A Novel Approach using Adaptive Neuro Fuzzy based Droop Control Standalone Microgrid in Presences of Multiple Sources

Similar documents
ENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG

Frequency and Voltage Control Strategy of Standalone Microgrids With High Penetration of Intermittent Renewable Generation Systems

ANFIS CONTROL OF ENERGY CONTROL CENTER FOR DISTRIBUTED WIND AND SOLAR GENERATORS USING MULTI-AGENT SYSTEM

Simulation Modeling and Control of Hybrid Ac/Dc Microgrid

POWER QUALITY IMPROVEMENT BASED UPQC FOR WIND POWER GENERATION

Control Scheme for Grid Connected WECS Using SEIG

International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering. (An ISO 3297: 2007 Certified Organization)

The hierarchical three layer protection of photovoltaic generators in microgrid with co-ordinated droop control for hybrid energy storage system

Combined Inertia and De-loading Frequency Response Control by Variable Speed Wind Turbines

Grid Stability Analysis for High Penetration Solar Photovoltaics

STUDY ON MAXIMUM POWER EXTRACTION CONTROL FOR PMSG BASED WIND ENERGY CONVERSION SYSTEM

Intelligent Control Algorithm for Distributed Battery Energy Storage Systems

Comparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators

Statcom Operation for Wind Power Generator with Improved Transient Stability

Design and Implementation of Reactive Power with Multi Mode Control for Solar Photovoltaic Inverter in Low Voltage Distribution System

Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1

A STUDY ON ENERGY MANAGEMENT SYSTEM FOR STABLE OPERATION OF ISOLATED MICROGRID

Simulation Analysis of Closed Loop Dual Inductor Current-Fed Push-Pull Converter by using Soft Switching

Design and Modelling of Induction Generator Wind power Systems by using MATLAB/SIMULINK

Control Application of PV Solar Farm as PV- STATCOM for Reactive Power Compensation during Day and Night in a Transmission Network

A Novel GUI Modeled Fuzzy Logic Controller for a Solar Powered Energy Utilization Scheme

Design of Active and Reactive Power Control of Grid Tied Photovoltaics

A Novel DC-DC Converter Based Integration of Renewable Energy Sources for Residential Micro Grid Applications

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

Reactive Power Sharing Droop Control Strategy for DG Units in an Islanded Microgrid

Performance Analysis of Transmission Line system under Unsymmetrical Faults with UPFC

Use of STATCOM for Improving Dynamic Performance of Wind Farms Connected in Power Grid

IJREE - International Journal of Research in Electrical Engineering ISSN:

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

Experimental Resultsofa Wind Energy Conversion Systemwith STATCOM Using Fuzzy Logic Controller

Wind Farm Evaluation and Control

Wind-Turbine Asynchronous Generator Synchronous Condenser with Excitation in Isolated Network

Load Frequency Control of a Two Area Power System with Electric Vehicle and PI Controller

APPLICATION OF STATCOM FOR STABILITY ENHANCEMENT OF FSIG BASED GRID CONNECTED WIND FARM

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

Modeling and Neuro-Fuzzy Control of DFIG in Wind Power Systems for Grid Power Leveling

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter

Co-Ordination Control and Analysis of Wind/Fuel Cell based Hybrid Micro-Grid using MATLAB/Simulink in Grid Connected Mode

ENHANCEMENT OF TRANSIENT STABILITY OF SMART GRID

Implementation of Bidirectional DC-DC converter for Power Management in Hybrid Energy Sources

Effect of crowbar resistance on fault ride through capability of doubly fed induction generator

A New Control Algorithm for Doubly Fed Induction Motor with Inverters Supplied by a PV and Battery Operating in Constant Torque Region

COMPARISON BETWEEN ISOLATED AND GRID CONNECTED DFIG WIND TURBINE

Journal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E

Integration of Large Wind Farms into Electric Grids

International Journal Of Global Innovations -Vol.2, Issue.I Paper Id: SP-V2-I1-048 ISSN Online:

Power Flow Management and Control of Hybrid Wind / PV/ Fuel Cell and Battery Power System using Intelligent Control

DESIGN AND ANALYSIS OF CONVERTER FED BRUSHLESS DC (BLDC) MOTOR

STABILITY ANALYSIS OF DISTRIBUTED GENERATION IN MESH DISTRIBUTION NETWORK IN FREE AND OPEN SOURCE SOFTWARE

International Journal of Advance Research in Engineering, Science & Technology

Speed Control of BLDC motor using ANFIS over conventional Fuzzy logic techniques

The Effect Of Distributed Generation On Voltage Profile and Electrical Power Losses Muhammad Waqas 1, Zmarrak Wali Khan 2

