INSTRUCTIONS FOR ACID FILLING AND FIRST CHARGING OF DRY, UNCHARGED EXIDE India TRACTION BATTERIES

Similar documents
Long Duration MCT LEAD CALCIUM H1T LEAD CALCIUM SECTION

Vented fibre structure Nickel Cadmium batteries for stationary systems

Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service

RAYLITE M-SOLAR BATTERIES

IEEE IAS Atlanta Chapter

Nominal Voltage. Capacity (C20)

Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service

TABLE OF CONTENTS BATTERY INSTALLATION INTRODUCTION CONSTRUCTION FEATURES SAFETY APPLICABLE STANDARDS OPERATING FEATURES MAINTENANCE BATTERY TEST

6 & 12 Volt Monobloc GEL Range

6 & 12 Volt Monobloc. Haze Battery Company Ltd

Service Department. Other Service Items. Battery Basics. How Do Lead Acid Batteries Work? Battery Construction. Service Address

AINO MICRO RANGE VRLA. Compact energy for increased security BATTERY SOLUTIONS. EverExceed power your applications

SECTION

Open-circuit voltages (OCV) of various type cells:

Pure Lead-Tin Technology

EV Power - A-Series 8 Cell, 16 Cell and 24Cell Chargers Installation & Usage Instructions.

SECTION A Division of Exide Technologies

Congratulations. on your purchase from Trojan Battery Company, the manufacturer of the

Standby Products SD-SDH. series. Technical Features. Applications. Product Features

Battery Storage Systems

Installation Manual. An Invensys company

Product Guide. An Invensys company

TROJAN BATTERY COMPANY Renewable Energy Warranty Claim Form

EcoSafe EOPzV. Operation Guide for Solar Applications

Power to keep you on the move

Installation, Maintenance and Warranty Flat Plate Battery

Haze Battery Company Ltd. Sealed Lead Acid 6 & 12 Volt. AGM Range. Monobloc

GNB Flooded. Long Duration MCT LEAD CALCIUM NAT LEAD ANTIMONY NCT LEAD CALCIUM HAT LEAD ANTIMONY HCT LEAD CALCIUM

Energy Storage. Electrochemical Cells & Batteries

Industrial Batteries Network Power Classic OGi Suitable universal energy storage.

Batteries and more. Powered by (CE, UL & ISO9001 APPROVAL)

Charging of HOPPECKE OPzV solar.power battery in Solar Applications

World Class Charging Systems. TEBETRON expert. Intelligent charging systems for traction batteries

CAMTECH/S/2005/LAC/2.0 1 LEAD ACID CELL

Flush with tap water if acid comes in contact with body parts and seek medical attention immediately.

Reference Number PDS 18 - (RIC Standard: EP SP)

Haze Battery Company Ltd. Sealed Lead Acid 6 & 12 Volt. AGM Range. Monobloc

12 VDC Power Sources For Your RV

POWER FOR TOMORROW. Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service

Haze Battery Company Ltd. Sealed Lead Acid 6 & 12 Volt. Gelled Electrolyte Range. Monobloc

TYPE TEST REPORT. OPzS CELLS AND BLOCK BATTERIES. According to IEC

FIAMM Industrial Batteries December 2012 FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual TABLE OF CONTENTS

[Charge] [Lead dioxide] [Lead] [Sulfuric acid] [Lead sulfate] [Lead sulfate] [Water]

1. Introduction Technical Features Construction Standards Certification Technology...

IMPORTANT SAFETY INSTRUCTIONS IMPORTANT: READ AND SAVE THIS SAFETY AND INSTRUCTION MANUAL. KEEP IT WITH OR NEAR CHARGER AT ALL TIMES.

