Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications

Similar documents
Compact NS. Installation recommendations

KEWTECH. KT56 digital multi function tester. Instruction manual

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications

FUSE TECHNOLOGY Ambient temperature

University of Houston Master Construction Specifications Insert Project Name

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

FACT SHEET Standard: Electrical Safety

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Selective Coordination

PORTABLE CURRENT SOURCE FOR CIRCUIT BREAKER AND MOTOR OVERLOAD TESTING INSTRUCTION MANUAL PI-250B. Release 1.0 April 5, 2013

Power systems Protection course

Design Standards NEMA

SURE TRIP RETRO KITS

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

Electropneumatic Timing Relays Series 7000 Industrial

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

INTERPLANT STANDARD - STEEL INDUSTRY

ECET Distribution System Protection. Overcurrent Protection

0.5 s to 30 h (30 s, 3 min, 30 min, 3 h, 30 h)

PD-Series Ground Fault Circuit Protection

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI

Electrical network protection VIP30, VIP35. User s manual 12/2008

Ultra-Rapid Fuse Links for the Protection of Semiconductor Rectifiers

Lab 9: Faraday s and Ampere s Laws

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

SURE-TRIP OEM RELACEMENT TRIP UNIT

COM Overcurrent Relay

Electromagnetic Industries LLP

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

DIP SWITCH BASED EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE CURRENT TRANSFORMER (CBCT / ZCT) EL SERIES

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

PRODUCT / TEST MANUAL 2C58K2 INSTANTANEOUS OVERCURRENT

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

PLATINUM SERIES SWITCHBOARD METERS

AF series contactors (9 2650)

SURE TRIP SLT-201 SECONDARY TEST SET

RVS-AX Instruction Manual

Protection and control VIP30, VIP35. Relays technical manual

IN2 Enclosed Switches and Circuit Breakers

OPERATORS INSTRUCTION MANUAL CIRCUIT BREAKER TEST SET MODEL DDA-1600

Phenix Technologies Inc. 75 Speicher Drive Accident, Maryland 21520

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

Owner s Manual. Series 165 Automatic Transfer Switches rated 100 and 200 amps, single phase, 240 V ac for automatic 2 wire start generators

PB-Series. GFCI/ELCI & Panel Seal

MaxPak Plus Analog DC V S Drive

A. Submit manufacturer's literature and technical data before starting work.

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

Single Pole Circuit Protectors 55. Multi-Pole Circuit Protectors 56. Configurations 58. Operating Characteristics 59.

MAGNETIC MOTOR STARTERS

Electronics Technology and Robotics I Week 2 Basic Electrical Meters and Ohm s Law

TITANIUM SUBLIMATION PUMP CONTROLLER MODEL TSP2 USER MANUAL ISSUE 3.5. For use with instruments, serial numbers Mxx onwards.

Exercise 6. Three-Phase AC Power Control EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Introduction to three-phase ac power control

Secondaries. arc flash note Introduction. By Mike Lang, engineer and. Services Supervisor

POLARISED, MONOSTABLE SAFETY RELAY with (mechanical linked) forced contacts operation

FR circuit breaker - hydraulic magnetic, railway, very high current. Datasheet

PowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ)

Advanced Test Equipment Rentals ATEC (2832)

design prefix 50 Hanover Road, Florham Park, New Jersey USA (ASCO), for service call (ASCO)

AP/UP, AP/MIL Series Magnetic Circuit Protectors

Electro-Proportional Terms and Definitions

ARAI Date of hosting on website: 27 th October 2015 Last date for comments: 27 th November 2015

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

ELECTRICAL INSPECTOR EXAMINATION 14 November 2015 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours

HT Dielectric Withstand Tester Volts AC Output 25mA Leakage Option

Q and M-Frame Circuit Breaker Instruction Leaflet for Installation and Operation for Thermal Magnetic Trip Units

AF series contactors (9 2650)

PowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

Btdin RCBO 6000A up to 63A (2P)

