Product manual cable glands type IR and IB. INDEX ELEKTRO BV Harregatplein VP Zuidland Netherlands

Similar documents
OPERATING INSTRUCTIONS

Operating Instructions

Operating Instructions

ABG Cable Glands Installation Procedure

Explosion protected terminal boxes type, GHG 72.

Armoured / Un-armoured Cable Gland

The safety you rely on.

Operating Instructions

Floodlight Series 6121

ILED Aquarius Illuminated Windsock. User Manual

EX CABLE GLANDS FOR HAZARDOUS AREAS ATEX & IECEX. Zones 1, 2, 21 and 22.

USER MANUAL FOR THE BULKHEAD LIGHT FITTING, TYPE /..

Linear Luminaire for Fluorescent Lamps Series ECOLUX METAL 6010/1

Ex m Solenoid Operator Type 0519

ADE 4F. > For armoured cable > IP68. > Compliance. > EX Performance. > Nickel plated brass and stainless steel

ILED Dorado. User Manual

ADE 6F ADE 6F. page 46

Linear luminaire with LED Series EXLUX 6002

Terminal Boxes in Stainless Steel SLS**.T

Zone 1 Linear Range - Installation Guide

Capri ADE 6F - for Armoured Cable

Linear Luminaire with LED Series EXLUX 6002

IS1 I/O-Modules. BusRail Series General Information. Symbols. Conformity to Standards. Safety instructions. Function/Characteristics

VALIADIS S.A. HELLENIC MOTORS

SPOOL VALVES solenoid air operated 1/4 to 1/2 tapped body and NAMUR for integrated pilot

Terminal Boxes Series 8125

Proportional pressure reducing valves type DHRZO and DHRZA standard and ex-proof version, direct operated, ISO 4401 size 06

ALUMINIUM AND STAINLESS STEEL ENCLOSURES - EJB... SERIES

Appleton s ATX product line includes a wide selection of both Increased Safety and Flameproof cable glands for use with unarmored and armored cable.

Wellglass fittings EVH, EVX Wellglass fitting all zones - zones 1, 2, 21 & 22

Operating Instructions

Ex-proof proportional relief valves Direct or pilot operated, without transducer - ATEX, IECEx, EAC or CULUS

Position Switches Series 8060/2

Leading the way in hazardous areas Features EATON

Linear Luminaire with LED Series EXLUX 6002/2 Version IIC

Linear Luminaire for Fluorescent Lamps Series EXLUX 6401

Floodlight Range Installation Guide

Installation Guidelines For BW Gland

Emergency Light Fitting for Fluorescent Lamps Series 6009

EVZ Series (Small body) Explosion protected luminaire Operating Instructions

Position Switches Series 8070/2

INSTRUCTION MANUAL (ATEX / IECEx)

Tubular fittings Tubular fluorescent fitting with automatic switch off XFP - Zones 1, 2 & 21, 22

HTSB system System overview

Emergency Luminaire with LED Series EXLUX 6009/1 Version IIC

Linear fittings EVDL LED fitting - zones 21, & 22

Emergency Luminaire with LED Series EXLUX 6409/1

STAINLESS STEEL PANEL MOUNT

INSTALLATION RULES for SCS/SENSOR Pt100

2.4. Ex-Emergency light fittings with a self-contained battery system for fluorescent lamps

Floodlight LED Series 6525

Position Switches Series 8074/2

Linear Luminaire with LED Series EXLUX 6402/2

Solutions Ex d IIB+H2, Stainless Steel EJBX*

Tubular fittings Tubular fluorescent fitting XFF - Zones 1, 2 & 21, 22

Operating Instructions Mechanical Temperature Switches ML1H,MT1H,L2H,T2H,L1X/L1X-EX,T1X/T1X-EX,T2X/T2X-EX

CCAI, CCAIF, CCAIF..H

INSTRUCTION MANUAL (ATEX / IECEx)

