Mounting & Maintenance Instructions OMT1 & OMT2 Motors

Similar documents
MOUNTING & MAINTENANCE INSTRUCTIONS FOR

ASYNCHRONOUS MOTORS THREE-PHASE MOTORS SINGLE-PHASE MOTORS BRAKE MOTORS INSTRUCCIONES DE SERVICIO OPERATING INSTRUCTIONS 2016

INSTALLATION OPERATION & MAINTENANCE INSTRUCTIONS For THREE-PHASE INDUCTION MOTORS TYPE HJN / HJA

1. SPECIFICATION. Altitude of motor installation. Information: Resistance and temperature specifications of the PTC thermistor / posistor/.

VEM motors Thurm GmbH

THREE PHASE AND SINGLE PHASE ASYNCHRONOUS ELECTRIC MOTORS OPERATION AND MAINTENANCE BOOKLET Rev

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS. Frames 143T - 449T

ASYNCRONOUS MOTORS OPERATING INSTRUCTIONS 2018

AC Induction Motors. Installation and operating instructions

Energy Saving Three Phase Motors

Starting of Induction Motors

Series E4F E5F

PERFORMANCE DATA 3-PHASE INDUCTION MOTOR

AEEB AEVB LOW VOLTAGE SERIES Three-Phase Squirrel Cage Induction Motor Conforming to SS530 (Occasional Use) Conforming to IE1

SERVO MOTORS BRUSHLESS SERVO MOTORS OPERATING INSTRUCTIONS 2016

A6C A5C-B6C B5C B5H A6C A5C B6C B5C B5H. Model. Up to kw. Power. Up to V. Voltages. Model IP55. Frame Pole 2, 4, 6, 8 and 10

Powerful + Efficient + Reliable

PERFORMANCE DATA 3-PHASE INDUCTION MOTOR

Cast Iron Frame Motors For Zone 21 Improved Efficiency EFF2

Squirrel Cage Induction Motors MA - A4 - BB - B4 - B5 SERIES SIZES. MarelliMotori ASI.CT.033.2

ELECTRIC MOTORS. Selection. Starting torque and nominal torque

THREE-PHASE ASYNCHRONOUS MOTORS EFFICIENCY CLASS ACCORDING IEC

SWE SERIES (IE3) WONDER ELECTRIC MOTOR (S) PTE LTD. Energy Saving Low Noise Environmental Friendly IEC Dimension Low Vibration European Design

Brake Motors Aluminium Frame Improved Efficiency EFF2

: B3; B5; B14; B34; B35; V1

ANNEX No 1. C 17/05/2006 SGA112B TERMINAL BOX ARRANGEMENT Ex e, Ex na &Ex td V (OPTION 2)

Maximum operating temperature for standard motors = 110 C. Shut down temperature in case of a malfunction = 115 C.

CONTENTS 1 GENERAL 2 STANDARDS. 3 TECHNICAL FEATURES 3.1 Basic Technical Data 3.2 Standard Accessories 3.3 Tolerances

Design Standard. Electric Motors. Detailed specifications follow. PART 1 - GENERAL

A. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents.

champion series motors

INSTALLATION, OPERATION AND CARE OF INTEGRAL HORSEPOWER INDUCTION MOTORS ( FRAMES) NAVY A-C MOTORS

Vent-Axia Sabre Sickle Roof Fans (VSR)

FCR asynchronous brake motors LS FCR. General information

Asynchronous, Low Voltage, Squirrel Cage, Three Phase Electric Motors

Premium Efficiency Exceeds Effciency Levels Mandated by CSA C390 and EPACT 92

Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-40 RX-63 RX-100

MODEL VBO-HV & VBO UPBLAST PROPELLER ROOF FANS

CONTENTS 1 GENERAL 2 STANDARDS. 3 TECHNICAL FEATURES 3.1 Basic Design Data 3.2 Standard Accessories 3.3 Tolerances