PRODUCT/TEST MANUAL 2C58K37 INSTANTANEOUS OVERCURRENT RELAY

Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Not all Low Voltage Switchgear is created equal

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

PORTABLE POWER SUPPLY MODEL NUMBER VMS-1 VERSION 1.0

Investigation into UK socket-outlets incorporating USB charging points

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

Service Entrance Methods

SL Series Application Notes. SL Series - Application Notes. General Application Notes. Wire Gage & Distance to Load

CBAM Load Share (LSL) Series

SEP 2016 Rev D2

M Series 140.D Data Sheet. Two-Point Controller with Moving-Iron or Moving-Coil Movement 90 Dial RW 96 RP 96

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

Emergency lighting units EM converterled. EM converterled ST 50 V SELFTEST series

Temperature Controllers

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

Bulletin 1489 Circuit Breakers. Selection Guide

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A

Temperature Controllers

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

Table of Contents. For latest version, visit:

Electronic Ballast EVG 2000-T

Transcription:

G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications

Contents 1. Laboratory Objective... 4 2. MECHANICAL OPERATION TESTS... 4 2.1 Purpose... 4 2.2 Procedure... 4 2.3 Results... 4 3. INSULATION RESISTANCE TEST... 4 3.1 Purpose... 4 3.2 Equipment... 5 3.3 Procedure... 5 3.4 Test... 5 3.5 Results... 5 4. INDIVIDUAL POLE RESISTANCE TEST (MILLIVOLT DROP)... 6 4.1 Purpose... 6 4.2 Equipment... 6 4.3 Procedure... 7 4.4 Test... 7 4.5 Results... 7 5. INVERSE TIME OVER CURRENT TRIP TEST... 7 5.1 Purpose... 7 5.2 Equipment... 7 5.3 Procedure... 7 5.4 Test... 7 5.5 Results... 8 6. INSTANTANEOUS OVER CURRENT TRIP TEST... 11 6.1 Purpose... 11 6.2 Equipment... 11 6.3 Procedure... 11 6.4 Test... 11 6.4.1 Run-Up Method... 11 6.4.2 Pulse Method... 12 6.5 Results... 13 7. RATED HOLD IN TEST... 13 7.1 Purpose... 13 2

7.2 Procedure... 13 7.3 Equipment... 13 7.4 Test... 13 7.5 Results... 13 8. Experiment data, recorded by student:... 14 9. Report... 15 3

1. Laboratory Objective To be familiar with measurement and test equipments used for C.B. testing To know different types of tripping units of C.B. To understand tripping characteristic curve of C.B To be familiar with main non-destructive testing applied on MCCB The following non-destructive tests may be used to verify specific operational characteristics of molded case breakers: A. Mechanical operation test B. Insulation resistance test C. Individual pole resistance test (millivolt drop test) D. Inverse time over current trip test E. Instantaneous over current trip test F. Rated hold-in test. Note All Tests above are according to ANSI/NEMA AB 4 2009 (Guidelines for Inspection and Preventive Maintenance of Molded Case Circuit Breakers Used in Commercial and Industrial Applications) 2. MECHANICAL OPERATION TESTS 2.1 Purpose To verify that the circuit breaker mechanism is operating freely. 2.2 Procedure After the circuit breaker is properly isolated, operate it ON and OFF 2 or 3 times. The breaker handle should operate smoothly without binding. Using an ohmmeter or other indicating device, verify that all circuit breaker contacts are open when the handle is in the OFF position and closed when the handle is in the ON position. For breakers that are provided with mechanical trip provisions (generally indicated by a test button) operate the tripping means according to the manufacturer's instructions. With the breaker in the tripped position, verify that the contacts are open using an ohmmeter (or other indicating device). Reset the breaker according to the manufacturer's instructions and operate the breaker to the ON and OFF positions. Use an ohmmeter (or other indicating device) to verify that all the contacts are closing and opening respectively. 2.3 Results The breaker should be replaced if: A. The contacts are not open with the breaker in the tripped or OFF position B. The contacts are not closed with the breaker in the ON position C. The breaker does not reset D. The mechanical trip provisions (if provided) do not trip the breaker 3. INSULATION RESISTANCE TEST 3.1 Purpose To determine the adequacy of the insulation between line and load terminals, between poles, and between each pole and ground. 4

