Catalog Swirl diffuser DAL 359

Similar documents
Catalog Swirl diffuser DAL 358

Catalog Linear Diffuser SAL 50

Ez = 1.1. Swirl diffuser. Catalog DAL 358

Ceiling swirl diffusers

Maintenance and installation guide

Ceiling swirl diffusers

Type VDL FOR HIGH ROOMS, WITH ADJUSTABLE AIR CONTROL BLADES. Homepage > Products > Air Diffusers > Swirl diffusers > Type VDL

Ceiling swirl diffusers with perforated face plate

Ceiling swirl diffusers with perforated face plate

Ceiling diffusers. Type VDR. For large temperature differences in heating mode, high penetration of air, with adjustable air control blades

emcoair quick selection catalogue 2017/18 Products Planning Prices Air diffusers Grids Dampers Controllers Price list is valid from

Type DCS FOR HORIZONTAL SWIRLING SUPPLY AIR DISCHARGE CREATING HIGH INDUCTION LEVELS, WITH FIXED AIR CONTROL BLADES

Catalog Duct diffuser RRA

Ceiling swirl diffusers

Linear diffuser SAL 50 Submittal

Ventilation grilles for installation into walls, sills or rectangular

Floor diffusers. The art of handling air. Type FB. In aluminium and plastic

ceiling swirl diffuser Model DQJA / DQJR

Ventilation grilles for installation into walls, sills or rectangular

ceiling swirl diffuser DQJ

Ventilation grilles for installation into walls, sills or rectangular

Ceiling diffuser 4DE

Ceiling Swirl Diffuser DQJ

Slot diffusers for ceiling installation

Ventilation grilles for installation into walls, sills or rectangular

Ceiling diffuser 4DF

series 90-GV Variable geometry units

IMP Klima. Swirl diffusers. Variable swirl diffusers

COLIBRI Ceiling QUICK FACTS. Square ceiling diffuser with discs for supply air

2/18/EN/2. Air Handling Lights. Type LR. Recommended for use in rooms with ceiling heights of approx m

Swirl Diffuser Model DQF

Slot diffusers, Round duct diffusers. IMP Klima

Disc valves. Type Z-LVS. For supply air. 03/2017 DE/en PD Z-LVS 1

Ceiling impulse diffuser Model PIL

PURELINE18 PARTICULARLY SLIM DIFFUSER FACE, AVAILABLE IN NUMEROUS VARIANTS FOR MANY DIFFERENT INSTALLATION SITUATIONS

Swirl Diffuser DHV Contents Description...3 Models and dimensions...4 Technical data...8

NAD Klima Ontario 2840, Argentia Road, Unit 6, Mississauga (Ont) L5N 8G4 (416) Ø Diameter. r Radius. Coudes et raccords

1/8/EN/6. Floor Diffusers. Type FB. in aluminium and plastic

Ceiling Slot Diffuser Model DSX

WALL VENTILATION GRILLES CBP

SRY. Ceiling mounted linear disc diffuser for supply air QUICK FACTS

SLOT DIFFUSERS, ROUND DUCT DIFFUSERS

Wall air diffusers with discs for supply air and flush mounting. Quick guide COLIBRI WALL

DRUM SLOT DIFFUSER TYPE: RT350

LINEAR SLOT DIFFUSERS

2/1/EN/3. Slot Diffuser. Type VSD15. with 15 mm wide diffuser face

C O L M A N. Air Distribution LINEAR SLOT DIFFUSERS CD SERIES SERIES

PSTI High Induction Diffuser

WGA Long throw nozzle grille

Optima EXHAUST GRILL AND AIR LOUVER. Perforated Ceiling Diffusers. Features: Standard square sizes:

EAGLE Wall. Wall air diffusers with discs for supply air and flush mounting QUICK FACTS

