on the left to fit the physical requirements of the installation.) Alternately, a second Loadbuster Disconnect is available in place of a fuse for applications where devices other than protective equipment are being bypassed for maintenance or inspection. S&C Recloser Bypass Disconnects are available in voltage ratings of 14.4 kv, 25 kv, and 34.5 kv and, depending on which S&C Recloser Bypass Disconnect is specified, can be applied on circuits having a continuous current level through 600 amperes. A complete listing of switch and fuse momentary and/or continuous current ratings is provided in the tables on pages 6 through 11. Construction S&C Recloser Bypass Disconnects feature an S&C Loadbuster Disconnect in series with a fuse (or a second S&C Loadbuster Disconnect) mounted to a rugged ³ ₁₆-inch-thick galvanized formed-steel base. Bases are provided with numerous mounting holes and slots for easy attachment to a user s supporting structure. S&C Recloser Bypass Disconnects are offered with a choice of Cypoxy a or porcelain station post insulators. The disconnect blade of the bypass disconnect is of double-member hard-drawn copper construction, formed for extra rigidity; the blade s broadbased hinge attachment augments the stability of the disconnect, thus ensuring positive contact engagement, even when closed from the side. Silverto-silver contacts at the latch end of the disconnect blade are backed by stainless-steel loading springs to keep contacts under constant pressure (ensuring minimum resistance at current-transfer points) and to provide a smooth, positive wiping action during each opening and closing operation. And the surface structure of the stationary contacts differs from that of the blade contacts, thus preventing sticking, galling, or seizing. Contacts won t weld, burn, or pit on overcurrents. The S&C Power Fuse or S&C Fuse Cutout mounted in series with the disconnect blade features springbacked silver-to-silver contacts at all current-transfer points. And the easily accessible trunnion pocket in the rugged cast bronze hinge makes inserting the holder or fuse unit (or fuse tube) an easy operation. Guide surfaces on the inner faces of the hinge casting ensure on-center approach of the fuse to the upper live parts upon closing. And a carefully positioned and proportioned bronze pull-ring makes opening with a conventional hookstick a simple operation. For details concerning the operation of S&C Recloser Bypass Disconnects, refer to the section headed Operation on page 4. a Cypoxy is the S&C trademark for S&C s cycloaliphatic epoxy resin system. Cypoxy is nontracking, self-scouring, nonweathering... there s never a compromise of insulation integrity. 2

Bronze pull-ring is carefully positioned and proportioned for ease of operation with a conventional hookstick SMU-20 Fuse Unit Rugged galvanized formedsteel base incorporates numerous mounting holes and slots for easy attachment to user s supporting structure Stainless-steel loading springs keep silver-tosilver contacts under constant pressure to produce minimum contact resistance. Positivewiping-action contacts won t weld, burn, or pit on overcurrents Trunnion pocket in rugged cast bronze hinge is easily accessible makes inserting the fuse unit an easy operation Double-member disconnect blade features hard-drawn copper construction, formed for extra rigidity, and a broadbased hinge attachment which ensures positive contact engagement even when closed from the side Blade Stop Pin is factory set for 160-degree opening can be readily fieldpositioned to provide for 90-degree opening Figure 1. Construction of S&C Recloser Bypass Disconnect with Type SMD-20 Power Fuse. 3

Operation S&C Recloser Bypass Disconnects are operated as illustrated in Figure 2. In the normal operating configuration, the fuse is removed from the recloser bypass disconnect, and loads are served through the circuit recloser. To bypass the recloser for repair or inspection, a fuse holder, fuse unit, or cutout fuse tube (as applicable) is installed in the recloser bypass disconnect and closed; the integral disconnect blade is then opened to isolate the recloser from the loadside circuit. Lastly, the source-side S&C Loadbuster Disconnect is opened to de-energize the recloser and to completely isolate it from surrounding circuits. A conventional hookstick can be used to perform each of the operations described above. To restore the recloser to service, the source-side S&C Loadbuster Disconnect and then the disconnect blade on the bypass disconnect are closed in with a conventional hookstick (the recloser should also be closed-in at this time if not already closed). Then the fuse is opened to interrupt the bypass circuit and the holder, fuse unit, or fuse tube is removed from the fuse mounting. (Outdoor fuses should not be left in the disconnect position for extended periods.) A conventional hookstick can be used to open the fuse. Normal Operating Configuration Station Bus Source-side Loadbuster Disconnect Recloser Load-side circuit Recloser Bypass Disconnect Bypass circuit open (fuse removed), with recloser bypass disconnect blade and source-side S&C Loadbuster Disconnect closed. Figure 2. Sequence of operation for S&C Recloser Bypass Disconnects. 4

