PRESSURE GAGES AND TEST TAPS

Similar documents
CAT231.1 PRESSURE GAUGE AND TEST TAP KIT SKID MOUNTING 220V, 50HZ, 1Ø OPERATING CONDITIONS 25 TO 100 PSI 100 F MAX IMUM TEMPERATURE SERIES METER

CAT231.1 SHUT OFF KIT (SOK) TO PREVENT BYPASS PRESSURE GAUGE AND TEST TAP KIT SKID MOUNTING 220V, 50HZ, 1Ø

DETAILED EQUIPMENT SPECIFICATION MR SERIES WATER SOFTENERS

DETAILED EQUIPMENT SPECIFICATION MDAS SERIES DEALKALIZERS

DETAILED EQUIPMENT SPECIFICATION MHC SERIES WATER SOFTENERS

TNT SERIES WATER CONDITIONERS

Plastic Valve Nest Epoxy Lined Section 7 Steel Filters - 18 thru 48

INDUSTRIAL GRADE WATER SOFTENERS LWTS INDUSTRIAL SERIES

AQT-56SE ELECTRONIC SERIES PROGRAMMING MANUAL CONTROL VALVES

DETAILED EQUIPMENT SPECIFICATION MRO-4 SERIES REVERSE OSMOSIS SYSTEMS

INDUSTRIAL GRADE WATER SOFTENERS LWTSF INDUSTRIAL SERIES

Clean and soft water for business needs. Commercial softening equipment. COMMERCIAL WATER SOFTENERS

Commercial Softeners

5600 Control Valve. Bypass Piping Boss Inlet & Outlet. Distributor Tube and basket. Brine Well. Brine Line. Over-Flow (Optional) $1.

SECTION 1. Fleck Fiberglass Softeners. *Shown with factory SKID & Interconnecting Plumbing

DETAILED EQUIPMENT SPECIFICATION HIGH PURITY LABORATORY WATER SYSTEM

AQT-56 POWERFLO SERIES SERVICE MANUAL CONTROL VALVES

Fleck Top Mount Section 1 Fiberglass Softeners

Specifications. Autotrol 255 Valve. Autotrol 255 Series Valve Specifications. Flow Rates (Valve Only) Regeneration Operation

Control Valves, Fittings and Accessories

BNT 85 /185 Valve Operation Manual

Installation and Operations Manual

Iron Gate Air Pump System Manual

Iron Gate Feed Pump Manual

INSTALLATION, OPERATING AND SERVICE MANUAL

AQUASTAR C6. (Comfort 6000) Next Generation Auto Backwash Valve System. (selectable time-pressure or remote cycle start)

Fleck Fiberglass Section 9 Chloride Dealkalizers

Control Valves, Fittings and Accessories

Weld tabs are standard on all media tanks and screen filter housings.

IWT 565 Series Valve Operation Manual

Installation and Operation Instruction Manual INSMAN-201. Industrial Multi Media Single Tank

65 Series. Valve Operation Manual

BLAKE WATER SOLUTIONS U.S. NORTHEAST REGION DISTRIBUTION CATALOG REV 09/09

WATER SOFTENER SEMI AUTOMATIC INSTALLATION & OPERATING INSTRUCTIONS. Serial No :

Fleck Epoxy Lined Section 2 Steel Softeners

ProFloSE. Downflow Brining Service Manual. IMPORTANT: Fill in pertinent information on page 2 for future reference.

8.2 Steel 13.5 Steel 16.5 Steel 20 Steel 17 FRP 20 FRP Single Systems & 104 S F 120F

AQT-275 SERIES SERVICE MANUAL CONTROL VALVES

IRON & MANGANESE REMOVAL FILTER INSTALLATION & OPERATING INSTRUCTIONS. Serial No :

COMMERCIAL UST ADD WATER BULLETIN; ISSUE 1

WATER SOFTENER SERIES DAY TIMER INSTALLATION & OPERATING INSTRUCTIONS. Serial No :

