Job Name: System Reference: SUBMITTL DT: MXZ-4C36NHZ MULTI-INDOOR INVERTER HET-PUMP SYSTEM M-SERIES Date: GENERL FETURES Quiet operation Built-in base pan heater to prevent ice in drain pan M-Net adaptor kits are available as an option* Limited warranty: five years parts and seven years compressors *Included standard in PC-MK30/50BC Branch Box CCESSORIES Three-port Branch Box (PC-MK30BC) Five-port Branch Box (PC-MK50BC) Distribution Pipe for Flare Connection (MSDD-50R; necessary for installing two branch boxes) Distribution Pipe for Brazed Connection (MSDD-50BR; necessary for installing two branch boxes) 3/8" x 1/2" Port dapter (MC-454JP) 1/2" x 3/8" Port dapter (MC-455JP) Outdoor Unit: MXZ-4C36NHZ 1/2" x 5/8" Port dapter (MC-456JP) 1/4" x 3/8" Port dapter (PC-493PI) 3/8" x 5/8" Port dapter (PC-SG76RJ) M-NET dapter (PC-IF01MNT-E) Drain Socket (PC-SH71DS-E) irflow Guide (PC-SH96SG-E) (For data on specific indoor units, see the MXZ-C Technical and Service Manual.) Cooling* (Non-ducted / Ducted) Heating at 47 F* (Non-ducted / Ducted) Heating at 17 F* (Non-ducted/Ducted) 2014 Mitsubishi Electric US, Inc. Specifications Unit Type Model Name MXZ-4C36NHZ Rated Capacity Btu/h 36,000 / 36,000 Capacity Range Btu/h 6,000-36,000 Rated Total Input W 2,5 / 3,180 Rated Capacity Btu/h 45,000 / 45,000 Capacity Range Btu/h 7,200-45,000 Rated Total Input W 3,340 / 4,0 Rated Capacity Btu/h 34,000 / 36,000 Maximum Capacity Btu/h 45,000 / 45,000 Rated Total Input W 3,500 / 4,590 Heating at 5 F* Maximum Capacity Btu/h 45,000 Power Supply Voltage, Phase, Hertz 208 / 230V, 1-Phase, 60 Hz Electrical Requirements Recommended Fuse/Breaker Size 50 MC 42 Voltage Indoor - Outdoor S1-S2 V C 208 / 230 Indoor - Outdoor S2-S3 V DC ± Compressor Hermetic Fan Motor (ECM) F.L.. 0.4+0.4 Sound Pressure Level Cooling 49 db() Heating 53 External Dimensions (H x W x D) In / mm 52-11/16 x 41-11/32 x 13+1 1338 x 1050 x 330+ Net Weight Lbs / kg 276 / 1 External Finish Munsell No. 3Y 7.8/11 Refrigerant Pipe Size O.D. Liquid (High Pressure) 3/8 / 9.52 In / mm Eight Ports Gas (Low Pressure) 5/8 / 15.88 Max. Refrigerant Line Length Ft / m 492 (150) Max. Piping Length for Each Indoor Unit Ft / m 262 (80) Max. Refrigerant Pipe Height If IDU is bove ODU 164 (50) Ft / m Difference If IDU is Below ODU 131 (40) Connection Method Flared/Flared Refrigerant R410 * Rating Conditions per HRI Standard: Cooling Indoor: 80º F (27º C) DB / 67º F (19º C) WB Cooling Outdoor: 95º F (35º C) DB / 75º F (º C) WB Heating at 47ºF Indoor: º F (21º C) DB Heating at 47ºF Outdoor: 47º F (8º C) DB / 43º F (6º C) WB Heating at 17º F Indoor: º F (21º C) DB Heating at 17º F Outdoor: 17º F (-8º C) DB / 15º F (-9º C) WB