3.2 Equipment This test requires an insulation resistance tester capable of applying a direct-current voltage of at least 500 volts. It should be also noted that more accurate information can be obtained when 1000 volt testers are used since they are more likely to detect deteriorated insulation systems (See Figure 1). Figure 1: Insulation Resistance Test Set-Up 3.3 Procedure After being properly isolated, remove the breaker from the enclosure. In cases where the circuit breaker can be safely isolated/disconnected from line and load connections as installed, the test may be performed with the circuit breaker in its equipment. 3.4 Test All exposed metal parts except line, load, and accessory terminals should be electrically connected to a metal base-plate. Using an insulation resistance tester, apply a direct-current voltage of at least 500 volts to determine the resistance. Voltage is to be applied as follows: a. Between line and load terminals of each individual pole with the circuit breaker in the OFF position and tripped position if possible. b. Between terminals of adjacent poles with the circuit breaker in the ON position. c. From line terminals to the metal base-plate with the circuit breaker in the ON position. 3.5 Results All resistance readings should be one megohm or greater for each measurement. Any reading less than one megohm may indicate the Circuit breaker is contaminated, flawed, or cracked insulating material, in this case; the circuit breaker should be replaced 5

4. INDIVIDUAL POLE RESISTANCE TEST (MILLIVOLT DROP) See Figure 2 and Figure 3 for typical test set up. Figure 2: Individual Pole Resistance Test Set Up Figure 3: Individual Pole Resistance Test Set Up 4.1 Purpose To assess the electrical integrity of internal connections and contacts in a circuit breaker. This can be done by conducting a millivolt drop test across the line and load terminals of each pole with the circuit breaker contacts closed. The millivolt drop (resistance) of a circuit breaker pole can vary significantly due to inherent variability in the extremely low resistance of the electrical contacts and connectors. Such variations do not necessarily predict unacceptable performance and should not be used as the sole criteria for determination of acceptability (See 4.5). 4.2 Equipment This test should be conducted using a 24 volt, or less, direct current power supply capable of supplying the rated current of the circuit breaker. For circuit breakers rated 6

higher than 500 amperes, the power supply should be capable of delivering no less than 500 amperes. If the above equipment is not available for field tests, a Digital Low Resistance Ohmmeter (DLRO), or 4-point tester, capable of 10 to 100 amperes (DC), may be used.. 4.3 Procedure After being properly isolated, remove the breaker from the enclosure. In cases where the circuit breaker can be safely isolated/disconnected as installed, the test may be performed with the circuit breaker in its equipment. 4.4 Test 4.4.1 The test is performed as follows: a) Apply test current across a pole equal to the breaker rating (or 500 Amperes minimum for breakers rated in excess of 500 Amperes). Record the millivolt drop and the test current. Do not maintain current for more than 1 minute. If this equipment is not available, use the following test. b) Apply test current across a pole of 10 Amperes, or the Ampere rating of the breaker, for breakers rated less than 100 Amperes. For breakers rated more than 100 Amperes, apply a test current across a pole of 100 Amperes. Record the millivolt drop and the test current, or resistance. Do not maintain current for more than 1 minute. c) De-energize the test circuit. Manually operate the breaker to the OFF and then ON positions. d) Repeat steps (a) and (b) for a total of three readings on the pole being tested. e) Repeat steps (a) through (c) for each of the remaining poles of the circuit breaker. 4.5 Results The results of test will vary according to the breaker frame type, ampere rating, and manufacturer. The manufacturer should be consulted to determine the maximum allowable voltage drop (Please see Appendix A). If the average test values of any pole of the breaker exceed the maximum allowable drop, the circuit breaker may have reached the end of life and additional tests may have to be conducted. 5. INVERSE-TIME OVER CURRENT TRIP TEST 5.1 Purpose To verify the operation of the inverse-time over current tripping function of a circuit breaker. This test is not applicable to instantaneous only breakers or molded case switches. 5.2 Equipment Variable low voltage power supply, including an RMS reading ammeter capable of delivering the required test current for the maximum test duration as shown in Table 1. Circuit breakers with electronic trip units are often equipped with integral test provisions for verifying the functional operation of the trip unit. Where integral test provisions are not included, separate test devices are frequently available from the circuit breaker manufacturer. When using either of these alternate test means, the instructions of the manufacturer must be followed. 5.3 Procedure After being properly isolated, remove the breaker from the enclosure. In cases where the circuit breaker can be safely isolated/disconnected from line and load connections as installed, the test may be performed with the circuit breaker in its equipment. 5.4 Test NOTE 1 These tests should be conducted on individual circuit breaker poles using a test current of 300% of the circuit breaker's rated current. This test current has been chosen because it is relatively easy to attain and the wattage per pole is low enough that the transfer of heat into the adjacent poles is minor and does not appreciably affect the test results. 7