VAF TM FILTRATION SYSTEMS HYDROCYCLONE SEPARATOR

TECHNICAL SHEET AUTOTROL PERFORMA CV CONTROL VALVE - LOGIX SERIES WATER PURIFICATION VALVES - AUTOTROL

Owners Manual Installation Instructions. For Models PTCF PTCF PTCF

Signature Series. Duplex Softener Service Manual

Reverse Osmosis Systems Section 11 Reverse Osmosis Systems

FILTRATION AMIAD PLASTIC FILTERS, SCREENS & DISCS

wd-2

Fleck 2510 Manual Sediment Filter Installation & Start-Up Guide

General Operation. To set Time of Day. To set Time of Regeneration / Backwash

Model 7000XTR. Service Manual. IMPORTANT: Fill in Pertinent Information on Page 3 for Future Reference

AquaMatic Series. A100 and A200 Stager Controls

Aqualine Active Carbon Filters with surface piping

COMMERCIAL / INDUSTRIAL WATER SOFTENERS

HMF, SMF & BMF Media Filters

Tech Manual Powerline Filter (PF) Series

Series 774 Automatic Skid Package

AQUAMATIC CONTROL VALVES, STAGERS AND CONTROLLERS

Assembled Engineered Systems. Softeners Filters Specialty Systems

OWNER S MANUAL FOR ALL GREENSAND SYSTEMS

05 Water Pressure Systems INTRODUCTION

255 Valve Specifications

SST Series Sand Media Filtration Systems

P/N: (Rev. G 1/19/10)

Water Specialist 1 Control Valve Series Model: WS1CS 1.25 Control Valve Series Model: WS1.25CS

FLECK 2850S SERVICE MANUAL. waterpurification.pentair.com

6700XTR Upflow. Service Manual. IMPORTANT: Fill in Pertinent Information on Page 3 for Future Reference

MASTER. Water Conditioning Corp. Installation and Operation Manual. MCA Combination Series Residential Units

AMERICAN RECIRCULATING SAND FILTER SYSTEMS

Installation and Operation Manual

Technical Manual. Models: Standard Softeners High Efficiency Softeners Combination Softeners S150 S250 S250 OD S350 S550 S650 S650 OD Q850 Q850 OD

Duplex Commercial Pressurizer -DCP

PRO-II SERIES SAND MEDIA FILTRATION SYSTEMS Kits and Parts Listing

FLECK 5600 SERVICE MANUAL. waterpurification.pentair.com

Panel Operation Quick Reference Guide

PRO II & SST Media Filtration Systems Installation and Operation Manual

GENERAL PUMPA member of the Interpump Group

Filtomat M100/MG Filters

Water Specialist 1 Control Valve Series Model: WS1CI 1.25 Control Valve Series Model: WS1.25CI

TOTAL ENGINEERED SOLUTIONS CSG PROCESS FILTER MODEL CL

FLECK 2850 CONTROL VALVE

Pumps and Filtration

Atomizer 36-DC User Guide

Chemical Free Iron Sulphur Filtration System Owner's Operation and Maintenance Manual

FLECK 2750 DOWNFLOW SERVICE MANUAL. waterpurification.pentair.com

Material of construction. Inner shell material: Polyethylene. Available inlets: See chart. Operating parameters. Maximum operating pressure: 150 psi

HWB Series GENERAL PUMP. Hydraulic Drive Triplex Plunger Pump INDUSTRIAL INDUSTRIAL FEATURES

SST & PRO II Media Filtration Systems Installation and Operation Instructions

2inch Valve S D S D

or OWNER S MANUAL MODEL R

COMMERCIAL CONTROL VALVES. Magnum Control Valve

Pre-Treatment Control Valve (Fleck 2850s) & Timer (Fleck SXT)

3 Spin Klin Battery Operation and Maintenance Manual

Engineering Design, Plans, and Specifications for an Air-Assisted Filter Backwash System at the Thomas Hill Energy Center Water Treatment Plant

Cartridge Filter Housings Nowata A Series

SINGLE-STAGE INJECTOR MODELS 200-3C, 200C, 201C, 202C, 203C, 204C, 206C, 208C

7500 Greensand Filter Installation & Start Up Guide

Water Specialist 1 Control Valve Series Model: WS1TC 1.25 Control Valve Series Model: WS1.25TC

BUILT SMART, CLEANS TOUGH!

Nautilus Gallon Per Day Modular Watermakers.