SECTION COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT

Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-10 RX-21 RX-25

5 Year Warranty Premium Efficiency, TEFC Enclosure Inverter Duty Motors Corona Resistant Magnet Wire CSA Certified, UL, CE NEMA MG1 (2003) Part 31,

1LG0 Low-voltage Motors

Bearing Handling. 15. Bearing Handling Bearing storage Installation

INTER PLANT STANDARD STEEL INDUSTRY

AESV / AESU / AESV-LA Series Squirrel Cage Induction Motor AESV1S / AESU1S / AESV1S-LA (IE1) STANDARD EFFICIENCY

PAC TRAINING PUMP MOTORS

LARGE THREE-PHASE SQUIRREL CAGE ASYNCHRONOUS MOTORS FOR HEAVY DUTY APPLICATIONS ADH SERIES

SERVO MOTORS BRUSHLESS SERVO MOTORS ATEX ZONE 2-22 OPERATING INSTRUCTIONS 2016

HT SERIES SMOKE VENTING EQUIPMENT

OIL CAPACITIES FOR SERIES HP APPROXIMATE CAPACITIES IN QUARTS AND GALLONS

THREE PHASE INDUCTION MOTORS

CEB 71204/a of 13 december 2005 SLSHR. 3-Phase Totally Enclosed Induction Motor Steel Housing Water-Cooled 30 to 1800 kw

Asynchronous motors. 7/2 Main spindle motors for SIMODRIVE 611 7/2 Introduction

MOTOR INSTALLATION. Knowledge of proper installation techniques is vital to the effective operation of a motor

KAT.NMST ENG NORM ELECTRIC MOTORS THREE PHASES SQUIRREL CAGE TEFC NMST

Standardmotoren Standard motors

Standard cast iron Motor

THREE PHASE ASYNCHRONOUS ELECTRIC MOTORS OPERATING MANUAL. (Original Instructions)

Ordering information. When placing an order, specify motor type, size and product code according to the following example.

GRUNDFOS INSTRUCTIONS MTC. Installation and operating instructions

CPLS Asynchronous motors for variable frequency. 95 Nm to 2900 Nm

INDEX NEMA PREMIUM EFFICIENCY

EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Introduction to Electrical Machines

From 4 to 20 poles ( over contact MM) IP 23. Available up to IP 44 with filters.

INTER PLANT STANDARD STEEL INDUSTRY. SPECIFICATION FOR GENERAL PURPOSE SQUIRREL CAGE INDUCTION MOTORS (Fifth Revision) BASED ON IS 325:1996

SECTION MOTOR REQUIREMENTS for HVAC

A. Fan motors and associated equipment shall be sized to operate at 110% of calculated loads and capacities.

INTRODUCTION GENERAL GUIDELINES ATTACHING THE DRIVE PARTS

ELECTRIC MOTORS 3SIE IE3

ODP SERIES PREMIUM INDUSTRIAL OPEN DRIP PROOF MOTORS C280M to C355LB Frame. Australian Version October 2013

MARLEY ENGINEERED PRODUCTS OPERATING INSTRUCTIONS AND PARTS LIST

INTER PLANT STANDARD STEEL INDUSTRY. Corresponding IS does not exist

Heavy duty slurry pumps

Three-phase asynchronous motors

AESV / AESU / AESV-LA Series Squirrel Cage Induction Motor AESV1S / AESU1S / AESV1S-LA (IE1) STANDARD EFFICIENCY

Operating Instructions

SLR / SLR-S/N. Instruction Manual. Walrus America Inc

Heavy duty slurry pumps

Low Voltage General Purpose Motors

Terminal Box Are to IP54, as standard, protected against dust and water from any angle allowing outside applications.

