LCD Annunciator Installation Instructions

Similar documents
MAPNET II Transceiver Installation Instructions

Expansion Signal (XSIG) Card Installation Instructions

Flex Amplifiers Installation Instructions

Audio Operator Interface Installation Instructions

Digital/Analog Amplifiers Installation Instructions

LED/Switch Modules Installation Instructions

TMS Series MP46x Flex Probes* Installation Instructions

INSTALLATION INSTRUCTIONS

Installation and Programming Manual Part: Building Network Interface Card Product: 4100ES

Cetra. Ceiling Power Entry Installation (AEC1, AEC14, or AEC16)

AMENDMENT ELECTRIC SERVICE MANUAL 2014

Demarcation Fuse/Circuit Breaker Alarm Panel 125DM08. Installation Guide

CP-1TT Remote System

CONTENTS. This Product is Certified by CANADIAN STANDARDS ASSOCIATION and Bears the Mark:

MS Application. Features. Proportional Valve Actuator General Instructions

CP-9301 CP Application. Features. Applicable Literature. Electronic Actuator Drives General Instructions

Assembly Instruction EL OCHITO WHITE CONTACTS 1000BASE-T/10GBASE-T TYPE I: PIN /SKT CABLE: S/FTP

M100F Incremental Motor Actuator R81F Interface Board

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION

SLC-811X Series. Single Loop Proportional Temperature Controller General Instructions APPLICATION SPECIFICATIONS

Nuheat WEATHER-READY HEAT TRACE PIPE FREEZE PROTECTION SYSTEM. Self-Regulating Heating Cable Installation Guide. UV Resistant Polyolefin Outer Jacket

CP (Vdc) CP (Milliamp) CP (Slidewire)

ACSI MODEL 1440 POWER SUPPLY INSTALLATION INSTRUCTIONS

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE

CP-8301-xxx Series. Application. Features. Applicable Literature. 1 to 15 Vdc Input Electronic Actuator Drive General Instructions

Assembly Instruction. EL OCHITO BLUE CONTACTS SuperSpeed USB TYPE I: PIN /SKT CABLE:

Electrical Wiring Practices

DS1 Plug-In Digital Signal Cross-Connect (PIX-DSX-1) 19-Inch Shelf Kit Installation Instructions

Understanding Electrical Terms

UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD

VACUUM AIR TUBE mm (4.5") DIA. TUBE SYSTEM OPERATOR UNIT (OVERHEAD DELIVERY) 15160, 15161, OR CUSTOMER UNIT (UNDERGROUND)

A.C.E.S. Series ACES 3 & 6 MODULE PANELS. System Manual. Touch-Plate Lighting Controls. ACES 3 & 6 Module System Manual

Product Instructions. Diverting Valve. Valve Cross Section. Features. Specifications. Operations

50A Dual-Feed 5/5 GMT Total Front Access Fuse Panel

ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI

MP461SC Flex Probes* Installation Instructions

E.S.P. Embedded Sensing Probes for Motor Brushes

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

WarmlyYours ET-SR Series Heating Cable Installation Manual for Roof & Gutter Deicing

Handyman Motor Capacitor Meter PART NO

!!!!! !!!!!!! !!!!! ! 16VAC input voltage, 13.5VDC output voltage BRANCHES COUNTRYWIDE

MODEL D-SBG Single Arm Barrier Gate Operator

FUEL MANAGEMENT SYSTEM SentryGOLD INSTALLATION MANUAL

Elvoron Home Elevator

Self Cleaning Hood System Installation, Operation, and Maintenance Manual

Installation/ Operation Maintenance. VariTrac Dampers

A. General: Deliver, store and handle wire and cable in accordance with the manufacturer's instructions and as specified in Division 1.

Engineering Service Specifications. Commercial Single-Phase Current Transformer Metering Schemes

AIS 5000 UPS kva 480 V. Installation Manual

SAVE THESE INSTRUCTIONS

MY F150 SuperCab 1. Tools Required. Page 1 of 12 9L3J-19A014-BA Copyright Ford 2013 FoMoCo

Installation Manual. For. Alumavator and Platinum. Vertical Installation. Elevator Boat Lifts

Creating An Accessible World ELVORON CPL.