Transcription:

CAT 500.1 FRF series filters. Polyglass 100 psi vessels with top mount Task Master II 1 ½ valve and single point PVC internals. FMF series filters. Carbon steel epoxy lined and coated vessels with side Task Master II 1 ½ valve side and multipoint PVC internals. FHF series filters. Carbon steel epoxy lined and coated vessels with side Task Master 2 valve side and multipoint PVC internals. OPTIONS BACKWASH INITIATION may be manual, by time clock, by water meter, or by differential pressure transducer. AUXILIARY BACKWASH may be supplied to feed systems with higher backwash flow demand than available when using filtered water from the systems. SKID MOUNTED units on welded structural steel frames are pre-piped, wired, and factory tested. Installation requires simple plumbing connections to the manifold inlet and outlet, a drain and brine connection, electrical connection, and loading of the tanks. Skids may be custom-built to meet almost any specifications. LOCKOUTS prevent twin or multiple units from backwashing at the same time. Interconnecting wiring between the two units prevents simultaneous backwash. SHUT-OFF KITS (SOK) prevent unfiltered water by pass during backwash cycles. The kit consists of a solenoid and diaphragm valve located on the outlet line and connected to the Task Master II control wiring. The diaphragm valve is automatically closed during regeneration. This option is required on twin alternating applications. (Part No. 720088 for a 1½ inch SOK.) PRESSURE GAGES AND TEST TAPS can be installed by requesting special taps be made in the valve body. Upon request the valve body can be tapped to accept inlet and outlet pressure gages and inlet and outlet sample taps. This allows the user to sample the inlet and outlet water quality and to monitor pressure losses through the system. ELECTRICAL REQUIREMENTS. Standard electrical specifications are 120 VAC, 60 Hz, 3 amps. A 220 VAC, 50 HZ, 1.5 amp configuration is available.

CAT 500.2 Filtration Cycles SERVICE. Filters the water flows downward through the media and is clarified. The solids accumulate in the media bed. BACKWASH. When the filter begins to clog or when the head loss though the bed increases, flow rates are dramatically reduced and often solids break through the filter and water quality deteriorates. To clean the filter bed, the flow is reversed, fluidizing the media bed, and is directed to drain. The flow required is specific to the media. If too much flow is applied, the bed can be flushed from the tank and if too little flow is applied, the bed will not fluidize properly and will not be cleaned. Improper cleaning leads to mud ball formation and channeling in the filter. The FRF, FMF, and FHF Series all use nozzle type backwash rate-of-flow controllers. Backwash is made possible by shifting the Task Master or Task Master II multiport valve so that it allows the water to enter the bottom of the filter tank and flow upward through the media bed, thus backwashing filtered solids to drain. FILTER TO WASTE. When a filter is returned to service after backwash, the initial effluent solids concentration from the filter is high. The bed must be repacked and begin to remove some particulates before it can become effective. Thus, the first few gallons of a filter run are usually wasted. This part of the cycle is called filter to waste. Water King filters based on the Taskmaster Valve Water King builds a complete line of filters using the Taskmaster valve to control and execute the backwash cycle. These filters designated FRF, FMF, and FHF to denote the configuration. This brochure covers the vessel and valves and provides an application chart. FILTER CONTROLS TIME CLOCK. Most filters are set to backwash daily or every other day with standard 6 day timers. To backwash on a given day of the week use a 7 day timer. DIFFERENTIAL PRESSURE. As a filter run progresses, the filter becomes clogged developing pressure loss across the bed. A differential pressure gauge placed between the filter inlet and outlet measures this head loss. Each filter can be equipped with an ARC cycle timer with backwash initiation by the differential pressure switch. MULTIPLE FILTERS. Filters operating in parallel all clog simultaneously and thus must be backwashed at the same time or sequentially. Water King often supplies multiple filters with a lead unit having a time clock and the remaining units having ARC timers. These can be set up to cause sequential backwash at a predetermined interval. 102 Charbonnet Road Duson, Louisiana 70529 337 988 2360 Fax 337 981 7922 wknginfo@waterking.com Revised 10/06/06 DELIVERING EXPERIENCE, QUALITY, AND SERVICE SINCE 1934

