COMMERCIAL INFORMATION TECHNICAL INFORMATION BA511*33

Similar documents
Overcurrent releases - description, specifications, characteristics specifications specifications description...

MOULDED CASE CIRCUIT BREAKERS BC160N

MOULDED CASE CIRCUIT BREAKERS BH630N, BH630S

Modeion MOULDED CASE CIRCUIT BREAKERS BL1600S

MOULDED CASE CIRCUIT BREAKERS BC160N

3VT Kompaktleistungsschalter bis 630A

MOULDED CASE CIRCUIT BREAKERS BL1600S

Varius SUMMARY OF MODELS

Basic function. Rated current. Appropriate for three-phase motors of output 2) [kw] I n. = 400 V a.c. 2) Appropriate for three-phase motors

Varius SUMMARY OF MODELS

Fuse switch-disconnectors

Fuse switch-disconnectors

3VT5 Molded Case Circuit Breakers up to 1600 A

Varius SUMMARY OF MODELS

3VT2 Molded Case Circuit Breakers up to 250 A

3VT5 Molded Case Circuit Breakers up to 1600 A

Connecting sets CS-FS CS-FS123-WD. Connecting space covers OD-FS00-.. OD-FS123-KP. Adapter for parallel outlet - HP-SE/K

max pole for t=15 ms

3VT1 Molded Case Circuit Breakers up to 160 A

FUSOMAT Visible breaking and tripping fuse switches from 250 to 1250 A

Devices for switching and control

cor Long Run Experience

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

DPX moulded case circuit breakers

IP20 degree of protection; IP40 degree of protection after installation in a distribution box

SENTRON 3VT Molded Case Circuit Breakers up to 1600 A

MULTIBLOC 2.RST8 Size 2, 400A, 690VAC, Design for bus bar installation, Triple Pole

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

MULTIBLOC 1.RST8 Size 1, 250A, 690VAC, Design for bus bar installation, Triple Pole

Horizontal fuse disconnects

DPX Thermal magnetic and trip-free switches DPX 3 -I 160

MULTIBLOC 3.ST8 Size 3, 630A, 690VAC, Design for Bottom Fitting, 3-,4-pole

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.

D509E. Manual Motor - Starters

RESIDUAL CURRENT CIRCUIT BREAKERS WITH OVERCURRENT PROTECTION OLE

Fuse switch disconnectors

Fuse switch disconnectors

MULTIBLOC 1.ST8 Size 1, 250A, 690VAC, Design for Bottom Fitting, 1-,2-,3-,4-pole

DPX 630 Thermal magnetic and trip-free switches DPX-I 630


RESIDUAL CURRENT CIRCUIT BREAKERS WITH OVERCURRENT PROTECTION OLFE (6 ka)

Vistop TM isolating switches 63 to 160A

MULTIBLOC 2.ST8 Size 2, 400A, 690VAC, Design for Bottom Fitting, 3-,4-pole

Protection components

Motorized switch-disconnectors OTM 40 to 125 Amperes

3 - Protection components Motor circuit-breakers

01 Spectra Plus - Introduction

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

SENTRON Switching and Protection Devices Switch Disconnectors

DPX Thermal magnetic and trip-free switches DPX 3 -I 250

DMX 3 -I 2500 switch disconnectors

Thermal magnetic and trip-free switches

Varius SUMMARY OF MODELS OF FUSE-BASE AND FUSE HOLDERS. Type SPB S3PB SPF SP4.. SP50

vertical fuse switch disconnectors

The breakers offer thermal-magnetic trip protection according to Z and K characteristics.

SIDERMAT Load break switches for power distribution from 250 to 1800 A with tripping function

Overview of Low voltage equipment - Moulded-case & Air circuit-breakers

DRX 100 B/N/H Circuit breaker (not adjustable)

MC FRAME SIZE 1 / UP TO 160A

DRX 125 Circuit breaker (not adjustable)

PIX-H Metal-clad switchgear up to 17.5kV

DPX Thermal magnetic and trip-free switches DPX 3 -I 630

125 to 4000 A. Functions. Conformity to standards. Approvals and certifications (1) General characteristics. Available on request

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489

3VU13, 3VU16 Circuit-Breakers

System pro M compact Miniature Circuit Breaker SU200 M for branch circuit protection acc. to UL 489