Sentinel Field Satellite Controller Metal Pedestal, Plastic Pedestal and Wall Mount Models Installation Instructions

Pretest Module 24 Three-phase Service Entrance

INSTALLATION INSTRUCTIONS

AUXILIARY BATTERY BOX INSTALLATION INSTRUCTIONS

WLP Series Wall Mounts (WLP Series Low Profile Wall Mount Enclosure) Installation Instructions

Manual No: Revision: F. Mag Probe Assembly Manual

FOSC-400A4 INSTALLATION INSTRUCTION

Standard Compression Dead End for ACSR and ACSS Conductor CAUTION: ACSR Dead Ends Cannot Be Used on ACSS HT Conductor

L5000 Plus. Installation & Setup Guide

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code

Owner s Manual. For Automatic Transfer Switch. 50 & 100 Amp. Model Number RTG10EZA1 RTG12EZA1 RTG16EZA1 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED:

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

User Manual. Solar Charge Controller 3KW

NorthStar. brand. Instruction Manual. SLIM Tach SL Thru-Shaft Diameter. Magnetoresistive Encoder Designed for GE Wind Energy

Models beginning with MO, MK, 7B, 6S, 6F or 5B. Product Description. Technical Specifications. Installation Instructions.

PowerOhm Installation Manual for LG ATV Series Braking Modules

Noran Tel. Fuse Panel Technical Practice N NCY 4/4TPA & 6/6 GMT NEBS Level 3 Certified

UV DISINFECTION UNIT MODEL 3G

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

10 Commercial, Industrial, Agricultural Services

INTECH Micro 2300-RTD6

C3000 SIGNAL TRANSMITTER. Introduction

MODEL D-WBG Wishbone Arm Barrier Gate Operator

CP CP

Electrical Installation

MY F150 CrewCab 1. Tools Required E F G. Page 1 of 10 9L3J-19A014-AA Copyright Ford 2013 FoMoCo

Unarmored Variable Frequency Drive (VFD) Cable Termination Guide

Mitsubishi Turbine: Hybrid XT Control Sensor Retrofit

FLEX PROBE INSTALLATION AND PROGRAMMING GUIDE

Series 206/208 Through-Hole DIP Switch

AMPLIFIER A OR B SELECTOR

AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-4800 BBS-4800E

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

The Green Meter Adapter (GMA) program will become effective on January 15, Customers may start applying for a GMA on January 15, 2018.

Carbon Monoxide Transmitter

Precision Power Center INSTALLATION, OPERATION, & MAINTENANCE MANUAL

Dispenser Pan Sensors & Containment Sump Sensors

The Reliable Choice. Field Pocket Guide

PowerWorx Power Distribution Products Select Series Circuit Breaker for ±24 or ±48 Vdc User Manual

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

For Conduit Inspections

NEC 2011 Code Changes

Heavy Duty Copper Battery Terminals

CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls

Load Sharing Module. Analog Output Installation, Operation, and Calibration Manual. Manual 26011

SUM340 SUMMATION BOARD

Transcription:

4603-9101 LCD Annunciator Installation Instructions Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify Simplex. ELECTRICAL HAZARD - Disconnect electrical power when making any internal adjustments or repairs. Servicing should be performed by qualified Simplex Representatives. STATIC HAZARD - Static electricity can damage components. Therefore, handle as follows: 1. Ground yourself before opening or installing components (use the 553-484 Static Control Kit). 2. Keep uninstalled component wrapped in anti-static material at all times. Overview There are several important notes to identify before installing the 4603-9101 LCD Annunciator. IMPORTANT: All circuits are power-limited only if the operating power and communications are provided by a 4020 Control Unit or by a system with the 4100/4120-6050 power-limited option. If other systems are used, no circuits are power-limited. Notes: 1. 4603-9101 LCD Annunciators can be either flush or surface-mounted. To flush-mount in masonry walls, use a RACO 965 (3-1/2 in. deep) masonry box or its equivalent. To flush-mount in plasterboard walls, use a RACO 590 (3-1/2 in. deep) gangable switch box with conduit entry or its equivalent. IMPORTANT: Conduit entry must be centered 2-3/4 in. (minimum) from the front of the box. To surface-mount, use a 2975-9206 Box. 2. The number of annunciators in a 4100+ Fire Alarm System cannot exceed 31. 3. The maximum operating current for a single 4603-9101 LCD Annunciator is 170 ma. 4. Do not use the 4603-9101 LCD Annunciator when the 4100+ Control Panel is configured for proprietary receiving service. IMPORTANT: An Earth ground connection must be provided to the back box for transient suppression. This connection must be made with an approved dedicated Earth connection in accordance with NFPA 70, Article 250. 1999 Simplex Time Recorder Co., Gardner, MA 01441-0001 USA 574-031 All specifications and other information shown were current as of publication, and are subject to change without notice. Rev. B

