220 to Volts. Generator Set Configurations U.S. EPA Certified for Stationary Emergency Use Only (Tier 2 Nonroad Equivalent Emission Standards)

Engine Specifications 3512C HD ATAAC, V-12, 4-Stroke Water-Cooled Diesel Compression Ratio 14.7:1 Aspiration

Voltage 208 to 600. Engine Specifications C27 ATAAC, V-12, 4-Stroke, Water-Cooled Diesel Compression Ratio 16.5:1 Aspiration

220 to Volts or 1800 RPM

220 to Volts or 1800 RPM

220 to volts. Electronic unit injection

Voltage 220 to or 1800 RPM. Engine Specifications C32 TA, V-12, 4-Stroke Water-Cooled Diesel 145 mm (5.71 in)

400 to 11,000 Volts. Standby, Prime, Continuous

220 to volts. Engine Specifications 3516C, ATAAC, V-16,4-Stroke Water-Cooled Diesel 170 mm (6.69 in) Compression Ratio 14.

Continuous, Prime, Standby, Mission Critical

1500 or 1800 RPM. Engine Specifications C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel 145 mm (5.71 in) 183 mm (7.2 in) Compression Ratio 14.

3412C Generator Set Electric Power. Specifications. Benefits and Features

Voltage 220 to or 1800 RPM

Specifications. 3406C Generator Set Electric Power

1500 or 1800 RPM. Engine Specifications C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel 145 mm (5.71 in) 183 mm (7.2 in) Compression Ratio 14.

like mission critical Backed by the worldwide l provide the reliabi Mission Critical LEHE1075

STANDBY 3000 ekw 3750 kva 60 Hz 1800 rpm 4160 Volts

PRIME. 50 Hz 1500 rpm 400 Volts DIESEL GENERATOR SET FEATURES

including r installations. Backed by the worldwide l provide the reliabi Prime LEHE1073

MISSION CRITICAL 800 ekw 1000kVA 60 Hz 1800 rpm 480Volts

CONTINUOUS 1600 ekw 2000 kva 50 Hz 1500 rpm 400 Volts

STANDBY 1500 ekw 1875 kva 60 Hz 1800 rpm 600 Volts

STANDBY 400 ekw 500 kva

PRIME 591 ekw 739 kva 60 Hz 1800 rpm 480 Volts

PRIME 256 ekw 320 kva 50 Hz 1500 rpm 400 Volts

STANDBY. 60 Hz 1800 rpm 480 Volts DIESEL GENERATOR SET FEATURES

Generator Set Configurations Low Fuel Consumption, EU Stage IIIA Nonroad Emission Standards, China Nonroad III Emission Standards

Specifications. C13 Generator Set Electric Power

MISSION CRITICAL STANDBY. 50 Hz 1500 rpm Volts DIESEL GENERATOR SET FEATURES

PRIME 1600 ekw 2000 kva 50 Hz 1500 rpm 400 Volts

STANDBY 1120 ekw 1400 kva 50 Hz 1500 rpm 400 Volts

MISSION CRITICAL STANDBY. 60 Hz 1800 rpm 480 Volts DIESEL GENERATOR SET FEATURES

Aftercooler (Separate Circuit) N/A N/A

Generator Set Specifications 100 ekw (125 kva)

Mission Critical Standby 1400 ekw 1750 kva 50 Hz 1500 rpm 400 Volts STANDBY DIESEL GENERATOR SET FEATURES

PRIME 225 ekw 281 kva

STANDBY 700 ekw 875 kva 60 Hz 1800 rpm 600 Volts

STANDBY 400 ekw 500 kva 50 Hz 1500 rpm 400 Volts

Mission Critical Standby 1120 ekw 1400 kva 50 Hz 1500 rpm 400 Volts STANDBY DIESEL GENERATOR SET FEATURES

STANDBY 320 ekw 400 kva 50 Hz 1500 rpm 400 Volts

PRIME 220 ekw 275 kva 50 Hz 1500 rpm 400 Volts

Standby 1000 ekw 1250 kva 60 Hz 1800 rpm 480 Volts

Generator Set Specifications 60 ekw (75 kva)

C18. STANDBY 560 ekw 700 kva 50 Hz 1500 rpm 400 Volts

DIESEL GENERATOR SET FEATURES

PRIME 800 ekw 1000 kva 50 Hz 1500 rpm 400 Volts

Standby 1000 ekw 1250 kva 60 Hz 1800 rpm 480 Volts

P R I M E e k W k V A 50 Hz 1500 rpm 400 Volts DIESEL GENERATOR SET FEATURES

STANDBY 880 ekw 1100 kva 50 Hz 1500 rpm 400 Volts

PRIME 545 ekw 681 kva 60 Hz 1800 rpm 480 Volts

Bore mm 4.35 in Displacement 8.8 L 535 in³ Stroke mm 4.5 in Compression Ratio 10.1:1