MULTIVERT 250A Size 1, 690VAC

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

Motor Circuit Breakers C4

DPX 630 Electronic release

DPX Magnetic only

ATyS S - ATyS d S Remotely operated Transfer Switching Equipment from 40 to 125 A

Switch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV

Siemens AG Switch Disconnectors SENTRON. Configuration. Edition 10/2015. Manual. siemens.com/lowvoltage

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

DPX 1600 Electronic release

The Complete Range. Drawing of the NH Fuse-Switch, 3-pole switching, horizontal design for busbar supply on a 60 mm busbar systems

DRX 250 B/N/H Circuit breaker (not adjustable)

SENTRON VL Series Product Specifications

ATyS range ATyS r, ATyS d, ATyS t, ATyS g, ATyS p from 125 to 3200 A

Electronic circuit breaker EBU10-T

MULTIVERT 1000A Main Incomer, 690VAC

MS25, MST25, MS20, MST20

SIRCO UL98 Load break switches standards UL and CSA 100 to 1200 A

System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077

BETA Switching Switches and Light Indicators

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

MS /27/2015. ABB contact for United States of America. General Information Extended Product Type: Categories

FUSERBLOC Fuse combination switches with rear connection for industrial fuses up to 400 A

DPX earth leakage DPX 3 -I earth leakage

MCCB Accessories to suit AF

DATA SHEET 3VT3 MCCB ACCESSORIES

Technical Information

Signal lamps RS, RSB A20. Technical data RS, RSB. Dimensional drawing of RS, RSB. Number of poles Rated voltage Un

MS General Information Extended Product Type: MS

Wall mounted switchgear

Product brochure. ABB Fusegear EasyLine Fuse switch disconnector

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications

RESIDUAL CURRENT CIRCUIT BREAKERS OFE (6 ka)

Transcription:

BA511*33 COMMERCIAL INFORMATION Type designation specification for ordering...146 (design and circuit breaker and switch-disconnector accessories selection, circuit breaker rated current selection) Connecting sets...147 Mounting sets...147 Accessories...148 Purchase order example...149 TECHNICAL INFORMATION Circuit breakers, switch-disconnectors - specifications...150 - wiring diagram...152 - connecting, installation...153 - de-ionization space...155 - dimensions...156 Overcurrent releases - description, specifications, characteristics...162 Connecting sets Switches Shunt trips - specifications...153 - specifications...163 - specifications...163 Undervoltage releases - specifications...163 Hand drives - description...164 144

BA511*33 SUMMARY OF MODELS AND ACCESSORIES CONNECTING SETS Front connection Rear connection Clamp type terminals CS-33-PP01 CS-33-PP02 CS-33-ZP03 CS-33-ZP04 CS-33-V005 FIXED DESIGN BA511*33-50... FIXED DESIGN, FRONT HAND DRIVE BA511*33-50...86 FIXED DESIGN, FRONT HAND DRIVE WITH ADJUSTABLE LEVER BA511*33-50...861 ACCESSORIES Terminal cover IP10 for fixed design Terminal cover IP10 for plug-in design Terminal cover IP20 for fixed design Terminal cover IP20 for plug-in design OD-33-KS03 OD-33-KS04 OD-33-KS01 OD-33-KS02 Cover for segmental contacts for plug-in design Signalling switch Locking inset OD-33-KS05 SO-33-1100 OD-33-KV03 RETROFITS CS-33-A021 CS-33-Z021 OD-33-MZ21 Circuit breakers BA511*33 and switch-disconnectors BN511.33 are designed for direct replacement of circuit breakers BA51*33 and switch-disconnectors BN51.33 145

