Power Systems PU HYOSUNG Standard High-voltage Switchgear ProSWGR Medium Voltage Metal-clad Switchgear
Power & Industrial Systems Performance Group Hyosung Power Systems has been continuously enhancing customer s value since it started its operations in 1962. With core values focused on customer-oriented management, technological innovation and reliable quality, Hyosung Power Systems has built strong customer relationships based on trust and respect over the years. It promises to continue its quest to provide value-added products that enhances industrial productivity while conserving both energy and environment for clients all over the world. Standard High-voltage Switchgear Control Panel UHV Power Transformer EHV Power Transformer Distribution Transformer Cast Resin Transformer Gas Circuit Breaker Gas Insulated Switchgear Welding Machine Electric Motor Gear Reducer Generator Chemical Process Equipment Industrial Machinery Ropeway CNG Refill Station
Power Systems Performance Unit Hyosung Power Systems strives to enhance the lives of people all over the world while conserving earth s natural resources. With the goal to become a Leading Global Energy Solution Provider, Hyosung will pave the way towards next-generation technology and green energy solutions. CONTENTS 04 05 08 08 09 11
ProSWGR KERI Certification ProSWGR is HYOSUNG s standard high-voltage distribution panel designed for safety of the clients first. With the compact design, the model reduces the required installation floor area by over 40% from the existing model. Complete separation of control unit, bus unit, circuit breaker unit and cable unit minimizes the ripple effect of accident. ProSWGR has passed KERI certification test and internal arc test in compliance with IEC62271-200, and supports various interlocks for safety of clients. KEMA Certification ISO14001 ISO9001 CESI Certification HYOSUNG ProSWGR Series ProSWGR Models Spec. Model HSA/A-12.XX.XX HSA/A-17.XX.XX HSA/A-24.XX.XX Shape External shape SIZE (W D H) 800 800 1000 1000 800 1000 1000 1350 2300 1000 1525 2300 Rated voltage 12kV 17.5kV 24kV Rating Rated current 1250A / 2000A / 2500A 3150A / 4000A 1250A / 2500A Instantaneous current 31.5/40kA 3sec 40kA 3sec 25kA 3sec
Leading the World best Features of HYOSUNG ProSWGR Compartment structure that meets LSC2B ProSWGR meets LSC2B in the service continuity level of IEC62271-200. ProSWGR has a control unit, a main bus unit, a circuit breaker unit and a cable unit in separate compartments. Under LSC2B, for VCB lead out, the shutter is closed automatically, separating the main bus unit from the cable unit both electrically and mechanically. LSC2B Busbar Compartment CB Compartment Cable Compartment Metallic partition structure The metallic partition structure consists of metal compartments and metal shutter, providing superior insulation and outside protection against arc accident. Metallic partitions maintain earthing status between live cables and inspection part, securing safety of operators. Operators can monitor operation through the inspection window while the CB door is closed, and the equipment supports interlock with front door according to the circuit breaker state. ProSWGR 04/05
ProSWGR Features of HYOSUNG ProSWGR Arc-resistance structure in compliance with IEC62271-200 ARC Proof IAC (Internal arc classified) - AFLR Duration - 31.5kA : 0.5 s - 40kA : 0.5 s Accessibility A : Type (restricted to authorized personnel only) Arc flow F : for Front side L : for Lateral side R : for Rear side For the safety of users, the arc-resistance test was performed in compliance with IEC62271-200 Annex A. Test conditions - Door or other covers shall not open. - No pieces that may cause injury shall burst out from distribution panel. - No hole shall be made outside the distribution panel that can be accessed. - No front, side or rear indicator shall burn out due to gas or fire. - All distribution panels shall maintain effective earthing state. Internal Arc Test
Leading the World best Interlock structure (Mandatory) It is impossible to connect/disconnect circuit breaker, while it is in the On position. You cannot switch On while connecting/disconnecting the circuit breaker. It is possible when the circuit breaker is in the Service position or the Test position. The circuit breaker can be switched off manually if there is no operating power or electric interlock at the Service or Test position of the circuit breaker. In the service position the control plug cannot be separated. You cannot connect the earthing switch when the circuit breaker is in the Service position. You cannot connect/disconnect VCB while the door is closed. The shutter can be operated via movement of the circuit breaker. You cannot handle it manually. Interlock structure (Option) LV Door LPS is equipped on the door. Switch Operation To prevent switch operation error, it is possible to control the switch with a software program. Control Plug You can disconnect the electric status contact point when connecting /disconnecting the control plug. Electric State Check (control panel) Electric contact point can be implemented to check the circuit breaker position and earthing switch status. Earthing Padlock Padlock can be installed at the earthing switch control. Door Padlock Padlocks can be installed on the CB compartment and the cable compartment. CB Door It is possible to check the VCB operation through the monitoring window. You cannot open the door if the circuit breaker is in the service position in uncertain position. A push button is on the door which can switch off the circuit breaker in emergency. Shutter Padlock When the circuit breaker is removed, you can install a padlock to each shutter for easy maintenance. Cable Door You cannot open the door when the earthing switch is not connected. It is possible to check the cable through the monitoring window. You cannot control the earthing switch when the cable part door is open. ProSWGR 06/07
