Don t Discriminate: The importance of selective coordination in electrical installations

Similar documents
Selective Coordination

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

NEW SERIES OF ETIBREAK EB2 IN VIEW OF SELECTIVITY

Miniature & Moulded Case

4-Day Power System Analysis, Coordination, System Studies

Fuses still the best form of overload protection

Recommended Procedures

Selective Coordination Requirements

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Transformer Protection

FUSE: SAFE & RELIABLE

Selective Coordination Enforcement:

Cascading & Discrimination

PROTECTION OF THE BRANCH CIRCUIT

Selective Coordination

Electrical Protection

Technical Section: Miniature Circuit Breakers

Evaluating Selective Coordination Between

Sentry Technical. Miniature Circuit Breakers (MCBs) Standards and approvals. Description. Technical specification

Alternator protection, part 1: Understanding code requirements

Now - Up To 400A Mains!

Power systems Protection course

Shippensburg University

Safety, Reliability and Performance verified with the KEMA KEUR mark. Series G Moulded Case Circuit Breakers

Are the New 2005 NEC Selective Coordination Requirements Causing an Increase in Arc Flash Energies and Reducing Distribution System Reliability?

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current-Limiting Circuit Breakers

18 th Edition. Overload Protection of RCCBs and Switches within Consumer Units

FUSERBLOC CD. The universal Fuse Combination Switch FROM 20 TO 1250 A. Industrial Switching & Protection Systems

High Voltage Electrical Maintenance Training

Motor Protection Circuit Breakers 3VU13 and 3VU16

Selective main circuit breakers S 750 series Technical Data

ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy

Zone Selective Interlock Module. For GE Circuit Breakers

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data

The Cement Industry. How can Kinetrol help your business? Cement Manufacturing Process. Pneumatic Vehicle Unloading. Silo Discharge.

Fusesaver specification form

Effective discrimination of protective devices

Engineering Dependable Protection

www. ElectricalPartManuals. com Engineering Dependable Protection

Perfection that Matters

Advanced Protective Relay Training

Technical Journal September 2012

Terasaki (Europe) Ltd

Arc-Flash Mitigation Technologies. Dennis Balickie

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

Fused Coordination Panelboard

Miniature circuit breaker Application guide

Demand side support in power system control allowing to accommodate more renewable energy sources

Miniature Circuit-Breakers (MCBs)

Cascading. Complementary technical information

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

400/230 Volt 60Hz UPS Power

Industry Automation Control Components

Optimizing Emergency Power Systems for Health Care Applications

Rated Impulse withstand voltage U imp Main circuit Between terminals, AC3500V for 1 minute 12kV terminal group to earth Control circuits

Air Circuit Breaker Retrofitting

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay

Disturbance in electrical system is an abnormal

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

DESIGN AND RETROFITTING OF LOW VOLTAGE AIR CIRCUIT BREAKERS.

Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual

FUSE TECHNOLOGY Ambient temperature

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

Unit Protection System for Pumped-Storage Power Stations

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv)

FUSES. Safety through quality

Mar H: SUPPLEMENTAL PARALLELING GEAR (16315-H)

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

Thermal-Magnetic Circuit Breaker 2210-S291-P9M A

Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Utility Main Service Transformers

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

Miniature Circuit-Breakers (MCBs)

Technical information No. 01. IT systems. The basis for reliable power supply

ABB UPS 3. November 2014

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

GLOBAL CAT RENTAL POWER SOLUTIONS

A Special Note To Our Customers

BUILDING ELECTRICAL SERVICES DESIGN FOR A PROPOSED COLLEGE ADMINISTRATION BLOCK

MINIATURE CIRCUIT BREAKER

BRANCH CIRCUIT PROTECTION FUSED COORDINATION PANELBOARD

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

Research Challenges for Automated Vehicles

Fuseology. High Speed Fuses

4. CIRCUIT BREAKERS (Continued)

CHINT. NM7 Moulded Case Circuit Breaker

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications

Potential Negative Impact on Reliability of Distributed Generation under Temporary Faults

THE PROTECTION OF INDUSTRIAL CAPACITOR BANKS BY CURRENT LIMITING FUSES. By M.J. Smart and B. Wadcock

Phase + Neutral, neutral on left side

Electronic Resettable Sectionalizer

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

Self-protected Combination Starters System PKZ 2-SP

Life cycle services for protection and control relays Full support from start to finish

Secondaries. arc flash note Introduction. By Mike Lang, engineer and. Services Supervisor