CAT 500.3 TASKMASTER TM VALVE IN FILTRATION SERVICE 1. THE PRECISION MEMORY SYSTEM by Water King controls time clock or semi-automatic operation. Water meter regeneration by totalized flow is also available. The valve design keeps timer and valve synchronized. Patent No. 3732738. 2. MOTOR DRIVEN OPERATION is not dependent on water pressure, and shifts smoothly without water hammer. The drive assembly accurately and consistently positions the plunger for each cycle. 3. RAW WATER BY-PASS up to 70 gpm on the FRF & FMF series, and 150 gpm on the FHF series is available during all regeneration cycles. 4. THREADED TAPS at the inlet and outlet ports provide easy installation of test taps and pressure gauges. 5. EVERY VALVE IS TESTED TWICE. Valves are hydrostatically pressure tested after initial assembly and then tested again as part of the completed filter. 6. ALL BRASS CONSTRUCTION in the valve body provides corrosion resistance. The valve has only one moving part the plunger. 7. NEMA 3 ENCLOSURES provide rainproof protection of electrical components. 8. ALL PLUMBING is made up to the tank adapter (FHF only). 9. INJECTOR SYSTEM (requried only on greensand filters) controls the injection of potassium permanganate in FRF greensand filters models 50 through 150. On other filters that do not feed chemicals, the injector port is plugged. Larger greensand filters use chemical injection pumps. 10. ELECTRICAL SYSTEM is designed to provide on/off signal for external electrical functions. 11. SERVICE & REGENERATION lights indicate service or backwash in filter applications.

CAT 500.4 FRF Series Filter Specification Mineral Tank. The mineral tank shall be polyglass consisting of an inner shell of virgin polyethylene and an external shell of continuous fiberglass roving. Tanks shall be rated at 150 psi operating pressure, 120ºF operating temperature with 4-8 UN threaded top opening. Internals. The distributor shall be a 2½ Ø single point molded distributor head with 2½ of slotted length and a 1½ inch female socket welded connection. The slots shall be 0.012" - 0.016" wide to retain mineral and the total slot area shall be equal to or larger than the unit pipe size. The distributor pipe shall be 1½ inch schedule 40 white PVC. Filtration Media. The media shall be supplied as per the application chart. Backwash rate shall match the media. Underbedding. The bottom of this mineral tank shall be filled above the distributor with #20 graded washed flint gravel sieved between 1/8 and 1/16. Control Valve. The main control valve(s) shall be the Task Master II controlled by a time clock to actuate the cycles of backwash, brine, slow rinse, fast rinse, and service. The control valve(s) shall be Task Master II 5-Cycle, 100 psi, multi-port control valve(s) with machined brass body, stainless steel piston assembly, Noryl inserts, Buna-N seals, service and regeneration lights, drive motor assembly, and NEMA 3 enclosure (120VAC/60Hz/3Amps). The valve shall operate with a single motor driven, cam positioned, piston. The valve shall be of a single piston design and not use multiple plungers or diaphragm valves. Each control valve shall be equipped with "Service" and "Regeneration" indicator lights. The valve shall be equipped with threaded ¼ FNPT ports for the installation of sample taps and pressure gauges. (Taps and gauges are optional.) Unfiltered water by-pass shall be available during all regeneration cycles at 70 gpm or at the peak flow rate of the unit, at a pressure drop less than 25 psi, whichever is less. Simplex units shall bypass during backwash unless optional shut off kits are provided. MF Series Filter Specification Mineral Tank (Standard Non Code Vessels). The non-code vessel shall be A36 carbon steel or better rated at 100 psi working pressure designed to a factor of safety of 3.0. The inlet and outlet shall be 3000 psi NPT full couplings. The inlet shall be in the side wall and the outlet shall be in the center of the tank bottom shell. Each tank shall have a top center fitting. Tanks 36 Ø and larger shall have lifting lugs. Tanks 20, 24, and 30 Ø inch tanks shall have a 4 x 6 handhole in the side shell and in the top head. Tanks 36 Ø and larger shall have a 4 x 6 handhole in the top dome and an 11 x 16 or larger manway in the side shell. Mineral Tank (Optional Code Vessels). ASME code stamped tanks shall be available. Tank shall be clearly specified as code or noncode with a specified working pressure. Tanks built to ASME code but not stamped shall not be acceptable as ASME code. An ASME U1 form shall be provided with each ASME code tank. Coating and lining. Tanks shall be prepared for internal and external coating with a SPCC 11 near white sand blast. Internal and external coating shall be two - 3 to 4 mill coats of white Series 20 Tnemic Epoxy. Paint shall be applied according to manufacturer s recommendations. Paint reports and mill thickness reports shall be provided if requested at the time the tank is ordered. Internals. The bottom distributor shall be a multipoint system using 2½ Ø single point molded distributor heads with 2½ of slotted length and a 1½ inch NPT female threaded connection. The slots shall be.012" -.016" wide to retain mineral and the total slot area shall be equal to or larger than the unit pipe size. A top dome splash distributor with an opening equal to or larger than the unit pipe size shall be installed in the mineral tank. The internal distributor piping shall be SCH 80 PVC. Media. The media shall be supplied as per the application chart. Backwash rate shall match the media. Piping. Face piping shall be 1 ½ threaded schedule 40 galvanized carbon steel pipe. Control Valve. (Same as FRF only side mounted on a brass tank adaptor.) Operating Conditions. Maximum temperature shall be 100 F. Pressure shall be 25 to 100 psi. 102 Charbonnet Road Duson, Louisiana 70529 337 988 2360 Fax 337 981 7922 wknginfo@waterking.com Revised 10/06/06 DELIVERING EXPERIENCE, QUALITY, AND SERVICE SINCE 1934