Installation Instructions Follow Steps 1 through 5 and refer to Figures 1 through 3 to install a 4603-9101 LCD Annunciator. 1. Terminate the annunciator s COMM and power lines as shown in Figure 1. Reference Field Wiring Diagram 841-731 for additional details. Figure 1. Terminating the COMM and Power Lines 2. Using Switch SW1 (see Figure 2), set the annunciator s address and baud rate in accordance with Chart 1. Note: Switches SW1-2 through SW1-8 set the annunciator s address; switch SW1-1 sets the annunciator s baud rate. SW1-1 OFF or OPEN = 1200 Baud SW1-1 ON or CLOSED = 9600 Baud 3. Using the two pan-head screws provided, mount the annunciator in its back box in accordance with Figure 3. 4. Using the four flat-head screws provided, mount the trim plate to the back box in accordance with Figure 3. Note: The trim plate covers a hole in the keyboard which provides access to the display s viewing angle potentiometer. 5. Call your local Simplex Branch Office (listed in the yellow pages) for checkout. Continued on next page 2

Installation Instructions (Continued) Refer to Figure 2 for the terminal block locations on the LCD Annunciator. Refer to Figure 3 for a detailed picture of the annunciator. SW1 TB2 TB1 Figure 2. Terminal Block Locations (Back of LCD Annunciator) Back Box LCD Assembly Pan-head Screws (2) Trim Plate Flat Head Screws (4) Notes: 1. The annunciator s back box is NOT supplied by Simplex. See Note #1 in the Overview section of this publication for a list of available back boxes. 2. Back box Earth ground connection is required. Figure 3. Expanded View of 4603-9101 LCD Annunciator 3