PRIME 400 ekw 500 kva 50 Hz 1500 rpm 400 Volts

DIESEL FEATURES GENERATOR SET

Standby 1200 ekw 1500 kva 50 Hz 1500 rpm 400 Volts

Standby 1500 ekw 1875 kva 60 Hz 1800 rpm 480 Volts

ESP 550 ekw 688 kva 60 Hz 1800 rpm 480 Volts

CONTINUOUS 728 ekw 910 kva 50 Hz 1500 rpm 400 Volts

Bore mm 4.0 in Displacement 5.7 L 350 in³ Stroke 88.4 mm 3.48 in Compression Ratio 9.4:1

STANDBY 2000 ekw 2500 kva 50 Hz 1500 rpm Volts

PRIME 725 ekw 906 kva 60 Hz 1800 rpm 480 Volts

PRIME 920 ekw 1150 kva 50 Hz 1500 rpm 400 Volts

Generator Set Specifications Rating (ekw) Rating (kva) Engine Specifications C32 ACERT TA, V-12, 4-stroke Water-cooled Diesel

PRIME 1825 ekw 2281 kva 60 Hz 1800 rpm 480 Volts

PRIME 910 ekw 1138 kva 60 Hz 1800 rpm 480 Volts

CONTINUOUS 800 ekw 1000 kva 50 Hz 1500 rpm 400 Volts

STANDBY 2000 ekw 2500 kva 60 Hz 1800 rpm Volts

STANDBY 2000 ekw 2500 kva 60 Hz 1800 rpm Volts

Enclosures. Options Caterpillar yellow or white paint Integral dual wall fuel tank base for total fluid containment (fuel, oil and coolant)

PRIME 2260 ekw 2825 kva 50 Hz 1500 rpm Volts

STANDBY 1000 ekw 1250 kva 60 Hz 1800 rpm 480 Volts

STANDBY 2480 ekw 3100 kva 50 Hz 1500 rpm 400 Volts

Engine Specifications C32 ACERT TA, V-12, 4-stroke Water-cooled Diesel. Compression Ratio 15.0:1 Turbocharged Aftercooled.

PRIME 1200 ekw 1500 kva 50 Hz 1500 rpm 400 Volts

PRIME 1600 ekw 2000 kva 50 Hz 1500 rpm 400 Volts

Package Performance Genset Power Rating with 0.8 Power Factor Genset Power Rating Aftercooler (Separate Circuit) N/A N/A

Package Performance Genset Power Rating with 0.8 Power Factor Genset Power Rating Aftercooler (Separate Circuit) N/A N/A

STANDBY 900 ekw 1125 kva 60 Hz 1800 rpm 480 Volts

STANDBY 1750 ekw 2188 kva 60 Hz 1800 rpm 440 Volts

Package Performance Genset Power Rating with 0.8 Power Factor Genset Power Rating Aftercooler (Separate Circuit) N/A N/A

PRIME 800 ekw 1000 kva 50 Hz 1500 rpm 400 Volts

C32 ACERT Generator Set Electric Power

PRIME 1200 ekw 1500 kva 50 Hz 1500 rpm Volts

STANDBY 200 ekw 250 kva

1500 or 1800 RPM. Engine Specifications C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel 145 mm (5.71 in) 183 mm (7.2 in) Compression Ratio 14.

Transcription:

Cat 3516C Diesel Generator Sets Bore mm in) 170 6.69) Stroke mm in) 215 8.46) Displacement L in 3 ) 78.1 4765) Compression Ratio 14.7:1 Aspiration ATAAC Fuel System EUI Governor Type ADEM A3 Image shown may not reflect actual configuration - kva ekw) 3125 2500) 3000 2400) 2750 2200) 2500 2000) 2250 1800) Emissions Performance Tier 2 Equivalent US. EPA Stationary Emergency 2750 2200) 2500 2000) 2250 1800) Low NOx 1/2 TA Luft) Standard Features Cat Diesel Engine Tier 2 Equivalent US. EPA Stationary Emergency) emissions standards or Low NOx 1/2 TA Luft) Reliable performance proven in thousands of applications worldwide Generator Set Package Accepts 100% block load in one step and meets other NFPA 110 loading requirements Conforms to ISO 8528-5 G3 load acceptance requirements Reliability verified through torsional vibration, fuel consumption, oil consumption, transient performance, and endurance testing Alternators Superior motor starting capability minimizes need for oversizing generator Designed to match performance and output characteristics of Cat diesel engines Cooling systems available to operate in ambient temperatures up to 50 C 122 F) Tested to ensure proper generator set cooling EMCP 4 Control Panels User-friendly interface and navigation Scalable system to meet a wide range of installation requirements Expansion modules and site specific programming for specific customer requirements Warranty 24 months/1000-hour warranty for standby ratings Extended service protection is available to provide extended coverage options Worldwide Product Support Cat dealers have over 1,800 dealer branch stores operating in 200 countries Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements Financing Caterpillar offers an array of financial products to help you succeed through financial service excellence Options include loans, finance lease, operating lease, working capital, and revolving line of credit Contact your local Cat dealer for availability in your region LEHE1343-00 Page 1 of 6

Optional Equipment Engine Air Cleaner Single element Dual element Heavy duty Muffler Industrial grade 15 db) Starting Standard batteries Oversized batteries Standard electric starters) Heavy duty electric starters) Air starters) Jacket water heater Alternator Output voltage 380V 6600V 400V 6900V 415V 10000V 300V 10500V 6300V 11000V Temperature Rise over 40 C ambient) 150 C 125 C/130 C 105 C 80 C Winding type Random wound Form wound Excitation Internal excitation IE) Permanent magnet PM) Attachments Anti-condensation heater Stator and bearing temperature monitoring and protection Power Termination Type Bus bar Circuit breaker 1600A 2000A 2500A 3000A 3200A 4000A 5000A UL IEC 3-pole 4-pole Manually operated Electrically operated Trip Unit LSI LSI-G LSIG-P Control System Controller EMCP 4.2B EMCP 4.3 EMCP 4.4 Attachments Local annunciator module Remote annunciator module Expansion I/O module Remote monitoring software Charging Battery charger 10A Battery charger 20A Battery charger 35A Vibration Isolators Rubber Spring Seismic rated Cat Connect Connectivity Ethernet Cellular Satellite Extended Service Options Terms 2 year prime) 3 year 5 year 10 year Coverage Silver Gold Platinum Platinum Plus Ancillary Equipment Automatic transfer switch ATS) Uninterruptible power supply UPS) Paralleling switchgear Paralleling controls Certifications IBC seismic certification EU Certification of Conformance CE) EEC Declaration of Conformity Note: Some options may not be available on all models. Certifications may not be available with all model configurations. Consult factory for availability. LEHE1343-00 Page 2 of 6

Package Performance Performance Engine Speed Frequency Gen set power rating with fan Gen set power rating with fan @ 0.8 power factor Emissions Performance number Fuel Consumption 2500 ekw 3125 kva EM2194-00 2400 ekw 3000 kva EM2125-00 100% load with fan L/hr gal/hr) 660.1 174.4) 639.8 169.0) 75% load with fan L/hr gal/hr) 514.2 135.8) 500.0 132.1) 50% load with fan L/hr gal/hr) 375.8 99.3) 365.4 96.5) 25% load with fan L/hr gal/hr) 223.1 58.9) 216.6 57.2) Radiator air flow restriction system) kpa in. water) 0.12 0.48) 0.12 0.48) Radiator air flow m 3 /min cfm) 2860 101000) 2860 101000) Engine coolant capacity L gal) 233.2 61.6) 233.2 61.6) Radiator coolant capacity L gal) 271.0 71.6) 271.0 71.6) Total coolant capacity L gal) 504.2 133.2) 504.2 133.2) Inlet Air Combustion air inlet flow rate m 3 /min cfm) 204.8 7230.3) 201.5 7114.8) Exhaust System Exhaust stack gas temperature C F) 491.8 917.2) 484.9 904.8) Exhaust gas flow rate m 3 /min cfm) Exhaust system backpressure maximum allowable) kpa in. water) Heat Rejection 556.9 19663.4) 542.0 19137.8) 6.7 27.0) 6.7 27.0) Heat rejection to jacket water kw Btu/min) 829 47131) 813 46258) Heat rejection to exhaust total) kw Btu/min) 2515 143045) 2431 138231) Heat rejection to aftercooler kw Btu/min) 791 44998) 761 43277) Heat rejection to atmosphere from engine kw Btu/min) 161 9180) 158 8973) Heat rejection from alternator kw Btu/min) 121 6881) 107 6085) Emissions Nominal) - Full Load NOx mg/nm 3 g/hp-h) 2354.5 5.33) 2318.0 5.22) CO mg/nm 3 g/hp-h) 198.8 0.43) 178.8 0.39) HC mg/nm 3 g/hp-h) 42.0 0.10) 42.4 0.11) PM mg/nm 3 g/hp-h) 14.3 0.04) 13.0 0.03) Emissions Potential Site Variation) - Full Load 106 NOx mg/nm 3 g/hp-h) 2825.4 6.40) 2781.6 6.27) CO mg/nm 3 g/hp-h) 357.8 0.77) 321.8 0.70) HC mg/nm 3 g/hp-h) 55.9 0.14) 56.3 0.14) PM mg/nm 3 g/hp-h) 20.1 0.05) 18.2 0.05) LEHE1343-00 Page 3 of 6

