COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

Similar documents
COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

Effective November 2016 Supersedes September 1998 (S )

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

Effective June 2016 New Issue

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

Effective November 2016 Supersedes February 2012 (S )

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

Effective March 2015 Supersedes S August 2012

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

High-voltage primary bushings installation instructions

Type NR oil switch installation and operation instructions

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

COOPER POWER SERIES. Electronic control battery testing, charging, and replacement instructions. Reclosers MN280074EN

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

Effective May 2017 Supersedes January 2003 (S )

Effective May 2017 Supersedes December 2004 (S )

COOPER POWER SERIES. KA146W5 single pole-mounting hanger; KA146W2 tank lifting windlass assembly and installation instructions. Reclosers MN280039EN

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions. Voltage Regulators MN225075EN

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

Figure 1. Kearney Type HX cutout.

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

COOPER POWER SERIES. Metal-enclosed capacitor banks installation instructions. Power Capacitors MN230010EN

COOPER POWER SERIES. Types D and DV recloser installation instructions. Reclosers MN280030EN

S Voltage Regulators GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Standards

COOPER POWER SERIES. Metal-enclosed, pad-mounted capacitor banks installation instructions. Power Capacitors MN230009EN

COOPER POWER SERIES. Manually-Operated M-Force Switch Installation and Operation Instructions. Switches and Disconnects MN008003EN

COOPER POWER SERIES. Externally fused block banks installation instructions. Capacitors MN230004EN

Factory Authorized Mechanism Enhancement (FAME)

COOPER POWER SERIES. Instructions for oil-filled, single-phase overhead distribution transformers. Distribution Transformers MN201003EN

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.

CCP2-FLR1-21_ flange-rod operating mechanism

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

Two-way cable interlock kit for Magnum fixed circuit breakers

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage

This Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers.

UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout

Two-way cable interlock kit for Magnum drawout circuit breakers

K-Limiter high ampere Companion II fuse

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to:

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage.

3-way multi-family drawout cable interlock kit - type 32 - RF

CMU medium voltage power fuses

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

Edison modular fuse, vault application products

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

ELF -LR current-limiting fuse

100 A externally operated one-, twoand three-phase tap-changer switch

Direct-connected capacitor fuse

25 kv class fused loadbreak elbow connector

O & M Manual for the EATON Generator Ready Loadcenter

COOPER POWER SERIES. Types VWE, VWVE27, VWVE38X, WE, WVE27, and WVE38X; threephase electronically controlled; installation and operation instructions

Instruction Booklet IB E. Contents

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

Two-position sidewall (horizontal) and cover (vertical) mounted loadbreak switches

X-Limiter full-range current-limiting fuse

COOPER POWER SERIES. Type MOST Fluid-Insulated Switchgear; Installation, Operation, and Maintenance Instructions

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

ELB ELB

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Technical specifications for 10 ka, heavy-duty class 1, 3 kv and 3.33 kv VariSTAR MOV disks

Vacuum Circuit Breaker (Vehicle)

Technical specifications for 10 ka, heavy-duty class 1, 4.5 kv and 5 kv VariSTAR MOV disks

600 A 35 kv class separable splices

SPX9000 FR10 FR12 Adjustable Frequency Drives

GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004

Magnum Breaker Remote Racking Device (MRR1000)

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description

Type DTU De-energized Tap Changer Application, Installation & Selection Guide. IL A Instruction Leaflet Page 1 September, 2003

600 A 15 and 25 kv class Cleer grounding elbow

KFE10010-E. Reclosers. Contents. Type KFVE and KFVME (27kV) Bus Bar Kit KRK710-1 Installation Instructions. Cooper Power Systems

COOPER POWER SERIES. RVAC Fluid-insulated Vacuum Switchgear; Installation, Operation, and Maintenance Instructions. Switchgear MN285005EN

600 A 25 kv class BT-TAP deadbreak connector

II DISTRIBUTION & SUBSTATION TYPE C

Transcription:

Capacitors MN230005EN Effective November 2016 Supersedes November 2001 (S230-30-3) Expulsion fuse installation instructions COOPER POWER SERIES

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. i

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... I SAFETY FOR LIFE... III SAFETY INFORMATION... III Safety instructions... iii EXPULSION FUSE OPERATION... 1 HORIZONTAL FUSE INSTALLATION.... 1 1. Receiving instructions...1 2. Ejector spring alignment...2 3. Fuse leader assembly...2 VERTICAL FUSE INSTALLATION.... 3 1. Receiving instructions...3 2. Ejector spring alignment...3 3. Fuse leader assembly...4 FUSE TUBE RATINGS... 5 Fuse tube design features...5 ii

