Development of Next-generation Switchgear Targeting High Reliability and Maintenance Savings

Similar documents
Development and Performance Evaluation of High-reliability Turbine Generator

Featured Articles Utilization of AI in the Railway Sector Case Study of Energy Efficiency in Railway Operations

MEDIUM VOLTAGE SWITCHGEAR

SWITCHCRAFT. Switchcraft Europe GmbH SWITCHCRAFT

Power Systems PU. HYOSUNG MV Gas Insulated Switchgear. ProGIS[MV GIS]

Extra-High-Voltage SF 6 Gas-Insulated Switchgear

THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com

IEC Standard Compliant Vacuum Circuit-Breaker (12 kv, 24 kv) for Southeast Asian Markets

Hybrid Wheel Loaders Incorporating Power Electronics

Substation Concepts for the Future

Power Systems PU. HYOSUNG Standard High-voltage Switchgear ProSWGR. Medium Voltage Metal-clad Switchgear

NXPLUS C Single busbar. Maintenance-free for lifetime

Metal Clad Air Insulated Switchgear

KYN28-12(GZSI-12Z)Armoured Middle-Mounted Metal. Enclosed Switch. 1.General. 2.Model Definition

ZX1.5-R. Gas-insulated medium voltage for railway application DISTRIBUTION SOLUTIONS. Gas-insulated medium voltage for railway application ZX1.

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

FIXED VCB AIR INSULATED SWITCHGEAR

Improving Onboard DS-ATC Equipment Functions in Response to Shinkansen Service Expansion

High voltage in motion Environmentally friendly circuit breakers and economic long-rod insulators

Gas-Insulated Switchgear. Type 8VN1 blue GIS up to 145 kv, 40 ka, 3150 A

Air-insulated switchgear UniGear type ZS1

Development of Japan s Next Flagship Launch Vehicle

Next-generation SCADA and Control Technologies for Large-scale Use of Photovoltaic Generation on Electric Power Grid

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv

11kV Compact Switchgear. tec - range. Minimum to Zero SF6 Insulation Gas. Outec Controls

123/145kV SF6 Gas-Insulated Switchgear incorporating VCB. 145kV-1250~2000A-31.5kA

Environmentally Conscious Green Mobility

with Vacuum Circuit Breaker HAF

W-VACi IEC medium voltage vacuum circuit breakers 12 kv, 17,5 kv and 24 kv

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

Gas-insulated medium-voltage switchgear. For the mining industry. Answers for energy.

GAS INSULATED VOLTAGE TRANSFORMERS.

Gas Insulated Switchgear

Gas Insulated Switchgear

Compact Gas Insulated Switchgear (GIS) up to 145kV 126kV,145kV Compact Gas Insulated Switchgear (GIS)

Overview Gas Insulated Switchgear Modular and flexible, kV. ABB Group April 17, 2009 Slide 1

NEXT STEP B) SAFETY :

First Domestic High-Efficiency Centrifugal Chiller with Magnetic Bearings: The ETI-MB Series

Overview Gas Insulated Switchgear Modular and flexible, kV. ABB Group May 15, 2013 Slide 1

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel

COMPACT AND EXTENSIBLE RING MAIN UNIT. insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker

Next-generation Inverter Technology for Environmentally Conscious Vehicles

SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv

Guidelines for Modernizing Existing Electrical Switchgear in LV and MV Networks

Alvin Xu & Johnny Wang, ABB Xiamen Switchgear Co,. Ltd., November, 2016 ABB lead the intelligent revolution Intelligent technology (Part 2)

Gas Insulated Metal-clad Switchgear, HMGS!

Metal Clad VCBs ~ Mk1

Safe, fast HV circuit breaker testing with DualGround technology

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

Introduction of Bulldozers D155AX-8/AXi-8

Power Interchange System for Reuse of Regenerative Electric Power

Hybrid Hydraulic Excavator HB335-3/HB365-3

Extremely High Load Capacity Tapered Roller Bearings

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Course Semester Subject Code Subject Name B.E EEE(M) V UAEE507 MARINE ELECTRICAL TECHNOLOGY UNIT-I

This small footprint makes a BIG impact

Development of the Single Phase PV Inverter SANUPS P61A

General. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment

Examples of Electric Drive Solutions and Applied Technologies

VPP: New Stage in Energy Management Smart Utilization of Self-Generation Facilities with Automated DR System

Introduction of Hydraulic Excavator PC240LC-11

Study of composition draft on automatic changeover system in neutral section railway catenary system for highspeed train line

Introduction of PC228US-8 Hydraulic Excavators

Investigating The Effect of Switching and tripping on Flashover and Breakdown in Circuit Breaker

Safety Design of CHAdeMO Quick Charging System

NEW CONCEPT FOR MEDIUM VOLTAGE GAS INSULATED SWITCHGEAR (GIS) by LJ Fleischer, Siemens Electricity + Control May 1999

Newly Developed High Power 2-in-1 IGBT Module

Experience on Deterioration Survey of Aged 550 kv GIS and Optimized Evaluation Model in Thailand

Gas-insulated medium-voltage switchgear. For marine and offshore applications. Answers for energy.

