Liebert PSA VA. Installer/User Guide

Similar documents
800VA/ 1000VA/ 1200VA/ 1500VA 2200VA/ 3000VA USER S MANUAL

Uninterruptible Power Supply

Liebert PSI XR 1000/1500/2200/3000, 120VAC. User Manual

Back-UPS 650 VA 230 V with AVR (BX650CI-ZA)

USER MANUAL. Uninterruptible Power Supply Line-interactive VCL Series UPS VA

BRAVER UPS. (Uninterruptible Power System) User s Manual

CP900EPFCLCD User s Manual K

User Manual Back-UPS BX650CI-MS 230 Vac with AVR

MM-AVR UPS Series User s Manual

User Manual Digital Energy Uninterruptible Power Supply ML Series UPS VA GE Digital Energy Power Quality

02/15/01. Powerware User s Guide VA.

USER MANUAL. Blazer Vista 1000/1400/2000. Uninterruptible Power System

Eclipse Plus VA UPS and Surge Suppressor User s Manual

User Manual. Digital Energy Uninterruptible Power Supply ML Series UPS VA. GE Digital Energy Power Quality. GE imagination at work

POWERWARE User s Guide VA.

Limousin II User Manual

UPS USER MANUAL F-11 LINE INTERACTIVE UPS GENERAL PURPOSE UPS 650VA/1200VA/2200VA

User Manual. NetGuard IMPORTANT. PSD 650/1200/1600 Line Interactive UPS Uninterruptible Power Supply System. UPS Monitoring Software

Installation and user manual 5SC 500 5SC 750 5SC SC SC 500G 5SC 750G 5SC 1500G ENGLISH. Copyright 2013 EATON All rights reserved.

Extended Battery Cabinet for Nfinity

PR1000ELCD / PR1500ELCD User s Manual

User Manual Easy UPS BV Series 500VA, 650VA, 800VA, 1000VA Safety and General Information

Installation and Operation Back-UPS BX550CI-CN

User Manual Back-UPS BC500-RS, BC650-RS 650 VA 230 V

USER MANUAL. PowerMust 1400/2000 LCD. Uninterruptible Power System

Match 19" GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match 19" UPS.

Uninterruptible Power System. Line Interactive Network Protection Pure Sine Wave Output UPS. Rack Mount Models 1000VA/ 1500VA/ 2000VA/ 3000VA

Powerware Vdc Extended Battery Cabinet User s Guide.

Installation and Operation Manual Back-UPS BR800/1100CI-IN

Liebert GXT3 UPS 230V 700VA-3000VA

Installation Guide Smart-UPS On-Line SRT1000/SRT1500 XLA Tower/Rack-Mount

400 Watt Backup Power System Owner s Manual

USER MANUAL English / Español

USER MANUAL. Power GUARD UPS. Uninterruptible Power System

Uninterruptible Power Supply USER MANUAL Version 1.4. Always On UPS Systems Inc. GES-801L, GES-102L, GES-152L, GES-202L, GES-302L

Informer Compact Series

Thank you for choosing EATON products. Safety information and operating instructions are included in this manual. Do not attempt to operate the UPS

POWER TROLLEY 8 INSTRUCTION MANUAL POWER TROLLEY 8. Model: SINE Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System

Installation and Operation Manual Back-UPS BR1000-CH

Installation and Operation Manual Back-UPS BX800CI-ZA/BX1100CI-ZA

SOS SERIES SOS1 SOS2. Spares On Site Battery Cabinet Installation Guide rEV3

Back-UPS CS Back-UPS CS 350

Back-UPS ES APC Back-UPS ES, 6 outlet 350VA, 120V, without auto shutdown software

Uninterruptible Power Systems. SDU DC Series

Liebert GXT MT+ User Manual VA Installer/User Guide

Home Solar 400 (HS 400) Home Solar 800 (HS 800) Home Backup 400 (HB 400) Home Backup 800 (HB 800) Owner s Manual

Installation and Operation Manual Back-UPS BX1100CI-CN

LIFT 1500 VA UNINTERRUPTIBLE POWER SUPPLY UPS USER MANUAL

1000 Watt Power Inverter INSTRUCTION MANUAL HT87112-AUOXY

Allen-Bradley. User Manual for 3000/5000 VA UPS. Tower/Rack-Mount 3U Uninterruptible Power Supply

User Manual V1.1 OptiFlex 1100 / OptiFlex 2000

Uninterruptible Power Supply ERA LCD 0.65 ERA LCD 0.85 ERA LCD 1.1. User s manual