OPERATING INSTRUCTIONS

F R O N T T E R M I N A L PRODUCT GUIDE Publication No: EN-VFT-PG-001 February 2003

SUBSTATION EQUIPMENT - Page 1 of 8

SEC. MICROLYTE +Plus. Industrial Battery Co. Supplied Worldwide by: Visit our website on Features. Application

Specification Approval Sheet

MODEL UC 14YFA. Hitachi. Power Tools TECHNICAL DATA AND SERVICE MANUAL CHARGER UC 14YFA SPECIFICATIONS AND PARTS ARE SUBJECT TO CHANGE FOR IMPROVEMENT

BATTERIES, CHARGERS & ALTERNATORS. Excerpt from G4 InverCharge Series Manual BY: VIJAY SHARMA ENGINEER

INSTALLATION AND OPERATING INSTRUCTIONS FOR FLOODED TUBULAR-HP MOTIVE POWER BATTERIES

PowerSafe OPzV Operation Guide for Solar Applications

Batteries, Alternators, and Chargers

Haze Battery Company Ltd

Haze Battery Company Ltd

Industrial Batteries / Network Power. Classic OPzS.»Proven high reliability energy storage for critical applications«

Industrial Batteries Classic OCSM Energy delivery with high efficiency.

2. Professionally managed team with years of market and technical knowledge. 3. Serving over chargers in the field in India and overseas.

Batteries. Eric Harris, Colin Hepton, Steven Hodgson, Martin Holland, Michael Hudson and Jonathan Ridyard. 14/11/2005

New energy for the future

EUROBAT EUROBAT GUIDE FOR MOTIVE POWER VRLA BATTERIES

Specification Approval Sheet

Installation & Maintenance Manual

Motive Power (Traction) Batteries & Cells

ANNEXURE XI. (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I.

POWERPLUS NICKEL CADMIUM BATTERIES SINTERED PLATE / POCKET PLATE 5AH to 1000AH / 20+ years long life

Haze Battery Company Ltd. Sealed Lead Acid 2 Volt Bloc. Gelled Electrolyte Range

CTC Battery, Inc. Lithium Iron Phosphate Battery Specification

Charge & Discharge. Ed Erny - NZ1Q August 2017

Proper Torque Values for Connection Hardware. 90 to 100 in-lbs

LIBERTY SERIES 1000 VALVE REGULATED LEAD-CALCIUM BATTERY For standby applications Capacities from 25 to 600 Ampere-hours

Deep Cycle AGM Range VRLA

Duracell Battery Glossary

IT 0335 US ARMY INTELLIGENCE CENTER INTRODUCTION TO CELLS AND BATTERIES

IT 0335 US ARMY INTELLIGENCE CENTER INTRODUCTION TO CELLS AND BATTERIES

User s Manual. Portable Environmental Electromechanical Voltage Supply (PEEVS)

PRODUCT GUIDE Publication No: EN-SBS-PG-001 February 2003

GLOSSARY: TECHNICAL BATTERY TERMS

Haze Battery Company Ltd

Specification Approval Sheet

Chapter 6. Batteries. Types and Characteristics Functions and Features Specifications and Ratings Jim Dunlop Solar

PowerSafe OPzV Operation Guide for Solar Applications

RS Stock number

2 Volt AGM Range. Haze Battery Company Ltd

PURE LEAD PLUS UPS APPLICATIONS. Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell

NCPP. Nickel Cadmium Pocket Plate Batteries. Block Cell Dimensional and Electrical Data

RF80-K Aircraft Battery Charger / Analyzer

Boat drive assembly manual

RAILROAD & DIESEL STARTER BATTERY USER MANUAL

RF80-M. Features. Lead Acid Batteries Multistep Programmable. Automatic Operation Stores 100 Programs

ELiTE Battery Information

EV Traction Dry Cell Battery Technology

Modular Max Range BATTERY SOLUTIONS. NEBS qualified. Reliable capacities. EverExceed power your applications

EV Traction Dry Cell Battery Technology

Station dc supply voltage. Electrolyte level. Inspect: Verify:

Forklift Battery Charging Methods

FEATURES & benefits. Constant Power Discharge Ratings - Watts per 77 F (25 F) Operating Time (in minutes) to 1.