Terminal Boxes Series 8252/1

JBEP Series Fiberglass Reinforced Polyester Terminal Junction Boxes for Instrumentation Applications Increased Safety. Factory Drilled and Equipped

Operating Instructions

Floodlight LED Series 6125

FHL. Ex d. Body in aluminium

Versions. Version with K VS Version with K VS 2.0. Fig. 1: Type 3967 Solenoid Valve

Linear Luminaire for Fluorescent Lamps

Assembly. Trunk IN + - S U, I U, I. Spur 1

K Series 3 Way Direct Acting Balanced Poppet Solenoid Valve

System 6000 Electropneumatic Converter for Direct Current Signals Type 6116 i/p Converter

Certificate of Conformity

Certificate of Conformity

Spring loaded resistance thermometer

Floodlight LED Series 6525

Solutions Ex d IIB+H2, Aluminum and Stainless Steel

1.4. Ex-Searchlight series SEB 8.., SEB 9.. and SEB 10. (Zone 1, 2, 21, 22) Search and working light

New products Ex Equipment 2015

ATEX CABLE GLANDS.

Number Size Gasket A1 Gasket A2 Gasket A3 Gasket A4 Gasket A5 Metric B - C

2.2. Ex-Linear LED light fittings. ellk/m 92 LED 400/800 / ellk/m 92 LED 400/800 V-CG-S / NE / NIB-HT / NIB-CSA (Zone 1, 2, 21, 22)

EStrong-series Emergency Stop

Compact Sheet-Steel Light Fittings Series 6114/1

Linear Luminaire with LED

SynergEX Panelboards. Installation & Maintenance Information IF Panelboards for Hazardous Locations SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

5.1. GHG 26 / EXKO 2.. Ex-Safety Switches Rated current from 10 A A

Linear Luminaire for Fluorescent Lamps Series ECOLUX 6600

J: Emergency lighting (optional) L: pole type X: ceiling type Mounting

2000 Series Flameproof Xenon and Fluorescent Beacons Installation and Service Instructions

Linear Luminaire for Fluorescent Lamps Series EXLUX 6001

USER MANUAL FOR EXPLOSION PROOF FLOODLIGHT tip RLF/

SOLENOID VALVES no voltage release (tamperproof) manual reset construction 1/4

Label Information: FPS75 FPS80 Cranking Warning Label

Level limit switch Series CN 4000 Selection list. Specifications 2. Applications 4

Floodlight Series 6521/4

Light Fitting for Fluorescent Lamps Series ECOLUX 6600

Pendant Light Fitting IEC

L: pole type. X: ceiling type. Lamp number Lamp wattage(w) Explosion-proof light fittings for fluorescent lamp BAY51-18 x 1L

GuaRdboX - Gd series IOM (Installation, Operation & Maintenance Manual) 0100-ENG rev.4

Compact Sheet-steel Emergency Light Fitting Series 6118/1

Type 3768 Inductive Limit Switch. Mounting and Operating Instructions EB 8356 EN

Amphenol Cable Glands and Cord Grips Amphenol

Linear fittings EVS fluorescent fitting with easy disconnect - zones 1, 2, 21 & 22

Transcription:

Product manual cable glands type IR and IB INDEX ELEKTRO BV Harregatplein 15 3214 VP Zuidland Netherlands T. +31(0)181 452120 http/www.indexelektro.nl email info@indexelektro.nl