Address Chart SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8 ON ON ON ON ON ON OFF = ADDRESS 1 ON ON ON ON ON OFF ON = ADDRESS 2 ON ON ON ON ON OFF OFF = ADDRESS 3 ON ON ON ON OFF ON ON = ADDRESS 4 ON ON ON ON OFF ON OFF = ADDRESS 5 ON ON ON ON OFF OFF ON = ADDRESS 6 ON ON ON ON OFF OFF OFF = ADDRESS 7 ON ON ON OFF ON ON ON = ADDRESS 8 ON ON ON OFF ON ON OFF = ADDRESS 9 ON ON ON OFF ON OFF ON = ADDRESS 10 ON ON ON OFF ON OFF OFF = ADDRESS 11 ON ON ON OFF OFF ON ON = ADDRESS 12 ON ON ON OFF OFF ON OFF = ADDRESS 13 ON ON ON OFF OFF OFF ON = ADDRESS 14 ON ON ON OFF OFF OFF OFF = ADDRESS 15 ON ON OFF ON ON ON ON = ADDRESS 16 ON ON OFF ON ON ON OFF = ADDRESS 17 ON ON OFF ON ON OFF ON = ADDRESS 18 ON ON OFF ON ON OFF OFF = ADDRESS 19 ON ON OFF ON OFF ON ON = ADDRESS 20 ON ON OFF ON OFF ON OFF = ADDRESS 21 ON ON OFF ON OFF OFF ON = ADDRESS 22 ON ON OFF ON OFF OFF OFF = ADDRESS 23 ON ON OFF OFF ON ON ON = ADDRESS 24 ON ON OFF OFF ON ON OFF = ADDRESS 25 ON ON OFF OFF ON OFF ON = ADDRESS 26 ON ON OFF OFF ON OFF OFF = ADDRESS 27 ON ON OFF OFF OFF ON ON = ADDRESS 28 ON ON OFF OFF OFF ON OFF = ADDRESS 29 ON ON OFF OFF OFF OFF ON = ADDRESS 30 ON ON OFF OFF OFF OFF OFF = ADDRESS 31 ON OFF ON ON ON ON ON = ADDRESS 32 ON OFF ON ON ON ON OFF = ADDRESS 33 ON OFF ON ON ON OFF ON = ADDRESS 34 ON OFF ON ON ON OFF OFF = ADDRESS 35 ON OFF ON ON OFF ON ON = ADDRESS 36 ON OFF ON ON OFF ON OFF = ADDRESS 37 ON OFF ON ON OFF OFF ON = ADDRESS 38 ON OFF ON ON OFF OFF OFF = ADDRESS 39 ON OFF ON OFF ON ON ON = ADDRESS 40 ON OFF ON OFF ON ON OFF = ADDRESS 41 ON OFF ON OFF ON OFF ON = ADDRESS 42 ON OFF ON OFF ON OFF OFF = ADDRESS 43 ON OFF ON OFF OFF ON ON = ADDRESS 44 ON OFF ON OFF OFF ON OFF = ADDRESS 45 ON OFF ON OFF OFF OFF ON = ADDRESS 46 ON OFF ON OFF OFF OFF OFF = ADDRESS 47 ON OFF OFF ON ON ON ON = ADDRESS 48 ON OFF OFF ON ON ON OFF = ADDRESS 49 ON OFF OFF ON ON OFF ON = ADDRESS 50 ON OFF OFF ON ON OFF OFF = ADDRESS 51 ON OFF OFF ON OFF ON ON = ADDRESS 52 ON OFF OFF ON OFF ON OFF = ADDRESS 53 ON OFF OFF ON OFF OFF ON = ADDRESS 54 ON OFF OFF ON OFF OFF OFF = ADDRESS 55 ON OFF OFF OFF ON ON ON = ADDRESS 56 ON OFF OFF OFF ON ON OFF = ADDRESS 57 ON OFF OFF OFF ON OFF ON = ADDRESS 58 ON OFF OFF OFF ON OFF OFF = ADDRESS 59 ON OFF OFF OFF OFF ON ON = ADDRESS 60 ON OFF OFF OFF OFF ON OFF = ADDRESS 61 ON OFF OFF OFF OFF OFF ON = ADDRESS 62 ON OFF OFF OFF OFF OFF OFF = ADDRESS 63 OFF ON ON ON ON ON ON = ADDRESS 64 OFF ON ON ON ON ON OFF = ADDRESS 65 OFF ON ON ON ON OFF ON = ADDRESS 66 OFF ON ON ON ON OFF OFF = ADDRESS 67 OFF ON ON ON OFF ON ON = ADDRESS 68 OFF ON ON ON OFF ON OFF = ADDRESS 69 OFF ON ON ON OFF OFF ON = ADDRESS 70 OFF ON ON ON OFF OFF OFF = ADDRESS 71 OFF ON ON OFF ON ON ON = ADDRESS 72 OFF ON ON OFF ON ON OFF = ADDRESS 73 OFF ON ON OFF ON OFF ON = ADDRESS 74 OFF ON ON OFF ON OFF OFF = ADDRESS 75 OFF ON ON OFF OFF ON ON = ADDRESS 76 OFF ON ON OFF OFF ON OFF = ADDRESS 77 OFF ON ON OFF OFF OFF ON = ADDRESS 78 OFF ON ON OFF OFF OFF OFF = ADDRESS 79 Position 1 Shown in ON Position Switch SW1 Valid Addresses = 1 thru 119 Baud Rate Switch (Shown set for address 13 and 9600 baud) SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8 8 7 6 5 4 3 2 1 Address Switches OFF = OPEN ON = CLOSED ON OFF OFF = OPEN ON = CLOSED Figure 3 Position 8 Shown in OFF Position = 1200 BAUD = 9600 BAUD OFF ON OFF ON ON ON ON = ADDRESS 80 OFF ON OFF ON ON ON OFF = ADDRESS 81 OFF ON OFF ON ON OFF ON = ADDRESS 82 OFF ON OFF ON ON OFF OFF = ADDRESS 83 OFF ON OFF ON OFF ON ON = ADDRESS 84 OFF ON OFF ON OFF ON OFF = ADDRESS 85 OFF ON OFF ON OFF OFF ON = ADDRESS 86 OFF ON OFF ON OFF OFF OFF = ADDRESS 87 OFF ON OFF OFF ON ON ON = ADDRESS 88 OFF ON OFF OFF ON ON FF = ADDRESS 89 OFF ON OFF OFF ON OFF ON = ADDRESS 90 OFF ON OFF OFF ON OFF OFF = ADDRESS 91 OFF ON OFF OFF OFF ON ON = ADDRESS 92 OFF ON OFF OFF OFF ON OFF = ADDRESS 93 OFF ON OFF OFF OFF OFF ON = ADDRESS 94 OFF ON OFF OFF OFF OFF OFF = ADDRESS 95 OFF OFF ON ON ON ON ON = ADDRESS 96 OFF OFF ON ON ON ON OFF = ADDRESS 97 OFF OFF ON ON ON OFF ON = ADDRESS 98 OFF OFF ON ON ON OFF OFF = ADDRESS 99 OFF OFF ON ON OFF ON ON = ADDRESS 100 OFF OFF ON ON OFF ON OFF = ADDRESS 101 OFF OFF ON ON OFF OFF ON = ADDRESS 102 OFF OFF ON ON OFF OFF OFF = ADDRESS 103 OFF OFF ON OFF ON ON ON = ADDRESS 104 OFF OFF ON OFF ON ON OFF = ADDRESS 105 OFF OFF ON OFF ON OFF ON = ADDRESS 106 OFF OFF ON OFF ON OFF OFF = ADDRESS 107 OFF OFF ON OFF OFF ON ON = ADDRESS 108 OFF OFF ON OFF OFF ON OFF = ADDRESS 109 OFF OFF ON OFF OFF OFF ON = ADDRESS 110 OFF OFF ON OFF OFF OFF OFF = ADDRESS 111 OFF OFF OFF ON ON ON ON = ADDRESS 112 OFF OFF OFF ON ON ON OFF = ADDRESS 113 OFF OFF OFF ON ON OFF ON = ADDRESS 114 OFF OFF OFF ON ON OFF OFF = ADDRESS 115 OFF OFF OFF ON OFF ON ON = ADDRESS 116 OFF OFF OFF ON OFF ON OFF = ADDRESS 117 OFF OFF OFF ON OFF OFF ON = ADDRESS 118 OFF OFF OFF ON OFF OFF OFF = ADDRESS 119 Chart 1. 4603-9101 LCD Annunciator Address Chart 4

