Ecoglo HYU Hybrid Photoluminescent Exit Signs: Compliance with NZBC F8/AS1

Similar documents
EMERGENCY LIGHTING TESTING

DALI Emergency LED Driver - 350/700/1000mA Constant Current

650mA Phase Dimmable LED Driver

BALT5-800 LOW-PROFILE FLUORESCENT EMERGENCY BALLAST

DALI 650mA LED Driver

1000mA - 650mA Phase Dimmable LED Driver

UL AND CODE COMPLIANCE

LED emergency exit signage from Channel Safety Systems

MAINTENANCE AND TESTING OF PORTABLE ELECTRICAL EQUIPMENT, RCDS AND TOOLS CS-OHS-33

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation Edition DRAFT

3. Please ensure the electricity connections conform to the National Electrical Code and local regulations if applicable.

BAL1400 FLUORESCENT EMERGENCY BALLAST Specification-grade One or two-lamp emergency illumination

A brief guide for identification of non-compliant construction machinery. Is this. Compactor / Roller compliant with European legislation?

Approval mark PL HCR 1a A

Installation Instructions

ARAI Date of hosting on website: 27 th October 2015 Last date for comments: 27 th November 2015

SubstiTUBE Value EM T8 (AUS Fighter Tube) ST8V-0.6M ST8V-1.2M ST8V-1.5M

KT-EMRG-1400-SL /B. 3. Please ensure the electricity connections conform to the National Electrical Code and local regulations if applicable.

Emergency lighting units EM converterled. EM converterled ST 90 V SELFTEST series

Emergency lighting units EM converterled. EM converterled ST 50 V SELFTEST series

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

REFERENCE REV CP_TSSPEC_016 1 TITLE SPECIFICATION FOR DATE: NOVEMBER 2010 LIGHTING TABLE OF CONTENTS Page FOREWORD INTRODUCTION

This standard covers the requirements of luminaires for emergency lighting chains. This standard covers safety and performance requirements.

2. 0 Test Records - All records of analysis and tests shall be kept in suitable forms approved by the Bureau of Indian Standards.

UWA Electrical Safety Procedure

GL1200T Cut & Seal. (GL1200 Seal only)

MANUFACTURED IN THE UK

2D products are warranted for one year, the expected life of the ballast and/or Emergency module is 5 years

Vehicles, Boats and Other Devices Propelled by an Internal Combustion Engine, Electrical Means or Both

AS/NZS :2016. Grid connection of energy systems via inverters AS/NZS :2016. Part 1: Installation requirements

Particular requirements (apply as applicable to luminaire type) Emergency Escape Lighting and Exit Signs for Buildings

Proposal for amendments to Regulations Nos. 19, 48 and 98.

Doc Ref: WD024/2/11/12 Fern-Howard Ltd. 2 Newman Lane, Alton, Hampshire, GU34 2QR. Reg. No

Emergency lighting units EM LED Light Engines

BAL3000 FLUORESCENT EMERGENCY BALLAST Specification-grade: Up to 3500 lumens One or two-lamp emergency illumination

LED AC DRIVERLESS FLOODLIGHTS WITH PIR FOR MODEL: FLAC10BPIR, FLAC20BPIR, FLAC30BPIR & FLAC50BPIR

DRAFT. Installation Instructions 1693 EV-LEDFIRE-III 1694 EV-LEDFIRE-III-PRO 1697 EV-LEDFIRE-III-PRO-B 1695 EV-LEDFIRE-III-ULT CONTENTS 1.

EMERGENCY ONE-LED TM SOLO TM NON MAINTAINED LED LAMP AND DRIVER KIT

Economic and Social Council

WELLINGTON, NEW ZEALAND. PURSUANT to section 152 of the Land Transport Act Land Transport Rule: Vehicle Standards Compliance 2002

3-Year Limited Warranty. See the Users Manual for the full warranty.

LED Emergency Luminaires

Last updated 13/02/2018 v01 Parking Bylaw 2017 Parking Bylaw 2017

DALI Switch Mechanisms DCDAL31 Series Installation Instructions

Environmental Management System

MANUFACTURED IN THE UK

2-Year Limited Warranty. See the Users Manual for the full warranty.