BA511*33 - Commercial information TYPE DESIGNATION SPECIFICATION FOR ORDERING Selection of accessories for circuit breakers and switch-disconnectors FOR TECHNICAL INFORMATION, see page BA511 - Circuit breaker up to 160 A for protection of LINES 150 150 BA511G Circuit breaker up to 160 A for protection of MOTORS 150 150 BN511. Switch-disconnector up to 160 A 150 50 Fixed design 77 Plug-in design No accessories 032 Auxiliary switch 001, relative switch 001 163 04 Auxiliary switch 002 163 06 Auxiliary switch 004 163 10 Undervoltage release 163 132 Undervoltage release, auxiliary switch 001, relative switch 001 163 14 Undervoltage release, auxiliary switch 002 163 20 Shunt trip 163 232 Shunt trip, auxiliary switch 001, relative switch 001 163 24 Shunt trip, auxiliary switch 002 163 No accessories 86 Front hand drive 1) 164 861 Front hand drive, adjustable lever 1) 164 33 -........ =>> CIRCUIT BREAKER AND SWITCH-DISCONNECTOR DESIGNS Circuit breaker and switch-disconnector designs Rated current Selection of circuit breaker rated current Circuit breakers are supplied with releases in standardized series of rated currents - regulation I n = -25% (values are found in Table). As regards ordering, the rated current of a release is selected so that its value is put down after the circuit breaker design. Example: BA511-33-50, I n = 100 A - circuit breaker of fixed design; no accessories; 100 A rated current of the release; protection of lines. FOR TECHNICAL INFORMATION, see page 162 I n [A] I r [A] 12.5 9.4 12 16 12 16 20 15 20 25 18.7 25 31.5 23.6 31.5 40 30 40 50 50 63 47 63 80 60 80 100 75 100 125 94 125 160 120 160 1) - it is necessary to put down your requirement for the red lever in your purchase order 146

CONNECTING SETS BA511*33 - Commercial information Type Product code Description S [mm 2 ] Connection Weight [kg] Packing [set] 1) CS-33-PP01 4087 Front connection up to 50 A 10 Cu cables 0.05 1 - FOR TECHNICAL INFORMATION, see page 154 CS-33-PP02 4089 Front connection up to 160 A Cu/Al busbars, cable lugs 0.22 1 - FOR TECHNICAL INFORMATION, see page 154 CS-33-ZP03 8116 Rear connection up to 160 A Cu/Al busbars 0.34 1 - For DIMENSIONS, see page 156 CS-33-ZP04 8117 Rear connection up to 160 A Cu/Al busbars 0.32 1 - For DIMENSIONS, see page 156 CS-33-V005 4238 Clamp type terminals 16 95 Cu/Al cables 0.25 1 - FOR TECHNICAL INFORMATION, see page 153 RETROFIT RETROFIT RETROFIT MOUNTING SETS CS-33-A021 13810 Reduction in return for J21U50 - front connection Cu/Al busbars, cable lugs 0.28 1 - FOR TECHNICAL INFORMATION, see page 153 - for complete replacement of the circuit breaker J21U50 with front connection, you need the mounting set OD-33-MZ211 CS-33-Z021 13812 Reduction in return for J21U50 - rear connection - FOR TECHNICAL INFORMATION, see page 153 Cu/Al busbars, cable lugs 0.58 1 - for complete replacement of the circuit breaker J21U 51 with front connection, you need the mounting set OD-33-MZ21 Type Product code Description Weight [kg] Packing [set] 2) OD-33-MZ21 13811 Reduction in return for J21U - front and rear connections 0.64 1 - for complete replacement of the circuit breaker J21U 50 with front connection, you also need the connecting set CS-33-A021 or for the circuit breaker J21U 51 with rear connection you also need the set CS-33-Z021 1) - one set makes possible to connect one end of the circuit breaker (the set contains three terminals with necessary connection accessories) 2) - one set enables to replace one circuit breaker ( the set contains necessary connection accessories to connect the circuit breaker with the mounting kit) RETROFIT - sets enabling replacement of old circuit breakers with the new ones without any switchgear adaptation 147

BA511*33 - Commercial information ACCESSORIES Type Product code Description Weight [kg] Packing OD-33-KS03 7509 Terminal protection - IP10 protection for fixed design with front connection 0.2 1 - included in every supply of circuit breakers OD-33-KS04 9174 Terminal protection - IP10 protection for plug-in design with front connection - included in every supply of circuit breakers 0.2 1 OD-33-KS01 4092 Terminal protection - IP20 protection for fixed design with rear connection - the cover can be sealed 0.25 1 OD-33-KS02 9173 Terminal protection - IP20 protection for plug-in design with rear connection - the cover can be sealed 0.25 1 OD-33-KS05 13974 Cover for segmental contacts - IP20 protection for segmental contacts and for plug-in devices 1 SO-33-1100 9172 Circuit breaker position signalling - for plug-in design 0.05 1 - I e = 0.5 A / AC 400 V OD-33-UV03 14853 Locking inset - enables to lock the circuit breaker lever in Switched off manually state 0.05 1 148