SPECIFICTIONS: MXZ-4C36NHZ, contd. Operating Range: Outdoor Cooling D.B 23 to 115 F. [ D.B. 5 to 46 C ]*1 Heating D.B. 13 to F [ D.B. to 21 C ] *1. D.B. 5 to 115 F [ D.B. 15 to 46 C ], when an optional ir Outlet Guide is installed. Energy Efficiencies: Indoor Unit Type SEER EER HSPF COP @ 47 F COP @ 17 F Non-ducted 19.10 14.00 11.30 3.95 2.85 Ducted and Non-ducted 17.45 12.67 10. 3.53 2.58 Ducted 15.80 11.30 10.10 3.10 2.30 Multi-zone Indoor/Outdoor Combination Table MSZ-FH* MSZ-GE* MFZ* MVZ* SEZ-KD* SLZ* PC ()* PL* PED* MXZ-4C36NHZ OK OK OK OK OK OK NO OK, 30, 36 OK * Refer to indoor unit submittal. Notes: Minimum of two Indoor Units must be connected to the MXZ-4C36NHZ. Minimum installed capacity cannot be less than 12,000 Btu/h. System can operate with only one Indoor Unit turned on. May connect to any style indoor unit or combination. Information provided at 208/230V. Refer to the MXZ-C Technical & Service Manual for detailed specifications and additional information per Indoor Unit Combination. Notes: 2014 Mitsubishi Electric US, Inc.
MXZ-4C36NHZ SYSTEM DESIGN Outdoor unit Connectable indoor unit Connectable branch box Rated capacity Cooling (kbtu/h) Heating Refrigerant Capacity Number of units Total system wide capacity Number of units MXZ-4C36NHZ 4HP 36 45 R410 Type 06 to Type 36 Caution: The indoor unit which rated capacity exceeds 36 kbtu/ h (Type 36) can NOT be connected. 2 to 4 units 33 to 130% of outdoor unit capacity (12 to 46.8 kbtu/h) 1 or 2 units Connectable indoor unit lineups (Heat pump inverter type) Wall mounted Ceiling concealed 4-way ceiling cassette Floor standing Multi-position Model type Deluxe Standard Low static pressure Middle static pressure 2 by 2 type Standard Model name MSZ-FE09/12/18N MSZ-FH09/12/15N MSZ-GE06/09/12/15/18/N SEZ-KD09/12/15/18N PED-/30/364 SLZ-K09/12/15N PL-12/18//30/36B4 MFZ-K09/12/18N MVZ-12/18//30/364 06 Capacity class [kbtu/h] 09 12 15 18 30 36 Branch box PC-MK50BC PC-MK30BC Number of branches 5 branches 3 branches Indoor unit that (MX. 5 units) (MX. 3 units) ( can be connected) Note: maximum of 2 branch boxes can be connected to 1 outdoor unit. If Using One Branch Box Flare connection employed (No brazing) Branch Box Combinations Three-port Five-port 1 0 0 1 1 1 2 0 0 2 (Up to 8 IDU) Branch box If Using Two Branch Boxes B B B B B 2 branches pipe (joint) : optional parts Branch box #1 The piping connection size differs according to the type and capacity of indoor units. Match the piping connection size of branch box with indoor unit. If the piping connection size of branch box does not match the piping connection size of indoor unit, use optional different-diameter (deformed) joints to the branch box side. (Connect deformed joint directly to the branch box side.) B B B B B Branch box #2 Installation procedure (2 branches pipe (joint)) Refer to the installation manuals of MSDD-50R-E and MSDD-50BR-E. 2013 Mitsubishi Electric US, Inc.