DKR - Multi-nozzle Ceiling Diffuser. Halton DKR. Multi-nozzle Ceiling Diffuser

Ceiling Slot Diffuser DSC

NSDZ. Swirl diffusers with adjustable air control blades

Ceiling Slot Diffuser DSC

IMP Klima. Swirl diffusers. Variable swirl diffusers

DKS - Multi-nozzle Ceiling Diffuser. Halton DKS. Multi-nozzle Ceiling Diffuser

PELICAN Ceiling. Square ceiling air diffuser for supply air and extract air QUICK FACTS

Ceiling Slot Diffuser DSC

Ceiling air diffuser INDULCLIP INDUDRALL KOMBICLIP

NTK floor twist outlet DB-N-DN 215

Round duct grille Model KG-RR

LINEAR SLOT DIFFUSERS

Round duct diffuser DBB-RR

KLIMA Active Chilled Beams

Wall and Ceiling Grille

Ventilation grille Model AL

C O L M A N. Air Distribution CIRCULAR DIFFUSERS LRS SERIES LRS SERIES

Linear Slot Diffusers Model Slot 20 & Model Slot 25

RPD ROUND PLAQUE DIFFUSER

Product Data. Features/Benefits. 36CBAC,AE,AF,AN, PB,PD,PS Series Active and Passive Chilled Beams. 11 to 190 cfm

ISF-AD. Inclined Floor Swirl Diffuser PRODUCT BROCHURE. Optional Features: Constant throw height adjustable airflow rate Electrical VAV operation

FALCON Ceiling. Circular ceiling air diffuser for supply air QUICK FACTS

SDV Vane Swirl Diffusers

Accessories. Front vane panel Coupling sleeve with gasket Galvanised steel Gasket of rubber compound

HIGH INDUCTION DIFFUSERS WITH VARIABLE GEOMETRY

Type ISH FOR INDUSTRIAL ZONES WITHOUT AIR POLLUTING PROCESSES

HIGH CAPACITY LINEAR SLOT DUFFUSERS

Total comfort control

1. Description Design Front panels - vanes setting Flow directions Dimensions and weights... 8

INDEX. Chapter1 1. A. Jet diffusers 1. Jet diffuser...: AJD-P

ACTIVENT System. Specifications. Product code example ACTA

Nozzle Jet Diffuser Model DSA

PRODUCT BROCHURE. Adjustable Helical Swirl Diffuser HSC-AD HSC-AD : smartemp.com

DFB - Conical Ceiling Diffuser. Halton DFB. Conical Ceiling Diffuser

Supply air unit DYBA. Specifications. Connbox. Quick Selection DYBA, without slot, 1:3 plenum box ATTC (50 Pa)

DFA - Conical Ceiling Diffuser. Halton DFA. Conical Ceiling Diffuser

THL - Conical Ceiling Diffuser. Halton THL. Conical Ceiling Diffuser

CornerAir. CornerAir. Active chilled beam

OptimAir NF. Active Chilled Beam OptimAir NF. Nov

Long Throw Nozzle WDA

Compact Grille Model KG

REK, LEK, ROK and LOK

THB - Perforated Ceiling Diffuser. Halton THB. Perforated Ceiling Diffuser

Multicore diffusers. introduction. type control. options. finish. sizes SQUARE AND RECTANGULAR DIFFUSERS

Krantz. Floor displacement outlet Q-B-DN 200. Air distribution systems

C O L M A N. Air Distribution PERFORATED FACE DIFFUSERS P SERIES SERIES

REK, LEK, ROK AND LOK

DRUM JET DIFFUSERS TYPE: DJA DJB DJAP DJBP

DSC-PLASTER Slot diffuser for plasterboard ceilings

Transcription:

Catalog 1.1.1 DAL 359

Restaurant, Lingen, Germany

DAL 359 Model Description, area of application and product benefits............ DAL 359 1 Configuration................................................... DAL 359 2 Method of operation........................................... DAL 359 3 Aerodynamic data and Range of application..................... DAL 359 4 Dimensions and Weights........................................ DAL 359 5 Diagrams....................................................... DAL 359 6 Critical air flow distance in cooling and example................. DAL 359 8 Specifications.................................................. DAL 359 9 Codification..................................................... DAL 359 10 content 1.1.1 DAL 359 C

Restaurant in Bockenem, Germany

Description, Areas of application and Benefits DAL 359 Diffuser type DAL 359 is a highly inductive swirl diffuser with a round or square front plate and fitted air control blades of ABS. It is suitable for use in both closed and open ceiling systems and allows optimal adaptation of the air distribution system to the prevailing site conditions. The large number of air conducting elements, with optimized airflow and acoustic characteristics, makes this device visually attractive and effective in managing high cooling loads in low ceiling heights. Step-by-step reduction of the discharge free area makes it possible to adjust the device to meet changes in volume flow and discharge temperatures even after installation. The use of blind elements or so-called double clips allows the discharge direction, length or airstream thickness to be varied while maintaining optical appearance. Areas of application - Comfort zone - Clean rooms - Administration areas - Computer rooms - Meeting rooms - Multipurpose hall - Department stores - Systems with constant and variable volume flow Product benefits - Low acoustic power level in high volume flow - Rapid reduction of velocity and temperature differences through high induction - Change of airflow direction and air stream pattern possible - Ability to influence the discharge velocity and thus penetration depth Subject to technical changes. Version 14 / 08 / 2012 1.1.1 DAL 359 1

Configuration Diffuser type DAL 359 consists of a round or square front plate and fi tted air control blades of ABS. Diffusers up to size 600 have the front plate attached to the plenum box with a concealed center screw with crossbar. Size 800 has 4 screws around the border. DAL 359-R-400 DAL 359-Q-400/400 DAL 359-Q-400/603 DAL 359-R-500 DAL 359-Q-500/502 DAL 359-Q-500/603 DAL 359-R-600 DAL 359-Q-600/603 DAL 359-R-800 DAL 359-Q-800/800 2 1.1.1 DAL 359 Subject to technical changes. Version 23 / 08 / 2012

Method of operation rotating discharge one-side horizontal discharge two-side horizontal discharge The blades, designed as wing-shaped profiles, produce a favorable deflection of the vertically streaming air into the horizontal direction of the face plate. Form-fitting bearings and grated components prevent any accidental or unallowable adjustment. Rotating around the bearing center achieves a defined and reproducible reduction by 50% of the discharge free area. A greater penetration depth and flat, horizontal air distribution is achieved with the same discharge volume flow. By using vertically discharging air control elements (double clips), the horizontal airstream can be enlarged. In flush mounted installations, this airstream pattern allows shorter distances between the diffusers, whereby higher air change can be achieved. Use of optional blind clips can further increase the discharge direction. ING, Saint-Hyacinthe Subject to technical changes. Version 14 / 08 / 2012 1.1.1 DAL 359 3

Aerodynamic data and Ranges of application DAL 359 Aerodynamic data Nominal size [-] V [m / h] Minimum spacing [m] p [Pa] LWA [db(a)] x crit [m] 300 5.2 23 30 2.2 360 6.7 34 35 2.7 440 8.6 51 40 3.3 430 6.4 19 30 2.7 530 8.4 29 35 3.3 650 10.5 42 40 4.1 550 4.2 17 30 1.9 650 5.5 25 35 2.4 800 7.3 38 40 3.0 1150 5.4 14 30 2.5 1360 6.8 20 35 2.9 1750 8.8 30 40 3.5 Specifications : The minimum spacing for heights of 3 m so that velocity in occupied areas does not exceed 0.2 m/s. Temperature difference T = -10 Note : The absorption of the room is not considered. For a comparison to north american values, reduce the noise power level of -10 db. DAL 359 Ranges of application = ideal range of application = possible range of application DN 800 DN 600 DN 500 DN 400 cfm 60 120 180 240 300 350 410 470 530 590 700 820 940 1060 1180 [m /h] Air volume flow V 0 [m 3 /h] 4 1.1.1 DAL 359 Subject to technical changes. Version 14 / 08 / 2012