User s Manual Lineage LI3000 UPS K

3000VA 120/208/230VAC

Liebert PowerSure PSI UPS

1. INTRODUCTION. Features:

Uninterruptible Power System

Installation Guide Smart-UPS On-Line SRT1000/1500 UXI-NCLI, SRT1000/1500 UXI-LI, Tower/Rack-Mount

Allen-Bradley. User Manual for 8000/10000 VA UPS. Tower/Rack-Mount 6U Uninterruptible Power Supply

USER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION SYSTEM DESCRIPTION... 4

Liebert. PSI & PSI-XR 750VA - 3kVA & 1kVA-3kVA High Performance Power Protection for Servers and Networking Equipment

Liebert PowerSure PSI

User s Manual Legend SB825 UPS K

PI1500X Power Inverter User s Manual

LINE INTERACTIVE LONG BACKUP TIME UPS EN-1000 / EN-2000 USER S MANUAL

Liebert GXT4. User Manual 700VA ~ 3000VA (230V)

Power Inverter. User s Manual. Diamond Series CPD1200EILCD

Sola/Hevi-Duty S3K Series Mini-Tower UPS

USER MANUAL. Uninterruptible power supply MODEL: 53965,

Installation and user manual. 5SC 500i 5SC 750i 5SC 1000i 5SC 1500i ENGLISH. Copyright 2013 EATON All rights reserved.

Pulsar Evolution 2200/3000/3000 XL

Nature Power Inverters. Modified Sinewave 1000w/1500w True Sinewave 1000w/2000w. Owner s Manual

FALCON ELECTRIC, INC.

AC Power For Business-Critical Continuity. Liebert PSI XR. User Manual 1000/1500/2200/3000VA, 50/60Hz, 230VAC

Solar Hybrid Power Generating System CPS1200EOH12SC CPS2200EOH24SC CPS3000EOH24SC. User s Manual K01-C

1. INTRODUCTION SYSTEM DESCRIPTION Front Panel CONNECTION AND OPERATION TROUBLESHOOTING...8

User s Manual. Automatic Switch-Mode Battery Charger

U P S. Uninterruptible Power System Unterbrechungsfreie Stromversorgung

Uninterruptible Power System

Nature Power Inverters. True Sinewave Inverter Modified Sinewave Inverter. Owner s Manual

USER MANUAL MPS 1-5KW SERIES

Uninterruptible Power System

UNISTAR SB-NET V 50/60Hz 800VA to 3kVA USER MANUAL

USER S MANUAL ENDURE 500VA ENDURE 750VA ENDURE 1000VA ENDURE 2000VA

230VAC Power Inverter 400W Owner s Manual

USER MANUAL. IPS home inverters with UPS function. IPS home inverter manual

Foreword

3 Uninterruptible Power Systems

ACCUSENSE CHARGE SERIES ON/OFF BOARD FULLY AUTOMATIC BATTERY CHARGER

Industrial On-Line UPS V, 700 VA VA. S4KC Series. Instruction Manual

3 Uninterruptible Power Systems

POWERSTAR INC. Operations / Maintenance Manual Model: PS VA Tower UPS

PROwatt 150 DC to AC Power Inverter. Owner s Guide

MODEL 2602A-12 3 STAGE AUTOMATIC BATTERY CHARGER OWNER S MANUAL SAVE THESE INSTRUCTIONS

SDU 24-BATEM. Instruction Manual. Technical Services External Battery. U.S.A... (800) International (847)

User Manual. English. APC Smart-UPS. 750/1000/1500 VA 100/120/230 Vac 2U Rack-Mount Uninterruptible Power Supply

Inverter User Manual

BT403. A Geno Technology, Inc. (USA) brand name. BT-300 Power Supply. Cat. No. BT

General Precautions. Personnel Precautions

Transcription:

Liebert PSA4 1000 1500 VA Installer/User Guide

Technical Support Site If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures. For additional assistance, visit https://www.vertivco.com/en-us/support/