MXZ-4C36NHZ COOLING ND HETING CPCITY ND CHRCTERISTICS 1. Method for obtaining system cooling and heating capacity: To obtain the system cooling and heating capacity and the electrical characteristics of the outdoor unit, first add up the ratings of all the indoor units connected to the outdoor unit (see table below). For Standard Capacity Diagram, please refer to the MXZ-C Technical & Service Manual. (1) Capacity of indoor unit Model Number for indoor unit (2) Sample calculation 1 Model 06 Model 09 Model 12 Model 15 Model 18 Model Model 30 Model 36 M series 6.0 9.0 12.0 14.0* 1 17.2* 3 15.0* 2 18.0* 4 22.5 P series Model Capacity 12.0 18.0.0 30.0 35.0 SEZ [kbtu/h] 8.1 11.5 14.1 17.2 SLZ 8.4 11.1 15.0 MVZ 12.0 18.0.0 30.0 36.0 * 1 The value is for MSZ-GE15N. * 2 The value is for MSZ-FH15N. * 3 The value is for MSZ-GE/FH18N. * 4 The value is for MSZ-FE18N or MFZ-K18N. 2 1 3 B 2. 2. Method for for obtaining the the heating and and cooling cooling capacity of an of indoor an indoor unit: unit: (1) The capacity of each indoor unit (kw) B o (2) Sample calculation (using the system described above in 4-1-1. (2) ): During cooling: During heating: 2013 Mitsubishi Electric US, Inc.
DIMENSIONS: PC-MK30BC ND PC-MK50BC BRNCH BOXES PC-MK30BC Unit: mm <in> 320 <12-5/8> When installing the conduit. Set the to the inner side of each panel. 20 </32> 58 <2-9/32> 28 <1-3/32> SUSPENSION BOLT : W3/8(M10) REFRIGERNT PIPE FLRED CONNECTION B C LIQUID PIPE 1/4F 1/4F 1/4F 3/8F GS PIPE 3/8F 3/8F 3/8F 5/8F 402 <15-7/8> 5- { 22<7/8> 105 <4-1/8> 48 <1-7/8> 48 <1-7/8> 129 <5-3/32> 12 <1/2> 1/2 inch Conduit 12 <15/32> 15 <19/32> 66 <2-19/32> 17 <21/32> (1:2) 46 <1-13/16> 450 <17-23/32> 208 <8-3/16> CP 91 <3-19/32> 73 <2-7/8> 96 <3-/32> 83 <3-9/32> 87 <3-7/16> 280 <11-1/32> 40 <1-17/32> 5-ELECTRIC WIRE INLET TO M-NET UNIT 1 <6-11/16> 65 <2-9/16> C B B C 111 <4-3/8> TB5 TB2B TB3 TB3C TB3B CP SERVICE PNEL (for LEV.THERMISTOR) CONTROL COVER CONDUIT PLTE PC-MK50BC OCH573 Unit: mm <in> When installing the conduit. Set the to the inner side of each panel. 320 <12-5/8> 20 </32> 58 <2-9/32> 28 <1-3/32> 105 <4-1/8> SUSPENSION BOLT : W3/8(M10) REFRIGERNT PIPE FLRED CONNECTION E TO DOUTDOOR C UNIT B LIQUID PIPE 1/4F 1/4F 1/4F 1/4F 1/4F 3/8F GS PIPE 3/8F 3/8F 3/8F 3/8F 1/2F 5/8F 402 <15-7/8> 12 <1/2> 5- { 22<7/8> 1/2 inch Conduit 12 <15/32> 15 <19/32> 66 <2-19/32> (1:2) 17 <21/32> 48 <1-7/8> 48 <1-7/8> 129 <5-3/32> 1 <6-11/16> 65 <2-9/16> 46 <1-13/16> 67 <2-9/16> 450 <17-23/32> E D C B E D C B 91 <3-19/32> 73 <2-7/8> 96 <3-/32> 83 <3-9/32> 87 <3-7/16> 280 <11-1/32 > 111 <4-3/8> 40 <1-17/32> 5-ELECTRIC WIRE INLET TB5 TB2B TO M-NET UNIT TB3 TB3C TB3E TB3B TB3D SERVICE PNEL (for LEV,THERMISTOR) CONTROL COVER CONDUIT PLTE 2013 Mitsubishi Electric US, Inc.
