DESCRIPTION TECHNICAL GUIDE AFFINITY SERIES SINGLE PACKAGE GAS/ELECTRIC AIR COOLED AIR CONDITIONERS 2 THRU 5 NOMINAL TON DNP024, 030, 036, 042, 048 AND 060 13 SEER York Affinity Series packaged cooling/heating air conditioners are designed for outdoor installation. Only utility and duct connections are required at the point of installation. The single or two stage gas-fired heaters have aluminized steel tubular heat exchangers and spark to pilot ignition. They are available in natural gas with field conversion to propane. FEATURING FACTORY MOUNTED TXV COOLING/GAS HEATING UNITS (NATURAL GAS, SIN- GLE OR TWO STAGE) LOW PROFILE QUIET OPERATION COMMON FOOTPRINT OPTIONAL SLIDE IN MOTORIZED DAMPERS OPTIONAL SLIDE IN ECONOMIZERS OPTIONAL PROPANE CONVERSION KIT OPTIONAL HIGH ALTITUDE CONVERSION KIT (NATURAL GAS/PROPANE) OPTIONAL LOW NOx KIT FULL PERIMETER BASE RAILS BOTTOM AND SIDE UTILITY CONNECTIONS 1 OR 2 CLEANABLE FILTERS STANDARD ON ALL 3 PHASE MODELS. OPTIONAL ON 1 PHASE MODELS WARRANTY - 1 PHASE 10 year compressor 20 year heat exchanger 5 year other parts WARRANTY - 3 PHASE 5 year compressor 10 year heat exchanger 1 year other parts FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
DESCRIPTION.............................. 1 STANDARD FEATURES/BENEFITS............ 3 FIELD-INSTALLED ACCESSORIES............. 4 TABLE OF CONTENTS LIST OF FIGURES 291626-YTG-B-0807 TYPICAL WIRING DIAGRAM NOTES.......... 44 MECHANICAL SPECIFICATIONS............. 45 Fig# Pg# 1 PRODUCT NOMENCLATURE................... 3 2 UNIT COMPONENT LOCATION................. 6 3 TYPICAL FIELD CONTROL WIRING DIAGRAM SINGLE STAGE THERMOSTAT - SINGLE STAGE GAS HEAT.................... 22 4 TYPICAL FIELD CONTROL WIRING DIAGRAM SINGLE STAGE THERMOSTAT - TWO STAGE GAS HEAT................................. 23 5 TYPICAL FIELD CONTROL WIRING DIAGRAM TWO STAGE THERMOSTAT - TWO STAGE GAS HEAT................................. 23 6 POWER WIRING FIELD DIAGRAM.............. 24 7 UNIT DIMENSIONS - FRONT.................. 25 8 UNIT DIMENSIONS - FRONT & BOTTOM........ 26 9 UNIT DIMENSIONS - BACK & BOTTOM.......... 26 10 TYPICAL SLAB ON GROUND INSTALLATION..... 27 11 TYPICAL ROOF CURB INSTALLATION.......... 27 12 TYPICAL DUCT APPLICATIONS................ 28 13 UNIT CENTER OF GRAVITY................... 28 14 ROOF CURB DIMENSIONS.................... 29 15 ROOF CURB CROSS SECTION................ 29 16 TYPICAL WIRING DIAGRAM D*NP 024 SINGLE STAGE GAS HEAT (208/230-1-60 POWER SUPPLY)................ 30 17 TYPICAL WIRING DIAGRAM D*NP 024 TWO STAGE GAS HEAT (208/230-1-60 POWER SUPPLY)................ 31 18 TYPICAL WIRING DIAGRAM D*NP 030-048 SINGLE STAGE GAS HEAT (208/230-1-60 POWER SUPPLY)................ 32 Fig# Pg# 19 TYPICAL WIRING DIAGRAM D*NP 030-048 TWO STAGE GAS HEAT (208/230-1-60 POWER SUPPLY)............... 33 20 TYPICAL WIRING DIAGRAM D*NP 060 SINGLE STAGE (208/230-1-60 POWER SUPPLY)......... 34 21 TYPICAL WIRING DIAGRAM D*NP 060 TWO STAGE (208/230-1-60 POWER SUPPLY)......... 35 22 TYPICAL WIRING DIAGRAM D*NP 030-048 SINGLE STAGE GAS HEAT (208/230-3-60 POWER SUPPLY)............... 36 23 TYPICAL WIRING DIAGRAM D*NP 030-048 TWO STAGE GAS HEAT (208/230-3-60 POWER SUPPLY)............... 37 24 TYPICAL WIRING DIAGRAM D*NP 060 SINGLE STAGE GAS HEAT (208/230-3-60 POWER SUPPLY)............... 38 25 TYPICAL WIRING DIAGRAM D*NP 060 TWO STAGE GAS HEAT (208/230-3-60 POWER SUPPLY)............... 39 26 TYPICAL WIRING DIAGRAM D*NP 030-048 SINGLE STAGE GAS HEAT (460/575-3-60 POWER SUPPLY)............... 40 27 TYPICAL WIRING DIAGRAM D*NP 030-048 TWO STAGE GAS HEAT (460/575-3-60 POWER SUPPLY)............... 41 28 TYPICAL WIRING DIAGRAM D*NP 060 SINGLE STAGE GAS HEAT (460/575-3-60 POWER SUPPLY)............... 42 29 TYPICAL WIRING DIAGRAM D*NP 060 TWO STAGE GAS HEAT (460/575-3-60 POWER SUPPLY)............... 43 30 TYPICAL WIRING DIAGRAM LEGEND........... 44 LIST OF TABLES Tbl# Pg# 1 PHYSICAL DATA.............................. 6 2 RATINGS COOLING/SINGLE STAGE GAS HEATING 7 3 RATINGS COOLING/TWO STAGE GAS HEATING... 8 4 DNP024 COOLING CAPACITIES - 2 TON.......... 9 5 DNP030 COOLING CAPACITIES - 2.5 TON........ 11 6 DNP036 COOLING CAPACITIES - 3 TON......... 13 7 DNP042 COOLING CAPACITIES - 3.5 TON........ 15 8 DNP048 COOLING CAPACITIES - 4 TON......... 17 9 DNP060 COOLING CAPACITIES - 5 TON......... 19 10 DNP024 SUPPLY AIR BLOWER PERFORMANCE.. 20 Tbl# Pg# 11 DNP030 THRU DNP060 SIDE SUPPLY AIR BLOWER PERFORMANCE.................... 21 12 DNP030 THRU DNP060 BOTTOM SUPPLY AIR BLOWER PERFORMANCE.................... 21 13 ADDITIONAL STATIC PRESSURE RESISTANCE - 2, 2-1/2, 3 TON.............................. 22 14 ADDITIONAL STATIC PRESSURE RESISTANCE - 3-1/2, 4 AND 5 TON.......................... 22 15 ELECTRICAL DATA.......................... 24 16 UNIT DIMENSIONS FRONT.................... 25 17 UNIT MINIMUM CLEARANCES................. 25 18 UNIT WEIGHTS AND CENTER OF GRAVITY...... 28 2 Unitary Products Group
PRODUCT CATEGORY D = Single Package Air Conditioner PRODUCT GENERATION 1 = 1st Generation 2 = 2nd Generation 3 = 3rd Generation PRODUCT IDENTIFIER NP = 13 SEER Gas Heat/Electric FIGURE 1 - PRODUCT NOMENCLATURE D 1 N P 0 3 6 N 0 3 6 0 6 NOMINAL COOLING CAPACITY (MBH) 024 = 24,000 BTUH 030 = 30,000 BTUH 036 = 36,000 BTUH 042 = 42,000 BTUH 048 = 48,000 BTUH 060 = 60,000 BTUH FACTORY INSTALLED NATURAL GAS HEAT N = Single Stage D = Two Stage VOLTAGE CODE 06 = 208/230-1-60 25 = 208/230-3-60 46 = 460-3-60 58 = 575-3-60 NOMINAL HIGH GAS HEAT OUTPUT CAPACITY (NOMINAL LOW GAS HEAT OUTPUT CAPACITY) 036 = 36,000 BTUH 056 = 56,000 BTUH (36,400 BTUH) 065 = 65,000 BTUH 072 = 72,000 BTUH (46,800 BTUH) 090 = 90,000 BTUH (56,160 BTUH) 110 = 110,000 BTUH (70,200 BTUH) STANDARD FEATURES/BENEFITS OPERATING EFFICIENCY - All units provide high operating efficiencies and have a minimum AFUE of 80% and SEER of 13.0. All efficiencies exceed legislated minimum levels. ON SITE FLEXIBILITY - All model sizes share a common, compact design cabinet in a single footprint. The installer has the flexibility of setting one curb and placing the proper tonnage unit on that curb after the internal load has been determined. Field convertible duct connections from side shot to down shot allows the installer