Airworthiness Physical Survey Report

3. Operating instructions: Minor 200

Certificate of Acceptance

COMHAIRLE CHONTAE NA GAILLIMHE GALWAY COUNTY COUNCIL

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY

Emergency lighting units EM converterled

PROCEDURE. Operative Date: 22/12/2016 Department: HSEC. Revision: Author: D Steel CONTENTS

EXI LED INTRODUCTION APPLICATION PRODUCT SPECIFICATION

Emergency lighting units EM converterled

Emergency lighting units EM LED Light Engines. EM ready2apply BASIC 1 2 W EM ready2apply

8-6 Heavy vehicle fifth wheel or ball coupling (for towing a semi-trailer)

CMP294: National Grid Legal Separation changes to CUSC Section 14. CUSC Modification Proposal Form

9120 EBCU Battery Charger MODELS: 9120EBCU96V 9120EBCU240V

Parking Control Bylaw 2014

Schedule No.: 13. Diesel Engine Driven Monoset Pumps for Agricultural Purposes

Amendment to Schedule 15 for Ballasts Electromagnetic & Electronic ballasts

QUALITY REQUIREMENTS FOR JUST IN TIME SERVICE PROVIDER (JIT S.P.) PROGRAM: ALL

Emergency lighting units EM powerled

TOPAS 2130A (Draft v3)

TECHNICAL COMMITTEE FOR STANDARDS AND PROCEDURES FOR TRAFFIC CONTROL AND TRAFFIC CONTROL EQUIPMENT (TCSP)

CUSC Modification Proposal Form CMP270

E/ECE/324/Rev.2/Add.102/Rev.1 E/ECE/TRANS/505/Rev.2/Add.102/Rev.1

WELLINGTON, NEW ZEALAND. PURSUANT to sections 152 and 155(a) and (b) of the Land Transport Act 1998

Report No.: Name of Ship: Plans referred during Initial Survey:

Electricity Safety (Electrical Installations) Regulation 2005

E/ECE/324/Add.5/Rev.6/Amend.2 E/ECE/TRANS/505/Add.5/Rev.6/Amend.2

EdgeLED TM Range. Installation and Operating Instructions EdgeLED TM E1, E7, S1 and S7 Recessed Ceiling Luminaires

Australian Standard. Uninterruptible power systems (UPS) Part 1.1: General and safety requirements for UPS used in operator access areas

MN/DOT Specification Light Emitting Diode (LED) Luminaire 03/20/2012

Electric Vehicle Charging Safety Guidelines Part 1: Safety Fundamentals Edition DRAFT

NCC CODE OF PRACTICE 502

Notice to all Users of the Weigh Northland Gantries

NOTICE 872 OF 2013 INDEPENDENT COMMUNICATIONS AUTHORITY OF SOUTH AFRICA

Installation & Maintenance Manual

Emergency lighting units EM converterled

Economic and Social Council

SPECIFICATION SHEET ORION ROAD LANTERN. IP66 RATED CRI. 230v /50hz

Switching DC Power Supply

MODVAR Low voltage reactive power compensation modules Installation manual

E/ECE/324/Add.3/Rev.3 E/ECE/TRANS/505/Add.3/Rev.3

Test specification : EN71 - Part1: Mechanical and Physical Properties Excluding Clause 7.1 Excluding Labeling Requirement of Clause

NCC Leisure Battery Verification Scheme. Leisure Accommodation Vehicles

2. All electrical items covered by Portable Appliance Testing must be tested on a regular basis by a certified competent person.

