User Manual Rittal PMC UPS 6kVA

Similar documents
1. INTRODUCTION SYSTEM DESCRIPTION Front Panel CONNECTION AND OPERATION TROUBLESHOOTING...8

USER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION... 4

USER MANUAL ONLINE UPS

USER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION SYSTEM DESCRIPTION... 4

USER MANUAL. PowerMust 1080 LCD (1KVA), Online, IEC PowerMust 2016 LCD (2KVA), Online, IEC PowerMust 3024 LCD (3KVA), Online, IEC

User Manual V1.1 OptiFlex 1100 / OptiFlex 2000

On Line UPS. LUC 1000E / LUC 2000E / LUC 3000E User Manual

User Manual. PF0.9 1K/2K/3K Online UPS. Uninterruptible Power Supply System. Version: 1.3

ULTIMA W SERIES. 1K/2K/3K Online UPS USER MANUAL

CONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION INVERTER OPERATION...

USER MANUAL DN / DN

User Manual V1.0 MaxiFlex 3000

User Manual Digital Energy Uninterruptible Power Supply ML Series UPS VA GE Digital Energy Power Quality

Liebert GXT MT+ User Manual VA Installer/User Guide

Users Manual. Defender 1 8.0KW to 14.0KW Online Emergency Lighting Inverter. Technical Manual # Revision B

User Manual. Digital Energy Uninterruptible Power Supply ML Series UPS VA. GE Digital Energy Power Quality. GE imagination at work

Users Manual. Cobra Plus Stand-By Emergency Lighting Inverter. Technical Manual # Revision B

1. Important Safety Warning

Centurion 1000/1500/2000/3000 Tower/Rackmount On Line UPS User s manual

Operating manual UPS - System

CONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION OPERATION... 9

NEWTECH PRO X KVA DSP LCD 1/1 ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL

User M anual. Rack/Tower Online UPS 1K/1.5K/2K/3K

Match 19" GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match 19" UPS.

Uninterruptible Power System

OPERATING INSTRUCTION UPS PROTECT A. PROTECT A PROTECT A. 1400

BRAVER UPS. (Uninterruptible Power System) User s Manual

User Manual. 6K/10K Online UPS. Uninterruptible Power Supply System

User Manual. PF0.9 6K/10K Online UPS

Thank you for choosing EATON products. Safety information and operating instructions are included in this manual. Do not attempt to operate the UPS

C VA. Tower VA. Installation/Manual. Service and support T: +44 (0)

USER MANUAL. E4 LCD TX 5000(S) / 6000(S) / (S) With Output Isolation Transformer. Uninterruptible Power Supply System

Pure sine wave charger inverter Product Manual

Technical Specifications. Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER

User Manual. NetGuard IMPORTANT. PSD 650/1200/1600 Line Interactive UPS Uninterruptible Power Supply System. UPS Monitoring Software

USER MANUAL. Blazer Vista 1000/1400/2000. Uninterruptible Power System

USER MANUAL ONLINE UPS 6000L(XL)/10000L(XL) Uninterruptible Power Supply

Uninterruptible Power System

Uninterruptible Power System

POWER TROLLEY 8 INSTRUCTION MANUAL POWER TROLLEY 8. Model: SINE Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System

General Precautions. Personnel Precautions

Technical Specification SENTINEL PRO

User Manual 1KVA/ 2KVA/ 3KVA INVERTER / CHARGER

User Manual. EGL - 6K/10K Online UPS. Uninterruptible Power Supply System

Uninterruptible Power Supply

User Manual. 6K/10K Online UPS with Isolation Transformer. Uninterruptible Power Supply System

USER MANUAL. IPS home inverters with UPS function. IPS home inverter manual

TECHNICAL SPECIFICATION FOR ENERGY STORAGE SYSTEM REV 6.0

1000VA/1500VA/2000VA/3000VA

FRUK+19 6K / FRUK+19 10K FRUK RM-01V / FRUK RM-01V

User Manual. 1P-1P 6KL/7.5KL/10KL Online UPS

User Manual Easy UPS BV Series 500VA, 650VA, 800VA, 1000VA Safety and General Information

Outdoor UPS. User Manual. Contents. Please read carefully this manual before installing and using this product. 1 Introduction Safety...