Power IT Air Insulated Cubicle Uniswitch

Rigid Dump Truck HD465/605-8 and HD325/405-8

Power Xpert UX 36 High-voltage switchgear system. Reliable and safe for high performance applications

Core Components for Large-scale PV Generation Systems

UPDATED LOW NOx COMBUSTION TECHNOLOGIES FOR BOILERS, 2003

Special edition paper

SVE135 Sealed High-Voltage Contactor Having High Overcurrent Withstand Capability

Global VPI Insulated Indirectly Hydrogen-Cooled Turbine Generator for Single-Shaft Type Combined Cycle Power Generation Facilities

the safe, reliable, and efficient choice for MV switchgear

High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv

Interruption Technology of Breakers for High-voltage Direct Current

Medium voltage products UniSec DY800 New 24 kv air-insulated medium voltage switchgear to e-distribuzione specifications

Stressless Gear Using Embedded System Technology

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

No.LV31JE To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual.

Nissin s Products for Electric Railway System

Product Specification

The 1,400-MW Kii-Channel HVDC System

Development of Compact & High Efficiency Polymer Electrolyte Fuel Cell System for Enclosed Spaces

M-RING 24. SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A)

Product brochure. Gas-insulated switchgear ELK-04 C, 145 kv Modular and reliable

A 500kV AIS Switchyard Rejuvenation in British Columbia using Hybrids

Vacuum Circuit Breaker VS1

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)

Safe and Reliable. Flexible, Compact Design. Easy Installation and Maintenance

Enhanced Breakdown Voltage for All-SiC Modules

UniGear. Technical Guide

Optimum Operation Control of Distributed Energy Resources Using ENERGYMATE-Factory

Learning Module 6: Medium Voltage Power Circuit Breakers. 101 Basic Series

GOVERNMENT STATUS REPORT OF JAPAN

Transcription:

Development of Next-generation Switchgear Targeting High Reliability and Maintenance Savings 208 Development of Next-generation Switchgear Targeting High Reliability and Maintenance Savings Nobuyuki Yamada Shigeru Yokosuka Keisuke Mikuni Takuya Kurogi OVERVIEW: Ensuring a reliable supply of electricity to commerce, public institutions, and industrial equipment has become even more essential in recent years due to circumstances such as the increasing sophistication of the information society and the construction of high-efficiency production equipment. Switchgear are key components in electricity distribution systems, and in addition to the requirement for high reliability they are also subject to a diverse range of other requirements associated with advances in technology including safety, ease of inspection and maintenance, and consideration for the environment. Hitachi has developed switchgear with solid-insulated bus bars to meet diverse needs by utilizing various technologies including a vacuum disconnecting switch, improved safety through the use of solid-insulated bus bars, and maintenance savings made possible by integrating the main circuit elements into a single unit. INTRODUCTION THREE keywords have come to have a high importance in the modern world. The first is safety and reliability. Industries of all types give top priority to safety and reliability in their product development and the high-voltage electricity distribution equipment industry is no exception. Airinsulated switchgear have exposed live components and serious electric shocks can occur if human error or similar results in a person getting too close to these high-voltage parts. Similarly there is a risk of earth faults occurring due to foreign material getting into Safety Reliability Longer operating life Easier maintenance bus bar Switchgear Leading-edge technology Environmentally friendly Fig. 1 Concepts Behind Switchgear with Bus Bars. The concepts behind Hitachi s environmentally friendly switchgear with solid-insulated bus bars which incorporate the company s leading-edge technologies to meet customer demands for safety, reliability, longer operating life, and easier maintenance are shown.