NOTE 2 Circuit breakers equipped with electronic trip units typically are provided with more than one long-time trip curve. The tests in this clause should be performed with the circuit breaker set at the longest time setting or at the end use setting, as preferred. NOTE 3 Circuit breakers equipped with electronic trip units incorporating ground fault protection should be tested with two poles or more in series to avoid an early trip via the ground fault trip circuit. NOTE 4 Plug-on or draw-out circuit breakers will require specialized connections or test fixtures. Conduct the test on each pole of the circuit breaker by connecting the line and load terminals of that pole to the test equipment by copper conductors not less than 4 ft (1.2 m) in length, sized in accordance with Table 2.A circuit breaker rated 1600 amperes or more may be tested with copper bus bars per Table 3 instead of cable. A circuit breaker rated more than 4000 amperes should be tested with copper bus bars unless it is marked for cable connections only. Tests should be conducted with the circuit breaker at a room ambient of approximately 25 C (77 F). a) Connect one pole (two or more poles for electronic trip circuit breakers equipped with ground fault protection) as indicated above. b) With the test circuit breaker closed, energize the test circuit and quickly adjust the transformer to the required 300% test current. c) With the test current at the correct value, start timing. d) Record trip time. e) Repeat steps (a) through (d) on each of the other individual poles. (Where ground fault protection [GFP] is supplied, repeat steps (a) through (d) using two additional combinations of poles.) Tests on adjacent poles should be made at no less than five minute intervals. For circuit breakers with thermal trip elements, wait at least 20 minutes before repeating tests on the same pole. For circuit breakers with electronic trip elements, consult the manufacturer s published instructions for required intervals between tests. If the intervals are shortened, subsequent tests may result in premature tripping. If more accurate results are required, the between-test intervals should be extended to permit the temperature of the circuit breaker to return to that of the surrounding ambient air. For information regarding testing of an electronic trip circuit breaker's ground fault trip element, consult the manufacturer's published instructions. 5.5 Results The circuit breaker should trip within the maximum times shown in Table 1. Circuit breakers that do not trip within these maximum time limits should not be accepted unless its tripping curve confirms with the C.B. manual published by manufacturer (Please see Appendix B) NOTE If there is concern that the trip time is too low, then the hold-in test should be conducted (See section 7). 8

Table 1 VALUES FOR INVERSE TIME TRIP TEST (At 300% of Rated Continuous Current of Circuit Breaker) 9