to have greater flexibility with less inventory. LOWER INSTALLATION COST - Installation time and costs are reduced by easy power and control wiring connections. The small base dimension means less space is required on the ground or roof, plus, the installer can fit this unit between the wheel wells of full size pick-up truck. All models are well under 500 pounds. All units are completely wired, charged with R-22 and tested prior to shipment. Unique test stations using a new state of the art computerized process system are used to insure product quality. Refrigerant charge and component part numbers are verified via computers at assembly. Vital run test statistics such as system pressure, motor currents, air velocity and temperature, unit vibration, and gas system safeties are monitored and recorded by the system to insure unit performance. Equal size, side supply and return duct connections allows easy hook-up of ducts to match low crawl spaces without transition pieces. UTILITY CONNECTIONS MADE EASY - Gas and electric utility knockouts are provided through the bottom as well as the side of the unit. Utility connections can be made quickly and with a minimum amount of field labor. A field supplied and field installed electrical disconnect switch must be installed. CONVERTIBLE AIRFLOW DESIGN - The bottom duct openings are covered when they leave the factory ready to be used for a side supply / side return application. If a bottom supply / bottom return application is desired, you simply remove the two panels from the bottom of the unit and place them in the side supply / side return duct openings. No panel cutting is required and no accessory panel is necessary. Convertible airflow design allows maximum field flexibility and minimum inventory. CONDENSATE PAN - A non-corrosive, long-lasting, watertight pan is positioned below the evaporator coil to collect and drain all condensate. Less collection of stagnate condensate will build-up. The condensate pan conforms to ASHRAE 62-89 standards (Ventilation for Acceptable Indoor Air Quality). CONDENSATE DRAIN - The heavy duty, 3/4 inch NPTI copper connection is more durable over time. The connection is rigidly mounted to assure proper fit and leak tight seal. DURABLE FINISH - With a heavy duty cabinet made of powder-painted, galvanized steel the neutral color blends into surrounding areas. The powdered paint provides a better paint to steel bond, which resists corrosion and rust creep. The special primer formulas and glossy finish insures less fading when exposed to sunlight and offers a more attractive on site appearance. This paint finish meets ASTM-B117 standards for 1000 hours salt spray rating. The highest in the industry. FULL PERIMETER BASE RAILS - The easily removable base rails provide a solid foundation for the entire unit and protects the unit during shipment. The rails provide fork lift access from all sides, and rigging holes are also provided so that an overhead crane can be used to place the units on a roof. On applications where the unit is placed on a pad, the base will keep the unit off the pad to deter corrosion. On applications where height is limited, the inch high base rails may be removed on location. Unitary Products Group 3
MORE ATTRACTIVE APPEARANCE - A single piece Water Shed top cover containing a top discharge condenser fan arrangement requires less square footage on installation and provides a wider variety of installations. The one piece design adds greater water integrity. Rounded corners with water drip edges add to the attractive appearance. The cabinet panels have a non-fibrous insulation that will not release insulation fibers into conditioned area. TOP DISCHARGE - The top discharge condenser fan does not disrupt neighboring areas or dry-out vegetation surrounding the unit. The warm air from the top mounted fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications. CONDENSER COIL GRILLE - A multi-piece totally enclosed, rigidly mounted condenser coil grille provides protection from objects after installation and provides protection during transit. LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise up and away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and compressor operating sounds. The unique formed base pan also aids in sound alterations with it's Super-Structure design. This design strategically places embossments in the pan for optimum strength and rigidity. FAN SYSTEM - All models operate over a wide range of design conditions with a multi speed direct drive fan motor. These units easily match all types of applications and provide greater on site flexibility to match comfort requirement. The cooling speed is factory set and can be field adjusted to a second speed. The heating speed is factory set to maintain mid point rise at the units heating input, but can be field adjusted. This allows maximum comfort conditions. SIMPLE CONTROL CIRCUIT - A low voltage printed circuit board contains a diagnostic indicator light and a low voltage terminal strip. An additional set of pin connectors is also provided to simplify the field interface of external controls. Maten-lock plug connectors are used. The electrical control box is not located in the compressor compartment. The controls are mounted on a Control-Tilt control panel to allow the access cover to be removed for trouble shooting and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/number coded. PROTECTED COMPRESSOR - The compressor is internally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protect the compressor if undesirable operating conditions occur. EXCLUSIVE COIL DESIGN - Grooved copper tubes and enhanced aluminum fin construction improves heat transfer for maximum efficiency and durability. HEAT EXCHANGERS - Are corrosion-resistant, aluminizedsteel tubular construction to provide long-life, trouble-free operation. The unique blow-through design also assures that condensate does not collect in humid areas when in the cooling cycle. This adds to longer heat exchanger life and higher long term efficiencies. POST PURGE INDUCED DRAFT COMBUSTION - Exhausts combustion products from the heat exchanger upon completion of the heating cycle