CALEFFI. Pressure independent control valve (PICV) 145 series 01262/14 GB B 51

Similar documents
Connection and regulation kit for HVAC terminal units

CALEFFI. Motorised temperature regulating unit for heating and air conditioning systems WYP UPM series 01254/17 GB

CALEFFI. Distribution manifold for radiant panel systems. 664 series 01260/14 GB

CALEFFI. Distribution manifold for radiant panel systems. 664 series 01260/18 GB. replaces 01260/14 GB

CALEFFI. Pre-assembled distribution manifolds for. heating and air-conditioning systems. 663 series 01065/18 GB. replaces dp 01065/06 GB.

CALEFFI. Direct supply unit for heating systems. 165 series 01237/17 GB. replaces dp 01237/15 GB. Function

ACCREDITED. brass EN CW617N brass EN CW614N brass EN CW614N, chrome plated PTFE PSU EPDM

CALEFFI. Composite manifolds specifically designed for radiant panel systems. 670 series 01126/18 GB. replaces dp 01126/11 GB.

CALEFFI. Motorised ball valve for central heating systems. 638 series 01196/18 GB. replaces dp 01196/12 GB

CALEFFI. Manifolds in composite specifically designed for radiant panel systems. 670 series 01126/05 GB. Function

FLOW RATE STATIC BALANCING Valves for radiators

CALEFFI. Motorised ball zone valves with 3-contact control BY series 01131/18 GB. replaces 01131/11 GB

COMPONENTS FOR SOLAR THERMAL SYSTEMS

CALEFFI. Modulating temperature regulating unit with distribution kit for primary circuit. 171 series 01153/15 GB. replaces 01153/07 GB

CALEFFI. Ball shut-off valve fitted for integrated flow rate measuring sensor. 111 series 01234/13 GB. (kpa) (mm w.g.) G (m 3 /h)

CALEFFI. Pre-assembled distribution manifold for radiant panel systems S1 series 01144/11 GB. Replaces 01144/07 GB.

COMPONENTS FOR SOLAR THERMAL SYSTEMS

Pressure Independent Control Valve

CALEFFI. Mixing valves and actuators series 01169/17 GB. replaces dp 01169/09. Function

V9000 PICV Pressure Independent Control Valve

CALEFFI. Solar pump stations 01166/14 NA. 278 and 279 series 01264/16 NA

CALEFFI. Pre-assembled distribution manifolds for radiant panel systems. series 663 & /05 NA. Function

THERMOSETTER Recirculation thermal balancing valve

Safety cap. Measuring probe. Seal. Operating principle. Advantages of balanced circuits. Balanced circuits have the following principal benefits:

THERMOSTATIC CONTROL HEADS:

CALEFFI. FLOWCAL Automatic flow balancing valve with polymer cartridge. 121 series 01141/11 NA. Function

FO-BV Series. Fixed-orifice balancing and control valves. Technical Data Sheet. WattsIndustries.com

Fan-coil valves Series

Direct/Factory Mounting Valve Set

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Product range. Technical specifications. Characteristic components

Terminator PICV. Technical Manual

TECHNICAL SPECIFICATIONS 63/2E DN15 Kvmax /4"E. ( 3 4"x18) 3/4"E

Technote. Frese OPTIMIZER - pressure independent 4-pipe coil control unit. Application. Benefits. Features.

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Important Product range Technical specifications

Technote. Frese OPTIMA Compact DN10-DN50 - pressure independent balancing & control valve. Application. Features. Benefits.

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Operating principle Application diagram. Regulator-actuator Wiring diagrams

CALEFFI. Hydraulic separator-manifold SEPCOLL. 559 series 01084/16 GB. replaces dp 01084/13 GB

132 Series. QuickSetter Balancing Valve with flow meter NA Function

R EGI S TERED. Function

Pre-assembled distribution manifolds for radiant panel systems

MOTORISED BALL VALVE. Uni/Bi-directional. patented. 3 points 2 points Price list root SR... SS... SY... Connection with ball valve.

2-port and 3-port ball valves PN 40

VP1000. Pressure Independent Control Valve. Product Bulletin

Type overview. R B2 en-gb subject to changes 1

Pressure Independent Control Series

1 DESCRIPTION 2 WORKING PRINCIPLE 2.1 REGULATION ST

BRONZE ZEUS PNEUMATIC ANGLE-SEAT VALVE

ZTV/ZTR. Externally threaded 2- and 3-way zone valves. Function. No leakage in closed position

Technote. Frese OPTIMA - Pressure independent control & balancing valve. Application. Features. Benefits.