Table 2 COPPER TEST CONDUCTOR SELECTION 10

Table 3 SIZE OF COPPER BUSBAR CONNECTIONS 6. INSTANTANEOUS OVER CURRENT TRIP TEST 6.1 Purpose To verify the operation of the instantaneous trip functions under field test conditions. Accordingly, the tolerances given in Table 4 are necessarily broader than the manufacturer's factory tolerances. 6.2 Equipment The same equipment as utilized in section 5 is required with the following exceptions: a. For the run-up method of testing a pointer-stop ammeter or other types of meters (digital) capable of reading and recording, the maximum current reached prior to tripping may be used. b. For the pulse method of testing, a calibrated image-retaining oscilloscope, or a high speed sampling rate digital ammeter (capable of accurately measuring a half-cycle pulse) is required instead of an ammeter 6.3 Procedure After being properly isolated, remove the breaker from the enclosure. In cases where the circuit breaker can be safely isolated/disconnected from line and load connections as installed, the test may be performed with the circuit breaker in its equipment. 6.4 Test Since the instantaneous trip characteristics of the circuit breaker can be influenced by stray magnetic fields, the test setup must be made in such a way that the fields caused by the test equipment itself, by steel enclosures, mounting plates, or by the conductors to the circuit breaker, do not affect the test results. Results can also be influenced by the wave shape of the current and, therefore, it is desirable to have sinusoidal output from the supply equipment. Manufacturers may be consulted for individual recommendations on mounting and wire routing if desired. The two methods which may be used for testing the instantaneous trip function are the "run-up" and the "pulse" methods. 6.4.1 Run-Up Method a. Connect one pole of the test breaker to the test equipment as indicated in section 5, adjust the trip setting to the desired position, and operate the breaker to the ON position. b. Set the current control to a point where approximately 60% of the current setting will flow when the circuit is energized. c. Turn the power ON and increase the current until the circuit breaker trips. The recommended time for increasing the current is between two and five seconds. If the circuit breaker does not open within five seconds, the supply circuit should be turned 11

OFF to prevent damage to the test equipment and overheating of the circuit breaker thermal elements. This method requires operator skill in recognizing the relationships between actual current and the meter indication. If the current is increased too slowly, tripping may be caused by the time delay element, especially if more than one test is run. If the current is increased too rapidly, an erroneous current reading may be obtained because the meter lags behind the actual current value due to meter damping. This problem can be overcome and the accuracy of this method may be improved by the use of a calibrated oscilloscope to read the current level at the time the breaker trips. 6.4.2 Pulse Method This method is more accurate than the run-up method, if done properly. However, it is subject to an error introduced by a distortion of the pulse current, commonly called offset or asymmetrical waveform, as depicted in Figure 4. This current offset can be minimized by controlling the closing of the circuit such that the circuit is closed at approximately the 90 point on the supply circuit voltage waveform. The pulse method involves the following steps: a. Connect one pole of the test breaker to the test equipment as indicated in 6.5, adjust the trip setting to the desired position, and operate the breaker to the ON position. b. Apply a pulse of current, approximately 5 to 10 cycles in duration, and at a level approximately 5% below the lower tolerance limit specified in Table 4 for the breaker setting. The breaker should not trip. c. Apply a pulse of current, approximately 5 to 10 cycles in duration and at a level equivalent to the high tolerance limit specified in Table 4. The breaker should trip. Figure 4: Current Wave Shapes 12

6.5 Results Test results should be in accordance with the values shown in Table 4. If the results differ significantly from those values, reexamine the test circuit and circuit breaker mounting arrangements (See 6.4). If there are no apparent problems with the test circuit or mounting arrangements, the circuit breaker should be replaced. 7. RATED HOLD-IN TEST 7.1 Purpose To verify the capability of a molded case circuit breaker to carry its rated current. 7.2 Procedure Remove the breaker from the enclosure. In cases where the circuit breaker can be safely isolated or disconnected as installed, the test may be performed with the circuit breaker in its equipment. 7.3 Equipment A low voltage power supply such as that described in section 5.2 is required to conduct this test. 7.4 Test The circuit breaker should be tested with the operating mechanism set to the ON position, in open air, with all poles connected in series by copper conductors not less than 4 ft (1.2 m) in length, selected in accordance with Table 2. The test should be performed at room ambient temperature approximately 25 C (77 F). The power supply should be adjusted to deliver rated current until the circuit breaker temperature stabilizes. Temperature stabilization usually occurs within one hour for breakers rated 100 amperes or less, but will take several hours for breakers of higher rating. Stabilization may be verified by taking three successive temperature measurements at intervals of 10 to 20 minutes between measurements at the same location on one or more of the circuit breaker connectors utilizing a temperature probe or thermocouple instrument. 7.5 Results The circuit breaker should not trip during the test. If it does trip, reset the breaker and turn it ON again while continuing to monitor connector temperatures for an indication of temperature stabilization. If the breaker continues to trip or if any of its terminals reach temperatures higher than 80ºC above ambient, it should not be accepted. 13