to prolong the heat exchanger life. SELF DIAGNOSTIC FAN CONTROL MODULE - Due to this self diagnostic control, less on site time is required to trouble shoot these units. SPARK TO PILOT IGNITION - Provides faster heat delivery. This ignition is highly reliable, durable and eliminates nuisance lockouts. MULTI PORT IN-SHOT BURNERS - No field adjustment is required to mix the air and gas. These burners are constructed of high-grade corrosion-resistant, aluminized-steel. LOW MAINTENANCE - Long life, permanently lubricated condenser and evaporator fan motor bearings need no annual maintenance adding greater reliability to the unit. Blower assembly can be easily cleaned by the unique Slip- Track slide-out blower assembly. SECURED SERVICE ACCESS PORTS - Protected, externally mounted, re-usable service access ports are provided on both the high and low lines for ease of evacuating and charging the system. No final field mounting required. EASY SERVICE ACCESS - A large, single panel covers the electrical and gas controls makes servicing easy. The blower compartment has an additional large panel with a built-in handle tab. Removing this panel will allow the blower assembly to slide-out for easy removal for maintenance and ease of trouble shooting. REPLACEMENT PARTS - The installer requires no special training to replace any of the components of these units and does not need to maintain an inventory of unique parts. SYSTEM INTEGRATION - Each unit has the internal ability to integrate an electronic air cleaner or humidifier to work in conjunction with the base unit. FIELD-INSTALLED ACCESSORIES LOW NOx KIT - Kit includes all the necessary hardware and instructions to field convert units to reduce emissions to less than 40 nanogram per Joule. California requirement on single phase models only. PROPANE CONVERSION KIT - Kit includes burner orifices, gas valve conversion and installation instructions necessary to field convert unit from natural gas to propane. HIGH ALTITUDE CONVERSION KIT (Natural Gas/Propane) - Kit includes all necessary labels and instructions to field alter units with natural gas/propane for installations above 4 Unitary Products Group
2000 feet. Burner orifices must be obtained from Source 1 Parts. Propane Conversion Kit must be obtained separately. ECONOMIZER DOWN DISCHARGE / SUPPLY KIT - Modulating integrated economizer provides simultaneous operation between the mechanical cooling and economizer operation. Independent blade design insures proper control and less than 1% leak rate. Includes hood and mesh bird screen filter integrated into the hood, dry bulb sensor and relief damper. Separate field accessories of single enthalpy and dual enthalpy are also available. A built-in barometric relief of 25% is provided. SINGLE ENTHALPY SENSOR - Sensor replaces dry bulb sensor standard in economizer kit. Provides improved economizer operation by sensing the dry bulb temperature from outdoors plus the enthalpy content of the outdoor air. DUAL ENTHALPY SENSOR - Additional sensor to single enthalpy sensor. Sensor senses both the return air temperature dry bulb and humidity in conjunction with the single enthalpy to determine the most economical mix. Single Enthalpy sensor also required. PRESSURE SWITCH UPGRADE KIT - Contains screw in type High pressure, Low Pressure/Loss of Charge switch, freeze protection switch and lockout relay. Switches are placed onto existing scharder ports located in the unit by furnished adapters. When abnormal conditions are sensed through the pressure switches, the unit will lock out preventing any further operation until reset or problem is corrected. Package agency approved. HAIL GUARD KIT - Kit contains protective grilles made of expanded aluminum with full perimeter frame. Sloped hoods are also included to assure maximum protection. ANTI SHORT CYCLE TIMER - Automatically prevents the compressor from restarting for 5 minutes after cycled off.not required if Thermostat 2ET07700224 and 2ET04700224 are used. FILTER / FRAME KIT (Single Phase only) - Kit contains the necessary hardware to field install return air filters into the base unit. Pre-cut filter racks and appropriate cleanable standard size filters are shipped in one kit. The filter rack is suitable for either 1" or 2" filters. (1" filter is supplied) This kit is available for single phase horizontal or vertical duct application only. Standard in all 3 Phase models. MOTORIZED FRESH AIR DAMPER - Designed for duct mounted side supply/return and unit mounted down supply/ return applications. Damper capable of providing 0% through 50% of outdoor air (field supplied). Closes on power loss, includes hood and screen assembly. RECTANGLE TO ROUND ADAPTERS - Kit includes one supply and one return air rectangle to round duct adapter. Adapters are preformed and designed to fit over current duct openings on the base unit. Transition is from side square duct opening to 14" round duct opening. ROOF CURBS - NRCA approved curbs provide proper fit to base unit for rooftop installations. Curbs are designed to be assembled through hinge pins in each corner. Kit also provides seal strip to assure a water tight seal. 8 and 14 inch high roof curbs are available. MANUAL OUTDOOR DAMPER - Provides 0% through 50% outdoor air capability (field adjustable). Designed for duct mounted side supply/return applications. Includes hood and screen assembly. WALL THERMOSTAT - The units are designed to operate with 24-volt electronic and electro-mechanical thermostats. All units can operate with single stage heat / single stage cool thermostats - with or without the economizer. LOW AMBIENT KIT - Kit provides necessary hardware to convert unit to operate in cooling cycle down to 0º F. Standard unit operation 45º F. TRANSFORMER KIT - Kit provides necessary hardware to provide single phase models from factory furnished 40 VA transformer capability to 75 VA transformer capability. (Required on installations with economizer or motorized damper.) Unitary Products Group 5