Package Performance Performance Engine Speed Frequency Gen set power rating with fan Gen set power rating with fan @ 0.8 power factor Emissions 2200 ekw 2750 kva Performance number EM2124-00 1800 ekw 2250 kva EM2122-00 Fuel Consumption 100% load with fan L/hr gal/hr) 590.2 155.9) 542.3 143.3) 497.5 131.4) 75% load with fan L/hr gal/hr) 464.1 122.6) 428.1 113.1) 394.6 104.2) 50% load with fan L/hr gal/hr) 339.5 89.7) 311.5 82.3) 286.3 75.6) 25% load with fan L/hr gal/hr) 203.6 53.8) 186.4 49.2 247.3 45.5 Radiator air flow restriction system) kpa in. water) 0.12 0.48) 0.12 0.48) 0.12 0.48) Radiator air flow m 3 /min cfm) 2860 101000) 2860 101000) 2860 101000) Engine coolant capacity L gal) 233.2 61.6) 233.2 61.6) 233.2 61.6) Radiator coolant capacity L gal) 271.0 71.6) 271.0 71.6) 271.0 71.6) Total coolant capacity L gal) 504.2 133.2) 504.2 133.2) 504.2 133.2) Inlet Air Combustion air inlet flow rate m 3 /min cfm) 192.6 6801.6) 182.3 6435.5) 171.6 6057.8) Exhaust System Exhaust stack gas temperature C F) 470.6 879.2) 462.7 864.8) 458 856.4) Exhaust gas flow rate m 3 /min cfm) 505.9 17864.9) 471.7 16654.4) 540.7 15575.5) Exhaust system backpressure maximum allowable) kpa in. water) Heat Rejection 6.7 27.0) 6.7 27.0) 6.7 27.0) Heat rejection to jacket water kw Btu/min) 774 44033) 733 41670) 693 39396) Heat rejection to exhaust total) kw Btu/min) 2232 126923) 2068 117612) 1917 109043) Heat rejection to aftercooler kw Btu/min) 685 38982) 607 34523) 534 30393) Heat rejection to atmosphere from engine kw Btu/min) 140 7940) Heat rejection from alternator kw Btu/min) 107 6085) 107 6085) 107 6085) Emissions Nominal) - Full Load NOx mg/nm 3 g/hp-h) CO mg/nm 3 g/hp-h) HC mg/nm 3 g/hp-h) PM mg/nm 3 g/hp-h) Emissions Potential Site Variation) - Full Load NOx mg/nm 3 g/hp-h) CO mg/nm 3 g/hp-h) HC mg/nm 3 g/hp-h) PM mg/nm 3 g/hp-h) 150 8518) 2198.9 4.93) 139.4 0.30) 44.6 0.11) 10.8 0.03) 2638.6 5.92) 250.9 0.54) 59.4 0.15) 15.1 0.04) 2000 ekw 2500 kva EM2123-00 144 8185) 2006.6 4.57) 123.2 0.27) 50.2 0.12) 11.1 0.03) 2408.0 221.8 66.7 15.5 5.48) 0.49) 0.17) 0.04) 1793.2 4.17) 118.3 0.26) 56.9 0.14) 12.2 0.03) 2151.8 212.9 75.7 17.1 5.01) 0.48) 0.19) 0.05) LEHE1343-00 Page 4 of 6

