Manual motor starter MS132

Similar documents
Manual motor starter MS132

Manual motor starter MS132

Manual motor starter MS116

Manual motor starter magnetic only MO325

Manual motor starter MS116

Thermal overload relay TF140DU and TF140DU-V1000

Thermal overload relay TF65 and TF96

Electronic overload relay EF65, EF96 and EF146

Electronic overload relays EF205 and EF370

Mini contactors B6, BC6 with 3 pole

Emergency-off application Manual motor starter MS116/MS132 Undervoltage release UA1

System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications

Thermal Overload Relays

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications

Phone: Fax: Web: -

MS General Information Extended Product Type: MS

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489

System pro M compact Miniature Circuit Breaker SU200 M for branch circuit protection acc. to UL 489

249.1 m3/h m3/h 7.23 MW m3/h 50.0 m3/h

Manual motor starters Overview and benefits

MS /27/2015. ABB contact for United States of America. General Information Extended Product Type: Categories

AF / AF38Z pole Contactors AC / DC Operated - with Screw Terminals

AF / AF30Z stack 3-pole Contactors AC / DC Operated - with Screw Terminals

AF / AF16Z pole Contactors AC / DC Operated - with Screw Terminals

Short form catalogue Motor protection and control Manual motor starters

AF / AF09Z pole Contactors AC / DC Operated - with Screw Terminals

AF / AF09Z pole Contactors AC / DC Operated - with Screw Terminals

NF31E-.. / NFZ31E-.. Contactor Relays AC / DC Operated - with Screw Terminals

Redundancy unit CP-C.1-A-RU Accessory for CP-C.1 range power supplies

Product index. 4 - Manual motor protectors. Phone: Fax: Web: -

Data Sheet Manual Motor Starters Ex9SN Series

Product index. 4 - Manual motor protectors. Manual motor protectors. Manual motor protectors Low Voltage Products & Systems 4.

Brochure. Motor protection and control DRAS enclosed direct-on-line starters

Selective main circuit breakers S 750 series Technical Data

ABB i-bus KNX HIL/S , Hotel IP Link, Bundle

ABB i-bus KNX Hotel IP Link, Bundle HIL/S , 2CDG110237R0011

ABB i-bus KNX DG/S x DALI-Gateway Basic

Contact us. ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F Chassieu cedex / France

VB6, VB7 3-pole mini reversing contactors with screw terminals 4 to 5.5 kw AC operated

Uncompromising safety and comfort Miniature Circuit Breaker SU 200 M for branch circuit protection per UL and CSA

AF40... AF96 3-pole contactors Technical data

AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals

SU200M Datasheet. Branch protection acc. to CSA C22.2 No.5 / UL 489

MS25, MST25, MS20, MST20

B6, B7, BC6, BC7, TBC7 3- and 4-pole mini contactors VB6, VB7, VBC6, VBC7 3- and 4-pole mini reversing contactors Technical data

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

Protection and Connection Motorized and automatic transfer switches IEC Technical guide

AF / AF12Z pole Contactors AC / DC Operated - with Screw Terminals

MAKING MODERN LIVING POSSIBLE. Technical brochure. Minicontactors CI 5-

Data Sheet DIN Rail Miniature Circuit Breakers Ex9 Series - B1

ZS4-S Screw Clamp Terminal Blocks Disconnect with blade

RSC09 RSC16 RSC22 RSC38 RSC43 RSC63 RSC-AUX

ZS4-PE Screw Clamp Terminal Blocks Ground

Technical Information

Short form catalogue. Motor protection & control

ZS4-SF1-R Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with blown fuse indicator

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC

ZS10 Screw Clamp Terminal Blocks Feed-through

AF40... AF96 3-pole contactors 30 to 60 hp at 480 V AC AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts

ASL09..S 3-pole Contactors - Spring Terminals

ZK2.5-SP-4P PI-Spring Terminal Blocks Disconnect with plug - with test socket

US Catalog January Motor protection and control Manual motor starters, contactors and overload relays