Dimensions and Weights DAL 359 Dimensions / Weights Square plenum box DAL 359 Dimensions / Weights Round plenum box Size DN 400 500 600 800 Size DN 400 500 600 800 Size A 400 502 603 800 Size Ø A 400 500 600 800 Size B 150 182 192 248 Size B 150 182 192 248 Size C 251 312 347 430 Size C 251 312 347 430 Size ØD 150 200 250 313 Size ØD 150 200 250 313 Size E 12 12 12 12 Cote E 8 8 8 8 Size F 387 487 587 790 Size Ø F 404 504 604 802 Weight [Kg] 5.2 7.1 11.5 14.6 Weight [Kg] 8.7 10.4 14.1 21.4 A eff [m 2 ] 0.0226 0.0356 0.0574 0.1148 A eff [m 2 ] 0.0226 0.0356 0.0574 0.1148 Hole for hanging, 4 x Ø6.3 ØD Hole for hanging Perforated plate throttle E C B E ØD Perforated plate throttle Perforated plate Perforated plate C F A ØF ØA Subject to technical changes. Version 23 / 08 / 2012 1.1.1 DAL 359 5

Diagrams DN 400 Ceiling stream rating A-rated acoustic power level L WA [db(a)] Air flow distance y [m] after conjunction Pressure loss p t [Pa] Air flow velocity v max Airflow distance x [m], Air volume flow V 0 [m 3 /h] DN 500 Ceiling stream rating A-rated acoustic power level L WA [db(a)] Air flow distance y [m] after conjunction Pressure loss p t [Pa] Air flow velocity v max Airflow distance x [m] Air volume flow V 0 [m 3 /h] 6 1.1.1 DAL 359 Subject to technical changes. Version 14 / 08 / 2012

DN 600 Ceiling stream rating A-rated acoustic power level L WA [db(a)] 2 Air flow distance y [m] after conjunction 5 Pressure loss p t [Pa] 3 Air flow velocity v max 6 Airflow distance x [m] 1 Air volume Subject flow to technical V 0 [m 3 changes. /h] Version 14 / 08 / 2012 DN 800 Ceiling stream rating A-rated acoustic power level L WA [db(a)] Air flow distance y [m] after conjunction Pressure loss p t [Pa] Air flow velocity v max Airflow distance x [m], Air volume flow V 0 [m 3 /h] Subject to technical changes. Version 14 / 08 / 2012 1.1.1 DAL 359 7

Critical air flow distance in cooling and Example Critical airflow distance x crit [m] Critical airflow distance x 8 DN 400 DN 500 T Temperature difference T Induction Ratio* Air volume flow V 0 [m 3 /h] DN 600 DN 800 7 Temperature difference 1 Air volume flow V 0 [m 3 /h] Critical airflow distance x Critical airflow distance x T Temperature difference Air volume flow V 0 [m 3 /h] T Temperature difference Air volume flow V 0 [m 3 /h] Temperature Ratio* Important : The critical airflow distanceshould always be greater than half the minimum clearance. Specification : Room height : H = 3.50 m Air volume flow per swirl diffuser: :. V0 = 600 m 3 /h Max. cooling temp. difference : T0 = -8 Max. air velocity at height of 1.80 m : V max = 0.2 m/s 4 Required : 1. Diffuser size 2. Acoustic power level L WA 3. Pressure loss Δp t 4. Minimum clearance between the diffusers 5. Critical airflow distance (removal of the airflow from the ceiling at cooling) 6. Induction ratio 7. Temperature ratio Solution : 1. The prefered size that follows from the Ranges of application is DN 600 2., 3., 4. From the ceiling stream rating diagram for the size DN 600 diffuser and a volume flow of 600 m 3 /h 1 the following values are evident: A-rated acoustic power level : 32 db ( 22 db considering the absorption of the room) Total pressure loss : 12 Pa 3 An installation clearance of : y = H - 1.80 = (3.50 m - 1.80 m = 1.70 m) 5 2 x 1.55 = 3.10 m 6 7 9 10 5. From the critical airflow distance with cooling an airflow distance of 1.90 m 8 results for diffuser size DN 600, a volume flow of 600 m 3 /h 1 and a temperature difference of 8. 7 i [ ] x + y [m] 6 Txy T x + y [m] 6 6. From the Induction Ratio diagram a lenght of the course of an airstream of (x+y) = 1.55 m + 1.70 m = 3.25 m and i = 28 6 + 4 7. From the Temperature Ratio diagram a temperature ratio of 0.07 10 results for the same lenght of the course of the airstream. 9 * For DN 400, 500, 600 and 800 8 1.1.1 DAL 359 Subject to technical changes. Version 14 / 08 / 2012