BA511*33 - Commercial information PURCHASE ORDER EXAMPLE You need the main circuit breaker to protect wiring in a small plant where rated current of the protected electrical equipment is 115 A and the maximum short-circuit current in the circuitry does not exceed 20 ka. The circuit breaker will be located in a cubicle switchgear and the incoming and outgoing leads for the Your purchase order: (do not enter the greyed text in your purchase order) circuit breaker will be copper cables supplied with lugs. When you wish to switch the circuit breaker off with the emergency STOP button using the undervoltage release and to indicate the state of the main contacts. You also need to control the circuit breaker manually through the switchgear door. 1) 1 pc BA511-33-5014861 I n = 125 A - circuit breaker with tripping characteristic for protection of lines in fixed design, (red lever) with undervoltage release, auxiliary switch and front hand drive with adjustable lever - overcurrent release rated current of 125 A with rated short-circuit ultimate breaking capacity 22 ka/ac 400 V 2) undervoltage release AC 230 V - rated voltage of the undervoltage release 3) 2 pcs CS-33-PP02 - connecting set to connect cables with lugs 149

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS Specifications CIRCUIT BREAKERS SWITCH- DISCONNECTORS Type BA511-33, BA511G33 BN511.33 Dimensions A x B x C + D [mm] 112.5 x 150 x 75 + 37 112.5 x 150 x 75 + 37 Weight m [kg] 1.85 1.85 Standards EN 60 947-2 IEC 947-2 Approval marks EN 60 947-3 IEC 947-3 Number of poles 3 3 Rated current I n [A] 160 160 Rated operating voltage AC DC U e [V] U e [V] max. 690 max. 250 max. 690 max. 250 Rated frequency f n [Hz] 50/60 50/60 Rated pulse withstand voltage U imp [kv] 8 8 Rated isolation voltage U i [V] 690 690 Utilization category (selectivity) AC 690 V A - Utilization category (switching mode) Rated short-time withstand current U e = AC 690 V Rated short-circuit ultimate breaking capacity Off-time at I cu AC DC AC 690 V DC 440V A - AC-21B DC-22B I cw [ka] / t [s] - 2/1 I cu see page 151 - [ms] [ms] Rated short-circuit ultimate breaking I cs see page 151 - capacity Rated short-circuit making capacity I cm [ka] / U e [V] see page 151 2.8 / 400 Losses per 1 pole at I n = 160 A [W] 15.2 15.2 Mechanical endurance [contact making] 20 000 20 000 Electric endurance [contact making] 4 000 4 000 Frequency of switching [contact making/hr] 40 40 Operating force [N] 65 65 Protection from the front of the unit Terminal protection IP10, IP20, IP66 1) IP10, IP20, IP66 1) Operating conditions Reference ambient temperature [ C] 40 40 Ambient temperature range [ C] -10 +55-10 +55 Working environment standard standard Max. sea level [m] 2000 2000 Seismic immunity 3g (8 50Hz) 3g (8 50Hz) 15 20 - - Dimensions Design modifications Front/rear connections / / Plug-in design Withdrawable design Accessories Switches - auxiliary/relative/signal/early / / / / / / Shunt trip Undervoltage release/with early switch / / Front hand drive/ with adjustable lever / / Load Wiring for DC circuits Motor drive/with operations counter / / Locking type lever available, unavailable 1) - upon agreement with the manufacturer 150