TABLE OF CONTENTS 1 Liebert PSA4 Overview 5 1.1 Controls and Indicators 6 1.2 Installation 7 1.3 Setup and Start-up 7 1.4 UPS Operation 8 1.5 Alarms 8 1.5.1 On Battery 8 1.5.2 Low Battery Warning 8 1.5.3 Weak/Bad Battery 8 1.5.4 Overload 8 1.5.5 UPS Fault 9 1.6 Troubleshooting 9 1.7 Maintenance and Battery Replacement 9 1.7.1 Battery Charging 9 1.7.2 Precautions 9 1.7.3 Battery Replacement Precaution 10 1.7.4 Information for the Protection of the Environment 10 1.7.5 Battery Replacement Procedure 10 1.7.6 Specifications 12 Appendices 15 Appendix 1: Technical Support 15 Vertiv Liebert PSA4 Installer/User Guide 3

Vertiv Liebert PSA4 Installer/User Guide 4

1 LIEBERT PSA4 OVERVIEW Thank you for purchasing the Liebert PSA4 Uninterruptible Power Supply. It is designed, manufactured, and tested to provide many years of reliable power protection. Please review this manual and the important safety instructions before installing, operating, or maintaining your Liebert PSA4 UPS. CAUTION: Connect the UPS only to a properly grounded/earthed outlet that is protected by an appropriate branch circuit protector (circuit breaker or fuse) that meets national and/or local electrical codes. The Liebert PSA4 should be located near the wall outlet. Do not use extension cords between the wall outlet and the UPS. The Liebert PSA4 is designed for small office and home use only. It is not recommended to be used with life-support equipment or applications. WARNING: Risk of Electric Shock. Observe all cautions and warnings in this manual. Failure to do so may result in serious injury or death. Refer all UPS and battery service to properly trained and qualified service personnel. Do not attempt to service this product yourself beyond the battery replacement procedures. Opening or removing the cover may expose you to lethal voltages within this unit even when it is apparently not operating and the input wiring is disconnected from the electrical source. Never work alone. In case of fire, use a dry chemical fire extinguisher to put out the fire. Using a fluid fire extinguisher may cause electric shock. In the event of an emergency, press and hold the ON/OFF button for at least one (1) second to turn off the UPS then unplug the UPS from the wall outlet. NOTICE: This equipment has been tested and found to comply with the limits for a Class B computing device in accordance with the specifications in Subpart J of Part 15 of FCC Rules and also meets the Class B limits for radio noise emissions from digital apparatus set out in the Radio Interference of the Canadian Department of Communications. These limits are designed to provide reasonable protection against such interference in a residential installation. This equipment generates and uses radio frequency and if not installed and used properly, that is, in strict accordance with the manufacturer's instructions, this equipment may cause interference to radio and television reception. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: Re-orient the receiving antenna. Relocate the computer with respect to the receiver. Move the computer away from the receiver. Shielded communication-interface cables must be used with this product. WARNING: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. Vertiv Liebert PSA4 Installer/User Guide 5

The Liebert PSA4 is shipped with the following items: CD with Liebert MultiLink Shutdown Software and User manual (electronic version) USB cable; one 1.8 m (6 ft.) long Coax cable; one 1 m (3 ft.) long User Manual with warnings safety instructions and WEEE recycling sheet (ISO 14001 compliance) 1.1 Controls and Indicators ITEM DESCRIPTION 1 On/Off button. 2 Scroll button. To scroll through the LCD-display parameters and, when on battery power, silences the audible alarm. 3 Fault LED (red). 4 Battery operation LED (amber). 5 On Utility LED (green). 6 LCD display with icons and: 7 State 1: Load Capacity bar in 20% increments. 8 State 2: Battery Capacity bar in 20% increments. 9 State 3: Numeric information to display UPS operational parameters. 10 Type B USB port for USB communication, monitoring and control. 11 RJ11/45 connectors for phone/fax/modem or network surge protection. 12 Battery-backed and surge-protected output power receptacles. 13 Coax Cable Line In for cable modem, DSS receiver, or cable-tv converter surge protection. Vertiv Liebert PSA4 Installer/User Guide 6