ZS4 Screw Clamp Terminal Blocks Feed-through

ZS6-S Screw Clamp Terminal Blocks Disconnect with blade

ZS10-ST Screw Clamp Terminal Blocks Test disconnect with sliding link

Data Sheet DIN Rail Miniature Circuit Breakers Ex9 Series - B1NQ

Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A

ZS4-T3 Screw Clamp Terminal Blocks Triple deck with 3 feed-through circuits

Technical data for manual motor starters Type MS325

ZS6-4S Screw Clamp Terminal Blocks Feed-through with 4 connections

ZS4-D2-S-T Screw Clamp Terminal Blocks Double deck with 1 disconnect circuit with test socket screws and 1 feed-through circuit

ZS35 Screw Clamp Terminal Blocks Feed-through

ZS6-D1-PE Screw Clamp Terminal Blocks Double deck with 1 ground circuit

ZS35-PEN Screw Clamp Terminal Blocks Ground + Neutral

ZS4-SF1 Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses

ZS4-SF Screw Clamp Terminal Blocks For 5 x 20 fuses

ZS50-PE Screw Clamp Terminal Blocks Ground

ZS4-SF1-T Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with test socket

ZS10-PE Screw Clamp Terminal Blocks Ground

ZS6-3S Screw Clamp Terminal Blocks Feed-through with 3 connections

ZS10-S-R2 Screw Clamp Terminal Blocks Disconnect with lever

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.

DBL distribution blocks 3x1 pole

Data Sheet Manual Motor Starter Ex9S32 Series

Technical Information

ZK2.5-SP PI-Spring Terminal Blocks Disconnect with plug - with test sockets

ZS4-PE Screw Clamp Terminal Blocks Ground

Data Sheet Manual Motor Starter Ex9S32 Series

ZK2.5-SF-R PI-Spring Terminal Blocks For 5x20 fuses - with blown fuse indicator

ZK2.5-PE-4P PI-Spring Terminal Blocks Ground with 4 connections

ZK4-4P PI-Spring Terminal Blocks Feed-through with 4 connections

Protection Equipment

ZS6 Screw Clamp Terminal Blocks Feed-through

ZK2.5-4P PI-Spring Terminal Blocks Feed-through with 4 connections

B Mini Contactor V Hz

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases

ZK4-PE PI-Spring Terminal Blocks Ground

Manual Motor Starter MS 116. Technical Catalogue

NSL..S 4-pole / 8-pole Contactor Relays - Spring Terminals

Transcription:

Data sheet Manual motor starter MS132 Manual motor starters are electromechanical protection devices for the main circuit. They are used mainly to switch motors manually ON/OFF and protect them fuse less against short-circuit, overload and phase failures. Fuse less protection with a manual motor starter saves costs, space and ensures a quick reaction under shortcircuit condition, by switching off the motor within milliseconds. Fuse less starter combinations are setup together with contactors. 2CDC241020F0009 Description Overload protection trip class 10 Phase loss sensitivity Disconnect function Temperature compensation from -25 +60 C djustable current setting for overload protection Suitable for three- and single-phase application Trip-free mechanism Status indication Clear switch position indication ON/OFF/TRIP Lockable handle pprovals Marks culus UL 508 a CE K CB scheme E CCC D GOST-R GOST-F Order data MS132 screw terminal Setting range Trip class Order code Packing unit PCE Weight per PCE 0.10...0.16 MS132-0.16 10 1SM0000R1001 1 0.215 0.16...0.25 MS132-0.25 10 1SM0000R1002 1 0.215 0.25...0.40 MS132-0.4 10 1SM0000R1003 1 0.215 0.40...0.63 MS132-0.63 10 1SM0000R1004 1 0.215 0.63...1.00 MS132-1.0 10 1SM0000R1005 1 0.215 1.00...1.60 MS132-1.6 10 1SM0000R1006 1 0.265 1.60...2.50 MS132-2.5 10 1SM0000R1007 1 0.265 2.50...4.00 MS132-4.0 10 1SM0000R1008 1 0.265 4.00...6.30 MS132-6.3 10 1SM0000R1009 1 0.265 6.30...10.0 MS132-10 10 1SM0000R1010 1 0.265 8.00...12.0 MS132-12 10 1SM0000R1012 1 0.310 10.0...16.0 MS132-16 10 1SM0000R1011 1 0.310 16.0...20.0 MS132-20 10 1SM0000R1013 1 0.310 20.0...25.0 MS132-25 10 1SM0000R1014 1 0.310 25.0...32.0 MS132-32 10 1SM0000R1015 1 0.310 kg P BS Lloyd s Register GL DNV RIN Note: MS132 with pre-assembled auxiliary contact HKF1-11, please order as follow 1SM0005Rxxxx