End Suction Range MARCH 2018

Flanged housings FNL series

INTERROLL DRUM MOTOR 113S

Installation and Operating Instructions Electric Vibrators HV/VFL Series

SUPER-MAX INDUCTION MOTOR

Three Phase Modifiable NEMA Horizontal Motors Accessories and Modifications

PROCESS PUMPS (INDIA) PVT LTD

Contents. Identification

General Specifications. Cooling Method 3M series are IC 411 Standard. IC 416, IC 418 can be provided Upon request

INSTRUCTION AND REPAIR MANUAL MODELS 341A, 342A AND 344A 6

Aluminium Frame Motors Improved Efficiency EFF2

Three-phase roller table motors with squirrel-cage rotor for the application at the frequency converters Series A21O, A20O, ARB, ARC.

Low Voltage General Purpose Motors

Installation, operating and maintenance instructions. VIMARC vibrator motors type AXP up to and including GXP. Explosion proof. Certified by FM & CSA

Three Phase Modifiable NEMA Horizontal Motors Accessories and Modifications

ELECTRIC VIBRATORS SPV & SPC

Variable speed asynchronous motors with FCR brake LSMV FCR. General information

READ AND SAVE THESE INSTRUCTIONS

THREE PHASE ASYNCHRONOUS MOTORS. MS/S Series (frame Aluminum) TC Series (frame Cast iron) Y Series (frame Cast iron)

Transcription:

Mounting & Maintenance Instructions OMT1 & OMT2 Motors Seite 1 von 10

Inhalt Seite 1 General information 3 2 Delivery 3 3 Mounting 3 4 Coupling 3 4.1 Direct coupling 3 4.2 Indirect coupling 4 4.2.1 Flat belt or V-belt 4 4.2.2 Spur gear transmission 4 4.3 Shaft couplings 4 5 Electrical connections 4 5.1 General information 4 5.2 Circuit details 5 6 Putting into service 6 7 Maintenance 6 7.1 Dust 6 7.2 Moisture 6 7.3 Wear & vibrations 7 7.4 Greasing 7 7.5 Replacement of ball or roller bearing 7 8 Bearing types 8 9 Regrasing interval of bearings 8 10 Disposal 9 11 Motor spare part list / exploded view 10 Seite 2 von 10

1 General information This manual concerns normal three phase induction motors with an output varying from small to middle size; they are externally cooled, totally enclosed, supplied in a cast iron or aluminium frame and provided with ball bearings or roller bearings, lubricated with grease. 2 Delivery After receipt, remove the package material, if any, and mind the parts that have been delivered loose. Check the motor to see whether transport damage has occurred. You should be able to rotate the shaft easily and smoothly by hand. Compare the details on the nameplate with those of the power network and with the requirements of the motor. 3 Mounting The motor must be fixed on a stable, clean and flat foundation with good fitting foundation bolts, using washers. Never mount a motor manufactured for a horizontal mounting on a surface with an angle of inclination of more than 15 degrees without consulting the supplier in advance. Foot & flange motors always have to be mounted in such a way that the drain holes, if any, are situated at the bottom, otherwise you risk that moisture will condensate in the motor and cannot be drained off. To this end you need to remove the drain plugs. Under no circumstances the entrance of cooling air, drafted by the cooling fan, may be obstructed. This will cause overheating of the motor. Special attention is required where motors will be located in small enclosed rooms. The ambient cooling temperature must not exceed 40 ºC, unless otherwise agreed upon at the time of ordering. 4 Coupling 4.1 Direct coupling The motor and driven shafts must be accurately aligned. In case of a flexible coupling, the manufacturers distance between the parts to be coupled must be adhered to, also the degree of misalignment must be within the makers tolerance. We do not recommend using solid couplings. Seite 3 von 10

