SECTION BASIC ELECTRICAL REQUIREMENTS

Similar documents
Generator Fire Safety: Generator assemblies should be located outside the building.

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

SECTION PANELBOARDS

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:

A. Submit manufacturer's literature and technical data before starting work.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

SECTION (15444) - DOMESTIC WATER PACKAGED BOOSTER PUMPS

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

A. This Section includes the following types of sectional overhead doors:

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

IN2 Enclosed Switches and Circuit Breakers

WARREN COUNTY, N.Y. M/E REFERENCE

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

Mipco Connections for Refrigerated Containers. No One Does It Like Mipco. The Mipco. Advantage. Reliability. Safety. Easy Installation & Service

Design Standard. Purpose: Design Standard:

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

SECTION HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY. A. Section Includes:

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

Applications. Illustrated Features

A. General: Deliver, store and handle wire and cable in accordance with the manufacturer's instructions and as specified in Division 1.

UL AND CODE COMPLIANCE

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Spring Test 10 due 05/11/2013

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

APPENDIX B: LISTS OF APPROVED MATERIALS

1. Field verify measurements and circuiting arrangements as shown on as-built drawings.

City of Ottawa Street Lighting. HID Shoebox Style Luminaire

BAL1400 FLUORESCENT EMERGENCY BALLAST Specification-grade One or two-lamp emergency illumination

D2P and EWP Factory Sealed Circuit Breaker Panelboards Explosionproof, Dust-Ignitionproof, Watertight, Corrosion-Resistant

East Central College

Benefits. Safety. Durability. Performance. Russellstoll. Heavy Industrial/ Marine

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

P-2 D2P and EWP Factory Sealed Circuit Breaker Panelboards: Explosionproof, Dust-Ignitionproof, Watertight, Corrosion-Resistant

SECTION DISTRIBUTION AND GROUNDING

Chapter 8 Interior Wiring and Lighting

A. This Section includes piping and related specialties for general-service compressed-air systems operating at 150 psig or less.

SECTION DC POWER SUPPLY/BATTERY CHARGER

CHAPTER V RESIDENTIAL WIRING

R. STAHL Schaltgeräte GmbH Geschäftsbereich Leuchten Nordstraße Weimar, Germany

Cutler-Hammer Molded Case Circuit Breakers Amperes. January 2001 Vol. 1, Ref. No. [0477] G-Frame

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING

Industrial Control Transformers

IVR15-SPI Solid State Illuminated Rail 2 Post Integral Power Supply

A. This Section includes natural gas piping, specialties, and accessories within the building.

SPECIAL SPECIFICATION 5066 Packaged Engine Generator System

Use the following standards for system design and performance requirements.

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

Lumencia. LLMPS SERIES Micro Power Systems. Multi-Unit Residential Lighting. Job Name: Type:

CHAPTER 10 ELECTRICAL

STATE OF NEW JERSEY DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625

NEC 2011 Code Changes

SECTION COMPRESSED-AIR PIPING FOR LABORATORY FACILITIES

SOLAR HEATING SYSTEM

LUMENTON. including poured concrete. Suitable for installation within 4 feet of ground. Product specifications subject to change without notice.

SECTION MOTOR CONTROL

2016 Photovoltaic Solar System Plan Review List

BAL3000 FLUORESCENT EMERGENCY BALLAST Specification-grade: Up to 3500 lumens One or two-lamp emergency illumination

A R C H I T E C T U R A L LO W L E V E L F LO O D L I G H T S E R I E S

CODE MANDATED INTERIOR EMERGENCY LIGHTING:

MECHANICAL AND ELECTRICAL COORDINATION SECTION MECHANICAL AND ELECTRICAL COORDINATION PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name

BALT5-800 LOW-PROFILE FLUORESCENT EMERGENCY BALLAST

Cutler-Hammer. January 2001

CHAPTER 10 ELECTRICAL. Notes:

UNDERGROUND SERVICES - SECONDARY

Document: PRODSPEC-140 Revision: G DCN No Date: October 1, 2014 Product: 10-amp EnerGenius NRG Battery Charger

Photovoltaic Solar Plan Review

Project: Type: Qty: QH2L. Options QH2L 27 3 /8" 23 3 /16" 3 1 /2" O.D. Pole. Options

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

Engineering Information. Solenoid Valves Principles of Operation. Solenoid Valves. Direct Acting Valves (Figures 1A, 1B)

NEC 2014 Code Changes

R. STAHL Schaltgeräte GmbH Geschäftsbereich Leuchten Nordstraße Weimar, Germany

FV Series Nonmetallic Fluorescent Luminaires For Hazardous and Adverse Locations

SECTION VALVES

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

HID/FLOODLIGHT: NEC/CEC EXPLOSIONPROOF. Applications. Options

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

RECESSED TRACK (120V) SPECIFICATIONS

TUBE. Precise construction encourages reliable IP rating. Bi-directional light output with single light source. Choices of light distribution angles.

