EDB6032_G/GB Antriebstechnik. Operating Instructions. Brake chopper 6032/6033/6034

Similar documents
EDBMB935X.;p] Ä.;p]ä. Operating Instructions. EMB9351 E, EMB9352 E, EMB9351 C, EMB9352 C Braking unit

Brake Chopper BC BC 4.1. Instruction and Operation Manual

Operating Manual (Edition 04/2004) sinamics. Braking Module / Braking Resistor SINAMICS G130

Aurora Wind Interface Box

DC-PMM/24V Power Management Modul für Positionier-Motor POSMO A Power Management Module for Positioning Motor POSMO A

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

Appendix: Safety and application notes for... 15

Appendix: Safety and application notes for 19

High Frequency SineWave Guardian TM

Instruction Manual. Harmonic Filter AHF 005/010. Drives Solutions

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

Accessories for Wind Power Inverter WINDY BOY PROTECTION BOX 400 / 500 / 600

SINAMICS G130. Motor reactors. Operating Instructions 05/2010 SINAMICS

For regenerative operation, the MOVIPRO is connected to an external braking resistor.

Data Bulletin. ALTIVAR FLEX58 Chassis Drive Controllers Class 8806 INTRODUCTION DESIGN CONCEPT. Bulletin No. 8806DB0102 August 2001 Raleigh, NC, USA

user's manual nx frequency converters brake resistors

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

PowerOhm Installation Manual for BM R Series Braking Modules

Braking Module / braking resistor SINAMICS. SINAMICS G130 Braking Module / braking resistor. Safety information 1. General. Mechanical installation

EPS/ELA-Series User Manual EPS/ELA 250W

Technical Manual Electrical Power Supply System T4002

SOLSTART Instruction Manual

PowerOhm Installation Manual for BM R Series Braking Modules

ABB component drives ACS150, 0.5 to 5 Hp

SINAMICS. SINAMICS G130 Braking Module / braking resistor. Safety information 1. General. Mechanical installation. Connection 4

Presentation Soft starters 0 Altistart 48 soft start - soft stop units

PowerOhm Installation Manual for LG ATV Series Braking Modules

Installation and Start-up Guide. ACS-BRK Brake Units

Braking Devices BR 230/ Assembly- and Commissioning Instructions

Ucontrol. 1 Data sheet. Multipurpose controllers for variable voltage 3 ~ fans PXDM Examples of application. 1.2 Equipment / Function

ABB machinery drives. Application guide Common DC system for ACS380 drives

SINUS K 13. ACCESSORIES Braking resistors APPLICATION TABLES 78/160 INSTALLATION INSTRUCTIONS

Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4. Braking Resistor Units 3G3IV-PCDBR2 B/4 B. Braking Units

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER

Varispeed E7. Varispeed E7. Varispeed. Varispeed E7. Varispeed E7. Varispeed E7 INVERTER SERIES

MCW Application Notes 24 th August 2017

LINEAR LED DRIVERS. ComfortLine Selectable Current (Output Terminal) ComfortLine SELECTABLE CURRENT (OUTPUT TERMINAL)

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Application Note CTAN #127

Solar Controller SUNGO S

Braking Unit for Frequency Inverter Serie 3CV V 18,5 bis 55kW

MaxPak Plus Analog DC V S Drive

Instruction Manual. Q Series 2 Motor Control Modules - OEM

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

DBR3, 4500W, 9R, TS - BRAKING RESISTOR

PKP Prozessmesstechnik GmbH Borsigstraße 24 D Wiesbaden-Nordenstadt Tel.: ++49-(0) Fax: ++49-(0)

High performance Vector Control. Ratings. System configuration

Miniature Circuit-Breakers (MCBs)

HIB Enclosed Inverter User Guide

Special voltages: Voltage >500 V AC are only permissible with external control box. 3-phase AC Voltages/frequencies. 1-phase AC Voltages/frequencies

TDBU Series Dynamic brake unit user manual

vacon nx ac drives brake resistors user manual

LED Driver Linear / area dimming industry. Driver LC 150W mA IND sl EXC EXCITE series

Quick guide. Plug-in fans GPPM with FC101_106 August 2014

16-Channel Digital Output Termination Card Introduced Power 24Vdc

Low voltage AC drives

Switching DC Power Supply

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

RVS-AX Instruction Manual

1 potential-free change-over contact (max. 24 V DC/1 A) for SIL collective failure signal SIL functions - safety functions Standard: Safe ESD

Emergency lighting units EM powerled

825-P Modular Protection System for motors Specification Guide

ABB Component Drives ACS150, 0.5 to 5 Hp

Braking unit Option Instruction Manual PB7-4132K

LED Driver Compact fixed output

LED Driver Compact fixed output

TA-05/C. Instruction and Operation Manual. valid for art.-no.: F-TA-05/C-ISO. (start at modification No. 1601)