EV Power - Battery Control Unit Instructions. 8 Cell 24V

Transcription:

INSTRUCTIONS FOR ACID FILLING AND FIRST CHARGING OF DRY, UNCHARGED EXIDE India TRACTION BATTERIES ACID FILLING INSTRUCTION: Fill the cells with battery grade sulphuric acid of 1.260 +/ 0.005 specific gravity at 30 deg C conforming to the following specifications: Iron ( as Fe ) percent by mass Chlorides ( as Cl ) percent by mass : 0.001 ( Max) : 0.0003 ( Max) Flip top vent plugs are fitted on the cell lids together with basket type electrolyte level indicators, the lower level corresponding to the minimum height of electrolyte in the cell. The stepped portion of the basket indicated the maximum level of electrolyte. However, the basket is visible only after opening the flip top. After initial filling, acid will soak into the plates and separators, and the level should be restored with more acid to the maximum level after around 6 8 hrs. * Note: If the electrolyte temperature exceeds 55 deg C, please allow it to drop below 42 deg C prior to the commencement of charging. If required, the cooling process should be facilitated by providing suitable fans / water bath ensuring that the same is accomplished with 4 to 6 hrs after pouring electrolyte. PROCEDURE FOR INITIAL CHARGING: During initial filling & charging, the batteries should be charged at Constant Current rate as specified in the catalogue, up to 2.75 volts per cell. The charging should be continued even after the battery reaches 2.75 volts per cell till no rise of the Voltage and sp. Gravity is observed in the cells and the readings remain constant for consecutive 3 to 4 hourly readings.

The sp. Gravity of all the cells to be adjusted to 1.285 +/ 0.005 (the service gravity), using 1.400 sp. Gravity Battery Grade Sulphuric Acid / Battery Grade Water conforming to the following specifications: ph level : 6.5 7.5 Heavy metals ( as Pb )mg/l : 0.1 (max) Iron & manganese mg/l : 0.1 ( max) Specific electrical conductivity At 25 C in dionic units: 5 ( max) Minimum Ah inputs should be 5 to 5.5 times of the Ah capacity of cell/battery. *Charging should be continued at constant current till a) All cells are gassing freely at top of charge voltage 2.75 volts per cell at finished rate. b) No rise of voltage for 3 to 4 consecutive hourly readings after 2.75 volts per cell (vpc). c) No rise of Sp.Gr. for 3 to 4 consecutive hourly readings after 2.75 volts per cell (vpc). d) Minimum Ah input (5 to 5.5 times of Ah capacity of cell/battery) is given. Theoretical inputs: Filling in Acid Sp. Gravity: 1.260 +/ 0.005 at 30 deg C. Soaking time : 6 8 hrs. Initial Charging Current (Amps) : At 6% rate of the Ah capacity of Battery up to 2.75 vpc, alternately 12% rate of Ah Capacity up to 2.36 vpc & at 6% rate up to 2.75 vpc, till end of charging. Minimum Ah Input : 5 5.5 times of Ah capacity of Cell/Battery. Approx. duration of initial charging: 75 to 80 hours, if required more.

During regular use the battery should be recharged with compatible Charger for traction batteries. INTERRUPTIONS: The charge may be given continuously or in cycles of not less than 8 hrs charge and not more than 16 hrs rest, until it is completed. ELECTROLYTE LEVEL: The level of electrolyte may fall slightly during the charge. Maintain it throughout the charge by adding acid as used for filling. ADJUSTMENT OF ELECTROLYTE: If at the end of first charge, the specific gravity of the electrolyte exceeds 1.290, withdraw some electrolyte and add battery grade water, continue the charge so that the water and acid are thoroughly mixed. If at the end of first charge, the specific gravity of the electrolyte is below 1.280 after voltage and specific gravities have remain constant for 2 to 3 hrs, withdraw some of the electrolyte and add acid of 1.350 to 1400 specific gravity, continuing the charge meantime. NEVER MAKE AN ADJUSTMENT ON A CELL WHICH DOES NOT GAS ON CHARGE. Final working specific gravity should be 1.285 at 30 deg C. Note: * The correction factor to be applied for variation of specific gravity with temperature. Add 0.007 to the observed reading for every 10 deg C above 30 deg C to obtain the corrected reading at 30 deg C. Subtract 0.007 from the observed reading for every 10 deg C below 30 deg C to obtain the corrected reading at 30 deg C.

REFRESHNING CHARGE PROCEDURE FOR EXIDE India TRACTION BATTERIES 1. Check the Acid-level should be at least above the separator level. 2. Charge at 0.1C5 Amps. for 12 hours minimum or till Specific gravity and Voltage of Pilot cells remain constant over a period of 3 hours. 3. Top-up to the maximum level with 1.260 1.280 gravity acid and continue charging at 0.05C5 Amps. for at least two more hours. 4. Give rest till electrolyte temperature comes down to 35 C before putting into application or conducting discharge test.

