HGM1750 Genset Security Module USER MANUAL Smartgen Technology

Similar documents
HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...

USER MANUAL ZHENGZHOU SMARTGEN TECHNOLOGY CO.,LTD

HGM501 Gen-set Controller USER MANUAL. Smartgen Technology

HGM72 Automatic Generator Module OPERATING MANUAL Smartgen Electronic

HGM7100N SERIES (HGM7110N/7120N) GENSET CONTROLLER USER MANUAL

HGM6100K Series Automatic Generator Module OPERATING MANUAL Smartgen Electronics

HSC940 Genset Controller CONTENTS 1 OVERVIEW PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION KEY FUNCTIONS...

HGM6000K Series Automatic Generator Module OPERATING MANUAL Smartgen Electronic

HGM72 Automatic Generator Module OPERATING MANUAL Smartgen Electronic

HGM6000K Series Automatic Generator Module USER MANUAL Smartgen Technology

HGM6100N SERIES (HGM6110N/6120N/6110NC/6120NC/6110CAN/6120CAN) GENSET CONTROLLER USER MANUAL SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD.

HGM6310D/6320D AUTOMATIC GENERATOR MODULE USER MANUAL

HGM6320T AUTOMATIC GENERATOR CONTROLLER USER MANUAL

GENSET CONTROL MODULE

HGM6320T AUTOMATIC GENERATOR CONTROLLER USER MANUAL

HGM6400 Automatic Genset Controller (With J1939 Interface) USER MANUAL Smartgen Technology

HGM9520 Genset Parallel (With Mains) Unit USER MANUAL. Smartgen Technology

HAT220A ATS CONTROLLER USERS MANUAL

DEEP SEA ELECTRONICS PLC

HGM9510 GENSET PARALLEL (WITH GENSET) UNIT USER MANUAL

Deep Sea Electronics Plc

DKG-215 MANUAL AND REMOTE START UNIT

DEEP SEA ELECTRONICS PLC

HGM7110DC DC Genset Controller USER MANUAL ZHENGZHOU SMARTGEN TECHNOLOGY CO.,LTD

HGM6410/6420. Automatic Generator Module. With J1939 Interface OPERATING MANUAL. Smartgen Electronics

DEEP SEA ELECTRONICS PLC

DKG-317 MANUAL AND REMOTE START UNIT

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

DEEP SEA ELECTRONICS PLC

HGM6410/6420 AUTOMATIC GENERATOR MODULE WITH J1939 INTERFACE SOFTWARE MANUAL

Generator Sets Controller 210. Operation Manual. Ver1.0

DKG-207 AUTOMATIC MAINS FAILURE AND REMOTE START UNIT

DEEP SEA ELECTRONICS PLC

702 AUTOMATIC START MODULE OPERATING INSTRUCTIONS

Flight Systems. Replacement for KASSEC DESCRIPTION

DKG-114 MANUAL AND REMOTE START UNIT

DKG-509 AUTOMATIC MAINS FAILURE UNIT

DKG-109 AUTOMATIC MAINS FAILURE UNIT

Code: KOHLER KDI1903M MECC-ALTE ECP 28-M/4. VOLTAGE HZ PHASE COS Ø PRP kva/kw LTP kva/kw AMP. (LTP) 400/ ,8 18,9/15,2 20,8/16,6 30,07

DKG-109J AUTOMATIC MAINS FAILURE UNIT

DEEP SEA ELECTRONICS PLC

GCU-10. Automatic Engine Control Unit Operators Manual

GENSET CONTROL MODULE A121A / A241A

5220 AUTOMATIC MAINS FAILURE MODULE OPERATING MANUAL

GSC300 Auto Start Engine Controller

HAT700 Series HAT700/HAT700I/HAT700B/HAT700BI/HAT700S ATS CONTROLLER USER MANUAL

STANDARD OWNER S MANUAL

Code: FPT F32AM1A MECC-ALTE ECP 28-VL / 4. VOLTAGE HZ PHASE COS Ø PRP kva/kw LTP kva/kw AMP. (LTP) 400/ ,8 30,0/24,0 32,5/26,0 46,97 ESPAÑA

EPM72 Engine Protection Module

GSC300 Auto Start Engine Controller

Code: VOLVO TAD 731 GE MECC-ALTE ECP 34-2L/4. VOLTAGE HZ PHASE COS Ø PRP kva/kw LTP kva/kw AMP. (LTP) 400/ ,8 150,0/120,0 165,0/132,0 238,44

TG350 User Manual. Manual Revision: Min. FW Revision: Date Released: 09/01/ DYNAGEN Technologies Inc

PPU Diesel Power 50/60Hz Containerized Generator Set

OPERATING INSTRUCTIONS ECON-M

DKG-707 MULTI GENSET PARALLELLING UNIT WITH J1939 INTERFACE

GENSET CONTROL MODULE A121H / A241H. User selectable time delays for engine start and engine stop (cool down).