Electronic Ballast EVG 2000-T

LED Driver Linear / area fixed output industry. Driver LCI 65W 150mA 400mA TOP INDUSTRY sl TOP series

The smd frequency inverter Compact, powerful, without compromise simply smart

LED Driver Linear / area fixed output industry. Driver LCI 100W 350mA 900mA TOP INDUSTRY sl TOP series

Capacitor Switching Contactors Type K3...-A, K3...-K

Open Chassis Star-Delta Starter User Guide

Emergency lighting units EM powerled

POWER kva

LED Driver Linear / area fixed output

SDC,Inc. SCR-Regenerative Ac Drive

B115...B180 RF200 RFN200 B250...B400 RF400 RFN400

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Filtered PWM Speed Control for Permanent Magnet DC Motors

Emergency lighting units EM series. EM PRO EZ-3, V PRO version

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

J1000. Compact Inverter Series.

APPLICATION NOTE AN-ODP March 2009

SmartVFD HVAC FEATURES APPLICATION SPECIFICATION DATA

multicond Power capacitors Data sheet: multicond

KNC-SRV-FD123-CA-000 Series Servo Driver

RE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & 6kW

Drive System Application

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD

Low voltage AC drives. ABB component drives ACS to 2.2 kw / 0.25 to 3 hp Catalog

Parker AC10 Frequency Inverter (to 22kW) Easy Start Guide

Plug-in relays Mini ISO relays

POWER kva Nominal output power (Cos φ0,8) kva Nominal output power (Cos φ1,0) kw >88 Efficiency (AC AC)

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN

3946 en / a. This manual is to be given to. the end user. HPM x44. A.C. motor. Installation and maintenance

Transcription:

EDB6032_G/GB 00376698 Antriebstechnik Operating Instructions Brake chopper 6032/6033/6034

These operating instructions are valid for the devices with the nameplate data: 6032_G.2E 6033_G.2E 6034_G.1A Type Built-in device IP00 Hardware version + index Corrected edition of: 09.01.1995 Date of print: 16.01.1995

How to use these Operating Instructions... To locate information on specific topics, simply refer to the table of contents at the beginning of these Operating Instructions. These Operating Instructions use a series of different symbols to provide quick reference and to highlight important items. This symbol refers to items of information intended to facilitate operation. Notes which should be observed to avoid possible damage to or destruction of equipment. Notes which should be observed to avoid health risks to the operating personnel. 1

Safety information The equipment described is intended for use in industrial drive systems. This equipment can endanger life through rotating machinery and high voltages, therefore it is essential that guards for both electrical and mechanical parts are not removed. The following points should be observed for the safety of the personnel: Only qualified personnel familiar with the equipment are permitted to install, operate and maintain the devices System documentation must be available and observed at all times. All non-qualified personnel must be kept at a safe distance from the equipment. The system must be installed in accordance with local regulations. A qualified person is someone who is familiar with all safety notes and established safety practices, with the installation, operation and maintenance of this equipment and the hazards involved. For more detailed definitions see IEC 364. These safety notes do not represent a complete list of the steps necessary to ensure safe operation of the equipment. For further information, please contact your nearest Lenze representative. The information given in these Operating Instructions only apply to the hardware and software versions that are indicated on the cover page. If the version of your equipment is not listed these Operating Instructions must not be used. Lenze cannot be held responsible for any malfunction resulting from the above. The specifications, processes and circuitry described in these Operating Instructions are for guidance only and must be adapted to your own specific applications. Lenze does not guarantee the suitability of the processes and circuitry described in these Operating Instructions for individual applications. The specifications in these Operating Instructions describe the features of the products without guarantee. Lenze personnel have carefully checked these Operating Instructions and the equipment described, but cannot be held responsible for its accuracy. 2

Content 1. Features 4 1.1. Scope of delivery 4 2. Technical data 4 3. Dimensions and installation 5 3.1. Installation of brake choppers 5 3.2. Dimensions 5 4. Selection of the brake resistors 6 4.1. Selection tables for brake resistors 7 4.2. Dimensions of brake resistors 8 4.2.1. Resistor with integrated temperature monitoring (50 to 200W) 8 4.2.2. Screened wire-wound resistors equipped with integrated temperature monitoring (300 and 600W) 8 4.3. Brake chopper connection 9 4.3.1. Brake chopper 6032G with frequency inverters 8201-8204 9 4.3.2. Brake choppers 6033G and 6034G with frequency inverters 8211-8216 10 5. Operation 11 5.1. Parallel connection of brake choppers 11 6. Accessories 11 3