Hitachi Review Vol. 58 (2009), No.5 209 the switch or the buildup of dust after the unit has been in use for a long period of time. Development of the new switchgear aimed to produce a safe and reliable product that could eliminate these risks. The second is maintenance savings. The requirement is for products with lower life cycle costs that are designed to make maintenance easier, such as allowing longer inspection cycles or not having to be cleaned inside the panel. Accordingly, Hitachi considered ease-of-maintenance and how to make maintenance savings when developing the switchgear. The third is consideration for the environment. The term eco-product is also used to refer to this idea. In Japan where land is expensive and scarce, the requirement in the past has been to try to make electricity distribution equipment as small as possible. This resulted in the use of SF 6 (sulfur hexafluoride) gas as an insulator to allow the production of distribution panels with a small installation footprint. However, because SF 6 gas has a very high global warming coefficient, and because it is not easy to handle and needs to be managed, Hitachi undertook research and development to create more environmentally friendly electricity distribution equipment that does not use SF 6 gas. The product developed based on these three keywords was the switchgear with solid-insulated bus bars. This article describes the features and example applications of the switchgear with solid-insulated bus bars developed by Hitachi (see Fig. 1). DEVELOPMENT OF SWITCHGEAR WITH SOLID-INSULATED BUS BARS Switchgear Structure and Overview Fig. 2 shows an overview of the switchgear with solid-insulated bus bars and its internal structure. The main features of the switchgear are as follows. (1) Two different types of solid-insulated bus bars (epoxy and silicon rubber) are used in the bus bar chamber at the rear of the panel. The surface of each bus bar is earthed for safety to prevent electric shock if someone touches the bus bar. (2) AIO (all-in-one) units that combine a VCB (vacuum circuit breaker), CT (current transformer), ZCT (zero-phase current transformer), and VT (voltage transformer) in a single unit are used in the top and middle chambers of the panel to make the internal components easier to maintain. (3) The circuit breaker chambers have a sealed Feature (3) Dustproof chamber (region enclosed by blue dashed line in figure) ICU Dustproof covers Feature (4) AIO unit (VDS) Feature (2) AIO units (VCB) AIO: all-in-one VCB: vacuum circuit breaker ICU: intelligent control unit VDS: vacuum disconnecting switch bus bars (silicon rubber) Feature (1) bus bars (epoxy) Fig. 2 Structure and Features of Switchgear with Solidinsulated Bus Bars. The four key features of the switchgear are safe design with no risk of electric shock if components are touched by mistake (1), easy maintenance due to use of AIO units (VCB) (2), dustproofing (3), and easy maintenance due to use of AIO units (VDS) (4). structure with dustproof covers on the front side of each chamber to protect the air-insulated parts from dust. (4) A newly developed VDS (vacuum disconnecting switch) is used in place of the air-insulated disconnecting switches used in the past. Like the VCB, the VDS is also integrated into an AIO unit to make the internal components easier to maintain. Product Concept Safety and reliability The switchgear uses two different types of solidinsulated bus bars. One type is coated in silicon rubber and used for the main bus bars that connect between panels. The other is coated in epoxy resin and is used for the conductors that connect between different circuits. As the surface of the solid-insulated bus bars made of silicon rubber are coated with electrically conductive rubber and the surface of the epoxy resin is painted with electrically conductive paint, the surface of the insulators can be earthed to eliminate any exposed live components inside

Development of Next-generation Switchgear Targeting High Reliability and Maintenance Savings 210 the panel. This improves safety by preventing the risk of electric shock if someone touches or gets too close to a bus bar. Reliability is also improved by covering the surfaces of the insulation between the bus bars with an earthed coating which makes the risk of inter-phase short circuits or similar accidents extremely low (see Fig. 3). ZCT VCB with an electromagnetic actuator (a) Front (b) Rear CT ZCT: zero-phase current transformer CT: current transformer Fig. 4 AIO Unit. The front and rear views of an AIO unit containing a VCB, ZCT, and CT are shown. bus bar (epoxy) bus bar (silicon rubber) Fig. 3 View of Bus Bars. The solid-insulated bus bars are shown. The surfaces appear black because they are coated in conductive rubber or conductive paint. Maintenance savings Potential ways of saving on maintenance include making maintenance work more efficient (by shortening the time required), reducing the need for cleaning inspections (simplification), and by allowing longer inspection cycles. (1) Shortening maintenance work Inspection work was made difficult in the past by having components such as the CT and ZCT attached inside the switchgear panel as this meant a technician needed to get inside the panel to perform the inspection. Hitachi has shortened the time required for inspection and simplified the inspection procedure by combining the VCB, ZCT, CT, and VT in the single pull-out unit shown in Fig. 4 that can be pulled out of the panel for inspection. The requirement to check the tightness of the bolt contacts required on previous air-insulated switchgear has been minimized by adopting solidinsulated bus bars. The number has been reduced by two-thirds from 18 locations per panel down to six. Air-insulated disconnecting switches were also attached to the inside of the switchgear panel in the past which meant that inspections had to be performed in the minimal space available. In response, Hitachi developed a new VDS by enhancing a VCB with an electromagnetic actuator that has been used successfully in the past so as to allow inspection to be performed from outside the panel by integrating the disconnecting switch into a pull-out unit like the VCB. On the VDS, the withstand voltage standard required for use as a disconnecting switch was satisfied by enlarging the gap between the contacts inside the vacuum valve used in the VCB. Because the VDS unit has the same structure as the VCB, it can be used in an AIO unit consisting of a VDS and VT. (2) Fewer cleaning inspections Because the circuit breaker chamber which houses the main circuit components is the part most likely to suffer from degraded performance caused by the accumulation of dust, a dustproof design was adopted. The dustproof chamber is designed to allow the circuit breaker to be inserted and removed by removing the dustproof cover. A small door is provided on the dustproof cover to allow the circuit breaker to be operated manually in case of an emergency and a window allows the state of the circuit breaker to be checked visually at any time while the switchgear is in use (see Fig. 5). The dustproof cover is also fitted with a pressureequalizing filter. When the VCB or VDS in the AIO unit is carrying a current it becomes a source of heat, and a pressure differential can occur due to the expansion or contraction of the air inside the dustproof chamber after the power is turned on to the switchgear or if there is a sudden change in the temperature of the surroundings. A pressure-equalizing filter has been fitted to release this pressure. This filter also allows any humidity that enters when the dustproof cover is open to pass out of the chamber.