Power Management with Solar PV in Grid-connected and Stand-alone Modes

Using energy storage for modeling a stand-alone wind turbine system

Dynamic Modelling of Hybrid System for Efficient Power Transfer under Different Condition

Behaviour of battery energy storage system with PV

Advance Electronic Load Controller for Micro Hydro Power Plant

Transient Stability Improvement of Squirrel Cage Induction Wind Turbine Generator using Plugging Mode

Performance Analysis of 3-Ø Self-Excited Induction Generator with Rectifier Load

ELECTRICAL POWER SYSTEMS 2016 PROJECTS

Analysis and Design of Improved Isolated Bidirectional Fullbridge DC-DC Converter for Hybrid Electric Vehicle

Fuzzy logic controlled Bi-directional DC-DC Converter for Electric Vehicle Applications

COMPARISON OF PID AND FUZZY CONTROLLED DUAL INVERTER-BASED SUPER CAPACITOR FOR WIND ENERGY CONVERSION SYSTEMS

Implementation Soft Switching Bidirectional DC- DC Converter For Stand Alone Photovoltaic Power Generation System

RESERVOIR SOLUTIONS. GE Power. Flexible, modular Energy Storage Solutions unlocking value across the electricity network

Speed Control of Dual Induction Motor using Fuzzy Controller

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

DYNAMIC BEHAVIOUR OF SINGLE-PHASE INDUCTION GENERATORS DURING DISCONNECTION AND RECONNECTION TO THE GRID

Multi-Port DC-DC Converter for Grid Integration of Photo Voltaic Systems through Storage Systems with High Step-Up Ratio

Study of DFIG based Wind Turbine for Reactive Power Generation Capability

This version is available at

Power Balancing Under Transient and Steady State with SMES and PHEV Control

Development of Novel Connection Control Method for Small Scale Solar - Wind Hybrid Power Plant

Small Electrical Systems (Microgrids)

Performance Analysis of Bidirectional DC-DC Converter for Electric Vehicle Application

Hybrid Energy Powered Water Pumping System

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor

Power Electronics & Drives [Simulink, Hardware-Open & Closed Loop]

VECTOR CONTROL AND DIRECT POWER CONTROL METHODS OF DFIG UNDER DISTORTED GRID VOLTAGE CONDITIONS

APPLICATION OF VARIABLE FREQUENCY TRANSFORMER (VFT) FOR INTEGRATION OF WIND ENERGY SYSTEM

Control System for a Diesel Generator and UPS

Reactive Power Sharing in Islanded Microgrid by Droop Control Method

ANFIS based MPPT and Droop Controller for Power Sharing in Interline Power System M.Gowri 1 V.Vinothkumar 2 Dr.K.Punitha 3

EMS of Electric Vehicles using LQG Optimal Control

Use of Microgrids and DERs for black start and islanding operation

Fuzzy Based Unified Power Flow Controller to Control Reactive Power and Voltage for a Utility System in India

Academic Year International/National Journal S.No Name of the Faculty Title of the Paper Name of the Journal

INVESTIGATION AND PERFORMANCE ANALYSIS OF MULTI INPUT CONVERTER FOR THREE PHASE NON CONVENTIONAL ENERGY SOURCES FOR A THREE PHASE INDUCTION MOTOR

Simulation and Analysis of a DFIG Wind Energy Conversion System with Genetic Fuzzy Controller

Improvement of Voltage Profile using ANFIS based Distributed Power Flow Controller

Hybrid Three-Port DC DC Converter for PV-FC Systems

OPTIMUM ALLOCATION OF DISTRIBUTED GENERATION BY LOAD FLOW ANALYSIS METHOD: A CASE STUDY

Implementation of FC-TCR for Reactive Power Control

ECEN 667 Power System Stability Lecture 19: Load Models

Electric Vehicles Coordinated vs Uncoordinated Charging Impacts on Distribution Systems Performance

Decoupling and Control of Real and Reactive Power in Grid-Connected Photovoltaic Power System

Transcription:

Powered by TCPDF (www.tcpdf.org) Scan to know paper details and author's profile A Novel Approach using Adaptive Neuro Fuzzy based Droop Control Standalone Microgrid in Presences of Multiple Sources Srinivas Singirikonda, B. Shalini ABSTRACT The frequency and voltage control strategy is applied for a Standalone micro grid with high penetration of intermittent renewable generation system. Adaptive Neuro Fuzzy logic Interface system (ANFIS) controller is used for frequency and voltage control for Renewable generation system. Battery energy storage system (BESS) is used to generate nominal system frequency instead of using synchronous generator for frequency control strategy. A synchronous generator is used to maintain the state of charge (SOC) of the BESS but it has limited capacity. For Voltage control strategy, we proposed reactive power/active power (Q/P) droop control to the conventional reactive power controller which provides voltage damping effect. The induced voltage fluctuations are reduced to get nominal output power. Simulation results prove the effectiveness of both frequency and voltage control and the outputs are represented in MATLAB SIMULINK software with ANFIS structure. Keywords: adaptive neuro-fuzzy interface system (ANFIS), battery energy storage system (BESS), state of charge (SOC), frequency control, Q/P droop control, standalone micro grid, voltage damping effect, voltage control. Classification: For Code: 090699, 080108 Language: English LJP London Journals Press LJP Copyright ID: 833323 ISBN 10: 153763156 ISBN 13: 978-1537631561 1 6 4 U K 2017. Srinivas Singirikonda, B. Shalini. This is a research/review paper, distributed under the terms of the Creative Commons Attribution- Noncommercial 4.0 Unported License http://creativecommons.org/licenses/by-nc/4.0/), permitting all non-commercial use. distribution, and reproduction in any medium, provided the original work is properly cited.

A Novel Approach using Adaptive Neuro Fuzzy based Droop Control Standalone Microgrid in Presences of Multiple Sources Srinivas Singirikonda α & B. Shalini σ I. ABSTRACT The frequency and voltage control strategy is applied for a Standalone micro grid with high penetration of intermittent renewable generation system. Adaptive Neuro Fuzzy logic Interface system (ANFIS) controller is used for frequency and voltage control for Renewable generation system. Battery energy storage system (BESS) is used to generate nominal system frequency instead of using synchronous generator for frequency control strategy. A synchronous generator is used to maintain the state of charge (SOC) of the BESS but it has limited capacity. For Voltage control strategy, we proposed reactive power/active power (Q/P) droop control to the conventional reactive power controller which provides voltage damping effect. The induced voltage fluctuations are reduced to get nominal output power. Simulation results prove the effectiveness of both frequency and voltage control and the outputs are represented in MATLAB SIMULINK software with ANFIS structure. Keywords: adaptive neuro-fuzzy interface system (ANFIS), battery energy storage system (BESS), state of charge (SOC), frequency control, Q/P droop control, standalone micro grid, voltage damping effect, voltage control. Author α: IEEE Member, Assistant Professor, TKRCET, Hyderabad, Telangana, India. σ : IEEE Student Member, M.Tech scholar TKRCET, Hyderabad, Telangana, India. II. INTRODUCTION Standalone micro-grids are generally exposed to frequency and voltage deviations. The grid becomes weaker than a conventional power system due to an isolated system. The high penetration of intermittent renewable generation such as PV and wind power makes problem [1], [2] worse. Mostly in an isolated power system, the diesel generator based on a synchronous generator which is used to generate nominal system frequency and voltage with the help of Adaptive Neuro-Fuzzy Interface system (ANFIS). The mapping point of an input to the output using Fuzzy Logic interface provides a basis from which decisions can be made and the patterns discerned. The SIMULINK software system can access the Fuzzy logic [3] test system in a block diagram. It describes all membership functions, logical operators and If Then rules. This control strategy is applied specially to penetrate the intermittent Renewable power generation to control the frequency and voltage for stable operation of the system. Several methods are being examined to support frequency control. The strategies enabling to dispatch wind power to operate in a similar manner of conventional power plant. Wind power is a fluctuating motive source, the effectiveness of active power control of wind turbine generators (WTG) will depend upon wind speed [4]. WTG's are supplemented with doubly fed induction generator (DFIG) to expand the flexibility of wind power procurement and enhance the controllability [5]. The control approach of DFIG is to set a point of active power at fixed pitch angle [6]. With the proper reference frame, I dr will come up with the electromagnetic 67