! SAFETY FOR LIFE Safety for life Eaton s Cooper Power series products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high-voltage lines and equipment and support our Safety For Life mission.! SAFETY FOR LIFE Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians, who are familiar with this equipment should install, operate and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high- and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a potentially hazardous situation which, if not avoided, could result In death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with high voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment. WARNING Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury and equipment damage. WARNING Power distribution equipment must be selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain this equipment can result in death, severe personal injury, and equipment damage. iii

Expulsion fuse operation An expulsion fusing system as used for protecting capacitors consists of three components which include the fuse tube, the fuse link, and the ejector spring (Figure 1). The proper operation of a fuse is dependent upon these components working in close harmony with each other. Proper assembly of the fusing system is critical to the successful operation of the fusing system whereas incorrect installation may result in severe damage to the fuses, the capacitors, and/or capacitor bank. As the amount of gas generation is dependent upon the amount of current being interrupted, the force with which the leader is ejected from the tube will also vary. Under high energy conditions, the sole purpose of the ejector spring is to control the motion of the ejected leader once it is in free air. For low energy interruptions, the ejector spring also serves to assist in the process of lengthening the arc and becomes an active component in the interruption mechanism of the fusing system. Each individual capacitor fuse has a specific rating and has been selected based upon the voltage and kvar rating of the capacitor. See Fuse Tube Ratings (Table 1) for specific information regarding the interrupting ratings of the fuse tubes. The catalog number of the replacement fuse link, fuse tube, and fuse ejector spring is listed on the index sheet of the capacitor bank instruction manual. Horizontal fuse installation Figure 1. Expulsion fusing system components When an excessive amount of current flows through the fuse link, the fusible portion of the link melts. This creates an arc where the fuse element was present which maintains a current path through the fuse assembly. Figure 3. Figure 2. Initial operation of fuse link The fuse tube is lined with a material which gases freely when heated by the arc. This gas vents through the open end of the fuse tube and forces the severed portion of the fuse link s leader wire towards the end of the tube. Both of these actions assist in the process of arc quenching by lengthening the arc and extinguishing it (Figure 2). Successful interruption of the circuit will occur when sufficient dielectric strength exists within the gap to prevent re-establishment of the arc once the voltage across the gap begins to build. This interruption occurs either at a system frequency (50 Hz or 60 Hz) current zero or a higher frequency current zero created by the inductance and capacitance of the individual capacitor block. 1. Receiving instructions Figure 3 illustrates the method used to assemble the fuse prior to shipment of the capacitor bank. The fuse holder, fuse tube, and fuse link are mounted to the fuse bus with the lead wire of the fuse link taped to the fuse tube. This method of shipping prevents damage to the fuse assembly during shipment. Figure 4. 1

The ejector spring is mounted to the capacitor terminal, and a heavy hex nut is provided to tighten the ejector spring in place. A clamp, lock washer, and second nut are provided to attach the fuse link lead wire to the capacitor terminal. Figure 4 illustrates the hardware arrangement onto the capacitor terminal. NNote: If the capacitors, fuses and ejector springs are shipped separately to be installed by the customer, all hardware will be included to properly assemble on the capacitor terminal. C. Thread the fuse link lead wire through the eye of the ejector spring as shown in Figure 6. It is important the lead wire be routed over the top of the eye then back through the eye as displayed. Pull the eye of the ejector spring to a point where it touches (or is directly beneath) the end of the fuse tube. 2. Ejector spring alignment The ejector spring and heavy hex nut should be placed on the capacitor terminal in the order shown in Figure 4. Align the ejector spring horizontally and vertically to achieve two objectives: A. The ejector spring must move in a true vertical plane as it rotates from its resting position to its working position at the end of the fuse tube. B. When the ejector spring is rotated up to its working position at the end of the fuse tube, there should be no more than one inch (25.4 mm) from the top of the ejector spring eye to the edge of the fuse tube. After proper alignment, tighten the inner nut using a torque of 16 to 19 ft-lb (21.7 to 25.8 N-m). 3. Fuse leader assembly A. Carefully remove the tape from the fuse tube and the leader wire used to secure the wire during shipment. B. Straighten the fuse link leader such that there are no entanglements (Figure 5). Figure 6. NNote: D. Wrap the end of the fuse link lead wire around the threaded stud of the capacitor terminal (between the heavy hex nut and the clamp) (Figure 7). Place the lock washer on top of the clamp taking care to assure the split in the washer is not aligned with the open end of the clamp. Tighten the outer nut using a torque of 16 to 19 ft-lb (21.7 to 25.8 N-m). An additional check of the torque may be required after several days. The fuse leader wire may flow from the compressed area requiring additional tightening of the outer nut to the proper torque value. Figure 7. Figure 5. 2