Functional description 1 Terminals 1L1, 3L2, 5L3 1 2 Switch position TRIP 3 Lockable handle 2 4 Status indication for short-circuit 3 4 5 6 7 2CDC241020F0009 5 Current setting range djustable current setting for overload protection 6 Test function 7 Terminals 2T1, 4T2, 6T3 pplication The manual motor starters protect the load and the installation against short-circuit and overload. They are three pole protection devices with thermal tripping elements for overload protection and electromagnetic tripping elements for shortcircuit protection. Furthermore, they provide a disconnect function for safely isolation of the installation and the supply and can be used for the manual switching of loads. The manual motor starters have a setting scale in amperes, which allows the direct adjusting of the device without any additional calculation. In compliance with international and national standards, the setting current is the rated current of the motor and not the tripping current (no tripping at 1.05 x I, tripping at 1.2 x I; I = setting current). Operation mode 2CDC242023F0009 2CDC242024F0009 Single-phase operation Three-phase operation Wiring diagram 2CDC242025F0009 2-2CDC131021D0201

Resistance and power loss per pole Setting range Resistance per pole Power loss per pole lower value upper value Ω at lower value W MS132-0.16 0.10 0.16 66.00 0.7 1.7 MS132-0.25 0.16 0.25 25.50 0.7 1.7 MS132-0.4 0.25 0.40 10.38 0.7 1.7 MS132-0.63 0.40 0.63 4.36 0.7 1.7 MS132-1.0 0.63 1.00 1.605 0.7 1.7 MS132-1.6 1.00 1.60 0.648 0.7 1.7 MS132-2.5 1.60 2.50 0.272 0.7 1.7 MS132-4.0 2.50 4.00 0.106 0.7 1.7 MS132-6.3 4.00 6.30 0.046 0.7 1.7 MS132-10 6.30 10.0 0.024 0.9 2.4 MS132-12 8.00 12.0 0.016 1.0 2.3 MS132-16 10.0 16.0 0.011 1.1 2.8 MS132-20 16.0 20.0 0.0057 1.5 2.3 MS132-25 20.0 25.0 0.0045 1.8 2.8 MS132-32 25.0 32.0 0.0030 1.9 3.1 at upper value W Dimensions in mm / inches 81,25 / 3,2" 81,05 / 3,19" 72,4 / 2,85" 72,2 / 2,84" 1,5 / 0,06" 5,5 / 0,22" 43,5 / 1,71" 1,5 / 0,06" 5,5 / 0,22" 43,3 / 0,22" 90 / 3,54" 1,7 / 0,1" 75 / 2,95" / 1,38" 45 / 1,77" 97,8 / 3,85" 1,7 / 0,1" 75 / 2,95" / 1,38" 45 / 1,77" 14 / 0,55" 45 / 1,77" 14 / 0,55" mm / inch 2CDC242015F0009 14 / 0,55" 14 / 0,55" 45 / 1,77" mm / inch 2CDC242016F0009 MS132 10 MS132 > 10 Ø 4,5 / Ø 0,18" 9 / 0," 5,4 / 0,21" Ø 4,5 / Ø 0,18" 9 / 0," 5,4 / 0,21" 122 / 4,8" 110 / 4,33" 122 / 4,8" 110 / 4,33" 17,5 / 0,69" mm / inch 2CDC242017F0009 17,5 / 0,69" mm / inch 2CDC242018F0009 MS132 10 with screw fixing kit FS116 (accessory) MS132 > 10 + with screw fixing kit FS116 (accessory) 2CDC131021D0201-3