Other items. A standard soft water soap test kit shall be provided. A complete set of instructions, including installation, loading, start-up, adjustments, servicing, and a parts list shall be provided with the equipment. Qualifications. A company that has continuously manufactured water softeners for at least twenty (20) years shall construct this equipment. Pressure gauge and test tap kit. A kit containing two liquid filled, stainless steel pressure gauges with 2 ½ Ø face, two brass ball valve sample taps with hose barb connections and associated brass connection fittings shall be provided for mounting in the 1/4" FNPT predrilled and tapped ports in the inlet and outlet of the Task Master II valve. FHF Series Filter Specification Mineral Tank. 100 psi non code pressure vessels which are the same as the FMF. Mineral Tank (Optional Code Vessels). ASME code vessels are available which are the same as FMF. Coating and lining. Epoxy lined and coated vessels are same as FMF. Internals (HF-150, 20 Ø to HF-900, 42 Ø). Slotted multipoint internals are the same as FMF. Media. The media shall be supplied as per the application chart. Backwash rate shall match the media. Face Piping. The piping connecting the tank to the tank adaptor and valve shall be 2 or 2 ½ SCH 40 galvanized steel pipe with NPT fittings. Control Valve. The main control valve(s) shall be the 2 or 2 ½ Task Master controlled by a time clock to actuate the cycles of backwash, brine, slow rinse, fast rinse, and service. The control valve(s) shall be 100 psi, multi-port control valve(s) with machined brass body, stainless steel piston assembly, Noryl inserts, Buna-N seals, service and regeneration lights, drive motor assembly, and NEMA 3 enclosure (120VAC/60Hz/3Amps). The valve shall operate valve. CAT 500.5 with a single motor driven, cam positioned piston. Maximum operating pressure of the valve shall be 80 psi. The valve shall be of a single piston design and not use multiple plungers or diaphragm valves. Each control valve shall be equipped with "Service" and "Regeneration" indicator lights. The valve shall be equipped with threaded ¼ FNPT ports for the installation of sample taps and pressure gauges. (Taps and gauges are optional.) Hard water by-pass shall be available during all regeneration cycles at 70 gpm or at the peak flow rate of the unit, at a pressure drop less than 25 psi, whichever is less. The valve shall be mounted to the piping using a tank adaptor and shall be removable without disturbing the installed piping. Specifications common to all filters Operating Conditions. Maximum temperature shall be 100 F. Pressure shall be 25 to 100 psi. Other items. A standard soft water soap test kit shall be provided. A complete set of instructions, including installation, loading, start-up, adjustments, servicing, and a parts list shall be provided with the equipment. Qualifications. A company that has continuously manufactured water softeners for at least 20 years shall construct the equipment. Pressure gauge and test tap kit. A kit containing two liquid filled, stainless steel pressure gauges with 2 ½ Ø face, two brass ball valve sample taps with hose barb connections and associated brass connection fittings shall be provided for mounting in the 1/4" FNPT predrilled and tapped ports in the inlet and outlet of the Task Master II.