Simplex Jobsite Wired Basin Package Non-Sparking Stainless Rail Non-Sparking, Class I, Group D, Division 1, w/fiberglass Cover

1. Wiring Diagrams: Power, signal, and control wiring.

LUM SERIES-PLED w/ POLE RATED FOR 100MPH SHAFT

SURFACE TRACK (120/250V) SPECIFICATIONS

SECTION MOTOR REQUIREMENTS for HVAC

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

Duplex Jobsite Wired Basin Package Non-Sparking Stainless Rail Non-Sparking, Class I, Group D, Division 1, with Steel Cover

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

CONSTRUCTION SPECIFICATION FOR THE INSTALLATION OF ROADWAY LUMINAIRES

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

7. Residential Single-Family and Duplex Buildings (Dwellings)

SECTION WIRING DEVICES

GE 8000-Line Motor Control Centers

LIGHTING: EXPLOSIONPROOF FLOODLIGHT. Applications. Options

Applications. Standard Materials

Transcription:

SECTION 16001 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Equipment 2. Raceway systems 3. Power and control wiring 4. Grounding 5. Interior and Exterior Luminaires 6. Exit and Emergency Battery Units 1.3 SUBMITTALLS A. List of proposed materials identifying manufacturer and type for conduit, wireways, boxes, wire and cable, and grounding hardware. B. Manufacturer s catalog sheets identifying manufacturer and type for transformers, power supplies, disconnect switches, circuit breakers, and other devices. 1.4 GENERAL REQUIREMENTS A. Determine required location, arrangement, size, ratings, and quantities of equipment and materials from Drawings. B. Systems provided shall be complete and operable, and shall include required accessories, fastenings, and supports. PART 2 - PRODUCTS 2.1 RACEWAYS A. Surface metal raceway: 1. Use for exposed wiring in publicly-accessible finished areas. 2. Style: 1-piece, as manufactured by Wiremold or equal. 3. Finish shall match the color of the surrounding wall or ceiling. B. Electrical metallic tubing (EMT): 1. Use for concealed wiring, or exposed wiring in limited-access unfinished areas. Do not use underground. 2. Material: Zinc-galvanized steel tube with smooth interior surface, as manufactured by AFC Cable Systems, Alflex, Allied Tube & Conduit, Anamet Electrical, Electri-Flex, Manhattan/ CDT/Cole-Flex, Maverick Tube Corporation, O-Z Gedney, or Wheatland Tube Company. 3. Couplings and fittings: rust-resistant steel, compression type. Provide box connectors with insulated insert in throat. 4. Provisions for moisture-proofing to be made at fittings and connections in locations susceptible to water or humidity. C. Heavy-wall plastic conduit: 1. Use for underground wiring, if required. 1415.27 - Excell Academy Expansion, CD 16001-1

2.2 BOXES 2. Material: Schedule 80 PVC plastic compound, Carlon or equal. 3. Couplings and fittings: Made from same material as conduit, threadless-type joined by solvent cement process. A. Pull boxes and junction boxes: Use for pulling and splicing wires. Boxes shall be of galvanized sheet steel or aluminum with silicon bronze machine screws. When used outdoors, gasketed covers are required. B. Outlet boxes: Four mounting of wiring devices. For indoor, general use areas use galvanized sheet steel boxes with knockouts. For outdoors and potentially wet indoor areas, use cast metal boxes with threaded hubs. C. Terminal boxes: Use for termination of control or instrument wiring. Boxes shall be of 14- or 16- gage galvanized or enameled sheet steel with gasketed cover and inside subpanel as manufactured by Hoffman Engineering. Terminal blocks shall have washer-head connecting screws for No. 12 AWG or smaller conductors as manufactured by General Electric or Penn- Union. 2.3 WIRE AND CABLE A. Power circuits (lighting and receptacle type): 600-volt rated, THHN 75-degree insulated copper wire, solid for No. 12 AWG and smaller, stranded for No. 10 AWG and larger, and as manufactured by Rome, Triangle PWC, or equal. B. Color-coding: Black, red, blue, white for phases A, B, C, and neutral respectively for 208/120 volt circuits. C. Fire alarm circuits: Annunciator, initiation, and notification circuit wiring shall be in accordance with Section 16740. 2.4 DISCONNECT SWITCHES A. Type: Fused 3-pole single-throw, 240 volt heavy-duty safety switches with NEMA 1 enclosure. Ampere rating as required by equipment. Switches shall have quick-make, quick-break operating mechanism and be suitable for locking in OFF position. Acceptable manufacturers are Square D, Cutler Hammer, GE, and Siemens. 2.5 FUSES A. Type: Dual-element, time delay cartridge type, rated for 250 volts, with 200,000 amperes rms interrupting current rating. Continuous current rating as shown on Drawings. Acceptable manufacturers are Bussman and Gould Shawmut. 2.6 CIRCUIT BREAKERS A. Type: Molded case, thermal-magnetic protective, quick-make quick-break, trip-free, tripindicating, common trip with number of poles as shown on Drawings. Voltage rating: 120 volts ac. Acceptable manufacturers are Square D, Cutler Hammer, GE, and Siemens. 2.7 WIRING DEVICES A. Provide wiring devices and cover plates as listed in Wiring Device Schedule; provide gang plates for multiple devices. 1415.27 - Excell Academy Expansion, CD 16001-2