E. Trim the excess fuse link lead wire (Figure 8). Approximately 3/8 inch (1 centimeter) of lead wire should extend beyond the clamp assembly. 1. Receiving instructions Figure 11 illustrates the method used to assemble the fuse prior to shipment of the capacitor bank. The fuse holder, fuse tube, and fuse link are mounted to the fuse bus with the lead wire of the fuse link taped to the fuse tube. This method of shipping prevents damage to the fuse assembly during shipment. Figure 8. F. Check the fuse ejector spring for proper working position and alignment. Figure 12. Figure 9. Figure 10. Vertical fuse installation Figure 11. The ejector spring is mounted to the capacitor terminal, and a heavy hex nut is provided to tighten the ejector spring in place. A clamp, lock washer, and second nut are provided to attach the fuse link lead wire to the capacitor terminal. Figure 12 illustrates the hardware arrangement onto the capacitor terminal. NNote: If the capacitors, fuses and ejector springs are shipped separately to be installed by the customer, all hardware will be included to properly assemble on the capacitor terminal. 2. Ejector spring alignment The ejector spring and heavy hex nut should be placed on the capacitor terminal in the order shown in Figure 12. Align the ejector spring horizontally and vertically to achieve two objectives: A. The ejector spring must move in a true vertical plane as it rotates from its resting position to its working position at the end of the fuse tube. B. When the ejector spring is rotated up to its working position at the end of the fuse tube, there should be no more than one inch (25.4 mm) from the top of the ejector spring eye to the edge of the fuse tube. After proper alignment, tighten the inner nut using a torque of 16 to 19 ft-lb (21.7 to 25.8 N-m). 3

3. Fuse leader assembly A. Carefully remove the tape from the fuse tube and leader wire used to secure the wire during shipment. B. Straighten the fuse link leader such that there are no entanglements (Figure 13). NNote: An additional check of the torque may be required after several days. The fuse leader wire may flow from the compressed area requiring additional tightening of the outer nut to the proper torque value. Figure 15. Figure 13. C. Thread the fuse link lead wire through the eye of the ejector spring as shown in Figure 14. It is important the lead wire be routed over the top of the eye then back through the eye as displayed. Pull the eye of the ejector spring to a point where it touches (or is directly beneath) the end of the fuse tube. E. Trim the excess fuse link lead wire (Figure 16). Approximately 3/8 inch (1 centimeter) of lead wire should extend beyond the clamp assembly. Figure 16. F. Check the fuse ejector spring for proper working position and alignment. Figure 14. D. Wrap the end of the fuse link lead wire around the threaded stud of the capacitor terminal (between the heavy hex nut and the clamp) (Figure 15). Place the lock washer on top of the clamp taking care to assure the split in the washer is not aligned with the open end of the clamp. Tighten the outer nut using a torque of 16 to 19 ft-lb (21.7 to 25.8 N-m). Figure 17. Figure 18. 4

Fuse tube ratings Fuse tube design features The fuse tube is constructed of bone-grade fiber overwrapped with epoxy-bonded filament-wound fiberglass or grade XX phenolic. The upper contact, depending on the rating, is either aluminum or tin-plated bronze. The fuseholder accepts ANSI standard removable or non-removable buttonhead fuse links. The function of the fuse tube is to confine the arc and produce arc-quenching gases which are expelled from the end of the tube. Voltage stress across the fuse tube is eliminated by the gap between the end of the tube and the capacitor terminal. There is no possibility of tracking and eventual flashover, even after exposure to weather and contaminants. When the spring ejects the leader, positive indication of a blown fuse can also be easily detected from a distance. Table 1. Fuse tube ratings Fuse voltage rating (kv) Capacitor mounting configuration (H or V)* Current rating (A) Power frequency interrupting rating (A) Symmetrical Asymmetrical Maximum parallelconnected energy (kj)** Catalog number 8.7 H 50 3600 5000 20 FN10B4 8.7 H 80 3600 5000 30 FN20B2 8.7 V 50 3600 5000 20 FN10B4 8.7 V 80 3600 5000 30 FN20B2 15.5 H 50 3600 5000 20 FN11B2 15.5 H 80 3600 5000 30 FN20B2 15.5 V 50 3600 5000 20 FN11B2 15.5 V 80 3600 5000 30 FN20B2 23.0 H 50 1800 2500 20 FN11B2 23.0 H 80 1800 2500 30 FN11B3 23.0 V 50 1800 2500 20 FN11B2 23.0 V 80 1800 2500 30 FN11B3 *H = Horizontal, V = Vertical **When used with the recommended unit spacing per IEEE Std 18-2012 and Eaton s Cooper Power series type SD, HD or XD capacitor units. 5

This page intentionally left blank. 6

This page intentionally left blank. 7

Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No. MN230005EN November 2016 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton's Cooper Power series product information call 1-877-277-4636 or visit: eaton.com/cooperpowerseries.