DIRECT DRIVE CONDENSER FAN MOTOR BLOW-THROUGH DESIGN WITH RELIABLE ALUMINIZED STEEL TUBULAR HEAT EXCHANGERS HIGHLY EFFICIENT ENHANCED COPPER TUBE/ALUMINUM FIN EVAPORATOR COIL LONG LASTING POWDER PAINT FINISH HIGHLY EFFICIENT ENHANCED COPPER TUBE/ALUMINUM FIN CONDENSER COIL DECORATIVE PROTECTIVE COIL GAURD REAR AND BOTTOM RETURN AIR AND SUPPLY AIR DUCT OPENINGS HIGH EFFICIENCY COMPRESSOR RIGIDLY MOUNTED PILOT ASSEMBLY HEAVY GAUGE REMOVABLE BASE RAILS DIRECT DRIVE BLOWER MOTOR WITH SLIDE-OUT BLOWER ASSEMBLY POWER VENTER MOTOR HIGH GRADE ALUMINIZED IN-SHOT BURNERS LOW VOLTAGE TERMINAL BLOCK SELF-DIAGNOSTIC CONTROLS AUTOMATIC GAS VALVE (1/2" - 14 NPTI) HIGH VOLTAGE TERMINAL BLOCK FIGURE 2 - UNIT COMPONENT LOCATION TABLE 1: PHYSICAL DATA EVAPORATOR BLOWER EVAPORATOR COIL CONDENSER FAN MODEL DNP 024 030-1Ø 030-3Ø 036 042 048 060 CENTRIFUGAL BLOWER (Dia. x W. in.) 10 x 8 10 x 8 10 x 8 11 x 10 12 x 11 12 x 11 12 x 11 FAN MOTOR HP 1/2 3/4 3/4 3/4 1 1 1 ROWS DEEP 2 3 3 3 3 3 3 FINS PER INCH 15 13 13 13 13 16 16 FACE AREA (Sq. Ft.) 3.5 3.5 3.5 3.5 4.5 4.5 4.5 PROPELLER DIA. (in.) 22 22 22 22 22 22 22 FAN MOTOR HP 1/4 1/4 1/4 1/4 1/4 1/3 1/3 NOM. TOTAL 2,200 2,400 2,400 2,400 2,400 3,000 3,500 ROWS DEEP 2 1 1 2 2 2 2 CONDENSER COIL FINS PER INCH 20 20 20 20 20 20 20 FACE AREA (Sq. Ft.) 11.7 11.7 11.7 11.7 14.7 14.7 14.7 CHARGE REFRIGERANT 22 (lbs./oz.) 6 / 4 5 / 4 4 / 9 6 / 12 9 / 6 8 / 4 8 / 8 FILTER FURNACE SECTION FACE AREA (Sq. Ft.) Size (Actual) 2.6 / 19 x 19.5 2.6 / 19 x 19.5 2.6 / 19 x 19.5 2.6 / 19 x 19.5 3.1 / 19.5 x 11.5 (2 Reqd.) 3.1 / 19.5 x 11.5 (2 Reqd.) 3.1 / 19.5 x11.5 (2 Reqd.) NATURAL GAS BURNER ORIFICE NO. (Drill Size) 43 43 43 43 40 40 40 PROPANE BURNER ORIFICE NO. (Drill Size) 55 55 55 55 53 53 53 GAS CONNECTION SIZE 1/2 NPTI 1/2 NPTI 1/2 NPTI 1/2 NPTI 1/2 NPTI 1/2 NPTI 1/2 NPTI COMPRESSOR HERMETIC TYPE, (Qty. = 1) Recip Rotary Scroll Scroll Recip Scroll Scroll 6 Unitary Products Group
TABLE 2: RATINGS COOLING/SINGLE STAGE GAS HEATING MODEL DNP NET COOLING CAPACITY 1 SOUND RATING MBH SEER 3 EER 4 (dbels) 2 INPUT (MBH) OUTPUT (MBH) GAS HEAT CAPACITY / EFFICIENCIES AFUE 5 (%) NUMBER OF BURNERS TEMP. RISE ( F) RANGE 024N03606 23.7 13 11 81 45 36 80.0 2 25-55 024N05606 23.7 13 11 81 70 56 80.0 3 30-60 030N03606 28.4 13 11.1 80 45 36 80.0 2 25-55 030N03625 28.4 13 11.1 80 45 36 80.0 2 25-55 030N03646 28.4 13 11.1 80 45 36 80.0 2 25-55 030N05606 28.4 13 11.1 80 70 56 80.0 3 30-60 030N05625 28.4 13 11.1 80 70 56 80.0 3 30-60 030N05646 28.4 13 11.1 80 70 56 80.0 3 30-60 036N03606 37.4 13.65 11.75 81 45 36 80.0 2 25-55 036N03625 37.4 13.65 11.75 81 45 36 80.0 2 25-55 036N03646 37.4 13.65 11.75 81 45 36 80.0 2 25-55 036N03658 37.4 13.65 11.75 81 45 36 80.0 2 25-55 036N05606 37.4 13.65 11.75 81 70 56 80.0 3 25-55 036N05625 37.4 13.65 11.75 81 70 56 80.0 3 25-55 036N05646 37.4 13.65 11.75 81 70 56 80.0 3 25-55 036N05658 37.4 13.65 11.75 81 70 56 80.0 3 25-55 036N07206 37.4 13.65 11.75 81 90 72 80.0 4 30-60 036N07225 37.4 13.65 11.75 81 90 72 80.0 4 30-60 036N07246 37.4 13.65 11.75 81 90 72 80.0 4 30-60 036N07258 37.4 13.65 11.75 81 90 72 80.0 4 30-60 042N06506 42 13 11.1 85 80 64 80.0 3 25-55 042N06525 42 13 11.1 85 80 64 80.0 3 25-55 042N06546 42 13 11.1 85 80 64 80.0 3 25-55 042N06558 42 13 11.1 85 80 64 80.0 3 25-55 042N09006 42 13 11.1 85 108 86 80.0 4 45-75 042N09025 42 13 11.1 85 108 86 80.0 4 45-75 042N09046 42 13 11.1 85 108 86 80.0 4 45-75 042N09058 42 13 11.1 85 108 86 80.0 4 45-75 048N06506 48 13.2 11.7 84 80 64 80.0 3 25-55 048N06525 48 13.2 11.7 84 80 64 80.0 3 25-55 048N06546 48 13.2 11.7 84 80 64 80.0 3 25-55 048N06558 48 13.2 11.7 84 80 64 80.0 3 25-55 048N09006 48 13.2 11.7 84 108 86 80.0 4 35-65 048N09025 48 13.2 11.7 84 108 86 80.0 4 35-65 048N09046 48 13.2 11.7 84 108 86 80.0 4 35-65 048N09058 48 13.2 11.7 84 108 86 80.0 4 35-65 048N11006 48 13.2 11.7 84 135 107 80.0 5 45-75 048N11025 48 13.2 11.7 84 135 107 80.0 5 45-75 048N11046 48 13.2 11.7 84 135 107 80.0 5 45-75 048N11058 48 13.2 11.7 84 135 107 80.0 5 45-75 060N06506 55.5 13 11.2 84 80 64 80.0 3 25-55 060N06525 55.5 13 11.2 84 80 64 80.0 3 25-55 060N06546 55.5 13 11.2 84 80 64 80.0 3 25-55 060N06558 55.5 13 11.2 84 80 64 80.0 3 25-55 060N09006 55.5 13 11.2 84 108 86 80.0 4 35-65 060N09025 55.5 13 11.2 84 108 86 80.0 4 35-65 060N09046 55.5 13 11.2 84 108 86 80.0 4 35-65 060N09058 55.5 13 11.2 84 108 86 80.0 4 35-65 060N11006 55.5 13 11.2 84 135 107 80.0 5 45-75 060N11025 55.5 13 11.2 84 135 107 80.0 5 45-75 060N11046 55.5 13 11.2 84 135 107 80.0 5 45-75 060N11058 55.5 13 11.2 84 135 107 80.0 5 45-75 1. Net Cooling Capacity = ARI 210 standard rating conditions. 2. (dbels) = ARI 270-95 3. Seasonal Energy Efficiency Ratio - the total cooling output in BTU s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period. 4. Tested in accordance with ARI 210 Standard Rating Conditions. 5. AFUE = Annual Fuel Utilization Efficiency. Unitary Products Group 7
TABLE 3: RATINGS COOLING/TWO STAGE GAS HEATING MODEL DNP NET COOLING CAPACITY 1 SOUND RATING MBH SEER 3 EER 4 (dbels) 2 INPUT (MBH) Full Fire/Low Fire GAS HEAT CAPACITY / EFFICIENCIES OUTPUT (MBH) Full Fire/Low Fire AFUE 5 (%) NUMBER OF BURNERS TEMP. RISE ( F) RANGE 024D05606 23.7 13 11 81 70/46 56/36 80.0 3 30-60 030D05606 28.4 13 11.1 80 70/46 56/36 80.0 3 30-60 030D05625 28.4 13 11.1 80 70/46 56/36 80.0 3 30-60 030D05646 28.4 13 11.1 80 70/46 56/36 80.0 3 30-60 036D05606 37.4 13.65 11.75 81 70/46 56/36 80.0 3 25-55 036D05625 37.4 13.65 11.75 81 70/46 56/36 80.0 3 25-55 036D05646 37.4 13.65 11.75 81 70/46 56/36 80.0 3 25-55 036D05658 37.4 13.65 11.75 81 70/46 56/36 80.0 3 25-55 036D07206 37.4 13.65 11.75 81 90/59 72/47 80.0 4 30-60 036D07225 37.4 13.65 11.75 81 90/59 72/47 80.0 4 30-60 036D07246 37.4 13.65 11.75 81 90/59 72/47 80.0 4 30-60 036D07258 37.4 13.65 11.75 81 90/59 72/47 80.0 4 30-60 042D09006 42 13 11.1 85 108/70 86/56 80.0 4 45-75 042D09025 42 13 11.1 85 108/70 86/56 80.0 4 45-75 042D09046 42 13 11.1 85 108/70 86/56 80.0 4 45-75 042D09058 42 13 11.1 85 108/70 86/56 80.0 4 45-75 048D09006 48 13.2 11.7 84 108/70 86/56 80.0 4 35-65 048D09025 48 13.2 11.7 84 108/70 86/56 80.0 4 35-65 048D09046 48 13.2 11.7 84 108/70 86/56 80.0 4 35-65 048D09058 48 13.2 11.7 84 108/70 86/56 80.0 4 35-65 048D11006 48 13.2 11.7 84 135/88 107/70 80.0 5 45-75 048D11025 48 13.2 11.7 84 135/88 107/70 80.0 5 45-75 048D11046 48 13.2 11.7 84 135/88 107/70 80.0 5 45-75 048D11058 48 13.2 11.7 84 135/88 107/70 80.0 5 45-75 060D09006 55.5 13 11.2 84 108/70 86/56 80.0 4 35-65 060D09025 55.5 13 11.2 84 108/70 86/56 80.0 4 35-65 060D09046 55.5 13 11.2 84 108/70 86/56 80.0 4 35-65 060D09058 55.5 13 11.2 84 108/70 86/56 80.0 4 35-65 060D11006 55.5 13 11.2 84 135/88 107/70 80.0 5 45-75 060D11025 55.5 13 11.2 84 135/88 107/70 80.0 5 45-75 060D11046 55.5 13 11.2 84 135/88 107/70 80.0 5 45-75 060D11058 55.5 13 11.2 84 135/88 107/70 80.0 5 45-75 1. Net Cooling Capacity = ARI 210 standard rating conditions. 2. (dbels) = ARI 270-95 3. Seasonal Energy Efficiency Ratio - the total cooling output in BTU s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period. 4. Tested in accordance with ARI 210 Standard Rating Conditions. 5. AFUE = Annual Fuel Utilization Efficiency. 8 Unitary Products Group