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

User Manual. 3/1 10K/20K Online UPS with Isolation Transformer. Uninterruptible Power Supply System

Installation Guide Smart-UPS On-Line SRT1000/SRT1500 XLA Tower/Rack-Mount

User Manual 1KVA-5KVA INVERTER / CHARGER

Installation and Operation Manual. RTA Series 1KVA to 3KVA Models Uninterruptible Power Systems (UPS)

The Ultimate UPS Security Concept

12 amp RMS Battery Charger

TACOMA HT 1K-3KVA On-Line UPS USER MANUAL

DC AC POWER INVERTER. LIV 10 / LIV 20 / LIV 30 User Manual

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD

Centurion. 6000/10000 VA Rack Online UPS. Users Manual.

USER MANUAL. PowerMust 1400/2000 LCD. Uninterruptible Power System

User Manual 200Ah INVERTER / CHARGER

User manual. Solar Hybrid 1-5KVA. Uninterruptible Power Supply / Charger

USER MANUAL. Power GUARD UPS. Uninterruptible Power System

800VA/ 1000VA/ 1200VA/ 1500VA 2200VA/ 3000VA USER S MANUAL

UPS USER MANUAL F-18 ONLINE DOUBLE-CONVERSION UPS. 1kVA/2kVA/3kVA

NB NB 1511 NB NB 4031 TRUE ON-LINE DOUBLE CONVERSION UPS

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Uninterruptible Power System

Manual for Inverter system type PCI05

Pulsar EXtreme CLA 1500C

Uninterruptible Power Supply ERA LCD 0.65 ERA LCD 0.85 ERA LCD 1.1. User s manual

USER MANUAL. Uninterruptible Power Supply Line-interactive VCL Series UPS VA

User Manual. 6K/10K Online UPS with Isolation Transformer

LIFT 1500 VA UNINTERRUPTIBLE POWER SUPPLY UPS USER MANUAL

User Manual SOLARMAX 1KVA/ 2KVA/ 3KVA INVERTER / CHARGER

USER MANUAL 3/3 10K~20K Online UPS

Solar Hybrid Inverter SP Brilliant Series

UTILITY INPUT MAINS OUTLET

USER MANUAL MPS 1-5KW SERIES

Ultra Sine Inverter (US) Generation 4 (G4) User Guide

User Manual 1KVA-5KVA (PF1) INVERTER / CHARGER. Version: 1.0

55185 EMERGENCY PACK FOR LED PANEL TECHNICAL DATA SHEET

Technical Data Sheets

User Manual 5KVA/5KW INVERTER / CHARGER. Version: 1.3

Solar inverter with MPPT AX II - M series: 4 / 5 kva, AX II - P series: 3 kva. With integrated star point grounding* according to VDE AR-E 2510-

MP V 8A Electronic Smart Charger. Instruction and Information Manual

1-50 KVA SINGLE-PHASE SERVO REGULATOR INSTRUCTIONS FOR USE SERVO SINGLE-PHASE VOLTAGE REGULATOR

User Manual / Manuel utilisateur

User manual Digital Energy Uninterruptible Power Supply GT Series UPS 6-10 kva

User Manual 1.5KVA-3KVA INVERTER / CHARGER. Version: 1.1

Limousin II User Manual

Technical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality

SAVER DSP SERIES. 3-10kVA USER MANUAL

Operating instructions EWB 200

Transcription:

User Manual Rittal PMC UPS 6kVA Germany Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Tel.: ++49-27 72-5 05-0 Fax: ++49-27 72-5 05-23 19 Internet: www.rittal.de 26

Contents 1. Introduction... 29 2. Safety Instructions... 30 3. Indicators and Operating Controls... 33 3.1 Front Panel... 33 3.2 Back Panel... 35 4. Installation and Start Up... 36 4.2 Permanently connected unit RITTAL PMC UPS 6KVA... 36 4.3 Battery extension... 40 5. Troubleshooting... 42 6. Maintenance... 45 6.1 Operation... 45 6.2 Storage... 45 7. Technical data... 46 7.1 Electrical specifications... 46 7.2 Typical stored energy time (Battery mode)... 47 7.3 Dimensions and weights... 47 7.4 Operating environment... 47 7.5 Port connectors... 48 7.5.1 RS232 interface... 48 7.5.2 Relay interface (Option)... 48 8. Appendix... 26 27

List of Figures Figure 1: Operating and display panel... 33 Figure 2: Slide buttons to select output voltage.... 35 Figure 3: Attaching the stabiliser to RITTAL PMC UPS 6KVA... 37 Figure 4: Connection diagram for RITTAL PMC UPS 6KVA... 38 Figure 5: Connection of battery extensions to RITTAL PMC UPS 6kVA.... 40 Figure 6: Circuit diagram of relay interface... 49 Figure 7: Front and back view of RITTAL PMC UPS 6KVA... 51 Figure 8: Back view of battery extension for RITTAL PMC UPS 6KVA... 52 28