Redflow Telco Application Whitepaper

Manual motor starters Overview and benefits

Thermal system protection of switchgear through high voltage fuse links with integrated temperature limiter under consideration of IEC 420:1990

Transcription:

Don t Discriminate: The importance of selective coordination in electrical installations Prepared by: Design Engineer: Anthony Unsworth anthonyunsworth@sudlows.com

What is Discrimination? Discrimination, is the practice of selecting protective devices and adjusting their settings in order to limit interruption to electrical installations under fault conditions. When the devices in a distribution path are coordinated it reduces nuisance tripping and makes it easier to identify where a fault has occurred. Hence, why it is also referred to as Selective Co-ordination. This design practice does not always receive its due attention and can be overshadowed by impressive critical power systems when designing data centres, especially in an industry which is dominated by UPS systems, emergency backup generators, redundant components and diverse distribution paths. The current requirements for Discrimination are outlined under section 536 of BS 7671 Wiring Regulations and are brief in their content. Regulation 536.2 states that: Where selectivity between overcurrent protective devices is necessary to prevent danger and where required for proper functioning of the installation, the manufacturer s instructions shall be taken into account. Fig 1: Electrical system showing Discrimination/coordination of circuit breakers

Business Downtime Loss of power can have a tremendous impact on business, especially in a mission critical environment, where interrupted business operations can culminate in serious financial implications. To cite an example, in 2012 a major UK bank suffered from an IT crash which resulted in a 56 million fine and cost a further 175 million in compensation and response. Following an investigation, the incident was put down to a very poor legacy of IT resilience and inadequate management of IT risks. Incidents such as these emphasise the need for correct coordination of circuit breakers and by doing so, a further crucial line of defence against unplanned downtime is provided. Essentially, if a protective device nearest to an electrical fault is operated without disturbing any upstream connected devices, this will improve reliability of the electrical distribution and maximise a facility s uptime. Achieving Discrimination There are two main forms to consider when understanding Discrimination:Time Discrimination and Current Discrimination. Time Discrimination works on adjustable time delay settings incorporated into the circuit breakers. These settings are adjusted in the upstream devices so that a given current value will trip the device after the delay. When using this method, the circuit breakers must be able to withstand the thermal and electrodynamic effects of the fault current during the delay period. Current Discrimination can also be divided into two types: Overload Discrimination and Short Circuit Discrimination.

Overload Discrimination is undertaken by selecting an upstream device with a higher current rating and instantaneous pickup level than the next downstream device. Short Circuit Discrimination is based on the principle that if a fault is close to the main source of supply, the prospective fault current will be higher. Therefore, Discrimination can be achieved by setting a circuit breaker to a limit that does not cause unnecessary trips. The most effective method of undertaking selective coordination is to observe the time/current curves which are produced by the manufacturers of circuit breakers. These show the characteristics of a protective device on a graph which can be overlaid with other devices in a distribution system to compare curves. If the curves, each representing a different device, overlap then Discrimination is not achieved. The parameters or settings of a circuit breaker can then be adjusted or breakers can be changed for different types so that the curves do not overlap. The separation between the curves means that Overload Discrimination has been achieved. In addition to Discrimination, another subject related to the coordination of circuit breakers is Backup Protection or Cascading. This is when an upstream device combines to enable a downstream device to break fault currents which are greater than its rated breaking capacity, protecting them from damage. Fig 2: Time/current curve demonstrating lack of Discrimination between devices

Fig 3: Time/current curve demonstrating Discrimination achieved between devices This process has been simplified by the creation of computer software packages which store the manufacturer s technical data for thousands of different types of protective devices. This way, the tripping characteristics of an electrical distribution system consisting of a combination of fuses, Moulded Case Circuit Breakers (MCCB s) and Minature Circuit Breakers (MCB s) can be quickly simulated and coordinated. Conclusion Electrical engineers will know that full discrimination cannot always be achieved between a set of protective devices and nor is it a requirement of BS 7671 to do so. It can prove to be impracticable and expensive when selecting types of devices in order to discriminate, especially where there are multiple levels of devices. Nevertheless, it is vital that a discrimination study is undertaken during the design period to ensure that the installation is as reliable as possible. Of course, a survey requires an engineer s time to produce and additional costs can be incurred with breaker enhancements and adjustment of their settings on site. However, it s a small price to pay for a business or facility where the main objective is to maintain power and avoid costly power outages.