Why is the Breaker Tripping?

Similar documents
B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE

Beware of Ghost Voltage

Overcurrent protection

3 Phase Voltage Imbalance

Miniature circuit breaker Application guide

SECTION 4 ELECTRIC MOTORS UNIT 20 TROUBLESHOOTING ELECTRIC MOTORS UNIT OBJECTIVES 3/21/2012

SECTION 4 ELECTRIC MOTORS UNIT 20 TROUBLESHOOTING ELECTRIC MOTORS

GET GROUNDED. Renewable Energy System Grounding Basics

MAGNETIC MOTOR STARTERS

I m going to come out and say it so you keep reading. What you were taught about hard start kits decreasing inrush amperage is wrong.

CSDA Best Practice. Hi-Cycle Concrete Cutting Equipment. Effective Date: Oct 1, 2010 Revised Date:

Electricity MR. BANKS 8 TH GRADE SCIENCE

Petrochemical processing Ship Yards Oil Fields Irrigation

Full file at

C.E. Niehoff & Co. N1601, N1602, N1603, and N1604 Alternator Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values

Electrical Equipment and Terminology

Troubleshooting Guide for Limoss Systems

High Frequency SineWave Guardian TM

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES UNIT OBJECTIVES 3/21/2012

C.E. Niehoff & Co. C653/C653A and C625 Alternators Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values

Installation and Construction Notes for EVSE4

Design Standards NEMA

Electrical Motor Controls Chapter 4 (Fourth Edition) Chapter 2 (Fifth Edition)

DC Series Motors by Thomas E. Kissell Industrial Electronics, Second Edition, Prentice Hall PTR

Building Operator Certification Level I

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

Electrical Safety. Introduction

Circuit Concepts (Residential)

Technical Information and Diagnostic Guide

C802/C802D/C802TD/C820 Alternators Troubleshooting Guide

Could be a damaged Rain Tracker interface module. See Bypassing the Rain Tracker on the next page.

A/C Generator Systems

Wiring diagrams on page 29 are for reference only. For detailed vehicle wiring refer to Navistar documents.

INSTALLATION INSTRUCTIONS

Modulating Furnace Information. Warning on Meter Setting - Read First!

ECET Distribution System Protection. Overcurrent Protection

CHARGING SYSTEM 8C - 1 CHARGING SYSTEM CONTENTS

Electric Motor Controls BOMA Pre-Quiz

Electricity. Teacher/Parent Notes.

CHARGING SYSTEM 8C - 1 CHARGING SYSTEM CONTENTS

Troubleshooting Guide for Okin Systems

Interpreting the Images: Data Errors in Thermography Electrical & Roofs

Service Manual. 9. Maintenance. 9.1 Precautions before Maintenance. discharge resistance or plug of soldering iron. Installation and Maintenance

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

EDITOR'S NOTE: This article replaces "Use PGM FI Data List to Help Troubleshoot Inoperative A/C," issued in June 2012.

Chapter 4 Utility Systems Electrical

Transformer Protection

Adapted from presentation developed by Scott Fausneaucht

reflect energy: the ability to do work

Charging Systems. ATASA 5 th. ATASA 5 TH Study Guide Chapter 19 Pages Charging Systems 42 Points. Please Read The Summary

PREVIEW ONLY. Course 106 INSTRUCTOR GUIDE. HVAC Systems Introduction and Overview. Module 1: Overview of Rail Car HVAC and General Safety Procedures

SECOND GENERATION Use this guide with unit serial number prefix beginning with BWF using Terra Power separator.

Electrical Systems. Introduction

Fault Finding. Standard/Fundamental Faults

2015 EDITION SUBMERSIBLE MOTORS AIM MANUAL. APPLICATION INSTALLATION MAINTENANCE 60 Hz, Single-Phase and Three-Phase Motors. franklinwater.

ADVANCED PID TROUBLESHOOTING

DC motor theory. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

OVERLOAD PROTECTION. All electrical circuits must have some means of protecting against overload.