8. Experiment data, recorded by student: Student Name: Sec.: B.N.: 1.Mechanical operation test A. The contacts are not open with the breaker in the tripped or OFF position B. The contacts are not closed with the breaker in the ON position C. The breaker does not reset D. The mechanical trip provisions (if provided) do not trip the breaker E. C. B is working 2. Insulation resistance test The C.B in OFF Position The resistance Between pole 1 "Line" and 1 "Load" The resistance Between pole 2 "Line" and 2 "Load" The resistance Between pole 3 "Line" and 3 "Load" The C.B in TRIP Position The resistance Between pole 1 "Line" and 1 "Load" The resistance Between pole 2 "Line" and 2 "Load" The resistance Between pole 3 "Line" and 3 "Load" The C.B in ON Position The resistance Between pole 1 and 2 The resistance Between pole 2 and 3 The resistance Between pole 1 and 3 3.Individual pole resistance test (millivolt drop test) The C.B in ON Position The resistance Between pole 1 "Line" and 1 "Load" The resistance Between pole 2 "Line" and 2 "Load" The resistance Between pole 3 "Line" and 3 "Load" 4. Tripping Curve Test Write C.B Protecting Setting I r =, T r =,I sd =,T sd =,I inst = % From I r Injected Tripping Fault Current Time Type Value Value Comments Value 14

9. Report a) Compare between the true RMS multi meter and general digital multi meter. b) What is the Circuit that may be used in the electronic MEGGER which can generate 5000 VDC from 6 VDC? Mention Circuit name, draw a figure for the circuit, and illustrate its operation c) Fill up a table of all devices used in the experiment and mention the function of each device d) Fill up a table for all readings recorded in the experiment e) What is the Hall Effect phenomena "brief description"? 15