ProSWGR Item Specifications of HYOSUNG ProSWGR Structure of HYOSUNG ProSWGR Basic structure Model HSA/A-12.XX.XX HSA/A-17.XX.XX HSA/A-24.XX.XX Rated voltage (kv) 12 12 12 12 17.5 17.5 24 24 Rated current (A) 1250 2000 1250 2500 3150 4000 1250 2500 Rated breaking current (ka) 31.5 31.5 40 40 40 40 25 25 Commercial frequency withstanding voltage (kv/60s) 28 28 28 28 38 38 50 50 Surge impulse withstanding voltage (kv) 75 75 75 75 95 95 125 125 Frequency (Hz) 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 Internal protective level IP 4X IP 4X IP 4X IP 4X IP 4X IP 4X IP 4X IP 4X External protection level IP 2X IP 2X IP 2X IP 2X IP 2X IP 2X IP 2X IP 2X Width (mm) 650 800 800 1000 1000 1000 800 1000 Height (mm) 2300 2300 2300 2300 2300 2300 2300 2300 Depth (mm) 1300 1300 1300 1300 1350 1350 1525 1525 Naming rule HSA/A - XX.XX.XX Unique name Rated voltage Rated current Rated breaking current D C B E A Arc Duct Indicator (Option) Protective Relay LPS (Option) Circuit Breaker Control Button (Option) Circuit Breaker Monitoring Window Circuit Breaker in/out Control Hole Cable Connection Monitoring Window LV Door Lock CB Unit Door Handle (Option: Padlock) Grounding Switch Control Hole Cable Door Handle (Option: Padlock) Circuit Breaker Circuit Breaker Door Lock (Option) Shutter Lever Cable Unit Door Lock (Option) Main Bus Branch Bus Safety Shutter Insulation Bushing Circuit Breaker Conductor Grounding Switch Current Transformer Cable Connection Bus Bar Cable Connector Cable Clamp A Main Bus B Circuit Breaker C Cable D Low Voltage Unit E Arc Duct
Leading the World best Structure of HYOSUNG ProSWGR by Type 12kV 31.5kA 2000A Part No. Part Name Part No. Part Name Part No. Part Name 01 Circuit Breaker 05 Current Transformer 09 Circuit Breaker Switch (Option) 02 Main Bus 06 Indicator (Option) 10 Circuit Breaker Monitoring Window 03 Branch Bus 07 Protective Relay 11 Circuit Breaker in/out Control Hole 04 Insulation Bushing 08 LPS (Option) 12 Cable Connection Monitoring Window ProSWGR 08/09
ProSWGR Structure of HYOSUNG ProSWGR by Type 17.5kV 40kA 4000A 24kV 25kA 1250A
Leading the World best Control Panel of HYOSUNG ProGIS(C-GIS) ProSWGR Metal Clad Switchgear Low Voltage Metal Enclosed Switchgear Advanced MV GIS with maximum reliability and stability, and minimum installation surface has been developed based on abundant experiences and technical capabilities acquired through contracts with many domestic / overseas clients. ProSWGR is a metal-clad type standard high-voltage switchgear with inner spaces completely separated by partitions. The switchgear supports system operations, such as circuit breaking and monitoring, from the front panel while the door is closed. Metal Clad Switchgear is selfdesigned and developed by HYOSUNG and have the high reliability & performance. Low Voltage Switchgear will provide safe power distribution with handy operation, easy to installation & maintenance. Motor Control Center Supervisory & Control Panel IPB (Isolated Phase Bus) NSPB(Non Segregated Phase Bus) Motor Control Center is designed with operator s safety and easy to handling. It will provide the motor s status supervision. Supervisory & Control Panel will provide the easy to operation protection and control of power system by humane facto application. IPB is designed for high current, critical equipment or large capacity power plants. IPB is applied to the bus with the rated voltage of 36kV or lower and the rated current of 5,000~50,000A. Metal Enclosed Bus is a good method for main bus application in power plants, substations, buildings and factories. 25.8kV SIS Spot Network System 25.8kV SIS is an environment-friendly product using epoxy solid insulation technology instead of SF6 gas. The model adopts dual buses for uninterrupted expansion and maintenance. The isolated phase bus technology prevents short-circuit and the surface grounding provides high stability of the system. Spot Network System will eliminate the care about a power interruption and will provide the optimized installation area. ProSWGR 10/11
HEAD OFFICE 450, Gongdeok-Dong, Mapo-Gu, Seoul, Korea 121-720 TEL : 82-2-707-7000 R&D CENTER 183, Hogye-Dong, Dongan-Gu, Anyang-Shi, Gyeonggi-Do, Korea 431-080 TEL : 82-31-428-1000 CHANGWON PLANT 454-2, Nae-Dong, Changwon-Shi, Gyeongsangnam-Do, Korea 641-712 TEL : 82-55-268-9114 JOCHIWON PLANT 518, Yungi-ri, Nam-Myeon, Yungi-Gun, Chungnam, Korea 339-823 TEL. 82-41-860-3114 DIRECT CONTACT Switchgear Sales Team TEL : 82-2-707-6257~9 CHANGWON PLANT Switchgear Design Team TEL : 82-55-268-9414~9