ITEM 14 15 DESCRIPTION Input Circuit Breaker. The input circuit breaker trips if the output load exceeds the UPS's power rating. Coax Cable Line Out for cable modem, DSS receiver, or cable-tv converter surge protection. 16 Input Power Cord. 17 Surge-protected-only output-power receptacles. 1.2 Installation Install the Liebert PSA4 in a temperature-controlled environment that is free of corrosive and conductive contaminants. Avoid locations near heat or water sources and exposed to direct sunlight. For proper ventilation, leave approximately 2 to 4 inches clearance on all sides of the UPS. The UPS unit ships with the internal battery connected. 1.3 Setup and Start-up Inspect the UPS for any signs of obvious damage. If damage is visible, do not proceed with the setup and call our warranty support line for a new replacement unit. The UPS has 4 battery-backed and surge-protected receptacles and 4 surge-protected-only receptacles. Plug your critical equipment (such as computer, monitors, etc.) into the battery-backed receptacles and your less-critical equipment (such as printers and other less-often used peripherals) into the surge-only receptacles. If you also want to protect your computer network connection or telephone, you can use the network/telephone surge-protection ports on the side. Use the IN port to connect the line from the wall jack and the OUT port to connect to your device port. Use of this feature is not required for proper operation of the UPS. If you also want to protect your cable modem, DSS Receiver, or cable-tv converter connection you can use the Coax surge protection ports on the side of the UPS. Use the IN port to connect the line from the wall jack and the OUT port to connect to your device port. Use of this feature is not required for proper operation of the UPS. If you wish to use the USB communications, plug the provided cable into the port on the UPS and the other end into an open USB port on your computer. This allows unattended shutdown of your computer using either the built-in feature within the Microsoft Windows operating system or the Liebert Multilink Shutdown software located on the CD that shipped with the UPS. Use of this feature is not required for proper operation of the UPS. You are now ready to start the UPS. Plug the UPS input cord into the wall outlet. To turn on the UPS, press and hold the ON/OFF button until you hear the UPS beep, then release the button. The connected equipment immediately receives power and the UPS starts a short, self system test (electronics and battery check). When the unit passes all self checks, only the green LED should be lit indicating normal operation. NOTE: While every precaution has been taken to ensure that the battery is in good condition, we recommend allowing the UPS to charge the battery for at least 4 hours prior to providing full back-up time protection for any utility-power abnormality. Vertiv Liebert PSA4 Installer/User Guide 7

1.4 UPS Operation The UPS is designed for easy operation. Once the UPS is plugged into the wall outlet, it begins to charge the battery whether the UPS has been turned on or not. To turn on the UPS, press and hold the ON/OFF button until the unit beeps, then release the button. To turn off the UPS, press and hold the ON/OFF button for at least 1 second then release the button. To completely stop all UPS operation, once the UPS is turned off, unplug the input cord from the wall outlet. During normal operation, the UPS protects the connected equipment from utility abnormalities, such as brownout/sags, over-voltage/surges, and complete outages. During utility sags and surges, the UPS AVR circuits will either Boost or Buck the input voltage to correct the voltage for the connected equipment that is plugged into the battery-backed outlets. During utility outages the UPS automatically draws power from the battery to support the connected equipment that is plugged into the battery-backed outlets. Note that equipment plugged into the surge-only outlets shut down in these conditions. If the utility power problems are long-term, the UPS will eventually shut down because all battery power is exhausted. Once utility power is restored to normal operating parameters for the UPS, it automatically restarts and begins to power the connected equipment and to recharge the battery for the next utility abnormality. 1.5 Alarms 1.5.1 On Battery When the UPS is operating on the batteries, the On Battery LED illuminates and the audible alarm sounds once every 5 seconds. The alarm stops once the UPS returns to the AC normal mode. 1.5.2 Low Battery Warning The UPS sounds 2 beeps every 5 seconds and the On Battery LED blinks on/off when the battery reserve runs low. This condition continues until AC returns or the UPS shuts down from battery exhaustion. 1.5.3 Weak/Bad Battery The UPS automatically tests the battery's condition and, if the battery fails the test because of weak capacity, bad battery, or battery disconnected: The Fault LED flashes on/off The Battery Capacity bar graph may show no segments. The alarm beeps 3 times every 30 seconds until the battery is reconnected or replaced. We recommend that the UPS charge overnight before performing a battery test to confirm a Weak/Bad Battery condition. 1.5.4 Overload When the amount of equipment connected to the UPS exceeds its power rating, the the Load Capacity bar graph is full, the Fault LED flashes on/off, and the UPS sounds 1 beep every half second (AC and Battery modes). The alarm remains on until the excess load is removed or the UPS's self-protection circuit shuts down the UPS. Vertiv Liebert PSA4 Installer/User Guide 8