torque (T em ) against turbines mechanical torque (T mech ) at some rotor speed. Consequently, the torque difference between T mech and T em can make rotor to accelerate / decelerate. J dw r dt dw r dt = T mech T em = 1 2H (T m T e ) (1) (2) Where, w r - Rotor speed, J - Inertia of motion, H -Inertia constant (s). The primary frequency support from de-loaded wind turbines using variable droop was developed [7]. In micro-grids with high penetration of wind energy, the fluctuations in the wind form output due to variations in wind speed cause frequency disturbances. A frequency droop control was applied to PV power generation [8]. Even though the fuel cost is free but its cost of installation is high. PV's operate in the maximum power point tracking (MPPT) model to generate maximum income. However, as penetration of PV's increase the frequency regulation capability (mainly provided by synchronous generators) and inertia from synchronous generators decrease which lead to severe frequency fluctuations under some disturbances. Moreover, load changes can lead to some significant frequency deviations if PVs don t have frequency regulation capability. In order to avoid this, the PVs are designed with virtual governor to have frequency droop characteristics similar to that of synchronous generator. However, frequency control strategies using intermittent renewable generation are not beneficial economically. There are various ways to control voltage drop by installing regulators in substations, using online transformer tap changers, shunt capacitors, increasing the size of conductors etc. Some sensors, such as smart meters (SM) measure voltage in ref [9-10] and current at each branch send this information/ recorded data to the control center. Decentralized voltage control is another method which uses local data to control voltage issues. But this device operates independently and there is no communication between loads and the substation. The effect and the reliability must be maintained for these methods. The linear quadratic tracking method is one of the voltage control method used to obtain desired results. The voltage is considered at each node then the controller increases / decreases voltage to minimize the error. The monitoring of controller is based on entire system conditions. This process can be categorized as decentralized control, but it increases system complexity and it needs more study. Analyzing and modeling of power distribution would become more complex and time taking. Most control strategies have applied optimization algorithms to meet specific objectives, such as minimizing loss, improving voltage profile, mitigating voltage fluctuation, maintaining voltage within regulated limits [11]. However, these methods will never be perfectly accurate, since they are based on forecasting load demand, wind speed and solar irradiance. The voltage compensator, shunt capacitors, LQT methods which leads to increased additional cost. Q/V droop control is widely used for voltage compensation, but the compensation is triggered by sensing the voltage deviation. Section II describes about proposed methodologies and the control strategy which includes Q/V droop control and ANFIS controller are explained in Section III. The test system operation and its simulation results are observed in different cases in Section IV. III. PROPOSED METHODOLOGY In a remote power system, the Active power / frequency (P/F) and Reactive power / voltage (Q/V) droop control are used to generate nominal system frequency, voltage and some voltage compensation devices are used for control strategy. If the generating system units droop is increased, it's response to the system frequency deviation diminishes. However, frequency control 68

strategies using intermittent renewable generation are not beneficial, because they cannot make the most of their ability to utilize free energy. BESS is used to support the frequency of micro-grid. The system stability and operational security can be improved by using BESS [12]. By improving the controllability of RES generators BESS provides a resolution to overcome the frequency control issues. Q/V droop control is widely used for voltage compensation, but the compensation is triggered by sensing the voltage deviation. The recommended strategies include. 1. BESS is used to generate small system frequency instead of using diesel generators which does not depend on the mechanical inertia of a synchronous generator. 2. SOC (state of charge) of the BESS is used by the diesel generator at a convinced value and the reference significance of the SOC is adjusted to limit the output power of the diesel generators to within a permissible range. 3. Q/P droop power is added to the renewable generation which has damping effect to avoid voltage fluctuations induced by its own active power fluctuations. 4. Adaptive Neuro fuzzy logic controller reduces the frequency and voltage fluctuations and improves the system performance. IV. CONTROL STRATEGIES To maintain frequency and voltage control there are many strategies to conventional power plant. A frequency control droop was added to PV generation. But these control strategies are not economically beneficial, since they cannot, maximize their usage of free energy. So, by adopting BESS (Battery energy storage system) the control strategies enabling to support system frequency deviating from its nominal value [13]. With the aid of Active power/frequency (P/F) and Reactive power/voltage (Q/V) droop control and voltage compensation devices are applied to the isolated power system. The Q/V droop control is widely used for mitigating voltage fluctuations, since the voltage fluctuations are triggered by sensing the voltage deviation. 4.1 System configuration The proposed control strategy with ANFIS (Adaptive Neuro-Fuzzy Interface system) is tested on the below test system as shown in fig 1, which shows bus numbers, line parameters, loads and power generation system. The line parameters are calculated by considering the distance between the loads and the location of loads. The ratings of the power generation using diesel generator, wind power, PV power, BESS are 14, 9.7, 1, 15MW respectively. Fig. 1: Power System configuration block diagram The nominal system frequency and voltage are 50HZ and 11KV respectively and the load demands during the day are shown in the table-1. The inverters are modeled as two-level type and 69

sinusoidal pulse width modulation were adopted to generate gate signals of the inverter. Table 1: System Load Demand BUS NUMBER DAY(MW) NIGHT(MW) 2 3 1.5 3 2 1 5 1 0.5 6 1 0.5 8 2 1 9 0.2 0.1 10 0.2 0.1 11 0.1 0.05 12 0.5 0.25 TOTAL 10 5 4.2 Frequency Control Strategy BESS is used to generate nominal frequency instead of using synchronous generator. Hence the system frequency is directly related to rotational speed of the rotor. To overcome this weakness we proposed BESS rather than diesel generator to form system frequency [14]. The BESS controls the nominal system frequency with the switching mechanism of power electronic devices. BESS is chosen to fulfill the frequency control strategy through its chargeable characteristic. This enables BESS to take twice the amount of load change than any other devices with same rate of power. The rapid charging and discharging characteristics of BESS can respond immediately to the output power fluctuations of renewable generation system[15]. However, BESS can neither adjust its SOC nor implement frequency droop by using control scheme of figure 2. Fig. 2: Control scheme of the grid-side inverter of the BESS BESS should work in synchronization with Diesel Generator where the frequency, voltage and phase are to be matched. To generate nominal system frequency, the diesel generator should be controlled [16]. During normal operation of diesel generator in Fig.3, the switch is connected to node A, to maintain SOC at the reference value SOC ref and hence the diesel generator is controlled. SOC load control is same as the load frequency control of conventional method. SOC ref is chosen as 0.5PU. However, it can be adjusted by an operator to charge or discharge of the BESS. Fig. 3: Control scheme of the output active power of the diesel generator 70

