INSTRUCTION MANUAL HIGH-VOLTAGE VACUUM CONTACTORS MOTOR& TRANSFORMER APPLICATION. May, 2001 TOSHIBA CORPORATION SOCIAL INFRASTRUCTURE SYSTEM COMPANY

Similar documents
EISHO TEK. Vacuum Circuit Breaker

HCV-6KAU Vacuum Contactor, 7.2kV 720A 7.2kA HCV-6KALU Vacuum Contactor, 7.2kV 720A 7.2kA

HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA

INSTRUCTION MANUAL. HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA INSTALLATION - OPERATION - MAINTENANCE

Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual

INSTRUCTION MANUAL. HCV-1JBU Vacuum Contactor, 1.5kV - 600A HCV-1KAU Vacuum Contactor, 1.5kV - 720A

PATENT PENDING. Phone: (877) Operation and Service Manual

User manual W-VACi. W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SG-B1 SERIES / SG-A1 SERIES

INSTRUCTION MANUAL. HV6FS Vacuum Circuit Breakers Fixed Type 4.8 & 7.2kV Voltage Classes (Fast Closing) INSTALLATION - OPERATION - MAINTENANCE

INSTRUCTION MANUAL. HV6AS Vacuum Circuit Breakers Fixed Type 4.8 & 7.2kV Voltage Classes INSTALLATION - OPERATION - MAINTENANCE

HV6FS-MLD Vacuum Circuit Breakers Drawout Type 4.8 & 7.2kV Voltage Classes (Fast Closing w/uv Release)

CR193 Vacuum Limitamp* Contactors

Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4. Braking Resistor Units 3G3IV-PCDBR2 B/4 B. Braking Units

Vacuum Circuit Breaker Type VAD-3

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

3TM Vacuum Contactors

SafeGear TM Motor Control Center Arc resistant metal-clad construction

RELAYS. Figure Relay construction.

TECHNICAL DESCRIPTION

ELECTRIC ACTUATOR. Unic Series ROTARY TYPE Unic Z, 05 Unic 10 Unic 20, 40 Unic 60, 100, 150, 200 OPERATION MANUAL. Koei Industry Co., Ltd.

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

RVS-AX Instruction Manual

Installation Sheet January, 2016 Supersedes February, 2013

Power Controller. (see note 1) 10 sec

Installation, Operation and Maintenance Manual

Publication No.: PSG

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive

Operation Manual. Document No.: KE KITZ EKSR Series Spring Return Type Electric Actuators. For KITZ Ball Valves

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

This chapter describes how to perform periodic inspection and maintenance to ensure the long operating life of the chamber.

INSTALLATION & OPERATION MANUAL

HS1E Series Full Size Solenoid Locking Switches

1. Inspection and Maintenance

INSTALLATION & OPERATION MANUAL

Outdoor Vacuum Circuit Breaker - Type OVB-SDB. Instruction for Storage, Installation, Service and Maintenance

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B Overcurrent Protective Device)

www. ElectricalPartManuals. com (fr} lite Imperial Carporatian ''- METAL-ENCLOSED, FUSED-INTERRUPTER SWITCH INSTRUCTIONS

Door Interlock Switches

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

www. ElectricalPartManuals. com INSTRUCTIONS TYPE CO CONTACT MAKING AMMETER INSTALLATION OPERATION MAINTENANCE I.. L APPLICATION

SERVICE AND REPAIR PARTS NEMA SIZE 3, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 4, SINGLE POLE, NORMALLY OPEN, P/N SERIES

Programmable Logic Controller. Mat Nor Mohamad

1. Safety practices General Introduction Standards...3

F3S-TGR-KHL1/-KHL3/-KHL3R

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B Overcurrent Protective Device)

Vacuum Circuit Breakers (Vehicle)

Low Surge Special WCAg contact limits the chopping current up to 1A to protect the load from high surge.

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

AMVAC TM technical guide Vacuum circuit breaker with magnetic actuator mechanism

panasonic.net/id/pidsx/global Solve issues related to machine safety and other safety measures with a safety door switch with key!