Bypassing the Recloser Isolating the Recloser Station Bus Station Bus Source-side Loadbuster Disconnect Load-side circuit Source-side Loadbuster Disconnect Load-side circuit Recloser Recloser Bypass Disconnect Recloser Recloser Bypass Disconnect Fuse installed in hinge and closed to, in effect, provide a parallel path around the recloser. Disconnect blade on recloser bypass disconnect and also source-side S&C Loadbuster Disconnect opened to de-energize and completely isolate the recloser. 5

Recloser Bypass Disconnect with Type SMD-20 Power Fuse (fuse on right illustrated*) *Also available in model with fuse on left. S&C Recloser Bypass Disconnect with Type SMD-20 Power Fuse, furnished with Cypoxy station post insulators Rating Catalog Number3 kv Amperes, RMS Cypoxy Station Switch Fuse Nom. Max BIL Cont. Mom.1 (Asym.) Max Interr.2 (Sym.) Porcelain Station 14.4 15.5 110 600 40 000 200Ed 14 000 192702-E 192712-E 192702 192712 25 27 150 600 40 000 200Ed 12 500 192703-E 192713-E 192703 192713 34.5 38 200 900 40 000 200Ed 10 000 192704-E 192714-E 192704 192714 1 One-second rating: 25,000 amperes RMS symmetrical; three-second rating: 16,000 amperes RMS symmetrical. 2 Symmetrical fuse interrupting ratings assigned to Recloser Bypass Disconnects furnished with SMD-20 Power Fuses are based on available short-circuit current at locations where the X/R ratio is 15; the interrupting ratings expressed in amperes RMS asymmetrical are 1.6 times the symmetrical ratings listed. 3 Includes fuse-unit end fittings. SMU-20 Fuse Units are not included. d SMD-20 Power Fuses accommodate SMU-20 Fuse Units in ratings through 200K amperes as well as 200E amperes. 6

Recloser Bypass Disconnect with Type SMD-40 Power Fuse (fuse on right illustrated*) *Also available in model with fuse on left. S&C Recloser Bypass Disconnect with Type SMD-40 Power Fuse, furnished with Cypoxy station post insulators Rating Catalog Number3 kv Amperes, RMS Cypoxy Station Switch Fuse Nom. Max BIL Cont. Mom.1 (Asym.) Max Interr.2 (Sym.) Porcelain Station 14.4 15.5 110 600 40 000 400E 25 000 192802-E 192812-E 192802 192812 25 27 150 600 40 000 400E 20 000 192803-E 192813-E 192803 192813 1 One-second rating: 25,000 amperes RMS symmetrical; three-second rating: 16,000 amperes RMS symmetrical. 2 Symmetrical fuse interrupting ratings assigned to Recloser Bypass Disconnects furnished with SMD-40 Power Fuses are based on available short-circuit current at locations where the X/R ratio is 15; the interrupting ratings expressed in amperes RMS asymmetrical are 1.6 times the symmetrical ratings listed. 3 Includes fuse-unit end fittings. SMU-40 Fuse Units are not included. 4 SMD-40 mountings can be equipped with an optional attachment hook to accommodate Loadbuster. Specify by adding suffix LB to the catalog number. 7