1.5.5 UPS Fault When the UPS detects a hardware fault, the Fault LED illuminates, the output power turns off, and the UPS sounds a constant alarm. The fault condition, in some instances, may be reset by turning the UPS off and then back on. 1.6 Troubleshooting SYMPTOM POSSIBLE CAUSE WHAT TO DO UPS will not turn on. On/Off/ button not pressed. Press and release the On/Off button to start UPS. UPS operates in battery mode only, even though normal AC power is present. Fault LED is illuminated. The AC mode LED is illuminated, but there is no output. The AC Mode LED is blinking UPS does not provide expected runtime. Battery Capacity bar graph is flashing on and off. Load Capacity bar graph is flashing on and off. Input AC circuit breaker is tripped. UPS has detected an internal fault. The UPS is being controlled via its communications port. The UPS is in buck or boost operating mode. The batteries may be weak or at the end of useful service life. Loose connections at the batteries, Weak batteries, Bad batteries. The load has exceeded the UPS's capacity. Reset circuit breaker by pressing the plunger back in. If the AC circuit breaker trips after UPS starts up, reduce the load on the UPS. Call for a replacement unit. Disconnect the computer cable from the UPS and press the On button. If UPS works normally, the software has control of the UPS. If the UPS still does not have output power, call for service. The UPS is operating normally, correcting abnormal input power. Charge the batteries for 8-hours and retest. If the run time is still less than expected, the batteries may need replaced, even though the Weak/ Bad Battery alarm is not sounding. Check battery connections, charge the batteries for 8-hours, replace the batteries. Check the "Specifications" on page 12 table that follows. Remove part of the load. 1.7 Maintenance and Battery Replacement 1.7.1 Battery Charging The batteries are valve-regulated, non-spill-able, lead acid and should be kept charged to attain their design life. The Liebert PSA4 charges the batteries continuously when it is connected to the utility input power. If the Liebert PSA4 will be stored for a long time, we recommend connecting the UPS to input power for at least 24 hours every 4 to 6 months to ensure full recharge of the batteries. 1.7.2 Precautions Although the Liebert PSA4 is designed and manufactured to ensure personal safety, improper use can result in electrical shock or fire. To ensure safety, observe the following precautions: Turn off and unplug the UPS before cleaning it. Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners. Never block or insert any objects into the ventilation holes or other openings of the UPS. Do not place the UPS power cord where it might be damaged. Vertiv Liebert PSA4 Installer/User Guide 9

1.7.3 Battery Replacement Precaution Before proceeding, please review the battery safety precautions. WARNING: Risk of electric shock and explosion. Can cause equipment damage, injury and death. Do not dispose of the battery in a fire. The battery may explode. Do not open or damage the battery. Released electrolyte is toxic and is harmful to skin and eyes. If electrolyte comes into contact with the skin, wash the affected area immediately with plenty of clean water and get medical attention. WARNING: Risk of electric shock. Can cause equipment damage, injury and death. A battery can present a risk of electrical shock and high short-circuit current. The following precautions should be observed when working on batteries: - Remove watches, rings and other metal objects. - Use tools with insulated handles.wear rubber gloves and boots. - Do not lay tools or metal parts on top of batteries. - Disconnect charging source prior to connecting or disconnecting battery terminals. - Determine if the battery is inadvertently grounded. If it is inadvertently grounded, remove the source of the ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if grounds are removed during installation and maintenance (applicable to a UPS and a remote battery supply not having a grounded supply circuit). 1.7.4 Information for the Protection of the Environment UPS SERVICING - This UPS makes use of components dangerous for the environment (electronic cards, electronic components). The components removed must be taken to specialized collection and disposal centers. NOTICE TO ALL CUSTOMERS: DISPOSAL OF OLD APPLIANCES - This product has been supplied from an environmentally aware manufacturer that complies with the Waste Electrical and Electronic Equipment (WEEE) Directive 2002/96/CE. The crossed-out wheelie bin & recycle symbol is placed on this product to encourage you to recycle wherever possible. Please be environmentally responsible and recycle this product through your recycling facility at its end of life. Do not dispose of this product as unsorted municipal waste. Follow local municipal waste ordinances for proper disposal provisions to reduce the environmental impact of waste electrical and electronic equipment (WEEE). 1.7.5 Battery Replacement Procedure 1. Turn the UPS on its side. 2. Remove and set aside the two battery-compartment retaining screws (item 1). 3. Slide the battery compartment cover outward and lift-off to expose the battery (item 2). 4. Grasp the battery and gently pull it out far enough to disconnect the battery wires. 5. Disconnect the battery positive (Red) wire and the battery negative (Black) wire. (item 3). 6. Remove the battery and set aside. Vertiv Liebert PSA4 Installer/User Guide 10