F3S-TGR-KM15/-KM16/-KH16

(with Class-1 AC resistive load) 3. G3PB-215B-2N-VD kW max. (25 A) G3PB-225B-3N-VD 2. G3PB-225B-2N-VD kw max. (35 A) G3PB-235B-3N-VD 2

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

Insulation method Zero-cross function Indicators Applicable output load Model number Phototriac coupler Yes Yes (See page 6) Main Circuit

Cable length. 3: 3 m. 4: Adjustable mounting (vertical) 4: 3NC (slow action) 5: 5 m. (Slow-action) Horizontal 1 m D4GS-N1R D4GS-N2R D4GS-N3R D4GS-N4R

HS1E Series Full Size Interlock Switch with Locking Solenoid

cause injury to humans and other physical damage. : Gives information that does not fall in the WARNING or CAUTION categories.

OPERATIONS MANUAL LEVER CHAIN HOIST

SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY OPEN, P/N SERIES

High Frequency SineWave Guardian TM

HS6B Series Subminiature Interlock Switch

Instruction Manual for Electric Vehicle (EV) Quick Charging Connector

Model Number Structure. Power Controllers G3PX. Single-phase Models. Model Number Legend

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

INSTALLATION & OPERATION MANUAL

Solid State Relays G3RV. Model Number Structure. Ordering Information. Model Number Legend. List of Models. SSR and Socket Combinations

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

Installation, Maintenance and Operation Manual

Manual Motor Starters. Meta-MEC

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

Radius, LLC Electric quarter turn actuator EW series Installation, Maintenance and Operating Manual

TL RELAYS. TYPICAL APPLICATIONS Head lamp, Fog lamp, Fan motor, etc. ORDERING INFORMATION TYPES. High Load Relay for Smart Junction Box ACTL.

INSTRUCTIONS. seconds. the tween the end of the bearing screw and the. top of the shaft. The moving contact is a small silver hemisphere

Instruction Manual 15kV KVAN-1125M 1200/2000A Maxi-Vac Medium-Voltage Vacuum Circuit Breaker

HS1B Series Full Size Interlock Switch. GS-ET-15 BG standard in Germany. Part Number Key

RAY TYPE 1 PRODUCT MANUAL

S&C Type FVR Substation Circuit Breaker

OPEN/CLOSE SERVICE ELECTRIC ACTUATORS OPERATION AND MAINTENANCE MANUAL COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION

Descriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

Quick Start Guide TS 910 & TS 920

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN

AE Installation Operation & Maintenance Instructions

Door Interlock Switches

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

EX Series. Electric Actuators for Ball and Butterfly Valves

Installation Sheet January, 2016 Supersedes June 2013

Quick Start Guide TS 910

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

MCset kv Medium voltage equipment

Transcription:

TOSHBA NSTRUCTON MANUAL HGH-VOLTAGE VACUUM CONTACTORS MOTOR& TRANSFORMER APPLCATON TYPE:CV-10HA TYPE:CV-1 OHAL 12/15kV-400A-5/4kA 12/15kV-400A- 5/4kA May, 2001 REV. 4 TOSHBA CORPORATON SOCAL NFRASTRUCTURE SYSTEM COMPANY TOSHBA Corporation 2001 All Rights Reserved.

TD SHBA CONTENTS 1. GENERAL DESCRPTON 2 2. PRECAUTONS N SPECAL APPLCATON 3 3. RECEVNG AND UNPACKNG 4 4. STORAGE AND HANDLNG 4 5. NSTALLATON 5 6. RATNG 6 7. OUTLNE DRAWNG 7 8. STRUCTURE 8 9. OPE RAT ON 9 10. TRAL OPERATON 13 11. NSPECTON AND MANTENANCE 14 12. CRTERA FOR DURABLTY 18