Recloser Bypass Disconnect with Type SM-5 Power Fuse (fuse on right illustrated*) *Also available in model with fuse on left. S&C Recloser Bypass Disconnect with Type SM-5 Power Fuse, furnished with porcelain station post insulators kv Nom. Max BIL Rating Cont. Switch Amperes, RMS Mom.1 (Asym.) Max Fuse Interr.2 (Sym.) Cypoxy Station Catalog Number3 Porcelain Station 14.4 15.5 110 600 40 000 400E 34 000 192722-E 192732-E 192722 192732 25 27 150 600 40 000 300E 20 000 192723-E 192733-E 192723 192733 1 One-second rating: 25,000 amperes RMS symmetrical; three-second rating: 16,000 amperes RMS symmetrical. 2 Symmetrical fuse interrupting ratings assigned to Recloser Bypass Disconnects furnished with SM-5 Power Fuses are based on available short-circuit current at locations where the X/R ratio is 15; the interrupting ratings expressed in amperes RMS asymmetrical are 1.6 times the symmetrical ratings listed. 3 SM-5 Holders and SM-5 Refill Units are not included. Models rated 14.4 kv require SM-5 Holder, Catalog Number 86152R2. Models rated 25 kv require SM-5 Holder, Catalog Number 86153R2. 8

Recloser Bypass Disconnect with Type XS Fuse Cutout (fuse on left illustrated*) *Also available in model with fuse on right. S&C Recloser Bypass Disconnect with Type XS Fuse Cutout, furnished with porcelain station post insulators Rating Catalog Number3 kv Amperes, RMS Cypoxy Station Switch Fuse Nom. Max BIL Cont. Mom.1 (Asym.) Max Interr.2 (Sym.) Porcelain Station 14.4 15 110 600 40 000 100 7 100 192742R1-El 192752R1-El 192742R1l 192752R1l 14.4 15 110 600 40 000 200 7 100 192762R1-Ef 192772R1-Ef 192762R1f 192772R1f 25 27 150 600 40 000 100 5 300 192763R1-Eh 192773R1-Eh 192763R1h 192773R1h 25 27 150 600 40 000 200 5 300 192743R1-Ef 192753R1-Ef 192743R1f 192753R1f 1 One-second rating: 25,000 amperes RMS symmetrical; three-second rating: 16,000 amperes RMS symmetrical. 2 Symmetrical fuse interrupting ratings assigned to Recloser Bypass Disconnects furnished with Type XS Fuse Cutouts are based on available short-circuit current at locations where the X/R ratio is 8 for 14.4-kV models, or 12 for 25-kV models; the RMS asymmetrical interrupting ratings are 10,000 amperes for 14.4-kV models, 8,000 amperes for 25-kV models. 3 Fuse links are not included. l Includes fuse tube, Catalog Number 89521R10. f Includes fuse tube, Catalog Number 89572R11. h Includes fuse tube, Catalog Number 89522R10. 9

Recloser Bypass Disconnect with Second Loadbuster Disconnect in Place of Fuse S&C Recloser Bypass Disconnect with Second Loadbster Disconnect in Place of Fuse, furnished with porcelain station post insulators kv Rating Nom. Max BIL Cont. Amperes, RMS Switch Mom.1 (Asym.) Cypoxy Station Catalog Number Porcelain Station 14.4 15.5 110 600 40 000 192782-E 192782 25 27 150 600 40 000 192783-E 192783 1 One-second rating: 25,000 amperes RMS symmetrical; three-second rating: 16,000 amperes RMS symmetrical. 10

Recloser Bypass Disconnect Type RA S&C Recloser Bypass Disconnect Type RA Ratings Leakage kv Amperes, RMS Cypoxy Insulators Distance to Ground, Counter- Minimum, Clockwise Mom.,1 Clockwise Nom. Max BIL Cont. Inches (mm) Blade Asym. Blade Opening Opening Catalog Number Porcelain Station Post Insulators Clockwise Blade Opening Counter- Clockwise Blade Opening 14.4 15.5 110 900 40 000 14.2 (361) 192522-E 192532-E 192522 192532 25 27 125d 900 40 000 24.2 (615) 192523-E 192533-E 192523 192533 1 For disconnects rated 900 amperes continuous, the 3-second rating is 25,000 amperes RMS symmetrical. d These disconnects equipped with Cypoxy Insulators meet requirements for 150-kV BIL rating. 11

Printed in U.S.A. Descriptive Bulletin 842-30 May 6, 2013 Offices Worldwide f www.sandc.com