The output limiter and the anti windup function are added at the output of the PI-controller to keep diesel generator output active power within specified range, from 0 p.u to 1 p.u. Hence the system frequency is mostly depending upon the BESS control strategy. The reliability problem may arise due to tripping action of BESS. To prevent this problem, the switch is connected to node B, when the BESS is tripped out of the system. During the node B connection of switch, the diesel generator is controlled same as conventional one. The output of the PI controller provides P di,ref, which is mechanical input to the synchronous generator, via a valve actuator and a diesel engine. T v and T d are the time constants of the valve actuator and the diesel engine with 0.05s and 0.5s respectively. P di is the output active power of the diesel generator. The diesel generator acts as secondary SOC control which is like frequency control, it supports the SOC rather than frequency. 4.3 Voltage control strategy The nominal system voltage is maintained by the excitation of the diesel generator. Unlike frequency, the voltage problem must be resolved locally. Fig.4 represents the Control scheme of the grid side inverter of the renewable generation system. To solve these voltage fluctuations caused by the intermittent renewable generation system, we propose Q/P droop control to the intermittent renewable generation system [17]. K QV = Q P rate V bus V base (3) Where v id and v iq are the inverter terminal voltage of the d- and q-components respectively, i id and i iq are the inverter terminal current of the d- and q- components, w s is the angular frequency of the system voltage, L f is the filter inductance, P and Q are the output active and reactive powers, K QP and K QV are the Q/P and Q/V droop coefficients, P o and Q o are the operating points of the active and reactive power,q maximum reactive power, V bus is the bus voltage where renewable generation is connected. Fig. 4: Control scheme of the grid side inverter of the renewable generation system Q o is set to 0, so that the generation system can operate in unity power factor when the voltage drop is not activated. K QV ranges between 0 and 25 by considering the capacity of power generation. Wind speed or solar irradiance is given to MPPT control scheme to generate reference active power value (P ref ). P ref, P measured value are given to PI controller converting it to i. i id,ref d which is parks transformation value. i id,ref is compared with i id value and the error is fed to PI controller generating V d *. It can be written as, V id,ref = V sd + V d * - ω s L f i iq (4) Q/P droop control is the comparison of active power whereas Q/V droop control is the comparison of voltage control. K QP, K QV are the Q/P and Q/V droop coefficients respectively. K QP and K QV convert the error to reactive power component. 71

Q ref = Q o + Q P + Q V (5) Where Q o is the operating point of reactive power and is set to zero. Again Q ref and Q are given to PI controller and generates i iq,ref. i iq,ref are compared with i q in the PI controller generating an error V q *. V = V * iq,ref q + V sq + ω s L f i id (6) Therefore, V id,ref and V iq,ref are fed as input to the dq-abc transformation and is converted into V iabc,ref using inverse parks transformation for sinusoidal pulse width modulation which generates six pulses for the inverter. The speed of the generator is taken as 1.2 P.U, pitch angle is 0 and the speed of the wind is 11m/s. Instead of using PI controller in the control schemes, Adaptive Neuro fuzzy logic controllers are used to improve stability and performance of the system. Solar irradiance is about 660W/m 2. By adding MPPT control scheme and Boost converters to maximize the utilization of free energy and to maintain constant output power. 4.4 Adaptive Neuro Fuzzy interface system (ANFIS) The Effective technique called ANFIS (Adaptive Neuro-Fuzzy Interface system) which was developed by Dr. Roger Jang. Among various functions of methodologies in soft computing, the fuzzy logic and Neuro computing has visibility, which leads to Neuro-fuzzy systems. We can use Fuzzy Logic Toolbox software with MATLAB software to solve problems with Fuzzy logic. The combination of Artificial Neural Network (ANN) and Fuzzy Interface systems (FIS) has attracted the interest of researchers in various applications. Fuzzy logic interface system is a mapping point to map an input space to output space from starting point to the ending for all. Fuzzy logic is an intriguing area of research because it has a premium quality of trading off among significance and precision. An adaptive neuro-fuzzy inference system (ANFIS) is a fuzzy system whose membership function parameters have been tuned using neuro-adaptive learning methods like those used in training neural networks. The backpropagation (BP) algorithm is used to trine the adaptive Neural network and 7*7=49 rule based fuzzy Logic command-line functions are used for training SUGENO-type fuzzy inference systems using given input/output training data [18] [19]. V. SIMULATION RESULTS To establish the effectiveness of the proposed control strategies, simulation results are observed during the day time in the standalone micro-grid with high penetration of renewable generation system. Voltage waveforms of PV, wind power, BESS and diesel generator are clearly presented in MATLAB simulation. The MATLAB simulation diagram for Adaptive Neuro Fuzzy Control Strategy for Standalone Micro Grid System with Multiple Renewable Sources show in Fig.5. Fig. 5: MATLAB simulation diagram of Adaptive NEURO fuzzy control strategy for standalone micro grid system with Multiple Renewable sources 72