TABLE 4: DNP024 COOLING CAPACITIES - 2 TON Air on Evaporator Coil 600 700 800 900 1000 600 700 800 900 1000 WB ( F) Net Capacity 1 (MBh) Total Input Power (kw) 2 Temperature of Air on Condenser Coil Sensible Capacity (MBh) Net Total Input Sensible Capacity (MBh) Return Dry Bulb ( F) Capacity 1 Power Return Dry Bulb ( F) 90 85 80 75 70 65 (MBh) (kw) 2 90 85 80 75 70 65 75 F 85 F 77 30.5 1.8 13.7 10.8 8.0 - - - 28.8 1.9 14.0 11.1 8.3 - - - 72 28.3 1.8 17.7 14.9 12.0 9.2 - - 26.5 1.9 17.7 14.9 12.0 9.2 - - 67 26.0 1.8 21.7 18.9 16.0 13.2 10.3-24.3 1.9 21.5 18.6 15.8 12.9 10.1-62 24.0 1.8 24.0 22.9 19.1 16.3 13.4 10.6 22.4 1.9 22.4 21.9 19.0 16.2 13.3 10.5 57 23.3 1.8 23.3 23.3 20.4 17.6 14.7 11.9 22.1 1.9 22.1 22.1 19.8 16.9 14.1 11.2 77 32.6 1.8 15.4 12.5 9.1 - - - 30.7 2.0 16.0 12.6 9.3 - - - 72 30.2 1.8 20.4 17.1 13.7 10.3 - - 28.3 2.0 20.2 16.8 13.5 10.1 - - 67 27.8 1.8 25.5 21.6 18.3 14.9 11.5-25.9 2.0 24.4 21.0 17.6 14.3 10.9-62 25.6 1.8 25.6 25.0 21.8 18.5 15.1 11.7 23.9 2.0 23.9 23.6 21.3 17.9 14.5 11.2 57 24.9 1.8 24.9 24.9 23.3 19.9 16.6 13.2 23.5 2.0 23.5 23.5 22.1 18.8 15.4 12.0 77 34.7 1.9 17.1 14.2 10.3 - - - 32.6 2.0 18.0 14.2 10.3 - - - 72 32.1 1.9 23.2 19.3 15.4 11.5 - - 30.0 2.0 22.7 18.8 14.9 11.0 - - 67 29.6 1.9 29.2 24.4 20.5 16.6 12.7-27.5 2.0 27.3 23.4 19.5 15.6 11.8-62 27.2 1.9 27.2 27.2 24.5 20.6 16.7 12.9 25.4 2.0 25.4 25.4 23.5 19.7 15.8 11.9 57 26.5 1.9 26.5 26.5 26.2 22.3 18.4 14.5 25.0 2.0 25.0 25.0 24.5 20.6 16.7 12.8 72 32.2 1.9 25.1 20.7 16.2 11.8 - - 30.2 2.0 24.6 20.2 15.7 11.3 - - 67 29.7 1.9 29.5 26.1 21.6 17.2 12.8-27.6 2.1 27.5 25.0 20.6 16.2 11.8-62 27.3 1.9 27.3 27.3 26.0 21.5 17.1 12.7 25.5 2.0 25.5 25.5 24.6 20.2 15.7 11.3 57 26.6 1.9 26.6 26.6 26.4 22.0 17.5 13.1 25.2 2.0 25.2 25.2 24.9 20.5 16.0 11.6 72 32.3 1.9 27.0 22.0 17.1 12.1 - - 30.4 2.1 26.5 21.5 16.6 11.6 - - 67 29.8 1.9 29.8 27.7 22.8 17.8 12.8-27.8 2.1 27.8 26.7 21.7 16.7 11.8-62 27.4 1.9 27.4 27.4 27.4 22.4 17.5 12.5 25.7 2.1 25.7 25.7 25.7 20.7 15.7 10.8 57 26.6 1.9 26.6 26.6 26.6 21.7 16.7 11.7 25.3 2.1 25.3 25.3 25.3 20.3 15.4 10.4 95 F 105 F 77 27.0 2.1 14.3 11.4 8.6 - - - 25.2 2.3 13.4 10.6 7.7 - - - 72 24.7 2.1 17.7 14.9 12.0 9.2 - - 23.1 2.2 17.1 14.2 11.4 8.5 - - 67 22.5 2.1 21.2 18.4 15.5 12.7 9.8-20.9 2.2 20.3 17.9 15.0 12.2 9.3-62 20.9 2.0 20.9 20.9 18.9 16.0 13.2 10.3 19.7 2.2 19.7 19.7 17.8 15.0 12.1 9.3 57 20.9 2.0 20.9 20.9 19.1 16.3 13.4 10.6 19.8 2.2 19.8 19.8 18.0 15.2 12.3 9.5 77 28.7 2.1 16.6 12.8 9.4 - - - 26.7 2.3 16.3 11.8 8.5 - - - 72 26.3 2.1 20.0 16.6 13.2 9.8 - - 24.4 2.3 19.2 15.8 12.4 9.1 - - 67 23.9 2.1 23.3 20.4 17.0 13.7 10.3-22.2 2.3 21.8 19.8 16.4 13.1 9.7-62 22.2 2.1 22.2 22.2 20.7 17.4 14.0 10.6 20.9 2.2 20.9 20.9 19.5 16.2 12.8 9.4 57 22.2 2.1 22.2 22.2 21.0 17.6 14.2 10.9 21.0 2.2 21.0 21.0 19.7 16.4 13.0 9.6 77 30.4 2.2 19.0 14.1 10.2 - - - 28.2 2.4 19.2 13.1 9.2 - - - 72 27.9 2.2 22.2 18.3 14.4 10.5 - - 25.8 2.3 21.3 17.4 13.5 9.6 - - 67 25.4 2.2 25.4 22.4 18.5 14.6 10.8-23.4 2.3 23.4 21.7 17.9 14.0 10.1-62 23.5 2.1 23.5 23.5 22.6 18.7 14.8 10.9 22.0 2.3 22.0 22.0 21.2 17.3 13.4 9.5 57 23.6 2.1 23.6 23.6 22.8 18.9 15.1 11.2 22.1 2.3 22.1 22.1 21.4 17.6 13.7 9.8 72 28.1 2.2 24.1 19.6 15.2 10.8 - - 26.0 2.4 23.1 18.7 14.2 9.8 - - 67 25.6 2.2 25.6 24.0 19.6 15.2 10.7-23.6 2.3 23.6 22.7 18.8 14.4 10.0-62 23.7 2.2 23.7 23.7 23.2 18.8 14.4 10.0 22.2 2.3 22.2 22.2 21.8 17.4 13.0 8.5 57 23.8 2.2 23.8 23.8 23.4 19.0 14.5 10.1 22.3 2.3 22.3 22.3 22.0 17.6 13.1 8.7 72 28.4 2.2 26.0 21.0 16.0 11.1 - - 26.3 2.4 24.9 19.9 15.0 10.0 - - 67 25.8 2.2 25.8 25.6 20.7 15.7 10.7-23.8 2.4 23.8 23.7 19.8 14.8 9.8-62 23.9 2.2 23.9 23.9 23.9 19.0 14.0 9.0 22.4 2.4 22.4 22.4 22.4 17.4 12.5 7.5 57 23.9 2.2 23.9 23.9 23.9 19.0 14.0 9.0 22.5 2.4 22.5 22.5 22.5 17.6 12.6 7.6 Unitary Products Group 9
TABLE 4: DNP024 COOLING CAPACITIES - 2 TON (Continued) Air on Temperature of Air on Condenser Coil Evaporator Coil Net Total Input Sensible Capacity (MBh) Net Total Input Sensible Capacity (MBh) WB Capacity 1 Power Return Dry Bulb ( F) Capacity 1 Power Return Dry Bulb ( F) ( F) (MBh) (kw) 2 90 85 80 75 70 65 (MBh) (kw) 2 90 85 80 75 70 65 115 F 125 F 77 23.5 2.5 12.6 9.7 6.9 - - - 21.7 2.7 11.7 8.9 6.0 - - - 72 21.4 2.4 16.4 13.6 10.7 7.9 - - 19.8 2.6 15.7 12.9 10.0 7.2 - - 600 67 19.4 2.4 19.4 17.4 14.5 11.7 8.8-17.8 2.5 17.8 16.9 14.1 11.2 8.4-62 18.5 2.4 18.5 18.5 16.8 14.0 11.1 8.2 17.4 2.5 17.4 17.4 15.8 12.9 10.1 7.2 57 18.7 2.4 18.7 18.7 17.0 14.1 11.3 8.4 17.6 2.5 17.6 17.6 15.9 13.0 10.2 7.3 77 24.7 2.5 16.0 10.9 7.5 - - - 22.7 2.7 15.7 9.9 6.5 - - - 72 22.6 2.4 18.4 15.0 11.7 8.3 - - 20.7 2.6 17.6 14.3 10.9 7.5 - - 700 67 20.4 2.4 20.4 19.2 15.9 12.5 9.1-18.6 2.5 18.6 18.6 15.3 11.9 8.5-62 19.5 2.4 19.5 19.5 18.3 15.0 11.6 8.2 18.2 2.5 18.2 18.2 17.1 13.8 10.4 7.0 57 19.7 2.4 19.7 19.7 18.5 15.1 11.8 8.4 18.5 2.6 18.5 18.5 17.3 13.9 10.5 7.2 77 26.0 2.5 19.4 12.0 8.1 - - - 23.7 2.7 19.7 10.9 7.1 - - - 72 23.7 2.5 20.4 16.5 12.7 8.8 - - 21.6 2.6 19.6 15.7 11.8 7.9 - - 800 67 21.4 2.4 21.4 21.1 17.2 13.3 9.4-19.4 2.6 19.4 19.4 16.5 12.6 8.7-62 20.5 2.4 20.5 20.5 19.9 16.0 12.1 8.2 19.0 2.6 19.0 19.0 18.5 14.6 10.7 6.8 57 20.7 2.4 20.7 20.7 20.1 16.2 12.3 8.4 19.3 2.6 19.3 19.3 18.7 14.8 10.9 7.0 72 23.9 2.5 22.1 17.7 13.3 8.8 - - 21.8 2.7 21.1 16.7 12.3 7.9 - - 900 67 21.6 2.5 21.6 21.5 18.0 13.6 9.2-19.7 2.6 19.7 19.7 17.2 12.8 8.4-62 20.7 2.5 20.7 20.7 20.4 16.0 11.5 7.1 19.2 2.6 19.2 19.2 19.0 14.5 10.1 5.7 57 20.9 2.5 20.9 20.9 20.6 16.2 11.7 7.3 19.5 2.6 19.5 19.5 19.2 14.8 10.3 5.9 72 24.2 2.6 23.8 18.8 13.9 8.9 - - 22.1 2.8 22.1 17.8 12.8 7.8 - - 1000 67 21.8 2.5 21.8 21.8 18.9 13.9 8.9-19.9 2.7 19.9 19.9 17.9 13.0 8.0-62 20.9 2.5 20.9 20.9 20.9 15.9 11.0 6.0 19.4 2.7 19.4 19.4 19.4 14.4 9.5 4.5 57 21.1 2.5 21.1 21.1 21.1 16.1 11.2 6.2 19.7 2.7 19.7 19.7 19.7 14.7 9.8 4.8 1. These capacities are Net Capacities. 2. These ratings include the compressor, condenser fan and supply air blower motors. 10 Unitary Products Group