TOSHBA Read this manual carefully to fully understand the operation. And keep for maintenance. WARNNG: Never remodel or disassemble the equipment nor mount nonstandard components. This equipment shall only be used inside a metal enclosure (grounded) in other establishments than domestic, or those that are connected to the public power source system. 1. GENERAL DESCRPTON ( 1 ) Ambient condition The type CV vacuum contactor is manufactured in accordance with EC 60470(2000). The vacuum contactor should be used in the following conditions. Table 1 Normal service condition -Altitude Less than 1 OOOm -Ambient temperature -S C min. to +40 C max. ts average over a period of 24h does not exceed +35 C - Relative humidity 45% min. to 85% max. -Vibbration 20Hz - 9.8m/s 2 or less CAUTON : Do not use in condition other than those specified above, please consult. (2) Locative condition The location where the contactor is to be installed should be free from dust. Corrosive gas and moisture. When it is be used in a chemical plant or in outdoor panels, take necessary precautions against corrosion, water seepage and condensation. See page 2. 2

TOSHBA 2. PRECAUTONS N SPECAL APPLCATON (outdoor cubicle etc.) n application, check the follow items, please carry out the maintenance frequently. or perform the countermeasure. (Visual inspection: once a month, regular inspection: once a year) Table 2 Precaution in special application Special condition nstance Caution items Contamination Dust, iron-dust etc. Reduction of ventilation is very more place. Setting of ventilation for Sea breeze Place where suffer the sea breeze. sea breeze. Frequent inspection. High humidity Place where very more Setting the space heater. snow and ice. Setting the ventilation. More humidity. Prevention of flooding Place where near the into the cable pit. cooling tower. Place where cause changing the temperature suddenly. Corrosion gas Corrosion gas which come Protection from corrosion into the airport, chemical gas. ndustry and water cleaning. Anti-gas treatment. (EX.) Examination of changing S02, Cl2, N02 of the insulation material. 3

TOSHBA 3. RECEVNG AND UNPACKNG WARNNG: f any parts are damaged or missing. Do not install that has been damaged. Make the following checks after unpacking : (1) Check if there is any damage, foreign matter trapped, or water seepage into the contactor. (2) Check the nameplate to see if the specifications on the plate are correct. (3) Check the contact wear gauge and control cable. (4) Check the tripping rod (Latched type). 4. STORAGE AND HANDLNG When the contactor is to be stored over a long period, the storage area should be dry and dust free area. f the contactor is left outdoors or in adverse conditions, corrosion from gas, rust or insulation deterioration may result. CAUTON : n handling, do not throw or drop contactor. The contactor may break. 4 -

TOSHBA 5. NSTALLATON When installing, protect from dust. Particularly when the contactor is installed while the building is under construction, shield it from cement dust and other foreign matter. The following precautions should be taken. (1) The mounting surface must be horizontal (level : less than + 1 mm). When the mounting surface is not horizontal, adjust with spacers. (2) There are four mounting holes. Use M10 bolts to securely mount the contactor. (3) n wiring the main circuit terminals, ground terminals and control circuit, wires should be given sufficient length to be flexible. The ground wires should be more than 5.5mm 2 in cross section. ( 4) Do not mount the contactor with its front inclined downward. This may result in malfunction. (5) Do not touch the vacuum interrupter surface with soiled hands. (6) When it is applied to a capacitor load, be sure to used a space heater to keep humidity low. CAUTON : Do not install on energize contactor that has been bad condition. 5 -

TOSHBA 6. RATNG DANGER: Do not exceed the ratings specified on the contactor. Table 3 Ratings Type- form CV-10HA CV-10HAL Operating mechanism Non-latched Latched Rated operation voltage (kv) 12/15 Rated insulation level (kv) AC.28, mp. 75 Rated operational current (A) 400 Thermal current (A) 450 Rated frequency (Hz) 50/60 Rated short-time withstand current (A-s) 5000-1 Rated peak withstand current (A) 12500 Rated duties Operations/hour 300 120 On load factor 40% Rated making capacity (ka) 4(C-10sX 100times) Rated breaking capacity (ka) 3.2( CO- 30s x 25times) Short-circuit making and breaking current 5/4 (ka) Duties 0-3min-C0-3min-CO Withstand overload current (ka-s) 8.0-1 sec, 2.4-30sec Mechanical operation (million) 0.25 Electrical operation (million) 0.1 Rated supply voltage Closing voltage 100-240VAC 100-240VAC (Standard) 100-220VDC 100-250VDC Tripping voltage - 100-110VDC Auxiliary switches Contact arranoement 4N0-2NC 2N0-1NC Life (million) 0.1 Operating current (A) Closing 6--7 (at 100V) Holdina/Triooina 0.6--0.7 3--4 6