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS Specifications Rated short-circuit ultimate breaking capacity I cu [ka] (rms value) - standard/reverse wiring I n [A] U e AC 230 V AC 415 V AC 500 V AC 690 V DC 220 V 12.5; 16 7/0 3/0 3/0 3/0 25/0 20 20/0 6/0 5/0 5/0 25/0 25 35/0 10/0 6/0 5/0 25/0 31.5 100 35/0 22/0 1) 14/0 10/0 25/0 125; 160 35/0 22/0 1) 14/0 10/0 25/0 1) - for AC 400 V I cu = 25/0 ka Rated short-circuit service breaking capacity I cs [ka] (rms value) - standard/reverse wiring I n [A] U e AC 230 V AC 415 V AC 500 V AC 690 V DC 220 V 12.5; 16 7/0 3/0 3/0 3/0 20/0 20 15/0 6/0 5/0 5/0 20/0 25 35/0 10/0 6/0 5/0 20/0 31.5 100 35/0 17/0 11/0 10/0 20/0 125; 160 35/0 15/0 11/0 10/0 20/0 Rated short-circuit making capacity I cm [ka] (peak value) - standard/reverse wiring I n [A] U e AC 230 V AC 415 V AC 500 V AC 690 V DC 220 V 12.5; 16 12 4.5 4.5 4.5 25 20 40 9 7.5 7.5 25 25 73 17 9 7.5 25 31.5 100 73 46 28 17 25 125; 160 73 46 28 17 25 Power losses I n [A] P [W] 12.5 3.7 16 5 20 5 25 5 31.5 5 40 5.5 50 6 63 6.5 80 7.2 100 9.5 125 12 160 15.2 - losses per 1 circuit breaker pole 151

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS Wiring diagram Circuit breaker 1 3 5 6 8 A2 S5 F1 F1or F2 F2 B2 V X1 Q 1 3 5 12 14 S1 22 24 S2 32 34 S3 42 44 S4 J - BA511*33 circuit breaker body Q - circuit breaker BA511*33 V - trip-free mechanism X1 - power terminals of the plug-in unit S5 - relative switch S1, S2 - auxiliary switches S3, S4 1) - auxiliary switches F1 1) - undervoltage release F2 1) - shunt trip S9 - signalling of position taken 1) - the circuit breaker may be supplied with optional switches S3, S4 or releases F1 and F2 J 5 A1 B1 2 4 6 11 21 31 41 S9 1 3 4 2 X1 2 4 6 Switch-disconnector 1 3 5 6 8 A1 S5 F1 F1or F2 F2 B2 V X1 1 Q1 3 5 12 14 S1 22 24 S2 32 34 S3 42 44 S4 O - BN511.33 switch-disconnector body Q1 - switch-disconnector BN511*33 V - trip-free mechanism X1 - power terminals of the plug-in unit S5 - relative switch S1, S2 - auxiliary switches S3, S4 2) - auxiliary switches F1 2) - undervoltage release F2 2) - shunt trip S9 - signalling of position taken 2) - the switch-disconnector may be supplied with optional switches S3, S4 or releases F1 and F2 O 5 A1 B1 2 4 6 11 21 31 41 1 3 S9 4 2 X1 2 4 6 152

CIRCUIT BREAKERS, SWITCH DISCONNECTORS Specifications States of switches Cavity S1, S2, S3, S4 S5 Switch name Switch designation Switch function Relative S5 indicates switching off of the circuit breaker by release Auxiliary S1, S2, S3, S4 indicates the position of main contacts Circuit breaker state Lever position of circuit breaker State of the main contacts Switched on 1 1 0 0 1 Manually switched off 0 0 1 0 1 Switched off by releases 0 0 1 1 0 note.: 0 - contact open, 1 - contact closed Connecting and installing Power circuit is connected using Cu, Al busbars, flexibars or cables, eventually by means of cables with lugs to provide wider choice of connecting, the following connecting sets are made, see page147 the feed lines are connected to input terminals 1, 3, 5 the load lines are connected to output terminals 2, 4, 6 input and output terminals are not allowed to be swapped it is recommended to apply paint on the busbars input and output conductors/busbars must be reinforced so as to avoid of transferring electrodynamic forces into the circuit breaker during short-circuits Auxiliary circuits switches, shunt trip or undervoltage releases are connected using flexible copper conductors with diameters of 0.5 1 mm 2 via the cable block located in the side of the circuit breaker /switch disconnector Recommended cross-sections of connecting cables and busbars I n [A] Cable S [mm 2 ] Cu Al 12.5 1.5 2.5 16 2.5 4 20 2.5 4 25 4 6 31.5 6 10 40 10 16 50 10 16 63 16 25 80 25 35 100 35 50 125 50 70 160 70 95 Connecting sets specifications Cable S [mm 2 ] Core type Sector-shaped conductor stranded Sector-shaped conductor solid Round conductor stranded Round conductor solid Type I max [A] Busbars W x H [mm] Dimensional drawing CS-33-V005 160 35 70 Cu / Al 35 95 Cu / Al 16 50 Cu / Al 16 50 Cu / Al CS-33-A021 160 RETROFIT - reduction in return for circuit breakers J21U with front connection page 160 CS-33-Z021 160 RETROFIT - reduction in return for circuit breakers J21U with rear connection page 160 153