TABLE 5: DNP030 COOLING CAPACITIES - 2.5 TON Air on Evaporator Coil 750 875 1000 1125 1250 750 875 1000 1125 1250 WB ( F) Net Capacity 1 (MBh) Total Input Power (kw) 2 Temperature of Air on Condenser Coil Sensible Capacity (MBh) Net Total Input Sensible Capacity (MBh) Return Dry Bulb ( F) Capacity 1 Power Return Dry Bulb ( F) 90 85 80 75 70 65 (MBh) (kw) 2 90 85 80 75 70 65 75 F 85 F 77 33.0 1.9 16.9 13.3 9.8 - - - 32.2 2.2 16.1 12.6 9.0 - - - 72 31.4 2.0 21.3 17.7 14.1 10.6 - - 30.4 2.2 20.6 17.1 13.5 10.0 - - 67 29.8 2.0 25.6 22.1 18.5 14.9 11.4-28.6 2.2 25.1 21.6 18.0 14.4 10.9-62 28.9 1.9 28.9 26.5 22.9 19.3 15.8 12.2 27.4 2.1 27.4 25.7 22.1 18.6 15.0 11.4 57 28.6 1.9 28.6 28.0 24.4 20.9 17.3 13.7 27.3 2.1 27.3 26.6 23.0 19.5 15.9 12.4 77 33.4 2.0 19.7 14.9 10.7 - - - 32.7 2.3 19.4 14.2 9.9 - - - 72 31.8 2.0 23.9 19.7 15.4 11.2 - - 30.8 2.3 23.3 19.1 14.9 10.7 - - 67 30.1 2.1 28.0 24.4 20.2 16.0 11.8-29.0 2.3 27.3 24.1 19.9 15.7 11.4-62 29.2 2.0 29.2 28.0 25.0 20.8 16.6 12.4 27.8 2.2 27.8 26.9 24.4 20.2 16.0 11.8 57 29.0 1.9 29.0 28.6 26.7 22.5 18.3 14.0 27.7 2.2 27.7 27.4 25.4 21.2 17.0 12.8 77 33.8 2.1 22.5 16.5 11.6 - - - 33.1 2.4 22.6 15.7 10.9 - - - 72 32.1 2.1 26.5 21.6 16.7 11.9 - - 31.3 2.4 26.0 21.2 16.3 11.4 - - 67 30.5 2.1 30.5 26.7 21.9 17.0 12.2-29.4 2.4 29.4 26.6 21.7 16.9 12.0-62 29.5 2.0 29.5 29.5 27.1 22.2 17.4 12.5 28.2 2.3 28.2 28.2 26.7 21.8 16.9 12.1 57 29.3 2.0 29.3 29.3 28.9 24.1 19.2 14.4 28.1 2.3 28.1 28.1 27.8 22.9 18.1 13.2 72 32.5 2.2 28.6 23.1 17.5 12.0 - - 31.7 2.4 28.2 22.7 17.2 11.6 - - 67 30.8 2.2 30.8 29.0 22.9 17.4 11.8-29.8 2.4 29.8 28.4 22.9 17.3 11.8-62 29.9 2.1 29.9 29.9 28.7 23.2 17.6 12.1 28.5 2.4 28.5 28.5 27.8 22.2 16.7 11.2 57 29.7 2.1 29.7 29.7 29.5 24.0 18.4 12.9 28.5 2.3 28.5 28.5 28.3 22.8 17.2 11.7 72 32.9 2.3 30.8 24.5 18.3 12.1 - - 32.1 2.5 30.4 24.2 18.0 11.8 - - 67 31.2 2.3 31.2 31.2 24.0 17.7 11.5-30.2 2.5 30.2 30.2 24.0 17.8 11.6-62 30.3 2.2 30.3 30.3 30.3 24.1 17.9 11.6 28.9 2.4 28.9 28.9 28.9 22.7 16.5 10.3 57 30.0 2.2 30.0 30.0 30.0 23.8 17.6 11.4 28.8 2.4 28.8 28.8 28.8 22.6 16.4 10.2 95 F 105 F 77 31.4 2.5 15.4 11.8 8.3 - - - 30.6 2.7 15.0 11.5 7.9 - - - 72 29.4 2.4 20.0 16.5 12.9 9.3 - - 28.2 2.7 19.3 15.7 12.2 8.6 - - 67 27.5 2.4 24.7 21.1 17.5 14.0 10.4-25.7 2.7 23.5 20.0 16.4 12.8 9.3-62 25.9 2.4 25.9 24.9 21.3 17.8 14.2 10.6 24.8 2.7 24.8 23.3 19.7 16.2 12.6 9.0 57 26.1 2.4 26.1 25.2 21.7 18.1 14.5 11.0 24.8 2.7 24.8 23.5 20.0 16.4 12.8 9.3 77 31.9 2.5 19.1 13.4 9.2 - - - 31.0 2.8 19.3 13.2 8.9 - - - 72 29.9 2.5 22.8 18.6 14.4 10.2 - - 28.5 2.8 22.1 17.9 13.7 9.5 - - 67 27.9 2.5 26.5 23.8 19.5 15.3 11.1-26.1 2.8 25.0 22.7 18.5 14.3 10.1-62 26.4 2.4 26.4 25.9 23.8 19.6 15.4 11.1 25.1 2.7 25.1 24.3 22.3 18.1 13.8 9.6 57 26.5 2.4 26.5 26.1 24.1 19.9 15.7 11.5 25.1 2.7 25.1 24.5 22.5 18.3 14.1 9.9 77 32.5 2.6 22.7 15.0 10.1 - - - 31.3 2.9 23.6 14.9 9.9 - - - 72 30.4 2.6 25.6 20.7 15.8 11.0 - - 28.9 2.9 25.0 20.1 15.3 10.4 - - 67 28.4 2.6 28.4 26.4 21.5 16.7 11.8-26.4 2.9 26.4 25.4 20.6 15.8 10.9-62 26.8 2.5 26.8 26.8 26.2 21.4 16.5 11.6 25.4 2.8 25.4 25.4 24.8 19.9 15.1 10.2 57 26.9 2.5 26.9 26.9 26.6 21.8 16.9 12.0 25.4 2.8 25.4 25.4 25.1 20.3 15.4 10.5 72 30.8 2.7 27.9 22.3 16.8 11.2 - - 29.4 3.0 27.2 21.8 16.3 10.7 - - 67 28.8 2.7 28.8 27.8 22.8 17.3 11.8-26.9 3.0 26.9 26.4 22.0 16.4 10.9-62 27.2 2.6 27.2 27.2 26.9 21.3 15.8 10.3 25.8 2.9 25.8 25.8 25.6 20.0 14.5 9.0 57 27.3 2.6 27.3 27.3 27.1 21.6 16.0 10.5 25.9 2.9 25.9 25.9 25.7 20.2 14.7 9.1 72 31.2 2.8 30.1 23.9 17.7 11.5 - - 29.9 3.0 29.4 23.5 17.3 11.1 - - 67 29.1 2.8 29.1 29.1 24.1 17.9 11.7-27.3 3.1 27.3 27.3 23.3 17.1 10.9-62 27.5 2.7 27.5 27.5 27.5 21.3 15.1 8.9 26.3 3.0 26.3 26.3 26.3 20.1 13.9 7.7 57 27.6 2.7 27.6 27.6 27.6 21.4 15.2 9.0 26.3 3.0 26.3 26.3 26.3 20.1 13.9 7.7 Unitary Products Group 11
TABLE 5: DNP030 COOLING CAPACITIES - 2.5 TON (Continued) Air on Temperature of Air on Condenser Coil Evaporator Coil Net Total Input Sensible Capacity (MBh) Net Total Input Sensible Capacity (MBh) WB Capacity 1 Power Return Dry Bulb ( F) Capacity 1 Power Return Dry Bulb ( F) ( F) (MBh) (kw) 2 90 85 80 75 70 65 (MBh) (kw) 2 90 85 80 75 70 65 115 F 125 F 77 29.8 3.0 14.7 11.1 7.6 - - - 29.0 3.2 14.3 10.8 7.2 - - - 72 26.9 3.0 18.5 15.0 11.4 7.9 - - 25.7 3.3 17.8 14.2 10.7 7.1 - - 750 67 24.0 3.0 22.4 18.8 15.3 11.7 8.2-22.3 3.3 21.3 17.7 14.2 10.6 7.0-62 23.6 3.0 23.6 21.7 18.1 14.6 11.0 7.4 22.4 3.2 22.4 20.1 16.5 13.0 9.4 5.8 57 23.6 3.0 23.6 21.9 18.3 14.7 11.2 7.6 22.3 3.3 22.3 20.2 16.6 13.0 9.5 5.9 77 30.0 3.0 19.6 13.0 8.6 - - - 29.0 3.3 19.9 12.7 8.4 - - - 72 27.1 3.1 21.5 17.3 13.1 8.9 - - 25.7 3.4 20.9 16.6 12.4 8.2 - - 875 67 24.2 3.1 23.4 21.6 17.5 13.3 9.1-22.4 3.4 21.8 20.5 16.5 12.3 8.1-62 23.8 3.0 23.8 22.8 20.8 16.5 12.3 8.1 22.5 3.3 22.5 21.3 19.2 15.0 10.8 6.6 57 23.7 3.0 23.7 22.9 20.9 16.7 12.5 8.3 22.4 3.4 22.4 21.3 19.4 15.1 10.9 6.7 77 30.2 3.1 24.5 14.8 9.7 - - - 29.1 3.4 25.4 14.7 9.6 - - - 72 27.3 3.2 24.5 19.6 14.7 9.9 - - 25.7 3.5 23.9 19.0 14.2 9.3 - - 1000 67 24.4 3.2 24.4 24.4 19.7 14.9 10.0-22.4 3.5 22.4 22.4 18.8 14.0 9.1-62 23.9 3.1 23.9 23.9 23.4 18.5 13.7 8.8 22.5 3.4 22.5 22.5 22.0 17.1 12.3 7.4 57 23.9 3.1 23.9 23.9 23.6 18.7 13.9 9.0 22.4 3.4 22.4 22.4 22.1 17.2 12.4 7.5 72 28.0 3.2 26.5 21.3 15.8 10.2 - - 26.5 3.5 25.9 20.8 15.3 9.7 - - 1125 67 25.0 3.3 25.0 25.0 21.1 15.6 10.0-23.1 3.6 23.1 23.1 20.3 14.7 9.2-62 24.5 3.2 24.5 24.5 24.3 18.7 13.2 7.6 23.2 3.5 23.2 23.2 22.9 17.4 11.9 6.3 57 24.5 3.2 24.5 24.5 24.3 18.8 13.3 7.7 23.1 3.5 23.1 23.1 23.0 17.4 11.9 6.3 72 28.6 3.3 28.6 23.0 16.8 10.6 - - 27.3 3.6 27.3 22.6 16.4 10.2 - - 1250 67 25.6 3.3 25.6 25.6 22.5 16.3 10.1-23.8 3.6 23.8 23.8 21.7 15.5 9.3-62 25.1 3.3 25.1 25.1 25.1 18.9 12.7 6.5 23.9 3.5 23.9 23.9 23.9 17.7 11.5 5.3 57 25.1 3.3 25.1 25.1 25.1 18.9 12.7 6.4 23.8 3.5 23.8 23.8 23.8 17.6 11.4 5.2 1. These capacities are Net Capacities. 2. These ratings include the compressor, condenser fan and supply air blower motors. 12 Unitary Products Group