Technical data IEC/EN Data at T = 40 C and at rated values, if nothing else indicated Main circuit Rated operational voltage U e 1L1-3L2-5L3 2T1-4T2-6T3 690 V a.c. 250 V d.c. Setting range - thermal overload protection see table Order data on page 1 Rated operational current I e Rated operational current DC-5 I e 3 conducting paths in series up to 250 V Rated instantaneous short-circuit current setting I i Rated service short-circuit breaking capacity I cs Rated ultimate short-circuit breaking capacity I cu Rated service short-circuit breaking capacity d.c. I cs 3 conducting paths in series up to 250 V see table below see Rated operational current I e see table below see table Short-circuit breaking capacity and back-up fuses on page 6 Trip class see table Order data on page 1 Rated frequency Number of poles 3 Resistance per pole Power loss per pole 10 d.c., 50/60 Hz see table Resistance and power loss per pole on page 3 Isolation data Rated impulse withstand voltage U imp 6 kv Rated insulation voltage U i 690 V Pollution degree 3 Electrical connection MS132 10 MS132-12, -16 MS132-20, -25, -32 Connecting capacity solid 1/2 x 1... 4 mm² 1/2 x 2.5... 6 mm² stranded 1/2 x 1... 4 mm² 1/2 x 2.5... 6 mm² flexible with ferrule 1/2 x 0.75... 2.5 mm² 1/2 x 1... 6 mm² flexible with ferrule insulated 1/2 x 0.75... 2.5 mm² 1/2 x 1... 6 mm² flexible without ferrule 1/2 x 0.75... 2.5 mm² 1/2 x 2.5... 6 mm² Stripping length 9 mm 10 mm 10 mm Tightening torque 0.8... 1.2 Nm 1.5 Nm 2 Nm Connection screw M3.5 M4 M4 Rated instantaneous short-circuit current setting l i MS132-0.16 1.56 0.16 MS132-0.25 2.44 0.25 MS132-0.4 3.90 0.40 MS132-0.63 6.14 0.63 MS132-1.0 11.50 1.00 MS132-1.6 18.40 1.60 MS132-2.5 28.75 2.50 MS132-4.0 50.00 4.00 MS132-6.3 78.75 6.30 MS132-10 150 10.0 MS132-12 180 12.0 MS132-16 240 16.0 MS132-20 300 20.0 MS132-25 375 25.0 MS132-32 480 32.0 Rated operational current l e 4-2CDC131021D0201

General data Mechanical durability 10 5 Electrical durability 5 x 10 4 Duty time 100 % Dimensions (W x H x D) see drawing Dimensions on page 3 Weight see table Order data on page 1 Mounting DIN-rail (EN 60715) Mounting position position 1-6 (optional for single mounting) Group Mounting on request Minimum distance to other units same type horizontal 0 mm vertical 150 mm Minimum distance to electrical conductive board horizontal, up to 400 V 0 mm horizontal, up to 690 V > 1.5 mm vertical 75 mm Degree of protection enclosure / terminals IP20 Utilization category ltitude up to 2000 m Maximum operating frequency 170 cycles/h Electromagnetic compatibility Electromagnetic compatibility not applicable Environmental data mbient air temperature Operation open - compensated without derating -25... +60 C open -25... +70 C Storage -50... +80 C Temperature compensation continuous Vibration (sinusoidal) acc. to IEC/EN 60068-2-6 (Fc) 5g / 3... 150 Hz Shock (half-sine) acc. to IEC/EN 60068-2-27 (Ea) 25g / 11 ms Standards / directives Product standard IEC/EN 60947 2 IEC/EN 60947-4-1 IEC/EN 60947-1 UL 508, CS 22.2 No. 14 Low Voltage Directive 2006/95/EC EMC Directive 2004/108/EC RoHS Directive 2002/95/EC 2CDC131021D0201-5

Short-circuit breaking capacity and back-up fuses l CS l CU o Rated service short-circuit breaking capacity Rated ultimate short-circuit breaking capacity No back-up fuse required, because short-circuit proof up to 100 230 V C 400 V C 440 V C 500 V C 690 V C I CS I CU gg I CS I CU gg I CS MS132-0.16 100 100 100 100 100 100 100 100 100 100 MS132-0.25 100 100 100 100 100 100 100 100 100 100 MS132-0.4 100 100 100 100 100 100 100 100 100 100 MS132-0.63 100 100 100 100 100 100 100 100 100 100 MS132-1.0 100 100 100 100 100 100 100 100 100 100 MS132-1.6 100 100 100 100 100 100 100 100 100 100 MS132-2.5 100 100 100 100 100 100 100 100 100 100 MS132-4.0 100 100 100 100 20 20 on request 20 20 on request 3 3 on request MS132-6.3 100 100 100 100 20 20 on request 20 20 on request 3 3 on request MS132-10 100 100 100 100 20 20 on request 20 20 on request 3 3 on request MS132-12 100 100 100 100 20 20 on request 20 20 on request 3 3 on request MS132-16 100 100 100 100 20 20 on request 20 20 on request 3 3 on request MS132-20 100 100 100 100 20 20 on request 20 20 on request 3 3 on request MS132-25 50 50 100 50 50 100 20 20 on request 10 10 on request 3 3 on request MS132-32 25 50 125 25 50 125 20 20 on request 10 10 on request 3 3 on request I CU gg I CS I CU gg I CS I CU gg 6-2CDC131021D0201