TRF.. series spring return rotary actuators for CCV

DESCRIPTION 9.4 G 3/4"M

Pressure independent balancing and control valve

FlowCon Energy FIT System

Pressure Independent Control Series

2-port seat valves PN16 with flanged connection

TA-6-way valve. NPT threads. Standard control valves 6-way valve for change-over systems

CALEFFI. zone valves. Z series 01115/14 NA. Replaces 01115/11 NA. Function

PRESSURE CONTROL VALVES SABS 198

ZEUS type BRONZE PNEUMATIC ACTUATED VALVE

950x. Description. Part List

HERZ-Connect 4 / Compact Connect 4 & Commissioning Centres

2-port shutoff valves and 3-port changeover ball valves, PN 40, with internally threaded connection

VPI45..Q with pressure test points. Combi valves, PN 25

HERZ-Motorised flow controler

WAY MOTORISED COMPACT ZONE VALVES

Angle Seat Control Valve 7020

Combined automatic balancing valve AB-PM valve DN 10-32, PN 16

HERZ 7217 V. Integral Fixed Orifice Control Valve HERZ 7217 V. Data sheet 7217 V, Issue Size in mm. STRÖMAX Fig No DN L Lm Rp H SW kv kvs

Pressure Independent Control Valve ---PICV(FCU)

Static Balancing Valve

VZ*19* VZ219E, VZ319E, VZ419E VZ219C, VZ319C, VZ419C

Combined automatic balancing valve AB-PM valve DN 15-25, PN 16

CT3202.0_01 EN February 2018

Open/close ball valves 2-port and changeover ball valves 3-port, PN40

ZONE CONTROLE / 2-WAY

Product Sheet Pre-Fabricated Flushing Bypass Assembly for Terminal Applications Mini-Flush 40

PCS. HVAC Products. Technical submission. Type of Product

BUN: 3-way valve with male thread, PN 16

Pressure independent balancing and control valve AB-QM DN

Series V2001 Valves Clean Tech Type 3321CT Globe Valve with pneumatic actuator

VPI45.. VPI45..Q. Combi valves, PN 25. Building Technologies. VPI45..Q with pressure test points ACVATIX

VE VVG Series Electronic Two-way Valves Normally Closed

Overview of types. Characterised control valves, 3-way, with internal thread For closed cold and warm water systems

CALEFFI. HydroMixer motorized temperature mixing unit. 167 series 01239/13 NA. Function

Flow controller with integrated control valve (PN 16) AHQM - return and flow mounting

VE-S_15-32 Pressure Independent Balancing & Control Valves

Connection. k VS -Value m 3 /h

R o L. WAFER PATTERN V-PORT BALL VALVE stainless steel 465 series SILVER LINE. Operation. Description. Edition

CALEFFI. QuickSetter Balancing Valve with flow meter. Installation Tip

T Series (NPT) 2-Way and 3-Way Terminal Unit Zone Valves 1/2 3/4" 1. Applications. Features. Terminal Unit Zone Valves (NPT)

Hydrocontrol VFC cast iron, PN 16 Hydrocontrol VFR bronze, PN 16 Hydrocontrol VFN nodular cast iron, PN 25 Double regulating and commissioning valves

LF24-SR US TF24-SR US TFX24 US LF24 US. B3 B Three-way Characterized Control Valve, Chrome Plated Brass Ball and Brass Stem

Two-port seat valves with male thread, PN16

ANSI version. The valve closes when the differential pressure rises

Leakage rate. Valve body. U.S. Registered Trademark EN0B-0308GE51 R1002 Copyright 2002 Honeywell Inc. All rights reserved

Combi valves, PN 25. for rooms, zones, ventilation and air-conditioning systems

Powers Controls Powertop Two-Way Valves Normally Open

Preassembled manifolds with flow meter, series CPRFL

Components for central heating

Series 46 Self-operated Regulators Differential Pressure and Flow Limiters Type 46-5 Type 46-6

Transcription:

Pressure independent control valve (PICV) 145 series CCREDITED CLEFFI 012/14 GB ISO 9001 FM 21654 ISO 9001 No. 0003 Function The pressure independent control valve is a device composed of an automatic flow rate regulator and a control valve with actuator. The device can adjust flow rate and keep it constant in the presence of changing differential pressure conditions of the circuit in which it is installed. Flow rate is adjusted in two different ways: manually on the automatic flow rate regulator, to restrict the maximum value automatically by the control valve in combination with a proportional (0 V) or ON/OFF actuator, in accordance with the thermal load requirements of the section of the circuit to be controlled. The pressure independent control valve (PIVC) is supplied complete with connections for upstream and downstream pressure test ports for checking of operating conditions. The device can be used in airconditioning systems. Product range 145 series Pressure independent control valve sizes DN (3/8 and 1/2 ), DN ( and 1 ) 145014 Proportional linear actuator for 145 series control valve 24 V electric supply (ac/dc) Technical specifications Materials Body: dezincification resistant alloy EN 12165 CW602N Headwork: dezincification resistant alloy EN 12164 CW602N Control stem and piston: stainless steel EN 0883 (ISI 303) Obturator seat: PTFE Obturator: EPDM Pressure regulator membrane: EPDM Springs: stainless steel EN 03 (ISI 302) Seals: EPDM Gasket: nonasbestos fibre Preadjustment indicator: P6G30 Knob: P6 Performance Medium: water, glycol solutions Max. percentage of glycol: 30% Maximum working pressure: 16 bar Max. differential pressure with code 145014 actuator and 656 series thermoelectric actuators: 5 bar Working temperature range: 1 C. Nominal Dp control range: 400 kpa Flow rate regulation range: 0,4 m 3 /h m 3 /h 1,2 m 3 /h ccuracy: ±% Max. flow rate with 656 series thermoelectric actuator installed, reduced by: % Connections main: 3/8, 1/2,, 1 M EN 21 (ISO 7/1) with union; M (ISO 21) for code 145014 and thermoelectric 656 series actuators: M 30 p.1,5 pressure test ports: 1/4 F (ISO 21) with plug Technical specifications for actuator code 145014 Proportional linear actuator Electric supply: 24 V (ac/dc) Power consumption: 2,5 V (ac) 1,5 W (dc) Control signal: 0 V Protection class: IP 43 mbient temperature range: 0 50 C Supply cable length: 1,5 m Connection: M 30 p.1,5 Dimensions C C B 51 95 132 DN B C C Mass (kg) 145430... 3/8 8 55 96 0,53 145440... 1/2 1 55 96 0,57 145550... 123 55 96 0,70 145560... 1 132 55 96 0,77 145552... 68 55 96 0,47

Operating principle The pressure independent control valve (PICV) is designed to regulate a flow of fluid that is: adjustable in accordance with the requirements of the part of the circuit controlled by the device; constant despite any variation in differential pressure conditions in the circuit. b) Device (B) regulates flow rate G by changing its bore cross section. The change in bore cross section determines hydraulic coefficient value (Kv) of the regulator device (B), which remains constantly at: a manually preset value the value determined by the actuator s regulating action. The device layout is shown in the diagram below: B p 1 p 2 p 3 B Where: p 1 = upstream pressure p 2 = intermediate pressure p 3 = downstream pressure (p 1 p 3 ) = total valve Dp Simone B Concisely: Since G = Kv x Dp by manually or automatically adjusting device B, Kv value and consequently G value can be set; once G value has been set, it remains constant thanks to the action of () in response to circuit pressure changes. For the device to keep the flow rate constant independently from G the (m circuit s 3 /h) differential pressure conditions, total valve Dp (p 1 p 3 ) must be in the range from the Dp value (see Flow rate adjustment tables ) and the maximum value of 400 kpa. G G 8 G 6 G p 1 p 3 G 1 8 p2 G 6 kpa 30 kpa 400 kpa a) Device () regulates Dp i (p 2 p 3 ) and keeps it constant across the device (B) by means of an automatic action (balancing between the force generated by the differential pressure and the internal opposing spring). If (p 1 p 3 ) increases, the internal Dp regulator reacts to close the bore and maintains (p 2 p 3 ) = constant; in these conditions the flow rate will remain constant. G 1 kpa 30 kpa 400 kpa Flow rate accuracy + % G X % + % G X % kpa 30 kpa 400 kpa kpa 30 kpa 400 kpa