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS Connecting, installation Front connection OD-33-KS01 IP20 OD-33-KS03 IP10 3.5 4.5Nm Cu 0.5 1mm 2 10Nm MIN. 4 MAX. 14 18 10. 5 25 CS-33-PP02 MAX.31 MAX.1 4 MIN.4 2-3Nm 12Nm M10 16 CS-33-PP01 2 MAX.10 mm 22 CS-33-V005 2 sm 35 70 mm 2 se 35 95 mm 2 rm 16 50 mm 2 re 16 50 mm Rear connection 10-14Nm CS-33-ZP03, CS-33-ZP04 CS-37-V013 154

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS De-ionization space BA511*33 - Technical information A, B, C minimum de-ionization space free of metal grounding structures (is ensured due to terminal cover OD-33-KS03, being part of every supply of circuit breakers) when distances A, B, C are not adhered to, it is necessary to supply the metal structure of the switchgear with a flameproof insulation cover 155

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS Dimensions Fixed design, front connection Drilling positions 82 41 26 72 10 4 2xØ9 2xM4 10 130 90 57 18.5 30 18 2xØ4.5 17 17 18 125 12.5 150 74 19 14 R74 5 16 13 12.5 125 112.5 75 12 112 Fixed design, rear connection Drilling positions 5.5 CS-33-ZP04 (CS-33-ZP03) 56 23 45 161 10 130 10 M10 93 ISOLATION Ø16 12.5 125 60 6xØ20 2xM4 CS-33-ZP03 (CS-33-ZP04) 156

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS Dimensions BA511*33 - Technical information Fixed design, front connection, IP10 protection Drilling positions 112.5 75 OD-33-KS03 2xM4 294 12.5 125 OD-33-KS03 Fixed design, front connection, IP20 protection Drilling positions 112.5 75 8 OD-33-KS01 2xM4 50 250 12.5 125 OD-33-KS01 157

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS Dimensions Plug-in design, front connection Drilling positions 71 112.5 10 10 170 20 190 94 45 100 4xØ9 4xØ4.5 19 14 4xM4 142 167 Plug-in design, front connection, IP10 protection Drilling positions 112.5 OD-33-KS04 142 167 4xM4 72 20 334 170 10 190 45 100 OD-33-KS04 75 158

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS Dimensions Plug-in design, front connection, IP20 protection Drilling positions 112.5 OD-33-KS02 167 142 45 290 170 190 50 10 100 4xM4 OD-33-KS02 75 Plug-in design, rear connection, IP20 protection Drilling positions CS-33-ZP04 (CS-33-ZP03) 56 112.5 23 10 201 170 M10 93 ISOLATION Ø16 45 100 60 CS-33-ZP03 (CS-33-ZP04) 6xØ20 4xM4 159

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS Dimensions Fixed design, rear connection, (connecting set CS-33-Z021, mounting set OD-33-MZ21) RETROFIT 130 112.5 1 75 Fixed design, rear connection, (connecting set CS-33-A021, mounting set OD-33-MZ21) 135 51 4 30 2.5 130 51 51 53 37,5 255 223 161 223 130 223 272 R74 36.5 255 12.5 28 23 51 51 135 2.5 31 4 112 RETROFIT Drilling positions 75 112 168 12.5 28 23 160

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS Dimensions Fixed design, front hand drive Drilling positions 112.5 2xM4 19 6 Ø24 125 20 R92 18 75 4 75 25 12.5 152 max.ø6 162 Fixed design, front hand drive, adjustable lever SWITCHGEAR DOOR 20 SAFETY PIN SEAL 60 60 75 12 IP55 PROTECTION OF ROTARY HAND MIN.160 MAX.330 max.ø6 SWITCHGEAR DOOR ADAPTATION MIN.150 35 17.5 EXTENSION SHAFT ADAPTATION R2.5 60 4xØ4.3 20 40 SHAFT END 20 40 161