2.8 GROUNDING HARDWARE A. Ground cable: Soft-drawn bare copper stranded cable. B. Ground cable connections: Thermic-welded type as manufactured by Erico Products or compression type as manufactured by Burndy. C. Grounding lugs: Provide for equipment and steel members to be grounded, compression type as manufactured by Burndy. 2.9 CONCRETE MATERIALS A. Use ready-mixed, air-entrained concrete having 28-day compressive strength of 3,500 psi. Conform to ASTM C94. 2.10 NAMEPLATES A. Provide black micarta self-adhesive nameplate with white engraved letters on each electrical panel. 2.11 INTERIOR AND EXTERIOR LUMINAIRES A. Product Data: For each type of lighting fixture, arranged in order of fixture designation. Include data on features, accessories, finishes, and the following: 1. Physical description of lighting fixture including dimensions. 2. Emergency lighting units including battery and charger. 3. Ballast. 4. Energy-efficiency data. 5. Life, output, and energy-efficiency data for lamps. 6. Photometric data, in IESNA format, based on laboratory tests of each lighting fixture type, outfitted with lamps, ballasts, and accessories identical to those indicated for the lighting fixture as applied in this Project. B. Ballasts: 1. All ballasts shall have ballast factor of 0.85 or higher, power factor of 0.98 or higher, and total harmonic distortion of less than 20 percent unless otherwise indicated. 2. Electronic Ballasts: Comply with ANSI C82.11; instant-start type, unless otherwise indicated, and designed for type and quantity of lamps served. Ballasts shall be designed for full light output unless dimmer or bi-level control is indicated. 3. Electronic Programmed-Start Ballasts for T5 and T5HO Lamps: Lamp end-of-life detection and shutdown circuit for T5 diameter lamps, automatic lamp starting after lamp replacement. 4. Temperatures 0 Deg F and Higher: Electronic type rated for 0 deg F starting and operating temperature with indicated lamp types. 5. Ballasts for Compact Fluorescent Lamps: Electronic programmed rapid-start type, designed for type and quantity of lamps indicated. Ballast shall be designed for full light output unless dimmer or bi-level control is indicated. Lamp end-of-life detection and shutdown circuit. Automatic lamp starting after lamp replacement. 6. Electromagnetic Ballast for HID Lamps: Comply with ANSI C82.4 and UL 1029. Constantwattage autotransformer or regulating high-power-factor type ballast circuit. Minimum Starting Temperature of Minus 22 deg F for single-lamp ballasts. Normal Ambient Operating Temperature of 104 deg F. Open-circuit operation that will not reduce average life. With epoxy-encapsulated low-noise ballast. C. Lamps: 1. T8 rapid-start low-mercury lamps, rated 32 W maximum, nominal length of 48 inches, 2800 initial lumens (minimum), CRI 75 (minimum), color temperature 3500 K, and average rated life 20,000 hours, unless otherwise indicated. 1415.27 - Excell Academy Expansion, CD 16001-3