TABLE 6: DNP036 COOLING CAPACITIES - 3 TON Air on Evaporator Coil 900 1050 1200 1350 1500 900 1050 1200 1350 1500 WB ( F) Net Capacity 1 (MBh) Total Input Power (kw) 2 Temperature of Air on Condenser Coil Sensible Capacity (MBh) Net Total Input Sensible Capacity (MBh) Return Dry Bulb ( F) Capacity 1 Power Return Dry Bulb ( F) 90 85 80 75 70 65 (MBh) (kw) 2 90 85 80 75 70 65 75 F 85 F 77 44.4 2.7 22.9 18.6 14.3 - - - 44.5 2.8 22.0 17.8 13.5 - - - 72 42.2 2.6 28.6 24.3 20.0 15.7 - - 41.3 2.8 27.7 23.4 19.2 14.9 - - 67 39.9 2.5 34.3 30.0 25.7 21.4 17.1-38.1 2.8 33.4 29.1 24.8 20.6 16.3-62 36.5 2.6 36.5 35.7 31.5 27.2 22.9 18.6 35.7 2.8 35.7 34.6 30.3 26.1 21.8 17.5 57 35.4 2.6 35.4 36.0 32.6 28.3 24.0 19.7 34.9 2.8 34.9 34.9 31.1 26.8 22.5 18.2 77 46.1 2.7 24.6 20.4 15.4 - - - 45.6 2.9 24.6 19.5 14.4 - - - 72 43.7 2.6 31.6 26.5 21.5 16.4 - - 42.3 2.9 30.6 25.6 20.5 15.5 - - 67 41.4 2.5 38.5 32.6 27.5 22.5 17.4-39.0 2.8 36.7 31.7 26.6 21.6 16.5-62 37.9 2.6 37.9 37.5 33.7 28.7 23.6 18.6 36.6 2.8 36.6 36.0 32.5 27.5 22.4 17.4 57 36.7 2.6 36.7 37.0 34.9 29.8 24.8 19.7 35.8 2.8 35.8 35.8 33.3 28.2 23.2 18.1 77 47.7 2.8 26.3 22.2 16.4 - - - 46.7 3.0 27.2 21.3 15.4 - - - 72 45.3 2.6 34.6 28.7 22.9 17.1 - - 43.3 2.9 33.6 27.7 21.9 16.1 - - 67 42.8 2.5 42.8 35.2 29.4 23.6 17.7-39.9 2.9 39.9 34.2 28.4 22.6 16.7-62 39.2 2.6 39.2 39.2 36.0 30.2 24.3 18.5 37.4 2.9 37.4 37.4 34.7 28.9 23.1 17.2 57 38.0 2.6 38.0 38.0 37.2 31.4 25.6 19.7 36.7 2.9 36.7 36.7 35.5 29.7 23.9 18.0 72 45.5 2.8 37.2 30.6 23.9 17.3 - - 44.0 3.1 36.4 29.8 23.2 16.5 - - 67 43.1 2.7 43.1 37.4 30.7 24.1 17.4-40.6 3.0 40.6 36.7 30.0 23.4 16.7-62 39.4 2.8 39.4 39.4 37.8 31.2 24.5 17.9 38.0 3.1 38.0 38.0 36.7 30.0 23.4 16.7 57 38.2 2.8 38.2 38.2 37.8 31.2 24.6 17.9 37.2 3.0 37.2 37.2 36.7 30.0 23.4 16.7 72 45.8 3.1 39.9 32.4 25.0 17.5 - - 44.7 3.2 39.3 31.8 24.4 16.9 - - 67 43.3 2.9 43.3 39.5 32.1 24.6 17.2-41.2 3.2 41.2 39.1 31.6 24.2 16.7-62 39.6 3.0 39.6 39.6 39.6 32.2 24.7 17.3 38.6 3.2 38.6 38.6 38.6 31.1 23.7 16.2 57 38.5 3.0 38.5 38.5 38.5 31.0 23.5 16.1 37.8 3.2 37.8 37.8 37.8 30.3 22.9 15.4 95 F 105 F 77 44.7 2.9 21.2 16.9 12.6 - - - 41.3 3.4 20.4 16.1 11.9 - - - 72 40.4 3.0 26.8 22.6 18.3 14.0 - - 37.6 3.4 26.0 21.7 17.4 13.2 - - 67 36.2 3.0 32.5 28.2 24.0 19.7 15.4-34.0 3.4 31.5 27.3 23.0 18.7 14.4-62 34.8 3.0 34.8 33.5 29.2 24.9 20.7 16.4 33.1 3.3 33.1 32.3 28.0 23.7 19.5 15.2 57 34.4 2.9 34.4 33.8 29.5 25.3 21.0 16.7 32.8 3.3 32.8 32.5 28.2 23.9 19.6 15.4 77 45.2 3.1 24.6 18.6 13.5 - - - 41.8 3.5 24.4 17.8 12.7 - - - 72 40.9 3.1 29.7 24.7 19.6 14.6 - - 38.1 3.5 28.8 23.7 18.7 13.6 - - 67 36.6 3.1 34.8 30.8 25.7 20.6 15.6-34.4 3.5 33.2 29.7 24.6 19.6 14.5-62 35.2 3.1 35.2 34.6 31.3 26.3 21.2 16.2 33.5 3.4 33.5 33.1 30.0 24.9 19.9 14.8 57 34.9 3.0 34.9 34.6 31.7 26.6 21.6 16.5 33.2 3.4 33.2 33.0 30.2 25.1 20.1 15.0 77 45.8 3.2 28.1 20.3 14.4 - - - 42.3 3.6 28.3 19.4 13.5 - - - 72 41.4 3.2 32.6 26.8 20.9 15.1 - - 38.5 3.6 31.6 25.7 19.9 14.1 - - 67 37.1 3.3 37.1 33.3 27.4 21.6 15.8-34.8 3.6 34.8 32.1 26.3 20.4 14.6-62 35.7 3.2 35.7 35.7 33.5 27.6 21.8 16.0 33.9 3.5 33.9 33.9 32.0 26.2 20.3 14.5 57 35.3 3.2 35.3 35.3 33.8 28.0 22.2 16.3 33.6 3.5 33.6 33.6 32.2 26.4 20.5 14.7 72 42.5 3.3 35.6 29.0 22.4 15.7 - - 39.6 3.7 34.5 27.9 21.3 14.6 - - 67 38.0 3.4 38.0 35.9 29.3 22.7 16.0-35.8 3.7 35.8 34.3 28.1 21.4 14.8-62 36.6 3.3 36.6 36.6 35.5 28.9 22.2 15.6 34.8 3.6 34.8 34.8 33.9 27.2 20.6 13.9 57 36.2 3.3 36.2 36.2 35.5 28.8 22.2 15.5 34.5 3.6 34.5 34.5 33.8 27.1 20.5 13.9 72 43.6 3.4 38.7 31.2 23.8 16.3 - - 40.6 3.8 37.5 30.1 22.6 15.2 - - 67 39.0 3.5 39.0 38.6 31.2 23.7 16.3-36.7 3.8 36.7 36.5 29.8 22.4 14.9-62 37.5 3.4 37.5 37.5 37.5 30.1 22.6 15.2 35.8 3.7 35.8 35.8 35.8 28.3 20.9 13.4 57 37.1 3.4 37.1 37.1 37.1 29.7 22.2 14.8 35.4 3.7 35.4 35.4 35.4 27.9 20.5 13.0 Unitary Products Group 13
TABLE 6: DNP036 COOLING CAPACITIES - 3 TON (Continued) Air on Temperature of Air on Condenser Coil Evaporator Coil Net Total Input Sensible Capacity (MBh) Net Total Input Sensible Capacity (MBh) WB Capacity 1 Power Return Dry Bulb ( F) Capacity 1 Power Return Dry Bulb ( F) ( F) (MBh) (kw) 2 90 85 80 75 70 65 (MBh) (kw) 2 90 85 80 75 70 65 115 F 125 F 77 37.8 3.8 19.7 15.4 11.1 - - - 34.4 4.3 18.9 14.6 10.4 - - - 72 34.8 3.8 25.1 20.8 16.6 12.3 - - 32.0 4.2 24.3 20.0 15.7 11.4 - - 900 67 31.8 3.7 30.6 26.3 22.0 17.8 13.5-29.6 4.1 29.6 25.3 21.1 16.8 12.5-62 31.4 3.6 31.4 31.1 26.8 22.5 18.2 14.0 29.7 3.9 29.7 29.7 25.6 21.3 17.0 12.7 57 31.1 3.6 31.1 31.1 26.8 22.6 18.3 14.0 29.5 3.9 29.5 29.5 25.5 21.2 16.9 12.6 77 38.3 4.0 24.1 16.9 11.9 - - - 34.8 4.4 23.8 16.1 11.1 - - - 72 35.2 3.9 27.8 22.8 17.7 12.7 - - 32.4 4.3 26.9 21.8 16.8 11.7 - - 1050 67 32.2 3.8 31.6 28.6 23.6 18.5 13.4-30.0 4.2 30.0 27.5 22.5 17.4 12.4-62 31.8 3.7 31.8 31.6 28.6 23.6 18.5 13.5 30.1 4.0 30.1 30.1 27.3 22.2 17.2 12.1 57 31.5 3.7 31.5 31.5 28.7 23.6 18.6 13.5 29.8 4.0 29.8 29.8 27.2 22.1 17.1 12.0 77 38.7 4.1 28.5 18.5 12.7 - - - 35.2 4.5 28.7 17.6 11.8 - - - 72 35.7 4.0 30.5 24.7 18.9 13.0 - - 32.8 4.4 29.5 23.7 17.8 12.0 - - 1200 67 32.6 3.9 32.6 30.9 25.1 19.2 13.4-30.3 4.3 30.3 29.7 23.9 18.1 12.2-62 32.2 3.8 32.2 32.2 30.5 24.7 18.8 13.0 30.4 4.1 30.4 30.4 29.0 23.2 17.4 11.5 57 31.9 3.8 31.9 31.9 30.5 24.7 18.9 13.0 30.2 4.1 30.2 30.2 28.9 23.1 17.2 11.4 72 36.7 4.1 33.4 26.8 20.2 13.5 - - 33.7 4.5 32.3 25.7 19.1 12.4 - - 1350 67 33.5 4.1 33.5 32.7 26.8 20.2 13.5-31.2 4.4 31.2 31.0 25.6 18.9 12.3-62 33.1 3.9 33.1 33.1 32.2 25.6 19.0 12.3 31.3 4.3 31.3 31.3 30.6 24.0 17.3 10.7 57 32.8 3.9 32.8 32.8 32.1 25.5 18.8 12.2 31.0 4.2 31.0 31.0 30.4 23.8 17.1 10.5 72 37.7 4.3 36.4 28.9 21.5 14.0 - - 34.7 4.7 34.7 27.8 20.3 12.8 - - 1500 67 34.4 4.2 34.4 34.4 28.5 21.1 13.6-32.1 4.6 32.1 32.1 27.2 19.8 12.3-62 34.0 4.1 34.0 34.0 34.0 26.5 19.1 11.6 32.2 4.4 32.2 32.2 32.2 24.8 17.3 9.9 57 33.7 4.0 33.7 33.7 33.7 26.2 18.8 11.3 31.9 4.4 31.9 31.9 31.9 24.5 17.0 9.6 1. These capacities are Net Capacities. 2. These ratings include the compressor, condenser fan and supply air blower motors. 14 Unitary Products Group