Engine Model: 4B3.9-G1 Engine Technical Data No. of Cylinders / Alignment: Cycle: 4 / In Line 4 Stroke Bore / Stroke: mm 102/120 Induction: Cooling Me

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

GENSET CONTROL MODULE LEVEL 1 A121CM / A241CM. Special logic to re-establish cranking following a false start.

DKG-705 AUTOMATIC MAINS FAILURE AND REMOTE START UNIT WITH PARALLEL TO MAINS AND DUAL GENSET PARALLEL FEATURES

Code: DEUTZ BF4M 1013 FC MECC-ALTE ECP 34-1L/4. VOLTAGE HZ PHASE COS Ø PRP kva/kw LTP kva/kw AMP. (LTP)

ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual

DSEULTRA DSE6000 Quick Start Guide Document Number

PowerView PV380-R2 Mechanical Configuration

DEEP SEA ELECTRONICS PLC

Deep Sea Electronics Plc

Code: KOHLER KDW 1404 ZANARDI ATO 28-1VS/4. VOLTAGE HZ PHASE COS Ø PRP kva/kw LTP kva/kw AMP. (LTP) 400/ ,8 10,0/8,0 11,0/8,8 15,9

DEEP SEA ELECTRONICS PLC DSE3210 CONTROLLER OPERATORS MANUAL

DGC-2020 DIGITAL GENSET CONTROLLER

USER MANUAL FOR GC500 GENSET CONTROLLER SEDEMAC ABSTRACT

Auto Mains Failure AMF Controller AE10113

AMF+ATS CONTROL PANEL

TE2010-GE Instructions manual

AUTOSTART 705S V1.00 AUTOSTART 710S / 720S / 730S V1.04 Programming Reference and Check Sheets

Deep Sea Electronics Plc

Annex A TECHNICAL SPECIFICATION FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF 400V (750KVA) DIESEL

DEEP SEA ELECTRONICS PLC DSEE100 Operator Manual

MB A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR

The measurements module provides the following engine features information:

PSM72H Push-Button Start Module

ICON 2 1. FEATURES AND CHARACTEIRICS

GENSET PRODUCTS 013 2

Code: VOLVO TAD 734 GE MECC-ALTE ECO 38-1LN. VOLTAGE HZ PHASE COS Ø PRP kva/kw LTP kva/kw AMP. (LTP) 400/ ,8 250,0/200,0 275,0/220,0 397,4

1 / Genset general description

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

The monitor can be placed on the dashboard, on the sun visor or mounted in any convenient place in the vehicle.

USERS MANUAL MCD REMOTE OPERATOR

GENSET CONTROL MODULE LEVEL 0 A120A. User selectable time delays for engine start and engine stop (cool down).

TG350 User Manual. Manual Revision: Min. FW Revision: Date Released: 18/12/ DynaGen Technologies Inc

LSP88S3. Powered by 50HZ. Water-cooled. Three Phase. Diesel KVA 88 KW 70. Standby Power

PREMIER POWER PACK INSTRUCTION MANUAL EN54-4 POWER SUPPLY UNIT INSTRUCTION MANUAL. GLT.MAN-138 Issue: /05/2016 N.R.P.J.

REVISED ATM72 Auto Transfer Module

Transfer switch GTEC open or delayed transition

WPS350/S EP Series. Features:

Energy Division

ALC-PRM-VFC. Ceiling Mounted Photocell. Product Guide. Overview. Features

EG1299. Variable Speed Engine Controller for Telecom Backup Gensets SEDEMAC EG1299 HIGHLIGHTS

Transcription:

HGM1750 Genset Security Module USER MANUAL Smartgen Technology

CONTENT 1. SUMMARY... 4 2. PERFORMANCE AND CHARACTERISTICS... 5 3. SPECIFICATION... 7 4. OPERATION... 8 5. PROTECTION... 9 6. PARAMETER RANGE AND DEFINATION... 11 6.1 PARAMETER DEFINITION AND RANGE... 11 6.2 PROGRAMMABLE INPUT... 13 6.3 SENSOR SELECTION... 14 7. CONNECTIONS... 15 8. CASE DIMENSIONS (PANEL CUTOUT 78*66MM)... 16 9. TYPICAL APPLICATION... 17

1. SUMMARY HGM1750 Genset Security Module is a security module that can display electrical parameters (e.g. voltage, speed, temperature, oil pressure and fuel level) and stop the unit when faults occurs (e.g. low oil pressure, high water/cylinder temperature, emergency stop and over speed). Graphical LCD monitor on the front panel displays fault conditions and provides effective alarm signals.