150mm<5-29/32> 15mm<19/32> 15 <19/32> Service space Front piping hole 60 <2-3/8> 5 <3/16> Front trunking hole ({ 37<1-15/32>Knockout) 92 <3-5/8> 75 <2-15/16> { 92 <3-5/8> 92 <3-5/8> 29 <1-5/32> { 92 <3-5/8> 30 <1-3/16> Max. Right trunking hole ( { 37<1-15/32>Knockout) ( { Knockout) 500 <19-11/16> Handle for moving 500 <19-11/16> 53 <2-3/32> Right piping hole ( { Knockout) Piping Knockout Hole Details *1...Indication of STOP VLVE connection location. 92 <3-5/8> Rear trunking hole FOUNDTION <Foundation bolt height> 92 <3-5/8> 75 <2-15/16> Rear piping hole { 92 > /8 <3-5 ( { 37<1-15/32>Knockout) Handle for moving Side ir Intake 1/2 inch Conduit { 22.2<7/8> Scale 1:5 101.5 <4> 110 <4-11/32> 45 <1-/32> 1 inch Conduit mm<inch> { 34.5<1-23/64> When installing the conduit. Set the to the inner side of each panel. Side ir Intake Handle for moving ( { Knockout) Rear ir Intake 4 PIPING-WIRING DIRECTIONS Piping and wiring connections can be made from 4 directions: FRONT, Right, Rear and Below. 3 FOUNDTION BOLTS 1 Refrigerant GS pipe connection (FLRE){ 15.88 (5/8F) 2 Refrigerant LIQUID pipe connection (FLRE){ 9.52 (3/8F) Example of Notes 1000mm<39-3/8> FREE Please secure the unit firmly with 4 foundation (M10<W3/8>) bolts. (Bolts and washers must be purchased locally.) 5<3/16> 2 SERVICE SPCE 5<3/16> 150 <5-29/32> Dimensions of space needed for service access are shown in the below diagram. 330 <13> 632 <-7/8> 369 <14-17/32> 160 <6-5/16> 362 <14-1/4> 2 <8-27/32> 160 <6-5/16> 160 <6-5/16> 42 <1-21/32> 56 <2-7/32> Drain hole (5-{ 33<1-5/16>) For the branch box power supply For the transmission line Bottom piping hole 2 1 Handle for moving Service panel Ground for the branch box power supply For concentration control Rear piping cover Front piping cover ir intake Ground for the transmission line Ground for concentration control For the power supply Terminal connection From left to right 53 <2-3/32> 33.2 <1-5/16> 0 56 <2-7/32> 2-U Shaped notched holes (Foundation Bolt M10<W3/8>) 2-12 36 Oval holes (Foundation Bolt M10<W3/8>) 2 <8-27/32> 81 <3-3/16> Ground for the power supply ("GR"marking position) 1050 <41-11/32> ir Discharge Installation Feet Rear ir Intake 600 <23-5/8> 417 <16-13/32> 1 FREE SPCE (round the unit) 5<3/16> 73 <2-7/8> 86 <3-3/8> 15mm<19/32> 73 <2-7/8> 27 <1-1/16> 27 <1-1/16> 73 <2-7/8> 27 <1-1/16> 1338 <52-11/16>.7 <31/32> 154 <6-1/16> 136 <5-11/32> 19 <3/4> 3 <14-9/16> 28 <1-3/32> 426 <16-/32> *1 2014 Mitsubishi Electric US, Inc. 1067 <42> FORM# MXZ-4C36NHZ for Multiple Indoor Unit Styles - 201409 510 <20-3/32> *1 The diagram below shows a basic example. Explantion of particular details are given in the installation manuals etc. DIMENSIONS: MXZ-4C36NHZ Unit: mm <in> 1340 Satellite Boulevard Suwanee, G 300 Toll Free: 800-433-4822 www.mehvac.com