Case I: Day time In day time, the speed of the wind ranges from 10.5 to 11.5 m/s and set to an average of 11m/s, the solar irradiance ranges at 660W/m 2. The active and reactive power of wind and PV are set to be 0.413 and 0.495 respectively. The BESS responds to any output fluctuations where as the diesel generator is used to maintain SOC, thereby supporting BESS. There are some oscillations of SOC at diesel level. This is due to slow Dynamics of diesel generator and output fluctuations of active powers of renewable generation systems. Without droop control, SOC decreases slightly due to small losses, such as filter and inverter switching losses. Using droop control method SOC fluctuations are reduced with the support of diesel generation. Although it fluctuations SOC is maintained at reference value. The frequency also deviates from its nominal value without droop but the deviations are reduced with droop control with this method. Fig. 6: Frequency control results for case I: (a) Active power of wind and PV (b) Active power of BESS (c) Active power of diesel generator (d) SOC (e) Frequency The Fig.6 Shows the output active power of PV and wind, and active power of BESS and diesel generator respectively without droop control, the diesel generator takes full response for the output fluctuation of the renewable generation system with droop control, BESS supports diesel generator to meet the power demand with P/F droop control method. Fig.7 shows reactive power of wind and PV power respectively without droop control, the renewable generation system has same power factor, but by applying Q/V droop control, the reactive power is controlled by compensating voltage deviation. By applying control method, the reactive powers of PV and wind are controlled, also mitigates the voltage fluctuation. Fig. 7: Voltage control results for case I: (a) Reactive power of wind power (b) Reactive power of PV power (c) Bus voltage of wind power (d) Bus voltage of PV 73

The bus voltage of PV and wind are kept closer to nominal value using Q/V droop control. However, the fluctuations are not effectively prevented. By adding Q/P droop control, the voltage fluctuations can be eliminated. The below fig 8 shows simulation results for Adaptive Neuro Fuzzy interface system (ANFIS) and PI-controller. ANFIS response rate is faster than PI controller and the simulation time to get output is less and easy to access. Fig. 8: Comparison of Active power with Adaptive Neuro Fuzzy logic controller and PI-controller during Day time Case II: Night time: At night time, the solar irradiance is 0 W/m 2 and the wind speed ranges from 7.1 to 10.2 m/s and set to an average of 8.5m/s. The reactive power K QP of wind and PV power are set to be as 0.473 and 0.514 respectively. Fig.10 shows output active power of PV and wind, also the output active power of BESS and diesel generator respectively. The output power response is like that of day time. While the output power diesel generator tends to fall in the simulation. At these times SOC ref is increased. The active power of diesel generator can be operated within allowable range. The frequency deviation becomes greater than during the day, the proposed method maintains the frequency at the nominal value. Fig. 9: Frequency control results for case II: (a) Active power of wind and PV (b) Active power of BESS (c) Active power of diesel generator (d) SOC (e) Frequency 74

Fig. 10: Voltage control results for case II: (a) Reactive power of wind power (b) Reactive power of PV power (c) Bus voltage of wind power (d) Bus voltage of PV The Fig.10 shows the voltage control of output power fluctuation of wind is greater than that during the day. The reactive power is compensated more since output power fluctuation of wind power is more during the day. Since there is no solar irradiance, the voltage fluctuations are prevented. The voltage of the PV power differs little between the droop and proposed method. In the below Fig.11, the violet color indicates the ANFIS controller output whereas the green color denotes the PI controller. Fig. 11: Comparison of Active power with Adaptive Neuro Fuzzy logic controller and PI-controller during Night time Case III: Worst Case (When there is no solar irradiance and wind speed): The worst case includes wind speed and solar irradiance varies from 0 to rated value. Since when solar irradiance has to be considered, the load demand is same as day time. Hence the K QP of wind and PV are set as 0.413 and 0.495 respectively based on day time data. Fig.12 shows active power of wind and PV power generation systems. However, frequency is maintained at nominal value. 75