Construction details Materials in dezincification resistant alloy and stainless steel Valve body (1) and headwork (2) are made of dezincification resistant alloy while springs (3), control stem (4) and piston (5) are in stainless steel. These materials prevent phenomena of corrosion, guarantee accuracy, reliable performance over time and a use compatible with glycols and additives, which are often used in the circuits of air conditioning systems. 4 3 7 2 6 1 EPDM obturator EPDM obturator (6) provides a perfect seal in the case of complete closing of the valve for circuit shutoff. Compact and practical device The easytoinstall valve features reduced dimensions and compact lines. Protective knob (7) can be removed by hand easily for flow rate regulation purposes and actuator fitting. 5 3 Pressure test ports The valve is supplied with upstream and downstream connections for fastplug pressure test ports (Caleffi code 0000) (8), to be fitted in the connections with the system cold and not in pressure. Use with actuators The device is fitted to function with a proportional linear actuator (code 145014). When controlled by a regulator, the valve can modulate the flow rate in accordance with the system thermal load. During operation the valve Dp generated by the fluid flow can be measured (with the Caleffi differential pressure measuring station code 130005/6) (9). By comparing this value with the working Dp range, correspondence of the valve effective flow rate and the selected flow rate can be checked. Shutoff The knob can be used to shutoff the circuit zone controlled by the valve. 8 9 s an alternative to a proportional linear actuator, the valve can also be controlled with an ON/OFF type thermoelectric actuator for simpler temperature control logic. Installation versatility The valve without actuator can be installed in any position. With an actuator fitted the valve can be installed in any position except upside down.

djustment procedure Maximum flow rate adjustment Unscrew the protective plug by hand to gain access to the maximum flow rate adjustment nut (), which can be turned with a hexagonal wrench. The adjustment nut is fixed to a position graduated scale, divided into steps corresponding to 1/ of the maximum available flow rate, which is also shown on the scale (11). Turn the adjustment nut to the numerical position 12 corresponding to the required flow rate (design flow rate), referring to the Flow rate adjustment table. The notch (12) on the valve body is the physical positioning reference. Turning adjustment nut (), which determines the number associated with the djustment position, results in opening/closing of the bore cross section in the external 13 obturator (13). Hence, each bore cross section set on the adjustment nut corresponds to a specific Gmax x value. djustment position 8 6 Gmax x Gmax Gmax 8 Gmax 6 11 1 Gmax 1 12 kpa 30 kpa 400 kpa utomatic flow rate adjustment with actuator and external regulator fter adjusting the maximum flow rate, fit the actuator (0 V) code 145014 (14) to the valve. Under the control of an external regulator the actuator can automatically adjust the flow rate from the maximum set value (E.g.: Gmax 8 ) to the value in accordance with the thermal load to be controlled. The actuator acts on the vertical displacement of control stem (4). This results in additional opening/closing, on the maximum bore cross section, by the internal obturator (). For example, if the maximum flow rate has been set to position 8, the flow rate can be adjusted automatically by the actuator from Gmax 8 to completely closed (zero flow rate). 14 4 Flow rate adjustment curve The valve adjustment curve is of the linear type. n increase or decrease in the valve opening cross section corresponds to a directly proportional increase or decrease of the device s hydraulic coefficient Kv. This characteristic produces the following benefits: the flow rate can be finetuned to intermediate/partial values that can be fully controlled in terms of modulation for optimal tracking of changes in thermal load; automatic and servoassisted control is achieved with 0 V actuators, which are widely used for applications of this type. Gmax 8 75% Gmax 8 50% Gmax 8 % Kv max 0 90 80 70 60 50 40 30 0 0 1 2 3 4 5 6 7 8 9 (V) 0 30 40 50 60 70 80 90 0 % stroke