SHIFNOID WIRING DIAGRAM FOR a B&M PRO RATCHET with SN5070 SOLENOID KIT


Electric Circuits. Lab. FCJJ 16 - Solar Hydrogen Science Kit. Goals. Background

Electrical Safety. Electrical Safety Webinar. Electrical. Printing Industries Alliance Printing Industries Alliance 1

Electrical Failure Investigations

Subject Underhood G System Error Codes and Symptoms System or Parts affected

GENERAL <ELECTRICAL>

GENERAL <ELECTRICAL>

INSTALL CIRCUIT PROTECTIVE DEVICES

Charles Sullivan, Associate Professor, Thayer School of Engineering at Dartmouth

Physics Work with your neighbor. Ask me for help if you re stuck. Don t hesistate to compare notes with nearby groups.

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton


Electromagnetic Industries LLP

UNIT 3: GENErAL ELECTriCAL SySTEM DiAGNOSiS

Electrical Protection

Power systems Protection course

Dry Type Distribution Transformers

Welcome to the SEI presentation on the basics of electricity

ELECTRICAL. 60 Minutes

Electrical Motor Controls (Fourth Edition)

Electronic Products ELECTRONIC MAINTENANCE

Go Power! Manual. GP-1750HD Inverter GP-2500 Inverter

Understanding RV Electrical Hazards. Do you really want to plug in here?

Basic Electronics, Reliable Wiring, and Mitigating ESD in FTC Robots FTC Kick-Off

Third Generation NITE Phoenix

Practical Thermography for Mechanical Applications Pub ITC 110 H Infrared Training Center

GFCI-AFCI FAQ. Where are AFCIs and GFCIs required?

Boardworks Ltd Mains Electricity

1333 (SERIES B & C) TROUBLESHOOTING GUIDE

Pretest Module 29 High Voltage Unit 1

An average of one worker is electrocuted on the job every day There are four main types of electrical injuries:

Series 1000 and Figure NOTE: The top terminals are showing normally closed at rest and the middle terminals are normally

Pure Sine Wave Inverter GP-HS1500. Owner s Manual

About this Troubleshooting Document

V 2.0 DC TO AC POWER INVERTER PWRINV500012W PWRINV500024W PWRINV500036W PWRINV500048W. Instruction Manual

Eastman Chemical Company Motor Analysis Stepping out of the Box

CALTRAP INSTALLATION AND OPERATIONS MANUAL

4 Electric Circuits. TAKE A LOOK 2. Identify Below each switch, label the circuit as a closed circuit or an open circuit.

UBW Family UL489 Molded Case Circuit Breakers

MGL Avionics AvioGuard. Fault protected, wide input range, isolated, DC to DC converter for avionics applications

Transcription:

Why is the Breaker Tripping? Breakers are designed to trip anytime the circuit draws a current above the rating for a period of time. The time the breaker takes to trip is a function of how high the circuit amperage in comparison to the breaker rating. The higher the amperage above the rating the faster the breaker will trip Breakers can accomplish this either thermally, by tripping on increased heat or inductively, by tripping on increased magnetic field when amperage increases. The majority of residential circuit breakers are thermal which means they are more prone to trip during high ambient temperature than during low ambient temperature. This is one factor in why you will receive more nuisance or intermittent breaker tripping calls on a hot Summer day. Many times breakers get replaced just for doing their job and tripping when they should. There are five common causes of breaker tripping. Improper

circuit design, Overload, ground fault, leg to leg short and breaker issues Improper Circuit Design Improper circuit design can result in an overload condition when the circuit ampacity (amperage capacity) or the circuit breaker size is not properly matched to the load to begin with and / or someone added additional load to the circuit later on. For HVAC equipment this means that the circuit size should be matched to to MCA (Minimum Circuit Ampacity) and the circuit breaker or fuse should be matched to the MOCP (Maximum Overcurrent Protection) If the conductor is smaller than the MCA rating or the breaker is smaller than the MOCP rating It can result in a tripping breaker. You will also see cases where more than one system will be connected to one circuit breaker which is incorrect unless the systems have additional, independent overcurrent protection. These issues usually causes an intermittent trip as it takes time under load to show up depending on the severity of the issue. Overload An overload condition occurs when the loads draw more current / do more more work than they are designed for. Common overload conditions would be a compressors locking up, motor bearings binding, blower belts too tight or sheaves adjusted improperly. And overload generally occurs with inductive (magnetic) loads like motors in cases where the motor is either being placed under a greater torque load than it s designed for or the motor itself is beginning to fail mechanically.