Fig. 12: Frequency control results for case III: (a) Active power of wind and PV (b) Active power of BESS (c) Active power of diesel generator (d) SOC (e) Frequency Fig. 13: Voltage control results for case III: (a) Reactive power of wind power (b) Reactive power of PV power (c) Bus voltage of wind power (d) Bus voltage of PV The Fig.13 represents the voltage control simulation results. As a result, there are some deviations around some points but the proposed method performs better than others. The simulation results of Fig.14 show the comparison of both PI and Adaptive Neuro-fuzzy logic controllers even in worst case has better performance. Fig. 14: Comparison of Active power with Adaptive Neuro Fuzzy logic controller and PI-controller during Worst case 76

Case IV: Load change and Tripping of BESS We consider two cases (i) Load change (ii) Tripping of BESS for the frequency control strategy. Fig. 15 shows the load change in day time. There is a load decrement at 0.5MW at 3sec of time. SOC and frequency are maintained same as previous cases. Fig. 15: Load change simulation results for case IV: (a) Active power of BESS and diesel generator (b) SOC (c) Frequency Fig. 16: Comparison of Active power during load change with Adaptive Neuro Fuzzy logic controller and PI-controller The Fig.16 shows the load change simulation of Adaptive fuzzy controller scheme and PI controller. Taking Time (sec) on X-axis and Active power (MW) on Y-axis. Fig.17 represents the results for the case of tripping of BESS. The BESS is tripped out of the system due to fault maintenance etc. The diesel generator operates its operation by changing its switch when BESS trips out of the system. Fig.18 shows the Tripping of BESS simulation results of Adaptive fuzzy controller and PI controller scheme. 77

Fig. 17: BESS tripping simulation results for case IV: (a) Active power of BESS and diesel generator (b) Frequency Fig. 18: Comparison of Active power with Adaptive Neuro Fuzzy logic controller and PI-controller during BESS tripping Case V: Considering PV bus only In this case, we consider active power fluctuation of the PV system while the output of wind power system is kept constant for voltage control strategy which affects the PV power system bus. The PV power system shows results in fig 19 and the reactive power is limited. Fig. 19: Simulation results for case V: (a) Reactive power of PV power (b) Bus voltage of PV power 78

Case VI: Adjusting charge/ discharge of BESS BESS should be controllable for the energy efficiency perspective. By adjusting the ramp rate of SOC, BESS is controlled to output the desired level of active power. Fig.20 shows charging of SOC at 1MW and active power of BESS and diesel generator. Fig. 20: Simulation results for case VI: (a) Active power of BESS and diesel generator during charging (b) SOC during charging If the diesel generator increments its output power the ramp rate of BESS is consequently adjusted to discharge the BESS as shown in Fig.21 simulation output. In this way, the BESS can be controlled to maintain the desired amount of active power by adjusting ramp rate of SOC which includes the controller of diesel generator. Fig. 21: Simulation results for case VI: (a) Active power of BESS and diesel generator during discharging (b) SOC during discharging 79