4.2 Indirect coupling 4.2.1 Flat belt or V-belt Mount the motor on slide rails in order to adjust belt tension. The belt pulley has to be fitted hard up the shoulder of the shaft. The pulley center line should be within the shaft center line. Use correctly sized belts with a correct profile and in sufficient numbers to drive without slip and undue tension. Align both pulleys accurately in such a way that the center of both pulleys are in line. A belt pulley, which is either too small or too wide, or too high, a tension on the belt may damage the bearing or cause a shaft break. In case of doubt, consult the supplier. 4.2.2 Spur gear drives The motor and the driven machine have to be positioned in such a way that the two gears align correctly. The motor should then be fixed with dowels. 4.3 Shaft couplings Remove the corrosion protection from the shaft extension and the coupling elements. The coupling parts, belt pulleys and gear wheels need to be dynamically balanced and fit easily on the shaft and to be provided with good fitting keyway. In the factory the rotor has already been dynamically half-key balanced. The dimension and the tolerances of the shaft extension and the key are indicated on the motor dimension sheet. Assembling the coupling elements has to be done with great care. Careless handling may damage the bearings, shaft or end shields. Do not file or emery on the shaft to achieve a fit! When fitting pulleys couplings or bearings, we recommend using heat elements; therefore the part to be mounted has to be heated till ± 100 C. A large washer and setscrew can be useful for pushing on pulleys using the tapped hole in the shaft. Only use proper tools for removing the above mentioned parts e.g. pulley drawers. 5 Electrical connections 5.1 General information On delivery the motor will rotate clockwise looking at the drive when the phases L1, L2 and L3 are connected respectively to the connection terminals U1,V1 and W1. Exchanging of any two-phase lines changes the direction of rotation. When a motor is Seite 4 von 10

only suited for one direction of rotation, it is indicated with an arrow on the motor fan cowl. Connecting cables must comply with the IEC regulations. Line fuses only protect the cables in case of short circuiting and do not constitute a safeguard against the overheating of the winding caused by overload. Therefore it is recommended that a motor start- and overload protection is mounted, giving single phase and overload protection. 5.2 Circuit details Normally our motors are provided with a terminal box with six connections, to which six leads from the winding are connected either in a delta connection or in a star connection by means of connection links. Usually two voltages are indicated on the rating plate of these motors, which mean that the motor can be connected to a circuit having one of these voltages. If the mains voltage is corresponding with the lowest indicated voltage, the winding has to be connected in delta connection (see figure 1); if it is corresponding with the highest indicated voltage, the winding has to be connected in star connection (see figure 2). A motor with e.g. 230/400V on its rating plate is suited to be switched on directly, on a circuit with a voltage of 230 V between phases with the winding connected in a delta connection, or on a circuit with a voltage of 400 V with the winding connected in a star connection. Δ - Connection Y - Connection V2 W1 V2 W1 U2 V1 U2 V1 low voltage W2 U1 high voltage W2 U1 Abb. 1: Delta connection L1 L2 L3 Abb. 2: Star connection L1 L2 L3 If the motor is switched on with a star delta starter the motor is only suited for a main voltage on the rating-plate, this is the delta voltage. In this case, the connection strips on the terminal box have to be removed when the motor is connected. The star/delta connection will be made successively during the start up. Seite 5 von 10

If only one voltage is indicated on the nameplate together with the delta sign, the motor can be switched on directly at the indicated voltage or with a star/delta starter. Pole change motors (for two or more speeds) are connected according to a diagram sent together with the motor. 6 Putting into service Before putting a motor into service, one should check especially when the motor has not been used for a long time that the insulation resistance of the winding is sufficient. The insulation resistance has to be at least 1.000Ω per Volt, what means at least 400.000 on a supply voltage of 400V. If the insulation resistance is not high enough, the motor has to be dried out revarnished or rewound. Check all connections and adjust the thermal protection units to the correct current. Switch the motor on in a no load state to determine the direction of rotation. Load the motor gradually and check whether it runs without vibration. The motor can be used under a variation of the main voltage ± 5% or frequency variation of max. ± 2% compared to the nominal frequency or nominal voltage, in compliance with the international regulations for electric machines. 7 Maintenance The totally enclosed and fan cooled three phase squirrel cage induction motors require very little maintenance. Nevertheless it is recommended to check the motor regularly in order to prevent a breakdown caused by dust, moisture, vibrations, too much or too little greasing. 7.1 Dust The outer parts of the totally enclosed motors, especially the cooling ribs or cooling channels, have to be kept as clean as possible in order not to obstruct the cooling air from the fan extracting the heat from the motor frame. 7.2 Moisture Motors that are stalled for a long time, should be started from time to time to prevent moisture affecting the windings in the long term. Before putting the motor into service, one should check especially when the motor has not been used for a long time that the insulation resistance of the winding is sufficient. Seite 6 von 10