LM-100 LM-120. Light Meters. Users Manual. For detailed specifications and ordering info go to

Installation and Operation Manual. LD LED Dimmer

NPS/003/002 Technical Specification for 30V Distribution Tripping Battery and Charger Systems

Emergency lighting units EM converterled. EM converterled BASIC 200 V BASIC series

INTERNATIONAL STANDARD

TITLE 165. CORPORATION COMMISSION CHAPTER 16. ANTIFREEZE EFFECTIVE SEPTEMBER 11, 2017

Gisborne District Traffic and Parking Bylaw DOCS_n144966

80 Series V Digital Multimeter Safety Information

Emergency lighting units PC COMBO

Transcription:

Ecoglo International Ltd 77 Kingsley Street, Christchurch New Zealand +64 3 348 3781 mark.watson@ecoglo.com www.ecoglo.co.nz 7 th September 2017 Ecoglo HYU Hybrid Photoluminescent Exit Signs: Compliance with NZBC F8/AS1 Ecoglo HYU hybrid exit signs are photoluminescent exit signs that are charged with an integrated light source. The light source ensures the signs are sufficiently charged at all times to meet the requirements of the New Zealand Building Code (NZBC) Clause F8/AS1. The following information provides a technical explanation of how Ecoglo hybrid signs comply with NZBC F8/AS1. As with Ecoglo S20 photoluminescent exit signs (S20 signs), the physical format of Ecoglo HYU hybrid photoluminescent exit signs (hybrid signs) meets all the relevant requirements of F8/AS1. Where hybrid signs differ from S20 signs is in the way the signs are charged. 1. NZBC F8/AS1 Requirements The relevant paragraph of NZBC Clause F8/AS1 is detailed below: 4.5.4 Photoluminescent signs Photoluminescent signs shall, in the event of a power failure, continue to provide a minimum luminance of 30 mcd/m 2 for the duration prescribed in NZBC Clause F6 whenever the building is occupied. Photoluminescent signs shall be maintained in a charged state such that in the event of an emergency when the building is occupied, the exit signs will be at full operational charge and will continue to operate at the prescribed level and for the prescribed time (refer to NZBC Clause F6). Illumination for charging the photoluminescent signage shall be not less than 100 lux and suitable for charging photoluminescent material.

Page 2 of 5 Key terms in F8/AS1 4.5.4 Minimum luminance of 30mcd/m 2 for the duration Luminance: NZBC Clause F6 requires luminance at 30mcd/m 2 for a minimum period of: Duration: 30 minutes duration for Risk Group C buildings; and 90 minutes duration for Risk Group B buildings. Ecoglo runs an in-house luminance test facility, which is validated by comparative testing with independent test laboratories. The in-house test facility enables the efficient testing of a wide range of photoluminescent materials. Ecoglo has carried out over 3000 in-house tests since 2003. The data below and chart (see Appendix) is extracted from Ecoglo records for the following in house test: Test ID Date Test Charging Lamp Illuminance on Charging Sample Type Sample Time HO63 11 May 2017 HYU1-RM Integral LEDs N/A 60 minutes F6 Risk Group C buildings: The test results revealed that the luminance at 30 minutes is 290mcd/m 2, clearly well above the 30mcd/m 2 required. At this level, even if the integrated light source were to lose as much as 50% of its initial brightness during its lifetime, there would still be sufficient luminance. F6 Risk Group B buildings: The test results revealed that the luminance at 90 minutes is 87mcd/m 2, clearly well above the 30mcd/m 2 required. At this level, even if the integrated light source were to lose as much as 50% of its initial brightness during its lifetime, there would still be sufficient luminance. Signs shall be maintained in a charged state During installation hybrid signs are connected to a permanent electrical supply to ensure that they will be maintained in a charged state. A suitably qualified electrical tradesperson is required to connect the signs to the lighting circuit supplying general lighting in the area concerned. The signs shall be powered through one circuit breaker per building and the breaker shall be labeled Emergency Lighting Supply Do not isolate.