General Wiring Precautions There are several general wiring precautions that must be followed when wiring the LCD Annunciator. 1. All wiring must be done with copper conductors only. 2. Wire lengths in excess of the maximum lengths listed within Tables 1 through 4 are not permitted. 3. If shielding is used, you must observe the following: Metallic continuity of the shield must be maintained throughout the entire length of cable. The entire length of the cable must have a resistance greater than one megohm to Earth ground. The shield must connect to a SHIELD terminal at each annunciator, and must be terminated only at the main panel. 4. Underground wiring must be free of water. 5. Wires must not be run through elevator shafts. 6. Wire runs in plenums must be in conduit unless rated for plenum use. 7. Splicing is permitted provided that: (a) all such connections are soldered (rosin-core solder), crimped in metal sleeves, or encapsulated with an epoxy resin; (b) when solder or crimped metal sleeves are used, the junction is insulated with a high-grade electrical tape as sound as the original insulating jacket; (c) the shield s continuity is maintained throughout the cable s length. 8. Only system wiring can share the same conduit. IMPORTANT: An Earth ground connection must be provided to the back box for transient suppression. This connection must be made with an approved dedicated Earth connection in accordance with NFPA 20, Article 250. 5

Specific Wiring Precautions When wiring the 4603-9101 LCD Annunciator there are a few specific wiring precautions that must be adhered to. A 4603-9101 LCD Annunciator cannot be used with wiring that goes outside the building (above or below ground) unless overvoltage suppression is provided at both ends. Communication and power wiring must meet the following conditions. 1. Use Simplex Model 2081-9044 Overvoltage Protectors (200 ma or less). There are no restrictions on wire routing. However, the maximum wire length is 2500 feet. 2. Using Simplex Model 2081-9027 (200 ma maximum) or 2081-9028 (5-amp maximum) Isolated Loop Circuit Protector. For underground wiring, select the appropriate isolated loop circuit protector. The circuit wiring must be run in a separate parallel wiring trough, separated from any commercial power distribution wiring. For overhead wiring, select the appropriate isolated loop circuit protector. The wiring is limited to one contiguous property and the total wire length must not exceed 2500 feet. The circuit wiring must be run on separate poles, separated from any poles supporting commercial power distribution wiring. The circuit wiring must be run in parallel with direct relation to the commercial power distribution. The separation is a minimum distance (whichever is greater) of 100 feet, or the maximum span between any two adjacent poles of either the system s circuit or the commercial power distribution circuit. 3. For maximum wire lengths when using circuit protectors, see Tables 1 through 4. 4. Contact your local Simplex branch with any questions you may have on your specific type of cable. 6