RECOMMEND PARTTON DSTANCE... 0 c -i r z m ~ ~ z G) - D en :c - m J:ll... r> co 11'>1 - c:- E 1 6 :+ i~ 63 5 t ~ ~ 1" MAN '1 1' '1 TERMNALS DA. l 3-6HOLES l l i ~ ~ 0 0 500 OPENNG FOR MANUAL TRP (LATCHED TYPE) 24 146 1 9 3 526 ';> le= 235 TYPE CV- 1 0 HA ( L) (HORZONTAL MAN TERMNALS) Fig.1 OUTLNE DRAWNG(mm) en 'Tl co C) 0...a. w

VACUUM NTERRUPTERS NSULATON BARRER CX> en - ::0 c (') - c ::0 m - 0 en ::c - ll,.. MAN TERMNALS co ARMATURE [r::::j] NDCATOR COUNTER (OPTON) OPENNG FOR MANUAL TRP FRONT(WTHOUT COVER) ATCH MECHANSM (LATCH TYPE) CONTROL CONNECTOR FRONT METAL COVER Fig. 2 STRUCTURE OF CV-10 O>,, co C) c ~ w

TD SHBA 9. OPERATON The drive unit for the electromagnet is installed in the bottom frame. Molded and wired on the printed circuit. The closing circuit can be operated using either in AC or DC by the drive unit. The optional latch trip circuit uses DC as standard. When a latched contactor is operated using AC power, it is recommended that a Capacitor trip device be used. The standard operating voltage is as follows: Non-latched type(normally energized) : 100-240 V AC /100-220V DC Latched type : 100-240V AC /100-250V DC closing voltage : 100-11 OV DC tripping voltage Di ode (Latched type) 52CC 2 U-----+-----' - - - - - - - - - - OSCLLATON SWTCHNG TMER POWER VOLTAGE DETECT Fig.3 nternal Configuration of Drive Unit CAUTON : Do not touch the drive unit without trouble. 9 -

TOSHBA (1) CONNECTON OF CONTROL POWER SUPPLY Fig.4 and Fig.5 show the internal connections of the normally energized type latched type respectively. According to there figures, connection should be made of the control power supply and open close command contact (power relay contact). r---- L~c:Dc Tl Tl 1 TS TS T7 TS T9 Tl 0 -------------- ------, AC/DC _J AUS 11 9 7 11-- 1 2 1 0 B -------------- _J T15T1ST17T1S Tl 9 T20!C ~ g f$ 52CC CLOSNG COL OF CONTACTOR Du DRVE UNT AUS AUX L ARY SWTCH 1... 6 CONTACTOR TERMNAL NUMBERS T6 TB TO Tl TS T7 T9 Tll TS T17 T19 T16 TlB T20 CONTROL CONNECTOR Fig.4 nternal connection of the normally energized type. L--~~.:_,,, Tl DC/AC Tl 1 TS TS T7 TS AUS,,--,-0--9-0--<7 >-- ~---- L1 2-o.-1-ao -B-0----0-- j TS T16 T17 TS T13 T3,,.. ----., j 12 ~ 52CC Du AUS 1... 6 52TC D Tl T3 Tl 1 Tl 3 ~ f$ CLOSNG COL OF CONTACTOR DRVE UNT AUXLARY SWTCH CONT ACTOR TERMNAL NUMBERS TRPPNG COL OF CONTACTOR D ODE TS T6 T7 TB Tl S Tl 7 Tl 6 Tl B 9 1 0 CONTROL CONNECTOR Fig.5 nternal connection of latched type. 1 0