Technical data UL/CS Main circuit Maximum operational voltage 600 V Manual Motor Controller ratings see table UL 508 Manual Motor Controller on page 8 Motor ratings Horse power see table below Full load amps (FL) Locked rotor amps (LR) see table below see table below Electrical connection MS132 10 MS132-12, -16 MS132-20, -25, -32 Connecting capacity stranded 1/2 x WG 16... 12 1/2 x WG 12... 8 flexible without ferrule 1/2 x WG 16... 12 1/2 x WG 12... 8 Stripping length 9 mm 10 mm 10 mm Tightening torque 10... 12 lb-in 14 lb-in 18 lb-in Connection screw M3.5 M4 M4 Motor rating, single phase hp FL Horse power Full load amps LR Locked rotor amps 220... 240 V C 440... 480 V C hp FL LR hp FL LR MS132-0.16-0.16 0.96-0.16 0.96 MS132-0.25-0.25 1.5-0.25 1.5 MS132-0.4-0.4 2.4-0.4 2.4 MS132-0.63-0.63 3.78-0.63 3.78 MS132-1.0-1 6-1 6 MS132-1.6 1/10 1.6 9.6-1.6 9.6 MS132-2.5 1/6 2.5 15 1/2 2.5 15 MS132-4.0 1/3 4 24 1/2 4 24 MS132-6.3 1/2 6.3 37.8 1 6.3 37.8 MS132-10 1-1/2 10 60 3 8.5 46 MS132-12 2 12 72 3 8.5 64 MS132-16 2 12 72 5 14 81 MS132-20 3 17 92 5 14 81 MS132-25 3 17 127 7-1/2 21 116 MS132-32 5 28 162 10 26 145 2CDC131021D0201-7

Motor rating, three phase hp Horse power FL Full load amps LR Locked rotor amps 110... 120 V C 220... 240 V C 440... 480 V C 500... 600 V C hp FL LR hp FL LR hp FL LR hp FL LR MS132-0.16-0.16 0.96-0.16 0.96-0.16 0.96-0.16 0.96 MS132-0.25-0.25 1.5-0.25 1.5-0.25 1.5-0.25 1.5 MS132-0.4-0.4 2.4-0.4 2.4-0.4 2.4-0.4 2.4 MS132-0.63-0.63 3.78-0.63 3.78-0.63 3.78-0.63 3.78 MS132-1.0-1 6-1 6-1 6 1/2 1 6 MS132-1.6-1.6 9.6-1.6 9.6 3/4 1.6 9.6 3/4 1.6 9.6 MS132-2.5-2.5 15 1/2 2.5 15 1 2.5 15 1-1/2 2.5 15 MS132-4.0-4 24 1 4 24 2 4 24 3 3.9 26 MS132-6.3 1/2 6.3 37.8 1-1/2 6.3 37.8 3 4.8 32 5 6.1 37 MS132-10 3/4 10 60 3 9.6 64 5 7.6 46 7-1/2 9 51 MS132-12 1-1/2 12 72 3 9.6 64 7-1/2 11 64 10 11 65 MS132-16 2 16 84 5 15.2 92 10 14 81 10 11 65 MS132-20 3 19.2 128 5 15.2 92 10 14 81 15 17 93 MS132-25 3 19.2 128 7-1/2 22 127 15 21 116 20 22 116 MS132-32 5 30.4 184 10 28 162 20 27 145 25 27 146 Manual Motor Controller for Motor Disconnect MS132-0.16 Circuit Breaker or Class R fuse per UL/ NEC 480 V / 600 V with minimum Maximum short-circuit current rating 480 V 600 V MS132-0.25 MS132-0.4 MS132-0.63 interrupting rating of,000 rms symmetrical amperes 30 30 30 18 18 18 MS132-1.0 30 18 30 18 MS132-1.6 30 18 MS132-2.5 30 18 MS132-4.0 30 18 MS132-6.3 30 18 MS132-10 30 18 MS132-12 30 18 MS132-16 30 18 MS132-20 30 18 MS132-25 30 18 MS132-32 30 18 8-2CDC131021D0201