2. PERFORMANCE AND CHARACTERISTICS Based on microprocessor, fitted with LCD screen with graphic icons and blue backlight which can display engine parameters and alarms; Power supply range (8~35)VDC,compatibility with 12V or 24V starter batteries; Generator input port; speed, temperature, pressure, liquid level sensor input ports; digitalized electric quantity display. Measured and displayed electric quantity: Generator voltage V Generator frequency Hz Engine temperature ºC Oil pressure kpa Engine Speed rpm Total running time Battery voltage Fuel level Generator voltage, battery voltage, engine speed, temperature, pressure, liquid level threshold value can be set. Warnings and alarms are as following: High temperature Low oil pressure Low fuel level Generator over voltage Generator over frequency Over speed Emergency shutdown Fail to stop Charge Alt Fail Battery over voltage Battery under voltage The controller can be set as an engine controller via software (generator voltage input is deactivated); Running status and alarm status are indicated by red LED on the panel; Charging generator excitation function;

Engine speed can be calculated by generator frequency or speed sensor. Compatibility with multiple temperature, pressure, fuel level sensors, which can be user-defined and used directly; With digital input ports, users can choose different functions; All parameters of the controller can be modified through configurable LINK port via PC software (SG72 adapter, produced by our company must be used). All parameters can be set via computer using one USB port of the computer, which also allows to avoid batteries: power supply for the controller can come directly from the PC USB port; Modular design, anti-flaming ABS plastic casing, embedded installation, compact structure, small volume, advanced SCM control, stable performance and convenient operation.

3. SPECIFICATION Item Working Voltage Power Consumption Alternator Input voltage Alternator Frequency Magnetic Pickup Voltage Magnetic Pickup Frequency Max. accumulative run time Stop Relay Output Alarm Relay Output Content DC8. 0V to 35. 0V, Continuous Power Supply Standby mode: 12V: 0.3W, 24V: 0.4W Working mode: 12V: 1W, 24V: 1.1W 1P2W 30V AC ~ 360 V AC (ph-n) 50/60Hz 1V to 24V (RMS) Max. 10kHz 99999.9 hours (After decimal point there is 1/10 of an hour, and it changes every six minutes) 7Amp B+ power supply 7Amp B+ power supply Digital Input Active when connected to B- Case Dimensions Panel Cutout Working conditions Storage Condition Protection Level Insulation Intensity Weight 90mm x 78mm x 44mm 78mm x 66mm Temperature: (-25~+70)ºC Humidity: (20~90)%RH Temperature: (-30~+80)ºC IP55: When waterproof rubber gasket installed between the controller and panel fascia. IP42: When waterproof rubber gasket is not installed between the controller and panel fascia. Object: among input/output/power Quote standard: IEC688-1992 Test way: AC1.5kV/1min Leakage current: 1mA 0.16kg

4. OPERATION PANEL KEYS Item Definition Description Power Running LCD ICON Turn Page Alarm Indicator Power Indicator Running Indicator Using this button you can scroll pages of the LCD monitor. This indicator will flash when an alarm occurs. This indicator will illuminate when controller is powered on. This indicator will illuminate when engine is start. Item Definition Item Definition High Temp. Alarm Low Oil Pressure Over Speed Alarm Emergency Stop High Voltage Fail To Stop Normal Running Gens Volts Indication Battery Volts Indication Speed Unit (Per Minute) Oil Pressure Unit Voltage Unit Battery Volts abnormal Fuel Level Unit (%) Auxiliary Alarm Fuel Level Low Temperature Unit Frequency Unit Hours Count