1. Introduction The Rittal PMC UPS 6kVA Series is an uninterruptible power supply incorporating double-converter technology. It provides perfect protection specifically for Novell, Windows NT and UNIX servers. The double-converter principle eliminates all mains power disturbances. A rectifier converts the alternating current from the socket outlet to direct current. This direct current charges the batteries and powers the inverter. On the basis of this DC voltage, the inverter generates a sinusoidal AC voltage which permanently supplies the loads. Computers and periphery are thus powered entirely independently of the mains voltage. In the event of power failure, the maintenance-free batteries power the inverter. This means an end to the switchover times from mains to battery operation which cannot be avoided on other systems. 29

2. Safety Instructions PLEASE READ THROUGH AND FOLLOW THE USER MANUAL AND THE SAFETY INSTRUCTIONS BEFORE INSTALLING THE UNIT AND STARTING IT UP! Transport Please transport the UPS system only in the original packaging (to protect against shock and impact). Set-up Condensation may occur if the UPS system is moved directly from a cold to a warm environment. The UPS system must be absolutely dry before being installed. Please allow an acclimatisation time of at least two hours. Do not install the UPS system near water or in damp environments. Do not install the UPS system where it would be exposed to direct sunlight or near heat. Do not block off ventilation openings in the UPS system s housing. Installation Please note the special installation aspects for the permanently connected units Rittal PMC UPS 6kVA in Chapter 4 Installation and Start Up. The building wiring socket outlet (shockproof socket outlet) must be easily accessible and close to the UPS system. 30

Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS system. Do not connect domestic appliances such as hair dryers to UPS output sockets. Do not connect appliances or items of equipment which would overload the UPS system (e.g. laser printers) to the UPS outlet socket. Place cables in such a way that no one can step on or trip over them. Operation Do not disconnect the mains cable on the UPS system or the building wiring socket outlet (shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads. The UPS system features its own, internal current source (batteries). The UPS output sockets may be electrically live even if the UPS system is not connected to the building wiring socket outlet. In order to fully disconnect the UPS system, first press the Standby switch then disconnect the mains lead or, on the permanently connected unit Rittal PMC UPS 6kVA, isolate the incoming feeder. Ensure that no fluids or other foreign objects can enter the UPS system. Maintenance, servicing and faults The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel. 31

Caution - risk of electric shock. Even after the unit is disconnected from the mains power supply (building wiring socket outlet), components inside the UPS system are still connected to the battery and are still electrically live and dangerous. Before carrying out any kind of servicing and/or maintenance, disconnect the batteries and verify that no current is present. Only persons adequately familiar with batteries and with the required precautionary measures may exchange batteries and supervise operations. Unauthorised persons must be kept well away from the batteries. Caution - risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present! Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specified below and any other measures necessary when working with batteries: - remove wristwatches, rings and other metal objects - use only tools with insulated grips and handles. When changing batteries, install the same number and same type of batteries. Do not attempt to dispose of batteries by burning them. This could cause battery explosion. Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic. Please replace the fuse only by a fuse of the same type and of the same amperage in order to avoid fire hazards. Do not dismantle the UPS system. 32

3. Indicators and Operating Controls 3.1 Front Panel Figure 1: Operating and display panel Switch ON - Switch Function 1. Turn on UPS system: By pressing the ON-Switch I the UPS system is turned on. 2. Deactivate acoustic alarm: By pressing this switch an acoustic alarm can be deactivated. 33

Standby- Switch Display LINE LED BATTERY- LED BYPASS- LED INVERTER -LED FAULT- LED The UPS system switches to Standby mode when the Standby button is pressed. It is then switched to Bypass and the inverter is off. The output sockets are supplied with voltage via the bypass if the mains power supply is available. Function 1. The green LINE LED lights up if mains voltage is applied to the UPS input. 2. LINE_LED blinks when the phase and neutral conductor have been reversed at the input of the UPS system. 3. If LINE-LED and BATTERY-LED light up, the mains power supply is out of tolerance. The orange-coloured BATTERY-LED lights up when the mains power supply has failed and the inverter is being powered by the batteries. The orange-coloured BYPASS LED lights up when the UPS system is supplying voltage provided by the mains power supply system via the bypass. The green INVERTER LED lights up if the inverter of the UPS is operating and supplying the UPS output with energy. The red FAULT-LED lights up and an acoustic warning signal is issued every second when the UPS is overloaded (load exceeds the maximum power of the UPS). The red FAULT LED lights up and an acoustic warning signal is issued when the UPS system is in fault condition. Press the Standby switch in order to turn off the warning tone. 34