Manual Motor Controller for Group Installation MS132-0.16 Circuit Breaker or Class R fuse per UL/ NEC 480 V / 600 V with minimum Maximum short-circuit current rating 480 V 600 V MS132-0.25 MS132-0.4 MS132-0.63 interrupting rating of,000 rms symmetrical amperes MS132-1.0 MS132-1.6 MS132-2.5 MS132-4.0 MS132-6.3 MS132-10 MS132-12 MS132-16 MS132-20 MS132-25 MS132-32 Manual Motor Controller for Group Installation in combination with current limitor S803W-SCLxxx-SR Maximum short-circuit current rating 480 V 600 V MS132-0.16 65 65 MS132-0.25 65 65 MS132-0.4 65 65 MS132-0.63 65 65 MS132-1.0 65 65 MS132-1.6 65 65 MS132-2.5 65 65 MS132-4.0 65 65 MS132-6.3 65 65 MS132-10 65 65 MS132-12 65 65 MS132-16 65 65 MS132-20 65 65 MS132-25 65 65 MS132-32 65 65 2CDC131021D0201-9

Self-Protected Combination Motor Controller ( E) and Combination Motor Controller ( F) UL 508 Self-Protected Combination Motor Controller ( E) in combination with feeder block S1-M3-xx Maximum short-circuit current rating UL 508 Combination Motor Controller ( F) Maximum short-circuit current rating Minimum contactor size UL 508 Manual Motor Controller for Tap Conductor Protection Maximum short-circuit current rating 480Y / 277 V 480Y / 277 V 480 V 600 V MS132-0.16 30 30 F26...F38 30 65 MS132-0.25 30 30 F26...F38 30 30 MS132-0.4 30 30 F26...F38 30 30 MS132-0.63 30 30 F26...F38 30 30 MS132-1.0 30 30 F26...F38 30 30 MS132-1.6 30 30 F26...F38 30 30 MS132-2.5 30 30 F26...F38 30 30 MS132-4.0 30 30 F26...F38 30 30 MS132-6.3 30 30 F26...F38 30 30 MS132-10 30 30 F26...F38 30 30 MS132-12 30 - - 30 30 MS132-16 30 - - 30 30 MS132-20 30 - - 30 30 MS132-25 30 - - 30 30 MS132-32 30 - - 30 30 Self-Protected Combination Motor Controller ( E) and Combination Motor Controller ( F) in combination with current limitor S803W-SCLxxx-SR UL 508 Self-Protected Combination Motor Controller ( E) in combination with current limitor S803W-SCLxxx-SR UL 508 Combination Motor Controller ( F) in combination with current limitor S803W-SCLxxx-SR Maximum short-circuit current rating Maximum short-circuit current rating Minimum contactor size 480Y / 277 V 480Y / 277 V MS132-0.16 65 65 F26...F38 MS132-0.25 65 65 F26...F38 MS132-0.4 65 65 F26...F38 MS132-0.63 65 65 F26...F38 MS132-1.0 65 65 F26...F38 MS132-1.6 65 65 F26...F38 MS132-2.5 65 65 F26...F38 MS132-4.0 65 65 F26...F38 MS132-6.3 65 65 F26...F38 MS132-10 65 65 F26...F38 MS132-12 65 - - MS132-16 65 - - MS132-20 65 - - MS132-25 65 - - MS132-32 65 - - 10-2CDC131021D0201

Contact us BB STOTZ-KONTKT GmbH Eppelheimer Straße 82 69123 Heidelberg, Germany Phone: +49 (0) 6221 7 01-0 Fax: +49 (0) 6221 7 01-13 25 E-Mail: info.desto@de.abb.com You can find the address of your local sales organization on the BB home page http://www.abb.com/contacts -> Low Voltage Products and Systems Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. BB G does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. ny reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of BB G. Brochure number 2CDC 131 021 D0201 (04.2011) Copyright 2011 BB ll rights reserved