5. PROTECTION 1. Low Oil Pressure (Pre-alarm/Shutdown): Once started successfully, after 10s delay, detection begins; if low oil pressure lasts for 2s, alarm or shutdown; 2. High temperature (Pre-alarm/Shutdown): Once started successfully, after 10s delay, detection begins; if high temperature lasts for 2s, alarm or shutdown; 3. Low fuel level warning: if fuel level stays below the pre-set level for 10 seconds, low fuel level warning signal is sent. Only warning and not shutdown, moreover, the warning is not latching ; 4. Over speed shutdown: When speed over the preset for 2s, alarm or shutdown; 5. Generator over voltage (Pre-alarm/Shutdown): if it is detected that voltage is above the pre-set level for 5 seconds, generator over voltage signal is sent and shutdown or pre-alarm is initiated; 6. Generator over frequency shutdown: if it is detected that frequency is above the pre-set level for 2 seconds, generator over voltage signal is sent and shutdown is initiated; 7. High Battery Voltage: if battery voltage stays above the pre-set value for 10 seconds, high battery voltage warning signal is sent. Only warning and not shutdown; 8. Low Battery Voltage: if battery voltage stays below the pre-set value for 10 seconds, low battery voltage warning signal is sent. Only warning and not shutdown; 9. Emergency Shutdown: if emergency shutdown input is activated, ETS output is immediately energized and emergency shutdown alarm is initiated. 10. Charge Alt fail: Once started successfully, after 10s delay, detection begins; if charger voltage D+ (WL) under 3V for 5s, charge alt fail warning signal is sent. Only warning and not shutdown; 11.Fail to stop: if the generator has not stopped after stop delay, fail to stop warning is initiated, moreover, the warning is not latching; 12.Common alarm: in case of over speed, over frequency, over voltage, high temperature, low oil pressure, emergency shutdown, fail to stop, charge alt fail, high battery voltage, low battery voltage (include pre-alarm), alarm indicator flashing and common alarm output is activated. NOTE: Conditions of crank disconnect:

1. When oil pressure is over 200kPa; 2. When generator frequency is over 40% of the rated frequency (e.g. set as 20Hz if the rated is 50Hz); 3. When engine speed is over 40% of the rated speed (e.g. set as 600rpm if the rated is 1500rpm) Any one of above is satisfied, crank disconnects and protection begins.

6. PARAMETER RANGE AND DEFINATION 6.1 PARAMETER DEFINITION AND RANGE No Items Range Default Description When the temperature value of the external temperature sensor exceeds this threshold, high temperature signal is sent. If the 1 High Temp. set value is 140, high (80-140)ºC 102 Shutdown temperature signal will not be sent (this only concerns temperature sensor, not high temperature signal via config. input port). When the temperature value of the external temperature sensor exceeds this threshold, high temperature signal is sent (Only warning and not shutdown). If 2 High Temp. the set value is 140, high (80-140)ºC 95 Warn temperature signal will not be sent (this only concerns temperature sensor and does not concern high temperature warning signal via configurable input port). When the external pressure sensor value falls below this threshold, low oil pressure signal is sent. If the set value is 0, low 3 Low OP oil pressure signal will not be (0-600)kPa 103 Shutdown sent (this only concerns pressure sensor and does not concern low oil pressure warning signal via configurable input port) 4 Low OP Warn (0-600)kPa 124 When the external pressure sensor value falls below this threshold, low oil pressure signal is sent (Only warning and not shutdown). If the set value is 0, low oil pressure signal will not be sent (this only concerns pressure sensor and does not concern low oil pressure warning signal via configurable input port)

No Items Range Default Description 5 Low Fuel Level Warn (0-100)% 10 6 Rated Voltage (80-300)V 230 7 8 Generator Over Voltage Shutdown Generator Over Voltage Warn (20-150)% 150 (20-150)% 115 When the liquid level of the external sensor falls below this value and stays so for 10 seconds, low liquid level signal is send (Only warning and not shutdown). If the set value is 0, low fuel level signal is not detected. Rated phase voltage of generator. When generator voltage exceeds this value and stays so for 5s, it is regarded as over voltage and Generator Over Voltage Shutdown alarm is initiated. If the set value is 150%, over voltage signal is not detected. When generator voltage exceeds this value and stays so for 5s, it is regarded as over voltage and Generator Over Voltage Warning is initiated (Only warning and not shutdown). If the set value is 150%, over voltage signal is not detected. 9 Rated Freq. (25-60)Hz 50 Rated frequency of genset. When generator frequency 10 Over Freq. (20-150)% 115 exceeds this value and stays so for 3s, it is regarded as over frequency and Generator Over Frequency Shutdown is initiated. If the set value is 150%, over frequency signal is not detected. 11 Poles (2-16) 4 Poles number of generator 12 Flywheel Teeth (10-300) 118 Tooth number of the engine, for inspecting the engine speed and over/under speed protection. 13 Rated Speed (750~5000)rpm 1500 Rated speed of engine. 14 Over Speed Shutdown (20-150)% 115 When engine speed exceeds this value and stays so for 3 seconds, this is regarded as over speed and Over Speed Shutdown signal is sent. If the set value is 150%, over speed signal is not detected.