INSTRUCTIONS FOR ACID FILLING AND FIRST CHARGING OF GREEN PLATE EXIDE India TRACTION BATTERIES (JAR FORMATION) ACID FILLING INSTRUCTION: Fill the cells with battery grade sulphuric acid of 1.250 +/- 0.005 specific gravity at 30 deg C conforming to the following specifications : Iron ( as Fe ) percent by mass Chlorides ( as Cl ) percent by mass : 0.001 ( Max) : 0.0003 ( Max) Flip top vent plugs are fitted on the cell lids together with basket- type electrolyte level indicators, the lower level corresponding to the minimum height of electrolyte in the cell. The stepped portion of the basket indicated the maximum level of electrolyte. However, the basket is visible only after opening the flip top. After initial filling, acid will soak into the plates and separators, and the level should be restored with more acid to the maximum level after 2 hrs. * Note: If the electrolyte temperature exceeds 55 deg C, please allow it to drop below 42 deg C prior to the commencement of charging. If required, the cooling process should be facilitated by providing suitable fans / water bath. PROCEDURE FOR INITIAL CHARGING: During initial filling & charging, the batteries should be charged using Constant Current charger as per schedule in annexure A. The charging should be continued even after the battery reaches 2.75 volts per cell till no rise of the Voltage and sp. Gravity is observed in the cells and the readings remain constant for consecutive 3 to 4 hourly readings.

The sp. Gravity of all the cells to be adjusted to 1.285 +/- 0.005 (the service gravity), using 1.400 sp. Gravity Battery Grade Sulphuric Acid / Battery Grade Water conforming to the following specifications : ph level : 6.5 7.5 Heavy metals ( as Pb )mg/l Iron & manganese mg/l : 0.1 (max) : 0.1 ( max) Specific electrical conductivity At 25 C in dionic units : 5 ( max ) Minimum Ah inputs should be 7.2 times of the Ah capacity of cell/battery. Maximum temperature permitted during charging is 55 o C. Preferred temperature range during formation is 45-52 o C. *Charging should be continued till a) All cells are gassing freely at top of charge voltage 2.75 volts per cell at finished rate. b) No rise of voltage for 3 to 4 consecutive hourly readings after 2.75 volts per cell (vpc). c) No rise of Sp.Gr. for 3 to 4 consecutive hourly readings after 2.75 volts per cell (vpc). d) Minimum Ah input (7.2 times of Ah capacity of cell/battery) is given. Theoretical inputs: Filling in Acid Sp. Gravity : 1.250 +/- 0.005 at 30 deg C. Pickling time : 2 hrs. During regular use the battery should be recharged with compatible traction battery Charger. INTERRUPTIONS: The charge should be given continuously. A maximum interruption of 2 hrs due to unforeseen parameters during first 60 hrs of charging may be allowed. Any interruption should be avoided at discharge step.

ELECTROLYTE LEVEL: The level of electrolyte may fall slightly during the charge. Maintain it throughout the charge by adding acid as used for filling. ADJUSTMENT OF ELECTROLYTE: If at the end of first charge, the specific gravity of the electrolyte exceeds 1.290, withdraw some electrolyte and add battery grade water, continue the charge so that the water and acid are thoroughly mixed. If at the end of first charge, the specific gravity of the electrolyte is below 1.280 after voltage and specific gravities have remain constant for 2 to 3 hrs, withdraw some of the electrolyte and add acid of 1.350 to 1400 specific gravity, continuing the charge meantime. NEVER MAKE AN ADJUSTMENT ON A CELL WHICH DOES NOT GAS ON CHARGE. Final working specific gravity should be 1.285 at 30 deg C. Note: * The correction factor to be applied for variation of specific gravity with temperature. Add 0.007 to the observed reading for every 10 deg C above 30 deg C to obtain the corrected reading at 30 deg C. Subtract 0.007 from the observed reading for every 10 deg C below 30 deg C to obtain the corrected reading at 30 deg C.