1. Features The brake choppers 6032, 6033 und 6034 are additional components for frequency inverters with DC bus. In generator mode, e.g. during deceleration of the drive, the machine feeds back energy into the DC bus of the controller. If, as a result, the DC bus voltage exceeds the maximum permissible value, pulse inhibit will be set and "Overvoltage" will be displayed. As soon as the voltage falls below this maximum permissible value, the controller will be enabled again. Enclosure IP00 for cabinet assembly Assembly on DIN rails, alternatively assembly on module resistors Dissipation of brake energy in form of heat Very short brake times possible If not defined, the controller will not set pulse inhibit during braking 1.1. Scope of delivery Brake chopper Snap-on assembly kit for DIN rails Operating Instructions 2. Technical data Brake chopper 6032_G 6033_G 6034_G Order no. 33.6032_G 33.6033_G 33.6034_G Article no. 340 917 340 918 366 190 Supply voltage Switching threshold Permanent brake power Peak brake power Max. brake enery Smallest brake resistor 270-380VDC 375VDC 1.5kW 3.0kW 60kWs 47Ω 470-660VDC 650VDC 2.6kW 5.1kW 100kWs 82Ω Temperature range 0-45 C Storage temperature -20 C to +70 C Humidity Humidity class G to DIN 40040 max. 85%, no condensation 520-730VDC 725VDC 2.6kW 5.1kW 100kWs 100Ω The following brake chopper types are available: 6032G: For frequency inverters with single-phase mains connection (Vrated 230V ) e.g. 8201-8204. 6033G: For frequency inverters with three-phase mains connection (Vrated 400V ) e.g. B. 8211-8216. 6034G: For frequency inverters with three-phase mains connection (Vrated 460V for application in e.g. USA) e.g. 8211-8215. 4

3. Dimensions and installation 3.1. Installation of brake choppers The housing must be assembled vertically, terminals at the bottom. To ensure the unimpeded cooling air circulation, a free space of 100 at the top and the bottom is required. The ambient temperature may not exceed +45 C. 3.2. Dimensions Dimension of the brake chopper: Brake Chopper g ON b d 630 a e Brake chopper Type a b d e g 6032_G 6033_G 45 109 95 127 4.5 6034_G 5

4. Selection of the brake resistors The resistance is calculated as follows: Resistance [ Ω] = (Threshold) 2 [V] 2 required peak power [W] The value may not fall below the minimum resistance of the brake chopper. Otherwise, the unit might be destroyed. After having calculated the resistance, determine the rated power of the brake resistor for cyclic braking operation. For most applications, the brake time remains under 15s. In cyclic braking operations, the relative ON period does not exceed max. 10%. Rated power [W] = ON period [s] required peak brake power [W] Cycle time [s] For single or cyclic braking operations the heat capacity of the brake resistor is calculated as follows: Heat capacity kws = ON period s required peak brake power W To avoid a thermal overload of the resistor, the heat capacity of the brake resistor must be considered (if necessary please contact the manufacturer). Brake resistors may reach surface temperatures of up to 350 C. Therefore the resistors mentioned above are equipped with temperature monitoring. When using other brake resistors, an appropriate overcurrent/overtemperature protection, e.g. thermal overcurrent sensors, must be provided. The thermostats of the brake resistors should be used to disconnect the inverter from the mains in case of overheating (see pages 9 and 10). 6

4.1. Selection tables for brake resistors Selection table for frequency inverters with a mains voltage of 190...260V (6032G): Rated motor Brake resistor power/kw Resistance/Ω Continuous power/w Order no. Article no. 0.37 470 50 ERBM470R050W 360115 0.75 200 100 ERBM200R100W 360114 1.5 100 150 ERBM100R150W 360113 2.2 82 200 ERBM082R200W 360112 Selection table for frequency inverters with a mains voltage of 330...450V (6033G): Rated motor Brake resistor power/kw Resistance/Ω Continuous power/w Order no. Article no.. 0.75 470 100 ERBM470R050W 361839 1.5 370 150 ERBM370R150W 357872 2.2 240 200 ERBM240R200W 357874 3.0 180 300 ERBD180R300W 357875 4.0 100 600 ERBD100R600W 357876 5.5 82 600 ERBD082R600W 365902 Selection table for frequency inverters with a mains voltage of 370...510V (6034G): Rated motor Brake resistor power/kw Resistance/Ω Continuous power/w Order no. Article no.. 0.75 470 100 ERBM470R050W 361839 1.5 370 150 ERBM370R150W 357872 2.2 240 200 ERBM240R200W 357874 3.0 180 300 ERBD180R300W 357875 4.0 100 600 ERBD100R600W 357876 All brake resistors are equipped with integrated temperature protection which must be used as safety protection (see pages 9 and 10). When using other brake resistors, appropriate overcurrent/overtemperature protection, e.g. thermal overcurrent sensors etc. must be provided. 7