Page 3 of 5 Charging illumination shall be not less than 100 lux Ecoglo has recorded in-house measurements to confirm the charging illumination. The luminance of Ecoglo hybrid signs when connected to an electrical supply is 150cd/m 2. Ecoglo photoluminescent material is typically 70% reflective during charging/ charged states, so using the following formula: Illuminance (lux) = luminance (cd/m 2 ) x Pi/reflectivity the charging illumination is shown to be 150 x Pi/70% = 670 lux. The result is clearly well above the required 100 lux. At this level, even if the integrated light source were to lose 50% of its initial brightness during its lifetime, there would still be sufficient charging illumination. 2. Compliance with Other Relevant Standards Compliance with AS2293 Standards The AS2293 standards do not cover photoluminescent exit signs, and are therefore not applicable to Ecoglo hybrid exit signs. Electrical Safety Testing The Ecoglo Supplier Declaration of Conformance confirms that Ecoglo hybrid signs comply with the relevant standards: AS/NZS 60598.1 Luminaires Part 1: General Requirements and Tests; and AS/NZS IEC 61347 Lamp Controlgear Part 1 and Part 2.13. Electomagnetic Compatibility Testing The Ecoglo Supplier Declaration of Conformance confirms that Ecoglo hybrid signs comply with the relevant standard: AS/NZS CISPR 15 Limits and Methods of Measurement of Radio Disturbance Characteristics of Electrical Lighting and Similar Equipment. 3. Ongoing Inspection and Maintenance The Ecoglo document Technical Justification for Ecoglo Photoluminescent Exit Signs v16.2 (available under Technical at www.ecoglo.co.nz) shows that ongoing verification of the performance of Ecoglo photoluminescent material is not necessary. Discharge testing as specified in AS/NZS2293.2 is required for battery back-up electrical exit sign systems because these systems have a relatively high frequency of fault/failure for a life safety building component. Ecoglo hybrid signs are intrinsically fail-safe and are electronically much simpler than battery back-up exit signs.

Page 4 of 5 The photoluminescent material will continue to provide useful glow for many hours after failure of the main lighting system, and requires no more than 5 minutes recharge after an extended loss of power to be fully operational again. It also still works as a standard photoluminescent exit sign even if the integrated light source fails. Nonetheless, hybrid signs do have electrical components, and all electrical components are subject to failure. Therefore, regular inspection is warranted to ensure that the integrated charging light is still operating. The following specified system information, and inspection and maintenance procedures are appropriate to the reasonably expected frequency of fault/failure of Ecoglo hybrid signs. They are recommended to be part of the Compliance Schedule for the building: 4. Specified System SS15/4 Exit Signs (only required if any of Specified Systems 1-6, 9, or 13 are required in the building) System Description Photoluminescent exit signage. Make Ecoglo Product Code and Quantity See drawing(s) titled XXXX, attached. Location To identify escape routes as per the Fire Report. Relevant Performance Standard NZBC Clause F8.3.1 and F8.3.3 as they relate to exit signage. Relevant Inspection and Maintenance Standard Photoluminescent Lighting Council Standard PLCS101 Photoluminescent Exit Signs, Part C: Inspection and Maintenance. The relevant requirements are detailed below. Inspection and Maintenance Procedures Planned preventative maintenance and responsive maintenance should be carried out in accordance with the corresponding table below to ensure signs remain correctly positioned and legible. Action All signs are still configured as at installation and there is no material damage to any of these products. All signs are clean from general dust build up and any other specific obscuring deposits. All signs are clearly visible and have not been covered up. All Ecoglo hybrid signs are still illuminated. Complete

Page 5 of 5 Monthly: Inspect the system, and carry out any maintenance necessary to confirm each statement in the table. Annually: Inspect the system, to confirm each statement in the table. Immediate Corrective Action Signs shall be replaced before they become illegible, and shall be replaced immediately should they be missing. Defects in illuminated signs shall be fixed immediately as they are apparent. Reporting Procedure All inspection and maintenance records of the above work are to be held on site in a durable, hard-bound log book, and are to be available to any authorised inspection agency. Responsibilities Monthly inspections and maintenance are to be carried out by the owner or their appointed agent. Annual inspection is to be carried out by an Independent Qualified Person. Inspection and maintenance records are to be maintained by the owner or their appointed agent. Mark Watson BE, MIPENZ, CPEng, IntPE(NZ), RPEQ (Fire, Mechanical) Technical Manager Ecoglo International Ltd.

Appendix Time (minutes) 10 100 1000 10 Luminance (mcd/m2) 100 1000 Ecoglo HYU1-RM Hybrid exit sign Minutes 10 20 30 60 90 120 11-May-17 h063 HYU1-RM mcd/m2 785 441 290 136.0 87.0 63.0