TOSHBA (2) STANDARD OPERATON CRCUT Shown below are the vacuum contactor and its auxiliary circuits (control and monitoring). Fig.6 represents the standard operation circuit of the normally energized type and Fig. 7 the latched type. Wiring should be done according to these circuit diagrams. > > C> C> C> C> C> C> (.) (.) <( 0 E OFF REMOTE E SWTCH *l El'l N 4 J-r cos l ~ ~~~~~LOCK ~14 l~, A TS T6 T7 TB T9 Tl 0 A A VMC ---- -, AUS 5 _J l l 2 l 0 8 4 STOP Du i NTERLOCK i 6 2 T Tl 1 v v v 115T16117 118 119 T20 i i Fig.6 Standard operation circuit of normally energized type. NOTE:e Be sure to use quickly AC auxiliary relay contact NO for self-holding. f the self-holding circuit is formed by using the auxiliary contact No of the vacuum contactor, welding of the main contact may result when the start button is pushed incompletely(refer to *1 in Fig.6). 1 1

TOSHBA > 0 "' 0 0 u 0 T16 T17 T18 T13 (a) Shunt trip REMOTE SWTCH E OFF \ 2E-RY T6 T7 TS > 0... N 0 0 - u < AUS 9 7 CTD Tl 6 Tl 7 Tl 8 Tl 3 (b) Capacitor trip Fig. 7 Standard operation circuit of latched type. NOTE : e Electrical trip-free circuit must be prepared outside the contactor. e A stable DC power source such as battery is recommended for the control circuit. f DC power source is not available, employ a AC closing and a Capacitor trip. e Be sure to use the control connector between No.3 and No.13 (auxiliary contact) for trip circuit. Connect the control connector between No.5 and No.15 (auxiliary contact) for control relay circuit. 1 2

TOSHBA 10. Trial operation Warning : Make sure main power is OFF. After mounting and wiring of the vacuum contactor, make the following inspections. 1 ) Check for any loose connections. 2) Check for any wiring errors. Perform this test with only the control circuit energized. confirm that the operation is correct. For the latched type contactor, check that the latch correctly engages and trips when the close/trip signals are applied. Also, manually trip the contactor using trip lever to verify proper operation. 1 3 -

TOSHBA 11. NSPECTON AND MANTENANCE To maintain the function and performance of the vacuum contactor for a long period of time, the following inspections and maintenance procedures are recommended. The intervals between inspections may vary depending on the conditions of use and the environment under which the contactor is used. The initial inspection should be carried out within one year of the start of equipment operation, and the succeeding check intervals should be determined according to the result of the initial inspection. See Section 2 for use under special environment as in outdoor cubicles. ( 1 ) Patrol nspection( every 1-6 months) With the cubicle energized, visu~lly check from out side the cubicle according to the check list of Table 4,5. WARNNG: When opening the door of the cubicle, do not come close to danger area. Table 4 Patrol inspection items Check item Abnormal noise Abnormal smell What to check Check if corona discharges or operation magnets are not producing noise. Check if corona discharges or overheat are not producing abnormal smell. Table 5 Patrol inspection items( cont.) Check item Abnormal discoloration Damage Open/close indication What to check s there not any discoloration due to overheat? s there not any crack, break or dislocation of insulating material or operation tools? s the OPEN/CLOSE indication (lamp) normal? 1 4 -

TD SHBA (2) Periodical nspection/detailed nspection( every 1-2 years or every 20,000 operations) The facility should be removed out of service and perform inspection According to the instruction given in Table 6. WARNNG: Contact with energized components can cause severe injury or death. Turn-off and lock out primary and control circuit before servicing. 1 5 -