7. Orient the new battery in the same direction as the original battery and place the new battery close enough to connect the battery wires. NOTE: Replace the battery with the same type and number as originally installed. 8. Connect the battery negative (Black) wire to the battery negative terminal. 9. Connect the battery positive (Red) wire to the battery positive terminal. NOTE: When connecting the last wire to the battery, there can be a small spark, this is normal. 10. Fully insert the new battery into the UPS and re-install the battery compartment cover (item 4). 11. Re-install the battery compartment retaining screw (item 5). 12. Properly dispose of the old batteries at an appropriate recycling facility or return them to Vertiv in the packing material for the new batteries. 13. The UPS is now ready for normal operation. Vertiv Liebert PSA4 Installer/User Guide 11

1.7.6 Specifications Table 1.1 System Specifications MODEL NUMBER PSA4-1000MT120 PSA4-1500MT120 Capacity (VA / W) 1000 / 600 1500 / 900 Unit Dimensions, in. (mm) W x D x H 3.43 x 15.1 x 10.6 (87 x 384 x 270) Unit Weight, lbs (kg) 28.7 (13.0) 30.2 (13.7) Shipping Dimensions, in. (mm) W x D x H 6.9 x 19.4 x 15.2 (175 x 494 x 385) Shipping Weight, lbs (kg) 33.7 (15.3) 33.9 (15.4) Input AC Nominal Voltage Voltage Range Frequency Range Protection Surge Energy Rating 120 VAC 90-150 VAC 50 or 60 Hz, ±5 Hz, auto-sensing Resettable Circuit Breaker 320 Joules Input Cord 6 ft. attached with NEMA 5-15P Output AC (On Utility) Nominal Voltage Voltage Range Frequency Range Efficiency 120 VAC 101-133 VAC 50 or 60 Hz, ±5 Hz, auto-sensing >90% at full load Output AC (On Battery) Nominal Voltage 120 VAC Voltage Range Nominal ±6% Frequency Range 50 or 60 Hz, ±1% Waveform Transfer Time Overload Capacity Protection PWM Simulated Sine wave 6 ms, typical 110% for 10 seconds, 120% immediate shutdown Electronic (over current, short circuit w/ latching shutdown) Backup Time (Full Load / Half Load), min 3 / 12 2 / 9 Battery Type Valve Regulated Lead Acid (VRLA) Battery Manufacturer / Model CSB / GP Leoch / DJW12-7.0 CSB / HRW Leoch / DJW12-9.0 Battery Quantity x VDC x Ah 2 x 12V x 7.0 / 7.2Ah 2 x 12V x 9.0Ah Battery Backed Outlets (4) NEMA 5-15R Surge Only Outlets (4) NEMA 5-15R Vertiv Liebert PSA4 Installer/User Guide 12

Table 1.1 System Specifications Environmental Requirements MODEL NUMBER PSA4-1000MT120 PSA4-1500MT120 Operating Temperature, deg(degc) Operating Elevation, feet (meter) Operating Temperature, degf (degc) Operating Elevation, feet (meter) Relative Humidity 32-104 (0-40) without derating 0-4,921 (0-1,500) without derating 32-95 (0-35) without derating 4,922-9,842 (1,500.5-3,000) without derating 0-95% non-condensing Storage Temperature, degf (degc) 5 to 113 ( 15 to 45) Storage Elevation, feet (meter) 0-49,212 (0-15,000) Audible Noise <40 dba @ 3 ft (1 m) from all sides Agency Safety RFI / EMI Surge Immunity Transportation FCC Subpart J, Class B ANSI 62.41 (IEC 62040-2 2nd Edition) ISTA Procedure 1A Vertiv Liebert PSA4 Installer/User Guide 13

This page intentionally left blank. Vertiv Liebert PSA4 Installer/User Guide 14

APPENDICES Appendix 1: Technical Support Our Technical Support staff is ready to assist you with any installation or operating issues you may encounter with your Liebert product. Please call or e-mail us: Technical support: Monitoring support: Warranty support: e: liebert.upstech@vertivco.com p: 1-800-222-5877 menu option 1 e: liebert.monitoring@vertivco.com p: 1-800-222-5877 menu option 2 e: microups.warranty@vertivco.com p: 1-800-222-5877 menu option 3 Vertiv Liebert PSA4 Installer/User Guide 15

This page intentionally left blank. Vertiv Liebert PSA4 Installer/User Guide 16

VertivCo.com Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA 2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice. SL-23304_REV2_3-17/590-1414-501C