OVERCURRENT RELEASES Characteristics I r = (0.75-1) x I n Setting of reduced current Description In relation to the protected current required, the rated current I r (the maximum value is set up by the manufacturer and the of the dependent release will be set up accordingly adjustment of currents within the marked range is linear). Ranges of overcurrent releases and their applicable adjustment (at 40 o C) Dependent Independent I n [A] I r [A] I rm [A] I rm [A] BA511-33 BA511G33 12.5 9.4 12.5 62 125 16 12 16 80 160 20 15 20 100 200 25 18.7 25 125 250 31.5 23.6 31.5 160 315 40 30 40 200 400 50 50 250 500 63 47 63 315 630 80 60 80 400 800 100 75 100 500 1000 125 94 125 625 1250 160 120 160 800 1600 Rated currents versus ambient temperature I n [A] I nϑ [A] + 55 C + 40 C + 20 C - 10 C 12.5 8.6 11.5 9.4 12.5 10.5 13.8 13 15.5 16 11 14.8 12 16 13.2 17.6 16 20 20 14 18.5 15 20 16.5 22 20 25 25 17.3 23 18.7 25 21 28 26 31 31.5 22 29 23.6 31.5 26.4 34.7 32.5 40 40 27.8 37 30 40 33 44 39 50 50 34.6 46 50 41 55 50.5 63 63 43.5 58 47 63 52 69 63 75 80 54 72 60 80 68 91 90 104 100 69 92.5 75 100 83 110 101 125 125 87 115 94 125 104 138 146 168 160 110 148 120 160 132 176 162 200 COLD START COLD START WARM START WARM START 162

BA511*33 - Technical Information SWITCHES 12 14 22 24 32 34 S1 S2 S3 11 21 31 6 8 42 44 S4 41 Specifications Type auxiliary relative Rated operating voltage AC U e [V] 230 230 Rated isolation voltage AC U i [V] 250 250 Rated frequency f n [Hz] 50/60 50/60 Rated operating current AC I e [A]/U e [V] 10 6 Thermal current I th [A] 10 6 Arrangement of contacts 001, 002, 004 01 Connection cross-section S [mm 2 ] 0.5 1 0.5 1 S5 5 Arrangement of contacts Number of contacts Contact types 001 1 change-over 002 2 change-over 004 4 change-over Switch name Switch designation Switch function Relative S5 indicates the switching off of circuit breaker by releases Auxiliary S1, S2, S3, S4 indicates position of main contacts SHUNT TRIPS B2 F2 B1 Fig. 1 - Recommended wiring 12 14 B2 S1 F2 11 B1 OFF Specifications Type Operating voltage AC U e [V] 24, 48, 110, 230, 400, 500 DC U e [V] 24, 48, 110, 220 Rated frequency f n [Hz] 50/60 Input power at 1.1 Ue AC [VA] DC [W] Characteristic 80 90 U 0.7 U e the circuit breaker must trip Loading time [s] 10 - for recommended wiring see fig. 1 UNDERVOLTAGE RELEASES A2 F1 A1 Specifications Type Operational voltage AC U e [V] 24, 48, 110, 230, 400, 500 DC U e [V] 24, 48, 110, 220 Rated frequency f n [Hz] 50/60 Input power at 1.1 Ue AC [VA] DC [W] Characteristic 1) 6 3 U 0.85 U e - circuit-breaker can be switched on U 0.35 U e - the circuit breaker must trip Loading time 1) - switching off of the release may be delayed using the delay unit BZ-BA-X230, for more detailed information, see page 217 163

HAND DRIVES Description The hand drive makes possible to govern the circuit-breaker by rotating the lever, e.g. to switch machines on and off. When a circuit breaker is ordered along with the hand drive, this unit will be installed in the circuit breaker by manufacturer and supplied complete. The hand drive with the so called adjustable lever is provided with an extra supply of an extension shaft and a bearing with an operating lever The hand drive makes it possible to control the circuit breaker: a) from the front panel of the circuit breaker (Fig. 1) - BA511*33-*****86 design - for dimensions, see page 161 b) through the switchgear door (Fig. 2) - BA511*33-*****861 design - for dimensions, see page 161 The hand drive bearing is attached to the switchgear door and provides protection IP55. Fig. 1 - Front hand drive Safety improvement for operators tending to electric equipment Hand drive lever makes it possible to lock up the circuit breaker in position switched off manually by means of three padlocks with the shank diameter up to 6 mm. Fig. 2 - Front hand drive with adjustable lever 164