Table 2: Comparison of results with and without controller Cases Without controller (pi controller) With adaptive neuro fuzzy logic controller Active power is 2.7MW at 1.4sec. Active power is 2.8MW at 1.2sec. The 1. Day time Frequency is 49.8HZ with some frequency is maintained 50HZ oscillations. SOC is 0.48P.U constant. SOC is 0.5P.U with less damp of oscillations and settles faster than PI Active power of wind and PV are Active power of wind and PV are 4MW, 2. Night time 3.8MW, Diesel generator is 3MW. Diesel generator is 3.2MW. Reactive Reactive power of wind is 0.48, and PV power of wind is 0.473, and PV is is 0.52. Bus voltage of wind and PV are 0.97 and 0.98 P.U 0.514. Bus voltage of wind and PV are 0.98 and 0.99 P.U 3. Worst case (No Active power is 2.6MW at 1.8sec time. Active power is 2.8MW at 1.5sec time. solar irradiance and Reactive power of wind and PV are Reactive power of wind and PV are wind speed) 0.413 and 0.495 MVAR 0.5and 0.8MVAR 4. i) Load change Active power is 4.9MW at 3.1sec of time Active power is 4.9MW at 2.8sec of time Active power is 2MW at 2.8sec of time ii) Tripping of BESS Active power is 2MW at 3.1sec of time and the frequency is maintained constant as 50HZ. VI. CONCLUSION To mitigate the problems of diminishing voltage and frequency fluctuations, Adaptive Neuro Fuzzy Interface system is used, which has quick response rate compared to PI-Controller. The response of BESS results in stable operation of the frequency without any deviation. For stable voltage control, Q/P droop control is added for reactive power controller of multiple Renewable generation system. The active power fluctuations are effectively prevented by voltage damping effect in the renewable generation. The output Active power of PI and Adaptive Neuro fuzzy controllers are compared and simulation results are observed on the graph during different cases. Simulation results are observed in MATLAB software by using these control strategies. The ANFIS controller improves system stability without any interruptions and produces effective performance. REFERENCES 1. D. Velasco de la Fuente, C. Trujillo, G. Garcera, E. Figueres, R. Ortega, Photovoltaic Power System with Battery Backup with Grid-Connection And an Islanded Operation Capabilities, IEEE. Trans. Ind. Electron., vol. 60, no. 4, pp. 1571 1581, Apr. 2013. 2. M. Park and I. K. Yu, Photovoltaic generation system simulation using real field weather condition, Journal of KIEE, vol. 5, no. 2, pp. 169 174, 2001. 3. D. Sumina, Fuzzy logic excitation control of synchronous generator, Master thesis, Faculty of electrical engineering and computing, 2005. 4. P. Keung, P. Li, H. Banakar, and B. Ooi, Kinetic energy of wind turbine Generators for system frequency support, IEEE Trans. Power Syst., vol. 24, no. 1, pp. 279 287, Feb. 2009. 5. J. Ekanayake, L. Holdsworth, and N. Jenkins, Control of DFIG wind Turbines, Power Eng. J., vol. 17, no. 1, pp. 28 32, Feb. 2003. 6. J. Ekanayake and N. Jenkins, Comparison of the response of doubly fed and fixed-speed induction generator wind turbines to changes in network frequency, IEEE Trans. Energy Convers., vol. 19, no. 4, pp.800 803, Dec. 2004. 7. G. Diaz, C. Gonzalez-Moran, J. Gomez- Aleixandre, and A. Diez, Scheduling of droop coefficients for frequency and voltage regulation in isolated micro-grids, IEEE 80

Trans. Power Syst, vol. 25, no. 1, pp. 489 496, Feb. 2010. 8. G. Lalor, A. Mullane, and M. O Malley, Frequency control and wind Turbine technologies, IEEE Trans. Power Syst., vol. 20, no. 4, pp. 1905 1913, Nov. 2005. 9. M. S. P. Carvalho, P. F. Correia, and Luı s A. F. M. Ferreira, Distributed reactive power generation control for voltage rise mitigation in distribution networks, IEEE Trans. Power Syst., vol. 23, no. 2, pp. 766 772, May 2008. 10. J. Schlabbach and D. Blume, Voltage quality in electric power system, Inst. Elect. Eng. Power Energy Ser., vol. 36, 2001. 11. Y.-J. Kim, Optimal control of DG output voltage considering switching operation of ULTC and SC in distribution power systems M.S. thesis, Dept. Elect. and Comput. Eng., Seoul Nat. Univ., Seoul, Korea, Aug. 2010. 12. Divya, K.C., Østergaard, J.: Battery energy storage technology for power systems an overview, Electr. Power Syst. Res., 2009, 79, (4), pp. 511 520. 13. Shayeghi, H., Shayanfar, H.A., Jalili, A.: Load frequency control strategies: a state-of-the-art survey for the researcher, Energy Convers. Manage., 2009, 50, (2), pp. 344 353. 14. Scott GW, Wilreker VF, Shaltens RK. Wind turbine generator interaction with diesel generators on an isolated power system. IEEE Trans Power App Sys 1984;103(5): 933 7. 15. Divya, K.C., ostergaard, J.: Battery energy storage technology for power systems an overview, Electr. Power Syst. Res., 2009, 79, (4), pp. 511 520. 16. T. Senjyu, Y. Miyazato, A. Yona, N. Urasaki, and T. Funabashi, Optimal distribution voltage control and coordination with distributed generation, IEEE Trans. Power Del., vol. 23, no. 2, pp. 1236 1242, Apr. 2008. 17. Serban, I., Marinescu, C.: Frequency control issues in microgrids with renewable energy sources. Proc. Int. Symp. Advanced Topics in Electrical Engineering (ATEE), Bucharest, Romania, May 2011, pp. 1 6. 18. Jang, J.-S. R., "ANFIS: Adaptive-Networkbased Fuzzy Inference Systems," IEEE Transactions on Systems, Man, and Cybernetics, Vol. 23, No. 3, pp. 665-685, May 1993. 19. Srinivas Singirikonda et al Int. Journal of Engineering Research and Applications ISSN : 2248-9622, Vol. 4, Issue 3( Version 1), March 2014, pp.389-395. 81