DAL 359 Specification 1- Description and physical characteristics 1.1 Square or round swirl air diffuser DAL 359 with adjustable air control clips made from ABS (black or white), arranged in radial. 1.2 Air control clips guarantee horizontal air flow 360 even with free suspension of the diffuser. 1.3 The edge of the front panel is suitable for both standard suspending ceiling and gypsum ceiling. 1.4 Front panel coating inside and outside according to RAL color chart. 1.5 Unless specified, items air control clips are supplied in black color. 3 - Mounting 3.1 The diffuser is complete with a plenum box from the manufacturer. The plenum made from galvanized steel 24 gages and should include a perforated plate. Plenum supported at each corner and the input at side or above the plenum. The interior borders of the plenum will be sealed with silicone. 4 - Balancing 4.1 Balancing of diffuser DAL 359 must be performed by a technician in HVAC systems. 4.2 The technician must factor in the air volume correction when a balometer is used (CFB factor) 2 -Performance 2.1 Diffuser performance DAL 359 is guaranteed by simulation software, indicating the pressure drop and sound power level generated and showing the nominal air velocity and the critical path of the flow depending on the initial temperature differential in heating mode, isothermal mode or cooling mode to 1.8 m above the floor or as requested by the engineer. 5 - Required quality : NAD Klima, DAL 359 model 2.2 The diffuser should provide comfort when in situation of variable air flow up to 25% of total flow. Subject to technical changes. Version 14 / 08 / 2012 1.1.1 DAL 359 9

Codification DAL 359 Product Q = Square - R = Round S = Standard swirl flow 1 = Flow on 1-side 2 = Flow on 2-side W = White blades B = Black blades O = without blades 9003 = White 9010 = Cream = RAL colours* (write the number of colour) Configuration Flow Blades Colour 400, 500, 600, 800 400, 502, 603, 800 Sizes DN (603 for 24''X24'' T-bar) Outer sizes DN S = Plenum with input on side T = Plenum with input on top X = Without plenum X = Without insulation I = With acoustic insulation F = With fireproof insulation and fireproof damper X = Without damper D = With damper (fot gypsum ceiling) Volet Plenum Insulation Damper DAL359 - Q - S - W - 9003-400 - 400 - S - X - X Example Notes : Blue : Standard *Write the number of 4-digits of the colour of RAL chart of colours. Any specification such as changing the height of the plenum or installing a firewall component, must be indicated. 10 1.1.1 DAL 359 Subject to technical changes. Version 23 / 08 / 2012

ING, St-Hyacinthe, Québec ING, St-Hyacinthe, Québec

www.nadklima.com NAD Klima 144, Léger St., Sherbrooke (Québec), Canada J1L 1L9 T : 819 780-0111 1 866 531-1739 F : 819 780-1660 info@nadklima.com