Purpose of these instructions - Working in hazardous areas, the safety of personnel and plant depends on complying with all relevant safety regulations. - Assembly and maintenance staff working on installations therefore have a particular responsibility. They require precise knowledge of the applicable standards and regulations. - These instructions give a brief summary of the most important safety measures. It supplements the corresponding regulations which the staff must study. SAFETY INSTRUCTIONS - Use the explosion-proof cable gland only for its intended purpose. - Explosion-proof cable glands are not suitable for Zone 0 hazardous areas! - Incorrect or impermissible use or non-compliance with these instructions invalidates our warranty provision. - No changes to the device impairing its explosion protection are permitted. - Use the explosion-proof cable gland only if they are clean and undamaged. - Any damage can invalidate the Ex-protection. - Observe the following during installation and operation: - National safety regulations; - National accident prevention regulations; - National installation regulations (e.g. IEC 60079-14); - Generally recognized technical regulations; - Safety guidelines in these operating instructions; Conformity to standards The explosion-proof cable gland is designed and manufactured according to standard of ISO 9001. The explosion-proof cable glands is conformity to the directive 94/9/EC, ATEX and the following standards: EN 60079-0 : 2009 EN60079-1 : 2007 EN 60079-7 : 2007 EN60079-31 : 2009 Applicable scope The series product can be used in zone 1, 2, 21 and zone 22. -1-

Model and implication Explosion-proof Cable glands I R/B B = Brass / N = nickel plated / S is Stainless Steel 316 M = Metrical or N = NPT Thread Dimentiones of seals - K = all sizes 0 = M16 / 3/8"NPT - 01 / 1 = M20 / 1/2"NPT Size of gland 12 / 2 = M25 / 3/4"NPT - 4 = M40 / 1.1/4"NPT - 3 = M32 / 1"NPT 5 = M50 / 1.1/2"NPT 6 = M63 / 2"NPT - 7 = M75 / 2.1/2"NPT 8 = M90 / 3"NPT Type of compression - N=single compression / AD=double compression Type of gland - R= standard gland / B=Barrier gland Productcode of Index Elektro BV Technical data Ex mark: I/II 2G / Ex d I/IIC Gb I/II 2G / Ex e I/IIC Gb III 2 D / Ex tb IIIC Db IP66 Test certificate ISSeP 10 ATEX 034X Special conditions for safe use (X) - Group I only: Cable entries may not be exposed to specific chemical agents (oils, greases and hydraulic liquids for mining applications) -Temperatures: * EPDM sealing rings: - 40 C to +100 C * Silicone sealing rings: - 70 C to +220 C Accessories / Spare parts Use only original spare parts as well as original accessories produceed by INDEX ELEKTRO BV. Maintenance / repairs - Observe the relevant national regulations for your country. - Only parts from our company that can be used to replace or maintenance and the operation should be carried out by professional staf. - The following points must be checked during maintenance: * Compliance with permitted temperatures * Check if the product has been fixed reliably. * Check if the gland is damaged. Disposal / recycling The respective valid national regulations for waste disposal shall be observed when disposing cable glands. We are pleased to answer any special questions you may have, Please contact INDEX ELEKTRO BV. -2-

Operation/installation - Transport and storage in original packaging only. National safety and installations regulations and the generally accepted rules of engineering practice must be observed when mounting and using this equipment. - Explosion-proof cable gland is suitable for use in hazardous areas, zones 1, 2, 21 and 22. - The choice, application and mounting of the cable gland must be at all times in accordance with the EN IEC 60079 part 14 - For cable entry in Ex d enclosures: * Single compression cable glands must be used for unarmoured cable. * Double compression cable gland must be used for armoured cable. - Use barrier glands ore use cable according IEC EN 60079-14 Mounting cable glands 1. Screw the gland for Ex d or Ex e applications into the box or device For Ex d application at least 5 windings 2. Glands for Ex e applications may be mounted with a locknut Type IRN(x) for non armoured cable 1. Feed the cable through the gland 2. Turn the head untill the cable is locked -3-

Type IRAD(x) dubble compression for armoured cable 6 ~10 mm. 1. Remove the external sheath of the cable and cut the amour to a length of 6~10 mm 2. Feed the cable through the gland and insert sheath between the conical rings 3. Turn the middel part untill the cable under the sheat is locked 3. Turn the head untill the cable is locked For all types IB - barrier glands Fill with 2 componenten resin 1. Mount the cable as described above 2. Cut the cable sheat just above the rubber and remove this From this point follow mounthing instructions of the IRN or IRAD type cable glands. Compound resin can be filled after wires have been connected. -4-