35

Load and battery capacity LED 1. These LEDs signal the UPS system load if the mains power is available (normal operation): 1st LED 1-35 % 2nd LED 35-55 % 3rd LED 55-75 % 4th LED 75-95 % 5th LED 95-100 %. 2. In the case of battery operation, the LEDs indicate the capacity of the batteries: 1st LED 1-35 % 2nd LED 35-55 % 3rd LED 55-75 % 4th LED 75-95 % 5th LED 95-100 %. 3.2 Back Panel Slide buttons on the back panel allow selection of the outgoing voltage of the UPS system. This can be changed only when the UPS system is switched off. Figure 2: Slide buttons to select output voltage. 36

4. Installation and Start Up 4.1 Permanently connected unit RITTAL PMC UPS 6kVA The system may be installed and wired only by qualified electricians in accordance with applicable safety regulations! When installing the electrical wiring, please note the nominal amperage of your incoming feeder. UPS> 6000 VA are not suitable for 16 A sub-distribution boards! 1) Inspect the packaging carton and its contents for damage. Please inform the transport agency immediately should you find signs of damage. Please keep the packaging in a safe place for future use. 2) Fit the supplied stabiliser, as shown in the illustration below, before installation: 37

Figure 3: Attaching the stabiliser to RITTAL PMC UPS 6KVA. The supports must be unscrewed adequately on both sides so that the castors are not contacting the ground! 3) Please ensure that the incoming feeder is isolated and secured to prevent it from being switched back on again. Set the I/P and the O/P switch on the back panel to position OFF. 4) Connect the UPS system to the mains at the screw terminals as shown in the diagram below: 38

Figure 4: Connection diagram for RITTAL PMC UPS 6KVA 5) Connect your computer to the screw-type terminals of the UPS system as shown in the above diagram. Caution! Do not connect equipment which would overload the UPS system (e.g. laser printers). Do not connect domestic appliances to the UPS system. 6) Set the I/P switch on the back panel to position ON. Note: Load capacity LEDs first light up simultaneously, then one after the other. After a few seconds the INVERTER-LED lights up and the BYPASS-LED turns off. 7) Fully charge the batteries of the UPS system by leaving the UPS system connected to the mains for 1-2 hours. You can also use the 39

UPS system directly without charging it but the stored energy time may then be shorter than the nominal value specified. 8) Set the O/P switch on the back panel to position ON. 9) Press the On button I on the front panel. Note: The INVERTER LED lights up after 10 seconds. The BYPASS LED then goes out and the ventilation system switches on. The UPS system is now operating correctly. 10) Test the function of the UPS system by either pressing the On button I or disconnecting the input of the UPS system from the power supply. Caution! The output sockets of the UPS system may still be electrically live even if the power supply system has been disconnected or if the I/P switch is in position OFF. 40

4.2 Battery extension External battery extensions are available for the UPS model. In order to connect them to the UPS system, proceed as shown below: 1. Disconnect the UPS system from the mains power supply and the load from the UPS system. 2. Connect the battery extensions to the UPS system with the included cables according to the following instructions: Figure 5: Connection of battery extensions to RITTAL PMC UPS 6KVA. 41

3. The UPS system can now operate normally. Note: Operating the system with external battery extensions prolongs charging to 24 hours with one battery extension and to 48 hours with two battery extensions after total discharge. 42

5. Troubleshooting If the UPS system does not operate correctly, please attempt to solve the problem using the table below. Problem Possible cause Remedy No indication, no warning tone even though system is connected to mains power supply No input voltage I/P switch has been disconnected Check building wiring socket outlet, check input cable Set the I/P switch to ON BATTERY- LED blinks LINE-LED blinks and BATTERY- LED lights up LINE-LED and BYPASS-LED light up even though the power supply is available Battery voltage < 12VDC per unit. Input power and/or frequency are out of tolerance Inverter not switched on When battery voltage > 12VDC per unit then clear warning signal. Check input power source and inform dealer if necessary Press On button I 43