4100+/4020 to LCD Annunciator Wiring for Serial Communication 4100+/4020 to LCD Annunciator Wiring for Operating Power When wiring a 4100+/4020 FACP to an LCD Annunciator for Serial Communication make note of the following: 1. Annunciator terminal blocks will accommodate 12-18 AWG wire. 2. When used with audio riser wiring, telephone wiring, and/or 4120 Network wiring, the communication lines must be twisted-shielded pair. 3. Parallel configurations are acceptable where the total distance of all series and/or parallel runs do not exceed the maximum permitted distance. (See Tables 3 and 4). When wiring a 4100+/4020 FACP to an LCD Annunciator for operating power make note of the following: 1. Annunciator terminal blocks accommodates 12-18 AWG wire. 2. 12-18 AWG wires required (See Tables 1 and 2). 3. Each 4603-9101 LCD Annunciator uses 170 ma (0.170A). 4. Operating power must be provided by the system power supply. Wire Length Tables Tables 1 through 4 show the maximum permitted wire pair lengths (in feet) that can be used when wiring a 4603-9101 LCD Annunciator. Table 1 and 2 show the maximum wire lengths possible when Power Wire (two wires) are used. Table 3 and 4 show the maximum wire lengths when Communication Line (a twisted-shielded pair of wires) are used. Notes: When using multiple annunciators and runs the total of all runs must not exceed 10,000 ft (including T-Taps). Four 2081-9044 Overvoltage Protectors and four 2081-9028 Isolated Loop Circuit Protectors are the maximum number permitted on any single communication loop. To convert feet to meters, multiply the number of feet by 0.3048. Power Wire Tables Table 1. With 2081-9044 Overvoltage Protectors Total Current (Amps) 12 AWG (3.309 mm 2 ) 14 AWG (2.801 mm 2 ) 16 AWG (1.309 mm 2 ) 18 AWG (0.823 mm 2 ) 0.100 2,500 ft 2,500 ft 2,371 ft 1,409 ft 0.200 2,500 ft 1,782 ft 889 ft 705 ft Continued on next page 7

Power Wire Tables (Continued) Table 2. Without Transient Suppression (or with 2081-9028 Isolated Loop Circuit Protectors) Total Current (AMPS) 12 AWG (3.309 mm 2 ) 14 AWG (2.081 mm 2 ) 16 AWG (1.309 mm 2 ) 18 AWG (0.823 mm 2 ) 0.100 2,500 ft 2,500 ft 2,500 ft 2,349 ft 0.200 2,500 ft 2,500 ft 1,482 ft 1,175 ft 0.300 2,500 ft 1,980 ft 988 ft 783 ft 0.400 2,361 ft 1,485 ft 741 ft 587 ft 0.500 1,889 ft 1,188 ft 593 ft 470 ft 0.600 1,574 ft 990 ft 494 ft 392 ft 0.700 1,349 ft 849 ft 423 ft 336 ft 0.800 1,181 ft 743 ft 371 ft 294 ft 0.900 1,049 ft 660 ft 329 ft 261 ft 1.000 944 ft 594 ft 296 ft 235 ft 1.100 859 ft 540 ft 269 ft 214 ft 1.200 787 ft 495 ft 247 ft 196 ft With 2081-9027 Isolated Loop Circuit Protectors 0.100 2,500 ft 2,500 ft 2,371 ft 1,409 ft 0.200 2,500 ft 1,782 ft 889 ft 705 ft Communication Line Tables Table 3. With 2081-9044 Overvoltage Protectors 12 AWG (3.309 mm 2 ) 14 AWG (2.081 mm 2 ) 16 AWG (1.309 mm 2 ) 18 AWG (0.823 mm 2 ) 2,500 ft 2,500 ft 2,450 ft 1,650 ft Table 4. Without Transient Suppression (or with 2081-9028 Isolated Loop Circuit Protectors) 12 AWG (3.309 mm 2 ) 14 AWG (2.081 mm 2 ) 16 AWG (1.309 mm 2 ) 18 AWG (0.823 mm 2 ) 2,500 ft 2,500 ft 2,500 ft 2,500 ft With 2081-9027 Isolated Loop Circuit Protectors 2,500 ft 2,500 ft 2,450 ft 1,650 ft 574-031 Rev. B