Overload conditions often don t trip a breaker because the motor itself will usually have an overload that specifically protects the motor. This is why when a compressor is locked it is much more likely to shut off on thermal overload than it is to trip a breaker even though it will draw far higher amps than the breaker rating on startup. In these cases the thermal overload is designed to respond quicker than the breaker. If a breaker is tripping because of an overload condition it will usually be after several seconds, minutes or even hours of operation. It will not be instantaneous unless someone installed the wrong breaker or fuse and used an instantaneous trip instead of a typical slow blow or slow acting type. This would be quite rare. Ground Fault A ground fault is a short circuit (no load path) between an energized circuit and equipment ground. A ground fault is the most common cause of instantaneous breaker tripping In most ground fault situations there will be very amperage, very quickly resulting in a breaker that trips right away. Common cases would a shorted motor, such as a shorted compressor or a rubbed out wire. A combination of visual inspection, isolation and ohm

measurement to ground and megaohm / hi-pot tests or hot verification as needed is the best way to diagnose a short to ground (ground fault). Leg to Leg Short (Bucking Phases) When you have two legs of power that have different sine wave patterns such a 240V single phase or 3 phase power you must prevent the legs from coming into contact except through a load. If they do come in contact there will be an enormous transfer of energy and a significant arc. This can happen when two wires rub out, when switch gear becomes compromised or within a motor. Many times techs will look for short circuits from leg to leg or winding to winding in a compressor or a motor without first measuring to ground. This is not a good idea Even when a motor does short winding to winding it is rare

that it just stays shorted. Usually it will ALSO be shorted to ground or it will be open after the arc flash that resulted from the short. Think of a circuit board. Circuit boards short out all the time and the result is a big black spot on the board and nothing works anymore (open). It rarely results in a continued short circuit because the arc from the short blew the connection apart. The reason I encourage caution is because I have seen many junior techs condemn good compressors due to a leg to leg short just because the ohm reading between Run and Common appeared low to them. The only way to know if a single phase compressor is shorted leg to leg with an ohmmeter is to know what the windings should read in the first place. On a three phase motor all three legs should read the same

ohms leg to leg which makes it considerably easier. When you do encounter leg to leg (only) short circuits it is more often on fan motors than on compressors. Breaker Issues Because most breakers trip due to heat, anything that causes the breaker to get hotter than normal can result in tripping. This can be due to a poor connection inside the breaker itself, but often it is due to a poor wire connection on the breaker or a poor connection between the breaker and the bus bar. Usually these types of breaker issues are caused by installation problems such as loose connection, wrong breaker type, failure to use anti-oxidation paste on alum to copper or excessive tripping / using the breaker as a switch.

Here are some tips for diagnosing a tripping breaker Tripping instantly Perform a visual inspection of all wires and connections. Look for signs of rubout, damage and arcing Isolate components and ohm to ground If you are unable to locate with an ohmmeter use a megohmmeter to ground (with caution especially on scroll compressors) Finally, once you believe you have identified the cause, fully disconnnect the shorted component and power the unit back up and make sure everything else functions. Tripping intermittently or after more than 3 seconds Visually inspect all electrical connections and ensure they are clean and tight. Inspect the breaker and bus bar connections Check breaker and wiring size Measure running voltage and ensure it is within +/- 10% rating Measure for voltage drop during startup (less than 15%) as well as between the power source and right at the unit (less than 5% overall) Measure component amperages while starting and running and compare to manufacturer specs Measure motor and compressor temperatures and watch for temperature increase over time. Infrared and thermal imaging can assist with this Watch for anything that can cause overload such as failing bearings, belts too tight, or sheaves adjusted for too much RPM Measure current right at the breaker, if it remains below the breaker rating and the breaker STILL TRIPS, only then replace the breaker.

I also learned recently that AFCI (Arc Fault) breakers generate heat internally which mean that you will see a hot spot on them with a thermal imaging camera or IR thermometer. Don t replace a breaker unless you know it s failed and don t condemn a part as being shorted unless you can isolate it out of the circuit and every other component still functions (as possible) Bryan