4.2. Dimensions of brake resistors 4.2.1. Resistor with integrated temperature monitoring (50 to 200W) e g c a k d b P/W R/Ω Order no. a 50 470 ERBM470R050W 60 240 50 225 60 5 7.5 100 470 ERBM470R100W 70 240 50 225 60 5 7.5 100 200 ERBM200R100W 80 160 70 145 95 5 7.5 150 370 ERBM370R150W 80 240 70 225 95 5 7.5 150 100 ERBM100R150W 80 240 70 225 95 5 7.5 200 240 ERBM240R200W 80 340 70 325 70 5 7.5 200 82 ERBM082R200W 80 340 70 325 70 5 7.5 b c d e g k 4.2.2. Screened wire-wound resistors equipped with integrated temperature monitoring (300 and 600W) e g d b f c a P/W R/Ω Order no. a 300 180 ERBD180R300W 479 89 430 64 115 326 13 600 100 ERBM100R600W 579 89 530 64 115 426 13 600 82 ERBM082R600W 579 89 530 64 115 426 13 b c d e f k 8

4.3. Brake chopper connection 4.3.1. Brake chopper 6032G with frequency inverters 8201-8204 L1 N PE Off K1 On The cross section of the PE connection must be at least as large as the cross section of the power connection. Cable protection ϑ RB K1 Mains contactor K1 Mains choke Operation of 8204E only with assigned mains choke Filter Mains filter Brake resistor RB L1 N PE and screen connections at inverter +UG -UG 8201E to 8204E RB1RB2 +UG -UG 6032G U V W Brake chopper Motor choke / motor voltage filter PE M 3~ Caution! All power terminals remain live up to 3 minutes after mains disconnection Screened cables and mains filter are required for radio interference suppression to EN 55011. Level A or B Terminal bus in control cabinet For group drives a motor protection relay is necessary. PTC thermistors or thermostats are recoended for temperature monitoring Motor interconnection: at 230/400V 9

4.3.2. Brake choppers 6033G and 6034G with frequency inverters 8211-8216 L1 L2 L3 N PE Off The cross section of the PE has to be at least as large as the cross section of the power connection On K1 ϑ RB K1 Cable protection fuse K1 K1 K1 Mains contactor Mains choke Operation of 8214E and 8218E only with assigned mains choke Filter Mains filter Brake resistor PE and screen connection at inverter RB L1 L2 L3 +UG -UG 8211E to 8218E RB1 RB2 +UG -UG 6033G 6034G Brake chopper Motor choke / motor voltage filter U V W Caution! All power terminals remain live up to 3 minutes after mains disconnection Screened cables and mains filters are required for radio interference suppression to EN 55011. Terminal bus in control cabinet PE M 3~ For group drives a motor protection relay is necessary. PTC thermistors or thermostats are recoended for temperature monitoring Motor interconnection: Y at 230/400V at 400/690V 10

5. Operation It is absolutely necessary to check the connection of the terminals +UG and -UG. Incorrect connection may cause destruction of the brake chopper and the frequency inverter. In case of mains overvoltage the brake chopper may be activated. When using resistors without overload protection the resistor may be destroyed. Therefore, only resistors equipped with integrated or external temperature monitoring must be fitted. All brake resistors recoended by Lenze are equipped with an integrated temperature monitoring. Due to the application of the brake chopper, the inverter exactly follows the prograed deceleration time. However, if the feedback power exceeds the peak power of the assigned brake resistor, the inverter will be inhibited and will display "Overvoltage". This results in an uncontrolled prolongation of the deceleration time. To overcome this problem, you must either prolong the Tif time or, if possible, select a lower-value brake resistor. LED ON (yellow) indicates the release of the brake chopper. 5.1. Parallel connection of brake choppers With high brake powers it may be necessary to reduce the brake resistance to the minimum permissible value (see table page 7). If this is not enough, two brake choppers can be connected to double the peak power. In this case, please note the following: Each brake chopper must be separately connected to +UG and -UG of the frequency inverter. Each brake chopper must be connected to a separate brake resistor (terminals RB1 and RB2). The thermostats of the brake resistors (break contacts) must be connected in series. The lowest resistance must not be smaller than the one indicated in the Technical Data of the specific brake chopper. 6. Accessories The brake chopper can also be assembled on module resistors by means of an assembly kit. This kit can be ordered under the order no. ER00370969. 11

12