TABLE 7: DNP042 COOLING CAPACITIES - 3.5 TON Air on Evaporator Coil 1050 1225 1400 1575 1750 1050 1225 1400 1575 1750 WB ( F) Net Capacity 1 (MBh) Total Input Power (kw) 2 Temperature of Air on Condenser Coil Sensible Capacity (MBh) Net Total Input Sensible Capacity (MBh) Return Dry Bulb ( F) Capacity 1 Power Return Dry Bulb ( F) 90 85 80 75 70 65 (MBh) (kw) 2 90 85 80 75 70 65 75 F 85 F 77 50.2 3.1 25.7 20.7 15.7 - - - 47.9 3.6 25.3 20.3 15.3 - - - 72 46.4 3.1 32.2 27.2 22.2 17.3 - - 44.3 3.4 31.6 26.6 21.6 16.6 - - 67 42.5 3.0 38.8 33.8 28.8 23.8 18.8-40.7 3.3 38.0 33.0 28.0 23.0 18.0-62 38.6 2.8 38.6 38.6 33.8 28.8 23.8 18.9 37.5 3.3 37.5 37.5 33.5 28.6 23.6 18.6 57 39.6 3.0 39.6 39.6 37.0 32.0 27.1 22.1 37.7 3.3 37.7 37.7 35.6 30.7 25.7 20.7 77 52.3 3.2 29.8 23.0 17.1 - - - 49.8 3.6 29.8 22.5 16.6 - - - 72 48.3 3.1 36.1 30.2 24.3 18.4 - - 46.1 3.5 35.4 29.5 23.6 17.7 - - 67 44.3 3.0 42.4 37.4 31.5 25.6 19.7-42.4 3.4 41.0 36.4 30.5 24.6 18.7-62 40.2 2.8 40.2 40.2 36.9 31.0 25.1 19.2 39.0 3.3 39.0 39.0 36.6 30.7 24.8 18.9 57 41.3 3.1 41.3 41.3 40.4 34.5 28.6 22.8 39.2 3.4 39.2 39.2 38.9 33.0 27.1 21.2 77 54.4 3.3 33.9 25.4 18.6 - - - 51.7 3.7 34.3 24.8 18.0 - - - 72 50.2 3.2 39.9 33.1 26.3 19.5 - - 47.9 3.5 39.1 32.3 25.5 18.7 - - 67 46.0 3.1 46.0 40.9 34.1 27.3 20.5-44.0 3.4 44.0 39.8 33.0 26.2 19.4-62 41.8 2.9 41.8 41.8 40.1 33.2 26.4 19.6 40.5 3.4 40.5 40.5 39.6 32.8 26.0 19.2 57 42.9 3.1 42.9 42.9 43.8 37.0 30.2 23.4 40.8 3.4 40.8 40.8 42.1 35.3 28.5 21.6 72 51.0 3.3 42.7 35.0 27.2 19.5 - - 48.4 3.7 42.3 34.5 26.8 19.0 - - 67 46.7 3.2 46.7 44.2 35.3 27.5 19.8-44.5 3.6 44.5 42.4 34.7 26.9 19.2-62 42.5 3.0 42.5 42.5 41.6 33.9 26.1 18.4 40.9 3.5 40.9 40.9 40.5 32.7 25.0 17.3 57 43.6 3.2 43.6 43.6 44.0 36.3 28.5 20.8 41.2 3.6 41.2 41.2 41.9 34.1 26.4 18.6 72 51.8 3.4 45.5 36.8 28.1 19.5 - - 49.0 3.9 45.5 36.8 28.1 19.4 - - 67 47.5 3.3 47.5 47.5 36.5 27.8 19.1-45.0 3.7 45.0 45.0 36.3 27.6 18.9-62 43.2 3.1 43.2 43.2 43.2 34.5 25.8 17.1 41.4 3.7 41.4 41.4 41.4 32.7 24.0 15.3 57 44.2 3.4 44.2 44.2 44.2 35.5 26.9 18.2 41.7 3.7 41.7 41.7 41.7 33.0 24.3 15.6 95 F 105 F 77 45.6 4.0 24.8 19.9 14.9 - - - 43.2 4.3 23.9 18.9 13.9 - - - 72 42.3 3.8 31.0 26.0 21.0 16.0 - - 40.0 4.2 30.0 25.0 20.0 15.1 - - 67 39.0 3.7 37.2 32.2 27.2 22.2 17.2-36.8 4.1 35.9 31.2 26.2 21.2 16.2-62 36.3 3.8 36.3 36.3 33.3 28.3 23.3 18.3 34.1 4.2 34.1 34.1 31.7 26.7 21.7 16.8 57 35.9 3.7 35.9 35.9 34.3 29.3 24.3 19.3 34.2 4.1 34.2 34.2 32.2 27.2 22.2 17.2 77 47.3 4.0 29.8 22.1 16.2 - - - 44.9 4.4 29.5 21.1 15.2 - - - 72 43.9 3.9 34.7 28.8 22.9 17.0 - - 41.5 4.3 33.7 27.8 21.9 16.0 - - 67 40.5 3.7 39.6 35.5 29.6 23.7 17.8-38.2 4.2 37.7 34.5 28.7 22.8 16.9-62 37.7 3.9 37.7 37.7 36.2 30.3 24.4 18.5 35.4 4.3 35.4 35.4 34.7 28.8 22.9 17.0 57 37.2 3.7 37.2 37.2 37.3 31.4 25.5 19.6 35.5 4.2 35.5 35.5 35.2 29.3 23.4 17.5 77 49.1 4.1 34.7 24.3 17.5 - - - 46.5 4.5 35.2 23.3 16.5 - - - 72 45.5 3.9 38.3 31.5 24.7 17.9 - - 43.0 4.3 37.4 30.6 23.8 17.0 - - 67 42.0 3.8 42.0 38.8 32.0 25.2 18.3-39.6 4.2 39.6 37.9 31.1 24.3 17.5-62 39.1 3.9 39.1 39.1 39.1 32.3 25.5 18.7 36.7 4.3 36.7 36.7 37.6 30.8 24.0 17.2 57 38.6 3.8 38.6 38.6 40.3 33.5 26.7 19.9 36.8 4.2 36.8 36.8 38.2 31.4 24.6 17.8 72 45.8 4.1 41.8 34.1 26.3 18.6 - - 43.3 4.5 40.3 32.9 25.2 17.4 - - 67 42.3 4.0 42.3 40.7 34.1 26.3 18.6-39.8 4.4 39.8 39.0 32.9 25.2 17.4-62 39.4 4.1 39.4 39.4 39.4 31.6 23.9 16.1 36.9 4.5 36.9 36.9 37.4 29.7 21.9 14.2 57 38.9 3.9 38.9 38.9 39.7 32.0 24.2 16.5 37.0 4.4 37.0 37.0 37.7 30.0 22.2 14.5 72 46.2 4.3 45.4 36.7 28.0 19.3 - - 43.6 4.7 43.2 35.3 26.6 17.9 - - 67 42.6 4.1 42.6 42.6 36.2 27.5 18.8-40.1 4.6 40.1 40.1 34.7 26.1 17.4-62 39.7 4.3 39.7 39.7 39.7 31.0 22.3 13.6 37.2 4.7 37.2 37.2 37.2 28.5 19.8 11.1 57 39.2 4.1 39.2 39.2 39.2 30.5 21.8 13.1 37.3 4.5 37.3 37.3 37.3 28.6 19.9 11.2 Unitary Products Group 15
TABLE 7: DNP042 COOLING CAPACITIES - 3.5 TON (Continued) Air on Temperature of Air on Condenser Coil Evaporator Coil Net Total Input Sensible Capacity (MBh) Net Total Input Sensible Capacity (MBh) WB Capacity 1 Power Return Dry Bulb ( F) Capacity 1 Power Return Dry Bulb ( F) ( F) (MBh) (kw) 2 90 85 80 75 70 65 (MBh) (kw) 2 90 85 80 75 70 65 115 F 125 F 77 40.9 4.6 22.9 17.9 12.9 - - - 38.6 5.0 21.9 16.9 11.9 - - - 72 37.8 4.6 29.0 24.0 19.1 14.1 - - 35.5 5.0 28.1 23.1 18.1 13.1 - - 1050 67 34.6 4.5 34.6 30.2 25.2 20.2 15.3-32.4 5.0 32.4 29.2 24.3 19.3 14.3-62 31.9 4.5 31.9 31.9 30.2 25.2 20.2 15.2 29.7 4.9 29.7 29.7 28.6 23.7 18.7 13.7 57 32.6 4.5 32.6 32.6 30.1 25.1 20.2 15.2 30.9 4.9 30.9 30.9 28.1 23.1 18.1 13.1 77 42.4 4.7 29.3 20.1 14.2 - - - 40.0 5.1 29.1 19.1 13.2 - - - 72 39.2 4.7 32.7 26.8 20.9 15.0 - - 36.8 5.1 31.8 25.9 20.0 14.1 - - 1225 67 35.9 4.6 35.9 33.6 27.7 21.8 15.9-33.6 5.1 33.6 32.7 26.8 20.9 15.0-62 33.1 4.6 33.1 33.1 33.2 27.3 21.4 15.5 30.8 5.0 30.8 30.8 30.8 25.8 19.9 14.0 57 33.8 4.6 33.8 33.8 33.1 27.2 21.3 15.4 32.0 5.0 32.0 32.0 31.0 25.1 19.2 13.3 77 44.0 4.8 35.7 22.2 15.4 - - - 41.4 5.2 36.2 21.2 14.4 - - - 72 40.6 4.8 36.4 29.6 22.8 16.0 - - 38.1 5.2 35.5 28.7 21.9 15.1 - - 1400 67 37.2 4.7 37.2 37.0 30.2 23.4 16.6-34.8 5.2 34.8 34.8 29.4 22.6 15.8-62 34.3 4.7 34.3 34.3 36.2 29.4 22.6 15.8 31.9 5.1 31.9 31.9 31.9 27.9 21.1 14.3 57 35.0 4.7 35.0 35.0 36.1 29.3 22.5 15.7 33.1 5.1 33.1 33.1 33.1 27.2 20.4 13.6 72 40.8 4.9 38.7 31.7 24.0 16.2 - - 38.3 5.3 37.2 30.6 22.8 15.1 - - 1575 67 37.4 4.9 37.4 37.3 31.8 24.0 16.3-34.9 5.3 34.9 34.9 30.6 22.9 15.1-62 34.5 4.9 34.5 34.5 35.4 27.7 19.9 12.2 32.0 5.3 32.0 32.0 32.0 25.7 17.9 10.2 57 35.2 4.8 35.2 35.2 35.7 28.0 20.2 12.5 33.3 5.3 33.3 33.3 33.3 26.0 18.2 10.5 72 41.0 5.1 41.0 33.8 25.2 16.5 - - 38.5 5.5 38.5 32.4 23.7 15.0 - - 1750 67 37.6 5.0 37.6 37.6 33.3 24.6 15.9-35.1 5.4 35.1 35.1 31.9 23.2 14.5-62 34.7 5.0 34.7 34.7 34.7 26.0 17.3 8.6 32.2 5.4 32.2 32.2 32.2 23.5 14.8 6.1 57 35.4 5.0 35.4 35.4 35.4 26.7 18.0 9.3 33.5 5.4 33.5 33.5 33.5 24.8 16.1 7.4 1. These capacities are Net Capacities. 2. These ratings include the compressor, condenser fan and supply air blower motors. 16 Unitary Products Group