INVERTER- LED lights up, warning tone at intervals (every 1 or 4 seconds) INVERTER-LED lights up, warning tone in intervals (1 to 4 seconds), mains power supply available Mains power supply has failed I/P switch disconnected Not necessary, battery operation; warning tone at intervals of 1 second means battery is almost empty Set the I/P switch to ON. If the problem persists, please inform your dealer. FAULT-LED lights up, warning tone once a second FAULT-LED lights up, permanent warning tone Emergency supply period shorter than nominal value Overload UPS-mistake Batteries not fully charged / batteries defective Reduce number of users at UPS output Notify dealer!! Charge the batteries for at least 1-2 hours. Check capacity. If the problem still persists, consult your dealer. 44

Please have the following information at hand before calling the After-Sales Service Department: 1. Model number, serial number 2. Date on which the problem occurred 3. Detailed description of the problem 45

6. Maintenance 6.1 Operation The UPS system contains no user-serviceable parts. If the battery service life (3-5 years at 25 C ambient temperature) has been exceeded, the batteries must be exchanged. In this case please contact your dealer. 6.2 Storage If the batteries are to be stored in temperate climatic zones, they should be charged every three months for 1-2 hours (see Chapter "Installation and Start Up"). You should shorten the charging intervals to two months at locations subject to high temperatures. 46

7. Technical data 7.1 Electrical specifications Model number INPUT Voltage Frequency Current (maximum) OUTPUT Power rating Voltage Frequency Wave form BATTERIES Number and type 6kVA 230 VAC (160 276 VAC) ± 3% 50/60 Hz ± 5 % automatic detection 29,6 A 6000VA 4200 W 220/230/240 VAC ± 0,5% (synchronized) 50/60 Hz ± 0,5 % (free-wheeling) Sinusoidal 20 x12v 7Ah The units bear the CE mark and comply with the following standards (limit value class B): EN 60950 (1992.8), EN 50091-1 (1994.4), pren 50091-3 (1994.4), EN 50081-1 (1992.2), EN 50082-1 (1992.2), IEC 801-2 Level 4, IEC 801-3 Level 3, IEC 801-4 Level 4, IEC 801-5 Level 2. 47

7.2 Typical stored energy time (Battery mode) Typical values at 25 C in minutes: Model 100 % Load 50 % Load RITTAL PMC UPS 6KVA 8 23 RITTAL PMC UPS 6KVA + 1 38 88 battery extension RITTAL PMC UPS 6KVA + 2 battery extensions 60 141 7.3 Dimensions and weights Model RITTAL PMC UPS 6KVA Battery extension for RITTAL PMC UPS 6KVA Dimensions W x H x D (mm) Net Weight, kg Gross Weight, kg 260 x 710 x 555 91 107 260 x 710 x 555 125 145 7.4 Operating environment Temperature: 3000 m Relative humidity: 10 C to 40 C, Installation height < 1500 m 0 C to 35 C, Installation height 1500 m to 20 to 90 %, no condensation 48

7.5 Port connectors A computer can be connected to the port connectors RS232 interface on the back panel of the UPS system.this allows the UPS system to be monitored, the mains system to be monitored, data to be backed up, the computer to be switched off and the UPS system to be switched off. There are various software packages for implementing these functions. Please consult your dealer for further details. 7.5.1 RS232 interface The 9-pin Sub-D connector (socket) makes an RS232 interface available. Description of the PIN assignment: Pin 2 RXD received data 3 TXD transmitted data 5 GND ground 7.5.2 Relay interface (Option) The 9-pin Sub-D connector (socket) makes a relay interface available. 49

Figure 6: Circuit diagram of relay interface Description of the PIN assignment: Pin No. Battery mode 2 normally open UPS shut-down in case of battery operation Battery capacity low PIN 2 is shorted to PIN 4 (ground) if the mains power supply fails or is out of tolerance. 6, 7 If, in the case of battery operation, a positive signal level (+5 V to + 12 VDC) is applied for 500 ms, the UPS system shuts down. 5 normally open PIN 5 is shorted with respect to PIN 4 if batteries have become discharged to such 50

Normal mode 3 normally closed an extent that the remaining emergency supply period at full load is less than 2 minutes. PIN 3 is shorted to PIN 4 during normal operation and opened, if the mains power supply fails or is out of tolerance 51

8. Appendix Figure 7: Front and back view of RITTAL PMC UPS 6KVA 52

Figure 8: Front and back view of RITTAL PMC UPS 6KVA BatteryPack 53