CAT 500.6 FILTER APPLICATION TABLE GENERAL SPECIFICATIONS. APPLIES TO ALL TYPES OF MEDIA. Model Dia. (in.) Side Bed Area Pipe Media Underbed Width Depth Height Sheet (ft. 2 ) (in.) (ft³) (ft³) (in.) (in.) (in.) FRF 50 12 52 0.79 1 ½ 1.50 0.25 18 12 59 FRF 70 13 54 0.92 1 ½ 2.00 0.30 18 13 61 FRF 100 14 65 1.07 1 ½ 3.25 0.35 18 14 72 FRF 120 16 65 1.40 1 ½ 4.00 0.55 18 15 72 FRF 150 21 62 2.40 1 ½ 5.00 2.00 22 21 69 FMF 240 24 54 3.14 1 ½ 8.00 2.50 24 35 71 FHF 300 30 60 4.90 2 10.00 3.00 30 44 81 FHF 600 36 60 7.10 2 20.00 4.00 36 50 83 FHF 900 42 72 9.60 2 30.00 5.00 42 57 99 MODEL Continuous Flow rate at 5 (gpm/ft 2 ) Fine Sand Filter AG HEAD LOSS IN PSI AT 5 GPM/FT 2 Activated Carbon Green Sand Multimedia Continuous flow rate at 15 (gpm/ft 2 ) FRF 50 3.9 4.0 0.6 0.5 1.0 5 11.8 FRF 70 4.6 6.3 0.8 0.7 1.9 7 13.8 FRF 100 5.4 6.5 1.0 0.9 2.1 7 16.0 FRF 120 7.0 7.3 1.2 1.2 2.4 8 21.0 FRF 150 12.1 7.0 2.3 2.3 2.8 9 36.0 FMF 240 15.7 8.5 2.7 2.7 3.5 10 47.1 FHF 300 24.5 8.1 0.8 0.8 2.4 10 73.5 FHF 600 35.4 8.4 1.8 1.8 2.8 10 106.5 FHF 900 48.1 10.2 2.5 2.7 4.0 10 144.0 BACKWASH RATE IN GPM MODEL Activated Fine Sand Filter AG Carbon Green Sand Multimedia FRF 50 8 5 5 8 8 FRF 70 10 8 8 10 15 FRF 100 15 10 10 15 15 FRF 120 15 12 12 15 20 FRF 150 30 20 20 30 35 FMF 240 35 25 25 35 50 FHF 300 60 40 40 60 75 FHF 600 90 60 60 90 100 FHF 900 115 90 90 115 140 SHIPPING WEIGHT IN POUNDS MODEL Activated Fine Sand Filter AG Carbon Green Sand Multimedia FRF 50 260 145 145 240 295 FRF 70 300 150 155 270 355 FRF 100 405 200 205 360 496 FRF 120 550 250 255 500 570 FRF 150 830 450 460 760 900 FMF 240 1390 790 800 1290 1485 FHF 300 1850 1100 1140 1725 2285 FHF 600 3375 1875 1930 3125 3200 FHF 900 4975 2725 2820 4590 4250 COMPONENTS FOR MULTI MEDIA FILTERS (FT 3 ) Model No. 1 Anthracite.45-.55 mm Sand 30/40 Garnet 8/12 Garnet NOTES: FRF 50 0.85 0.56 0.28 0.17 Continuous flow rates at 5 gpm/ft 2 for all except multimedia, FRF 70 1.25 0.75 0.40 0.25 which is rated at 15 gpm/ft 2 FRF 100 1.50 1.00 0.50 0.30 Peak flow rating is 10 gpm/ft 2. FRF 120 2.00 1.50 0.75 0.40 Flow rates in gpm. FRF 150 3.00 2.00 1.00 0.50 Make certain sufficient backwash FMF 240 4.50 3.00 1.50 1.00 flow is available. FHF 300 7.00 5.00 2.50 1.50 Specifications listed are not skid FHF 600 10.00 7.00 4.00 2.00 mounted systems. Skid dimensions FHF 900 14.00 9.50 4.50 2.50 - given upon request. 102 Charbonnet Road Duson, Louisiana 70529 337 988 2360 Fax 337 981 7922 wknginfo@waterking.com Revised 10/06/06 DELIVERING EXPERIENCE, QUALITY, AND SERVICE SINCE 1934