Hitachi Review Vol. 58 (2009), No.5 Pressure-equalizing filter 211 Dustproof cover Empty space Empty space VCB+VT VCB VCB Window Door (a) During normal operation VCB (AIO unit) (b) With door open Fig. 5 Dustproof Cover. The dustproof cover during normal operation and with the door open is shown. The door can be opened in an emergency to operate the switchgear manually. (3) Longer inspection cycles A grease-less electromagnetic actuator is used in the VCB and VDS to eliminate the need for the periodic lubrication and other maintenance required by spring-operated units. The new switchgear also uses long-life materials such as silicon rubber for the packing around the dustproof cover. Accordingly, the combination of a dustproof design and a greaseless electromagnetic actuator makes lubrication and cleaning unnecessary and this eliminates the need to open the dustproof cover except for periodic inspections or in case of an emergency and allows the inspection cycle to be made longer. VCB+VT (a) Two-tier design (b) Three-tier design VT: voltage transformer Fig. 6 Space Savings Achieved by Three-tier Design. The two-tier design used previously was changed to a three-tier design to save on space. Consideration for environment Because the switchgear with solid-insulated bus bars uses solid insulation on its bus bars and air insulation for some parts of the circuit breaker, it provides the safety and reliability of GIS (gasinsulated switchgear) without using SF6 gas. Whereas SF6 gas needs to be handled and managed carefully because it has an extremely high global warming coefficient, the new switchgear is an environmentally friendly product for which such concerns are unnecessary. APPLICATION IN PRODUCTS Space Saving Enhancements Whereas VTs were produced as standalone units in the past [see Fig. 6 (a)], the new switchgear integrates the VT into the VCB unit to allow a threetier design. As a result, a device that previously comprised two panels can now be produced as a single panel [see Fig. 6 (b)]. Fig. 7 View of Switchgear with Bus Bars. Switchgear are installed at a substation for the Shinkansen rail system. Actual Installations The first switchgear with solid-insulated bus bars produced using the technologies described above were delivered to a customer in September 2008 (see Fig. 7). The switchgear with solid-insulated bus bars in this installation comprised a number of panels in a row. CONCLUSIONS This article has described the features and example applications of the switchgear with solidinsulated bus bars.

Development of Next-generation Switchgear Targeting High Reliability and Maintenance Savings 212 The switchgear with solid-insulated bus bars developed based on the concepts of safety, maintenance savings, and consideration for the environment are next-generation switchgear that combine the reliability of GIS with the extendibility of open-air panels. Future demand for these highly reliable and environmentally friendly products is anticipated to come from various different sectors. ABOUT THE AUTHORS Nobuyuki Yamada Joined Hitachi, Ltd. in 1997, and now works at the Substation Systems Section, Electrical Systems Engineering Department, Electrical Solution Business Division, Power & Industrial Systems Division, Power Systems Company. He is currently engaged in the planning of substation systems. Shigeru Yokosuka Joined Hitachi, Ltd. in 1989, and now works at the Switchgear Manufacturing Section, Switchgear Design and Manufacturing Department, Kokubu Engineering & Product Division, Hitachi Works, Power Systems Company. He is currently engaged in the manufacturing of switchgear equipment. Keisuke Mikuni Joined Hitachi, Ltd. in 1993, and now works at the Switchgear, Control and Protection QA & Inspection Section, Switchgear Design and Manufacturing Department, Kokubu Engineering & Product Division, Hitachi Works, Power Systems Company. He is currently engaged in the inspection of switchgear equipment. Takuya Kurogi Joined Hitachi, Ltd. in 2003, and now works at the Switchgear Equipment Development Section, Switchgear Design and Manufacturing Department, Kokubu Engineering & Product Division, Hitachi Works, Power Systems Company. He is currently engaged in the development of switchgear equipment.