2. T5HO rapid-start, high-output low-mercury lamps, rated 54 W maximum, nominal length of 45.2 inches, 5000 initial lumens (minimum), CRI 85 (minimum), color temperature 3500 K, and average rated life of 20,000 hours, unless otherwise indicated. 3. 4-Pin, low mercury compact fluorescent lamps, CRI 80 (minimum), color temperature 3500 K, average rated life of 10,000 hours at 3 hours operation per start,unless otherwise indicated. 4. HID Lamps: ANSI C78.1372, with a minimum CRI 65, and color temperature 4000 K. D. Poles: 1. Seamless, extruded structural tube complying with ASTM B 429, Alloy 6063-T6 with access handhole in pole wall. 2. Round, straight. Butt flange for bolted mounting on foundation or breakaway support. 3. Pole-Top Tenons: Fabricated to support luminaire or luminaires and brackets indicated, and securely fastened to pole top. 4. Grounding and Bonding Lugs: Welded 1/2-inch threaded lug, listed for attaching grounding and bonding conductors of appropriate type and size, and accessible through handhole. 5. Aluminum Finish: Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for recommendations for applying and designating finishes. 6. Natural Satin Finish: Provide fine, directional, medium satin polish (AA-M32); buff complying with AA-M20; and seal aluminum surfaces with clear, hard-coat wax. 2.12 EXIT AND EMERGENCY BATTERY UNITS A. Internally Lighted Exit Signs: 1. Lamps for AC Operation: LEDs, 70,000 hours minimum rated lamp life. 2. Self-Powered Exit Signs (Battery Type): Integral automatic charger in a self-contained power pack. 3. Battery: Sealed, maintenance-free, nickel-cadmium type. 4. Charger: Fully automatic, solid-state type with sealed transfer relay. 5. Operation: Relay automatically energizes lamp from battery when circuit voltage drops to 80 percent of nominal voltage or below. When normal voltage is restored, relay disconnects lamps from battery, and battery is automatically recharged and floated on charger. 6. Test Push Button: Push-to-test type, in unit housing, simulates loss of normal power and demonstrates unit operability. 7. LED Indicator Light: Indicates normal power on. Normal glow indicates trickle charge; bright glow indicates charging at end of discharge cycle. 8. Integral Self-Test: Factory-installed electronic device automatically initiates code-required test of unit emergency operation at required intervals. Test failure is annunciated by an integral audible alarm and flashing red LED. B. Emergency Lighting Battery Units: 1. Battery: Sealed, maintenance-free, lead-acid type. See Luminaire Schedule on plans for battery requirements or connection to emergency generator. 2. Charger: Fully automatic, solid-state type with sealed transfer relay. 3. Operation: Relay automatically turns lamp on when power supply circuit voltage drops to 80 percent of nominal voltage or below. Lamp automatically disconnects from battery when voltage approaches deep-discharge level. When normal voltage is restored, relay disconnects lamps from battery, and battery is automatically recharged and floated on charger. 4. Test Push Button: Push-to-test type, in unit housing, simulates loss of normal power and demonstrates unit operability. 5. LED Indicator Light: Indicates normal power on. Normal glow indicates trickle charge; bright glow indicates charging at end of discharge cycle. 6. Wire Guard: If indicated on plans provide heavy-chrome-plated wire guard to protect lamp heads or fixtures. 1415.27 - Excell Academy Expansion, CD 16001-4

7. Integral Self-Test: Factory-installed electronic device automatically initiates code-required test of unit emergency operation at required intervals. Test failure is annunciated by an integral audible alarm and flashing red LED. PART 3 - EXECUTION 3.1 QUALITY CONTROL A. Install equipment and materials in strict accordance with manufacturer s recommendations. B. Electrical construction shall be performed in strict accordance with NEC, unless otherwise indicated on Drawings or in Specifications. 3.2 ELECTRICAL INSTALLATION A. Determine location and arrangement from Drawings. Locations shown are approximate unless dimensioned. B. Repair factory finishes where they become damaged during construction. C. Install cable and raceways concealed inside walls or above drop-down acoustical ceilings, Where cables cannot be concealed in publicly-accessible areas, surface metal raceway shall be used in accordance with Part 2. D. Support boxes independently of the conduit system. E. Anchor equipment securely to permanent walls, floors, or building steel. Use expansion anchors in concrete and masonry. Install equipment level and plumb. F. Remove non-conducting material from contact surfaces before making grounding connections. G. A separate grounding wire shall be installed in each raceway containing Lighting and Receptacle circuits. Grounding wire shall be colored green and properly sized according to NEC 250. H. For rooms labeled as Class 1 Division 1 explosion-proof on the Drawings, install only devices, conduit, and connections that are rated for use in such areas. I. Adjust aimable lighting fixtures to provide required light intensities. 3.3 EXCAVATION A. Provide excavation required for underground raceways and grounding. B. Use hand excavation near existing foundations and utilities. C. Backfill with material from excavation, but exclude large stones, organic material, rubbish and frozen material. Thoroughly compact backfill layers not exceeding 8 in thickness. 3.4 CONCRETE INSTALLATION A. Vibrate concrete while placing to work concrete into corners and around reinforcing. B. Float surface to true, even place with wood or cork float. Use edger on exposed edges. C. Cure concrete by applying liquid membrane-forming curing compound on exposed concrete surfaces or keep continuously wet for 7 days. 1415.27 - Excell Academy Expansion, CD 16001-5

D. Take precautions to prevent concrete from freezing. END OF SECTION 16001 1415.27 - Excell Academy Expansion, CD 16001-6