7.3 Wear & vibrations To prevent abnormal wear & vibration, one should: a. Take care that the tension of the belt or the chain is not too high; b. Check whether the mounting of directly coupled machines is correct; c. Check whether the foundation bolts to fasten the motor and the slide rails are tightly fixed. 7.4 Greasing Before the motor leaves the factory, the bearings are filled with a high quality Lithium base grease. This grase can be mixed with most of the commonly used ball bearing greases that are lithium-based so that nearly every grease can be used for regreasing. Motors from frame size 56 up to frame size 250 are fitted with both sides sealed ball bearings ( 2RZ ) those filled with grease by the bearing manufacturer for life time. The bearings for those frame sizes without regreasing-divices are completely free of maintenance. Regular checks can be limited only towards temperature and noise. Motors from frame sizes 280 up to frame size 400 are equipped with open bearings, that are filled for 2/3 when the motor leaves the factory. The drive-end shields are fitted with bearing covers. The lubrication must take place when the machine is running. The old grease ejects from the grease valve thus maintaining the correct level and avoiding overfilling which would be harmful. 7.5 Replacement of ball or roller bearing When a bearing has to be replaced, the old bearing has to be removed from the shaft with proper tools in order not to damage the shaft. Thereupon the bearing location on the shaft has to be cleaned and checked thoroughly. After the new ball bearing resp. the inner ring of aroller bearing has been heated-up to ca. 80 C till 90 C, it must be mounted on the shaft very soon. If necessary, a short pipe that fits onto the inner bearing ring can be used to push the bearing to its corret position. In no case, it is allowed to blow on the outer ring of the bearing. Do not mount the end shield until the bearing has cooled down. Seite 7 von 10

8 Bearing types Motortype Poles Drive-end Non-drive-end OMT2-56 2/4 6201 2RZ C3 6201 2RZ C3 OMT2-63 2/4 6201 2RZ C3 6201 2RZ C3 OMT2-71 2/4/6 6202 2RZ C3 6202 2RZ C3 OMT1/OMT2-80 2/4/6/8 6204 2RZ C3 6204 2RZ C3 OMT1/OMT2-90 2/4/6/8 6205 2RZ C3 6205 2RZ C3 OMT1/OMT2-100 2/4/6/8 6206 2RZ C3 6206 2RZ C3 OMT1/OMT2-112 2/4/6/8 6306 2RZ C3 6306 2RZ C3 OMT1/OMT2-132 2/4/6/8 6308 2RZ C3 6308 2RZ C3 OMT1-160 2/4/6/8 6309 2RZ C3 6309 2RZ C3 OMT1-180 2/4/6/8 6311 2RZ C3 6311 2RZ C3 OMT1-200 2/4/6/8 6312 2RZ C3 6312 2RZ C3 OMT1-225 2/4/6/8 6313 2RZ C3 6313 2RZ C3 OMT1-250 2/4/6/8 6314 2RZ C3 6314 2RZ C3 OMT1-280 2 6314 C3 6314 C3 OMT1-280 4/6/8 6317 C3 6317 C3 OMT1-315 2 6317 C3 6317 C3 OMT1-315 4/6/8 6319 C3 6319 C3 OMT1-355 2 6317 C3 6317 C3 OMT1-355 4/6/8 6322 C3 6322 C3 OMT1-400 2 6320 C3 6320 C3 OMT1-400 4/6/8 6326 C3 6326 C3 9 Regrasing interval of bearings By the term greasing interval we mean the number of working hours after which the bearing lubricant has to be replaced. Electric motors have such a wide range of application that they must cope with many adverse conditions as for instance dust, moisture, vibration, temperature, chemicals, marine atmosphere and of course, the mounting position and loading of the driven machine. Generally we can say lubrication life is a product of time, speed and the bearing size. Due to the impact of all these factors, it is practically impossible to determine any exact values that are valid under all circumstances. Nevertheless it is necessary to provide at least some guidelines concerning greasing to the user. Seite 8 von 10