APPENDIX A 16

Installation recommendations Power loss/ Resistance Compact NSX equipped with thermal-magnetic trip units DB115052 Compact NSX thermal power loss values are used to calculate total temperature rise in the switchboard in which the circuit breakers are installed. N L1 L2 L3 With a Vigi module, the deviation of the N and L3 bars required to pass through the toroid results in higher power losses compared to those of the L1 and L2 bars. The values indicated in the tables below are typical values for a device at full rated load and 50/60 Hz. Power loss per pole (P/pole) in Watts (W) The value indicated is the power loss at I N, 50/60 Hz, for a three-pole or four-pole circuit breaker. Measurement and calculation of power loss are carried out in compliance with the recommendations of Annex G of standard IEC 60947-2. Resistance per pole (R/pole) in milliohms (mω) The value of the resistance per pole is provided as a general indication for a new device. The value of the contact resistance must be determined on the basis of the measured voltage drop, in accordance with the manufacturer's test procedure (ABT instruction document no. 1 - BEE - 02.2 -A). Note: this measurement is not sufficient to determine the quality of the contacts, i.e. the capacity of the circuit breaker to carry its rated current. Additional power loss Additional power loss is equal to the sum of the power dissipated by the following: b Vigi module: note that the deviation of the N and L3 bars required to pass through the toroid results in higher power losses compared to those of the L1 and L2 bars (diagram opposite). When calculating total power loss, use L1, L2, L3 for a 3P device and N, L1, L2, L3 for a 4P device b disconnecting contacts (plug-in and withdrawable devices) b ammeter module b transformer module. Calculation of total power loss Total power loss at full rated load and 50/60 Hz is equal to the sum of the device and additional power losses per pole multiplied by the number of poles (2, 3 or 4). If a Vigi module is installed, it is necessary to differentiate between N and L3 on one hand and L1 and L2 on the other. Compact NSX100 to 250 equipped with TM-D and TM-G trip units Type of device Fixed device 3/4 poles Rat. (A) R/pole P/pole Vigi (N, L3) Additional power / pole Vigi Plug-in / Ammeter (L1, L2) withdr. module NSX100 16 11.42 2.92 0 0 0 0 0 25 6.42 4.01 0 0 0.1 0 0 32 3.94 4.03 0.06 0.03 0.15 0.1 0.1 40 3.42 5.47 0.10 0.05 0.2 0.1 0.1 50 1.64 4.11 0.15 0.08 0.3 0.1 0.1 63 2.17 8.61 0.3 0.15 0.4 0.1 0.1 80 1.37 8.77 0.4 0.2 0.6 0.1 0.1 100 0.88 8.8 0.7 0.35 1 0.2 0.2 NSX160 80 1.26 8.06 0.4 0.2 0.6 0.1 0.1 100 0.77 7.7 0.7 0.35 1 0.2 0.2 125 0.69 10.78 1.1 0.55 1.6 0.3 0.3 160 0.55 13.95 1.8 0.9 2.6 0.5 0.5 NSX250 125 0.61 9.45 1.1 0.55 1.6 0.3 0.3 160 0.46 11.78 1.8 0.9 2.6 0.5 0.5 200 0.39 15.4 2.8 1.4 4 0.8 0.8 250 0.3 18.75 4.4 2.2 6.3 1.3 1.3 Transfo. module Compact NSX100 to 630 equipped with MA/1.3-M trip units Type of device Fixed device Additional power / pole 3 poles Rat. R/pole P/pole Vigi Vigi Plug-in / Ammeter (A) (N, L3) (L1, L2) withdr. module Transfo. module NSX100 2.5 148.42 0.93 0 0 0 0 0 6.3 99.02 3.93 0 0 0 0 0 12.5 4.05 0.63 0 0 0 0 0 25 1.66 1.04 0 0 0.1 0 0 50 0.67 1.66 0.2 0.1 0.3 0.1 0.1 100 0.52 5.2 0.7 0.35 1 0.2 0.2 NSX160 150 0.38 8.55 1.35 0.68 2.6 0.45 0.45 NSX250 220 0.3 14.52 2.9 1.45 4.89 0.97 0.97 NSX400 320 0.12 12.29 3.2 1.6 6.14 1.54 1.54 NSX630 500 0.1 25 13.99 7 15 3.75 3.75 B-10

Compact NSX equipped with electronic trip units The values indicated in the table below are typical values for a device at full rated load and 50/60 Hz. The definitions and information are the same as that for circuit breakers equipped with thermal-magnetic trip units. Compact NSX100 to 630 equipped with Micrologic trip units Type of device Fixed device Additional power / pole 3/4 poles Rat. R/pole P/pole Vigi Vigi Plug-in / Ammeter (A) (N, L3) (L1, L2) withdr. module Transfo. module NSX100 40 0.84 1.34 0.1 0.05 0.2 0.1 0.1 100 0.468 4.68 0.7 0.35 1 0.2 0.2 NSX160 40 0.73 1.17 0.4 0.2 0.6 0.1 0.1 100 0.36 3.58 0.7 0.35 1 0.2 0.2 160 0.36 9.16 1.8 0.9 2.6 0.5 0.5 NSX250 100 0.27 2.73 1.1 0.55 1.6 0.2 0.2 250 0.28 17.56 4.4 2.2 6.3 1.3 1.3 NSX400 400 0.12 19.2 3.2 1.6 9.6 2.4 2.4 NSX630 630 (1) 0.1 39.69 6.5 3.25 19.49 5.95 5.95 (1) The power loss values for the Vigi modules and withdrawable circuit breakers are given for 570 A. B-11

APPENDIX B