TOSHBA Table 6 Periodical inspection and detailed inspection Location What to inspect Decision criteria What to do Contactor as Appearance Abnormal appearance Check by sight. Replace broken a whole damage Parts. nsulating Check if moisture or Material dust adheres to the insulator. Check by sight. Clean. Under dusty environments, frequent inspection should be done. Operating Sliding parts Check for wear, loose or devices seized parts. Spring Rust, deformation, discoloration, or damage. Electromagnets Discoloration, rust, Check bye sight. Clean parts and wear, or loose mounting. f necessary, remove foreign check correct matters. Latch Check for scores and operation. Pour oil in mechanism wear Also check loose Adequate Closing coil, Check for discoloration fastenings. amount. trip coil and burned parts. Fastenings Check for loose bolts or nuts. Primary Terminal, Discoloration of terminal Check by sight. Retighten. circuit movable and coupling conductor, check the f necessary, conductor loose fastenings. tightness. investigate the cause and replace parts. nterrupter Vacuum Check contact wear and See Table 7. Replace vacuum Contact wear wipe. nterrupter. Vacuum Check moisture and dust Check by sight. Clean. container adhering to the surface. Vacuum level Check vacuum level by Apply AC 17kV f found abnormal, withstand voltage test. for 1 minutes. inform the maker. 1 6

TOSHBA Location What to inspect Decision criteria What to do Control wiring Check for discoloration - Retighten. equipment and tightness. Auxiliary switch Amount of dust attached. Check by sight. Replace if damage is excessive. Drive unit Overheat, discoloration. Check by sight. Replace if abnormal nsulation Main circuit Measure insulation More than SOM Q When the insulation resistance resistance between resistance is phases, between below the standard electrodes and between level, investigate the circuits and ground. cause and, if (Measurement is taken necessary, replace by 1 OOOV megger.) parts. Operation Measure insulation More than 1 M Q circuit resistance between circuits and ground. (Measurement is taken by SOOV meqqer.) Dielectric Main circuit Measure dielectric AC 1.SE for f found abnormal strength strength between phases, 10 minutes. inform the maker. between electrodes and between circuits and ground. Open/close operation Perform open/close f found abnormal, operation by electric check and repair. operation test to confirm f necessary, the correct operation. replace faulty parts. Remarks: For extraordinary (unscheduled) inspections, pick up check items from the above table. 1 7

TOSHBA Table 7 Gap/wipe standard value (mm; Parts name Gap Wipe Allowable wear Vacuum Normally energized interrupter type 7.0-7.5 More than 3.0 2.0 Latch type 7.0-7.5 More than 2.8 1.8 12. CRTERA FOR DURABLTY ( 1) Electrical service life The electrical service life of the vacuum interrupter is defined by the electrode wear the number of open/close operations (mechanical life). To determine the electrode wear, measure the gap between the lever and washer (dimension A) in a closed start, as shown in Figure8. With the vacuum interrupter closed, if a contact wear gauge or a 1.0mm thickness gauge cannot be inserted, this means the end of life is reached. For the components listed below, replacement or detailed inspection and cleaning are recommended after the indicated number of operations. Table 8 Electrical service life Parts. name Electrical service life Vacuum interrupter 100,000 operations or 15 years Auxiliary switch 100,000 operations or 10 years Drive unit 100,000 operations or 10 years Movable conductor 100,000 operations or 15 years Hence, parts should be replaced around electrical service life operations. CONTACT SPRNG LEVER WASHER (MB) Fig.8 Parts to be inspected 1 8 -

TOSHBA (2) Mechanical service life The normally energized type has the mechanical service life of 0.25 million operations, and the latch type 0.25 million operations. (The mechanical service life of the vacuum interrupter is 100,000 operations.) For the components listed below, replacement or detailed inspection and cleaning are recommended after the indicated number of operations. Table 9 Recommended replacement parts Parts name Vacuum interru ter Auxilia switch Movable conductor Latch mechanism Closin tri coil Movable core Stationary core No. of o eration for re lacement 100,000 o erations or 15 ears 100,000 o erations or 10 ears 100,000 o erations or 15 ears 250,000 o erations or 10 ears 250,000 o erations Detailed inspection and cleaning eve 100,000 o erations. Detailed inspection and cleaning eve 100,000 o erations. 1 9