Package Performance Performance Engine Speed Frequency Gen set power rating with fan 2200 ekw 2000 ekw 1800 ekw Gen set power rating with fan @ 0.8 power factor 2750 kva 2500 kva 2250 kva Emissions Low NOx Low NOx Low NOx Performance number EM2128-00 EM2127-00 EM2126-00 Fuel Consumption 100% load with fan L/hr gal/hr) 617.9 163.2) 564.1 149.0) 529.1 139.8) 75% load with fan L/hr gal/hr) 460.2 121.6) 429.2 113.4) 395.7 104.5) 50% load with fan L/hr gal/hr) 332.7 87.9) 308.7 81.5) 281.9 74.5) 25% load with fan L/hr gal/hr) 199.7 52.8) 181.5 48.0) 168.5 44.5) Radiator air flow restriction system) kpa in. water) 0.12 0.48) 0.12 0.48) 0.12 0.48) Radiator air flow m 3 /min cfm) 2860 101000) 2860 101000) 2860 101000) Engine coolant capacity L gal) 233.2 61.6) 233.2 61.6) 233.2 61.6) Radiator coolant capacity L gal) 271.0 71.6) 271.0 71.6) 271.0 71.6) Total coolant capacity L gal) 504.2 133.2) 504.2 133.2) 504.2 133.2) Inlet Air Combustion air inlet flow rate m 3 /min cfm) 201.7 7121.0) 189.3 6683.8) 183.3 6471.9) Exhaust System Exhaust stack gas temperature C F) 498.0 928.4) 497.9 928.2) 492.0 917) Exhaust gas flow rate m 3 /min cfm) 487.1 17198.9) 451.3 15937.3) 431.4 15232.4) Exhaust system backpressure maximum allowable) kpa in. water) Heat Rejection 6.7 27.0) 6.7 27.0) 6.7 27.0) Heat rejection to jacket water kw Btu/min) 750 42688) 693 39436) 678 38545) Heat rejection to exhaust total) kw Btu/min) 2501 142239) 2311 131449) 2242 127481) Heat rejection to aftercooler kw Btu/min) 721 40977) 624 35475) 557 31683) Heat rejection to atmosphere from engine kw Btu/min) 161 9166) 155 8801) 153 8680) Heat rejection from alternator kw Btu/min) 107 6085) 107 6085) 107 6085) Emissions Nominal) - Full Load NOx mg/nm 3 g/hp-h) 1714.6 3.72) 1629.6 3.56) 1375.4 3.12) CO mg/nm 3 g/hp-h) 320.8 0.71) 255.1 0.56) 303.4 0.69) HC mg/nm 3 g/hp-h) 36.1 0.09) 39.2 0.10) 37.2 0.10) PM mg/nm 3 g/hp-h) 31.5 0.08) 26.0 0.07) 35.7 0.10) Emissions Potential Site Variation) - Full Load106 NOx mg/nm 3 g/hp-h) 2057.5 4.47) 1955.5 4.27) 1650.5 3.74) CO mg/nm 3 g/hp-h) 577.4 1.27) 459.2 1.01) 546.2 1.25) HC mg/nm 3 g/hp-h) 48.0 0.12) 52.1 0.13) 49.5 0.13) PM mg/nm 3 g/hp-h) 44.1 0.12) 36.4 0.10) 50.0 0.13) LEHE1343-00 Page 5 of 6

Weights and Dimensions C A B Dim A mm in) Dim B mm in) Dim C mm in) Dry Weight kg lb) 8457 330.0) 2569 101.1) 3007 118.4) 23 393 51573) Note: For reference only. Do not use for installation design. Contact your local Cat dealer for precise weights and dimensions. Ratings Definition Output available with varying load for the duration of the interruption of the normal source power. Average power output is 70% of the standby power rating. Typical operation is 200 hours per year, with maximum expected usage of 500 hours per year. Applicable Codes and Standards AS1359, CSA C22.2 No100-04, UL142, UL489, UL869, UL2200, NFPA37, NFPA70, NFPA99, NFPA110, IBC, IEC60034-1, ISO3046, ISO8528, NEMA MG1-22, NEMA MG1-33, 2014/35/EU, 2006/42/EC, 2014/30/ EU. Note: Codes may not be available in all model configurations. Please consult your local Cat dealer for availability. Data Center Applications Tier III/Tier IV compliant per Uptime Institute requirements. ANSI/TIA-942 compliant for Rated-1 through Rated-4 data centers. Fuel Rates Fuel rates are based on fuel oil of 35º API [16 C 60ºF)] gravity having an LHV of 42,780 kj/kg 18,390 Btu/lb) when used at 29ºC 85ºF) and weighing 838.9 g/liter 7.001 lbs/u.s. gal.) 3516 PGHL LEHE1343-00 7-17) www.cat.com/electricpower 2017 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International System of Units SI) is used in this publication. CAT, CATERPILLAR, their respective logos, ADEM, Caterpillar Yellow, the Power Edge trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.