Flow rate adjustment table djustment position nut colour/range G DN Size 1 2 3 4 5 6 7 8 9 145430 H40 m 3 /h 145430 H80 0 m 3 /h 145440 H40 m 3 /h 145440 H80 0 m 3 /h 145550 H40 m 3 /h 145550 H80 0 m 3 /h 145550 1H2 1, m 3 /h 145560 H40 m 3 /h 145560 H80 0 m 3 /h 145560 1H2 1, m 3 /h 145552 H40 m 3 /h 145552 H80 0 m 3 /h 145552 1H2 1, m 3 /h 3/8 3/8 1/2 1/2 1 1 1,5,5,5,5,5,5,5,5,5,5,5,5,5 0,6 0,6 0,6,5,5,5,5,5,5,5,5,5,5,5,5,5,5 4,5,5,5 4,5,5,5 4,5,5 0,96,5 0,96,5 0,96,5,5 1,08,5 1,08,5 1,08,5 29 29 1,2 1,2 1,2 Minimum differential pressure required To choose the pump you need to add the pressure difference required by the device to the fixed head losses of the most disadvantaged circuit. This value corresponds to working range starting Dp min value shown in the table (H pump = Dp circuit + Dp min ). ccessories 130 Electronic flow rate and differential pressure measuring station. Supplied complete with shutoff valves and connection fittings. May be used for Dp measurements and setting of balancing valves. Bluetooth transmission between Dp measuring station and remote control unit. Versions complete with remote control unit with Windows Mobile or with ndroid application for Smartphones and Tablets. Measurement range: 0 00 kpa Static Pmax: 00 kpa. Electric supply from battery. 6562 6564 656212 656214 Voltage V 224 224 6562 tech. broch. 01198 Thermoelectric actuator. Normally closed. With opening position indicator. Quickcoupling installation with clip adapter. Electric supply: V (ac) or 24 V (ac)/(dc) uxiliary microswitch contact rating ( V). Power consumption: 3 W. Starting current: 1. mbient temperature range: 0 50 C. Protection class: IP 54. Electric supply cable: 80 cm. 130006 130005 complete with remote control unit without remote control unit, with ndroid application 0000 tech. broch. 041 Couple of quickfit pressure/temperature ports. Brass body. EPDM seals. Max. working pressure: 30 bar. Working temperature range: 5 130 C. Connections: 1/4 M. 656302 656304 656312 656314 6563 tech. broch. 01142 Thermoelectric actuator. Normally closed. With manual opening knob and position indicator. Electric supply: V (ac) or 24 V (ac)/(dc) uxiliary microswitch contact rating ( V). Running power consumption: 3 W. Starting current: 1. mbient temperature range: 0 50 C. Protection class: IP 40. Electric supply cable: 80 cm. Voltage V 24 24 lternatively, a 6561 series thermoelectric actuator can be used

Pressure independent control valve applications ( ) To ensure that the required amount of medium flows through each terminal. To guarantee the design flow rates (with open or closed valve) to the various zones of a system. SPECIFICTION SUMMRY 145 series Pressure independent control valve (PICV). Size DN (and DN ). Main connections 3/8 (from 3/8 to 1 ) M (ISO 7/1) with union; M (ISO 21). Pressure test port connections 1/4 F (ISO 21) with plug. Connection for code 145014 and 656. series thermoelectric actuators M 30 p.1,5. Dezincification resistant alloy body and headwork. Control stem, piston and springs in stainless steel. Pressure regulator membrane, obturator and seals in EPDM. Gasket in sbestosfree fibre. Preadjustment indicator in P6G30. Knob in P6. Medium water and glycol solutions; maximum percentage of glycol 30%. Maximum working pressure 16 bar. Maximum differential pressure with actuator code 145014 (and 656. series) installed 5 bar. Working temperature range 1 C. Nominal Dp control range 400 kpa. ccuracy ±%. Maximum flow rate, with 656. series thermoelectric actuator fitted, reduced by %. Flow rate adjustment range 0,4 m 3 /h ( m 3 /h and 1,2 m 3 /h). 145014 Proportional linear actuator for 145 series control valve. Proportional linear actuator. Electric supply 24 V (ac/dc). Power consumption 2,5 V (ac), 1,5 W (dc). Control signal 0 V. Protection class IP 43. mbient temperature range 0 50 C. Connection M 30 p.1,5. Electric supply cable length 1,5 m We reserve the right to make changes and improvements to the products and related data in this publication, at any time and without prior notice. Caleffi S.p.. S.R. 229 n. 0 Fontaneto d gogna (NO) Italy Tel. +39 0322 8491 Fax +39 0322 863723 info@caleffi.com www.caleffi.com Copyright 14 Caleffi