Under normal load and environmental conditions the quality of the grease ensures proper operation of the motor for about 20000 service hours with 2-pole design and 40000 service hours with multi pole design. If not otherwise agreed upon the grease need not be refilled during this period. Nevertheless the condition of the grease filling should be occasionally checked also within the said lubricating intervals. The stated service hours are only current under operation with rated speed. For relubrication thoroughly clean the bearings with a suitable solvent and use the same or substitute grades specified by the motor manufacturer. Bear in mind, however, that the bearings should be filled only up to about 2/3 of their free space as a complete filling of the bearings and bearing covers results in an increased bearing temperature and therefore in increased wear. For bearings with relubricating facility regrease at the grease fitting with the motor running according to the grease amount required for the motor in case. The relubrication intervals should be looked up in the following table: A chemically aggressive environment, extreme moistness, strong vibrations, high or low ambient temperatures are not normal circumstances and such conditions must be taken into account. Frame size Motors with 2 poles Motors with 4 and multi-poles from 280 up to and incl. 400 2.000 hours 4.000 hours 10 Disposal The applicable national regulations are to be observed with regard to disposal of the machines. It is furthermore to be ensured that oils and greases are collected for disposal in accordance with the corresponding regulations on waste oils. They must not be contaminated with solvents, cold cleaners and paint residues. The individual materials should be segregated for recycling. The most important components are grey cast iron (housing), steel (shaft, stator and rotor lamination, small parts), aluminium (rotor), copper (windings) and plastics (insulation materials, such as polyamide, polypropylene, etc.). electronic components such as circuit boards (converter, sensors, etc.) are recycled separately. Seite 9 von 10

11 Motor spare part list / exploded view Three-phase motor with squirrel-cage rotor 1 V-ring, oil seal DE 22 Mounting screw adoption plate 2 Mounting screw bearing cover DE 23 Lifting eye 3 Outside bearing cover DE 24 Circlip bearing DE 4 Grease-inlet for regrasing device DE 25 Bearing DE 5 Grease-outlet for regreasing device DE 26 Inside bearing cover DE 6 B5-shield DE 27 Key DE 7 B3-shield DE 28 Rotor 8 Mounting screw shield DE 29 Shaft 9 Motor housing 30 Inside bearing cover NDE 10 Gasket terminal box / motor housing 31 Bearing NDE 11 Terminal box 32 Non-drive-end shield 12 Mounting screw terminal box 33 Mounting screw shield NDE 13 Terminal board 34 Outside bearing cover NDE 14 Mounting screw terminal board 35 Mounting screw outside bearing cover DE 15 Connetor pin 36 V-ring, oil seal NDE 16 Nut for connector pin 37 Grease inlet for regreasing device NDE 17 Gasket terminal box / terminal box cover 38 Grease outlet for regreasing device NDE 18 Terminal box cover 39 Fan 19 Mounting screw terminal box cover 40 Circlip fan 20 Adoption plate for cable glands 41 Fan cover 21 Cable gland 42 Mounting screw fan cover Seite 10 von 10