No Items Range Default Description When battery voltage exceeds this value and stays so for 10 15 seconds, this is regarded as Battery Over (12-40V) 33.0 battery over voltage and Battery Voltage Over Voltage Warning signal is sent (Only warning and not shutdown). When battery voltage below this value and stays so for 10 16 seconds, this is regarded as Battery Under (4-30V) 8.0 battery under voltage and Voltage Battery Under Voltage Warning signal is sent (Only warning and not shutdown). 17 ETS Hold Solenoid (0-120)s 20 The time of powering up the electromagnet during stop procedure. 18 Digital Input (0-4) 2 Default: Aux. shutdown. 19 Digital Input Active delay time for digital input (0-20.0)s 2.0 Delay ports. 20 Temp. Sensor (0-10) 06 SGD(120ºC Resistor type) 21 Pressure Sensor (0-10) 06 SGD(10Bar Resistor type) 22 Fuel Level Sensor (0-7) 0 Not Used 6.2 DIGITAL INPUT No Description Notes 0 Not used 1 Auxiliary Warn Only warning and not shutdown if the input is active. 2 Auxiliary Shutdown Shutdown alarm will be immediately initiated if this input is active. 3 Not used 4 Not used

6.3 SENSOR SELECTION (TABLE 3) No Item Content Remark 0 Not used 1 Digital closed 2 Digital open 3 User defined resistor type 4 VDO Digital closed and Digital open both are digital signal; low or high electrical level can be selected to be active, connecting to earth point will mean that low electrical level 1 5 SGH is selected, hang in air Temperature 6 SGD means high electrical level is sensor 7 CURTIS selected; can not be 8 DATCON 9 VOLVO-EC 10 Not used connected to power supply positive. The range of user-defined resistor type sensor is 0-999.9 Ohm, by default 2 3 Oil pressure Sensor Fuel oil level sensor 0 Not used 1 Digital closed 2 Digital open 3 User defined resistor type 4 VDO 10Bar 5 SGH 6 SGD 7 CURTIS 8 DATCON 10Bar 9 VOLVO-EC 10 Not used 0 Not used 1 Digital closed 2 Digital open 3 User defined resistor type 4 SGH 5 SGD 6 Not used 7 Not used SGD sensor is selected. Digital closed and Digital open both are digital signal; low or high electrical level can be selected to be active, connecting to earth point will mean that low electrical level is selected, hang in air means high electrical level is selected; can not be connected to power supply positive. The range of user-defined resistor type sensor is 0-999.9 Ohm, by default SGD sensor is selected. Digital closed and Digital open both are digital signal; low or high electrical level can be selected to be active, connecting to earth point will mean that low electrical level is selected, hang in air means high electrical level is selected; can not be connected to power supply positive. The range of user-defined resistor type sentor is 0-999.9 Ohm, by default Not used is selected

7. CONNECTIONS Terminal1 (B-): Connect to the negative of the start battery. Terminal 2 (B+): Connect to the positive of the start battery. Terminal 3 (Em. stop input): Emergency stop input (active when connect to B+), external connect to emergency shutdown normally closed button. Terminal 4 (Magnetic pickup): Magnetic pickup signal input, shielded wire is recommended. Connect to GND at one end only. Terminal 5 (Oil Pressure Switch): Low oil pressure input port, active when connected to B-. Terminal 6 (Engine Temp Switch): High water/cylinder temperature input port, active when connected to B-. Terminal 7 (Level Sensor): Liquid level sensor input, can connect fuel level sensor. Terminal 8 (Oil Pressure Sensor): Oil pressure sensor input port. Terminal 9 (Engine Temp. Sensor): High water/cylinder temperature sensor input port. Terminal 10 (L), 11 (N): External connect to generator voltage signal to judge successful start and provide over frequency protection. Terminal 12 (Aux. Input): Programmable digital input port, active when connected to B-. Terminal 13 (D+ Input): Connect to charging generator WL (or D+) terminals. Controller provides charge current. When the charger charging fails (D+ terminal voltage < 3V), charge alt fail alarm is sent. (Only warning and not shutdown) Terminal 14 (Alarm Output): Alarm output port (B+ voltage output). Contact capacity is 7A. Terminal 15 (Stop Output): ETS (energized to stop) output port (B+ voltage output). Contact capacity is 7A. PC configurable socket (LINK): Connect to SG72 module and PC via USB port for parameter setting.

8. CASE DIMENSIONS (Panel Cutout 78*66mm)

9. TYPICAL APPLICATION