Failure of Transformer Cable box A case study

Similar documents
Alstom Grid provides smart, efficient and environmentally-friendly solutions to deliver electricity reliably across the world GRID

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

LEARNING BY FAILURES A TRANSFORMER CASE STUDY A QUALITY PRESPECTIVE

POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010

CHAPTER 4 PROTECTION REQUIREMENTS

ABB PTTR SPAIN. Zaragoza. The product: Cast coil transformers

PRAGATI ENGINEERING COLLEGE

Double earth fault in a PSP during back to back launching sequence

PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering

Nexans Switzerland. Global expert in cables and cabling system. Cossonay Production Plant

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions

Distribution transformers Efficiency over life-cycle

Transformers for Power Applications

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

Retrofit for gas-insulated high voltage switchgear (GIS) - 8D1 and 8D2

Pretest Module 29 High Voltage Unit 1

Chapter 6 Generator-Voltage System

DETAILS OF THE EXPRESSION OF INTEREST(EOI) NO.: PL.G03.EOI

Maximum temp. rise in oil by 40 thermometer above design ambient (deg C) specified time Short circuit rating (Sec) for As per IS 2026

Warning. Document ref: A October 2015

Energy Transmission & Distribution Services - Italy. SVEPPI laboratory...our services for your success. Answers for energy.

MOBILE SUBSTATION DESIGN Brad Bozich & Vitor Vieira 2755 Northwoods Parkway Norcross, Georgia

www. ElectricalPartManuals. com lncoming-6900 through 69,000 volts Outgoing-2400 through 13,800 volts Ratings:

Refurbishment & Upgrade of the Celilo HVdc Converter Station

TRANSFORMERS UP TO 750 kv

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

VEIKI-VNL Electric Large Laboratories Ltd. H-1158-Budapest, Vasgolyó utca 2-4. HUNGARY

Electrical Systems - Course 135 COMPOSITE ELECTRICAL PROTECTIVE SCHEMES: PART II

LEAP - Life Expectancy Analysis Program For Electrical Rotating Machines. Marcio Gennari ABB Brazil Automation Products Machines Service Osasco

4Electrically propelled vessels

ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com. Energy. Fast.

Key features. DESIGNS: - Conservator type - Hermetically sealed

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices

Transformer Protection

UNIT 6: BATTERIES, UPS AND CABLES

DIAMOND ROLLER CHAIN. For Agricultural and Construction Equipment

Dr Joerg Friedel Product Application Specialist Shell Technology Centre Hamburg, Germany

MECHANICAL INTEGRITY CHECKING OF GENERATOR STATOR OVERHANG BY NATURAL FREQUENCY MEASUREMENT

ANNEXURE-I : LIST OF ITEMS H.O. PURCHASE ITEM LIST:

BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2

No. of Single leaf Sector Gates 2 Clear span of opening 7.0m Cylinder rebate size. Sill level inner gate Gate crest level - inner.

September 2008 TEC, INTELLIGENT MONITORING SYSTEM

Oil Circuit Breakers

High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

33kV Connection up to 90MVA

DESIGN CONSIDERATIONS FOR APPLICATION OF SHUNT CAPACITORS IN HEAVY HATER PLANT (TUTICORIN)

POWER SYSTEM OPERATING INCIDENT REPORT TRIPS OF YALLOURN W POWER STATION UNITS W1 AND W3 ON 14 NOVEMBER 2012

Medium and high pressure pumps

Extensible Unit - VCE2a

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system.

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.

/ I S S : / S T S I

POWER SYSTEM OPERATING INCIDENT REPORT SIMULTANEOUS TRIP OF 5A6 MT PIPER BANNABY 500 KV LINE AND MT PIPER NO. 2 UNIT ON 9 FEBRUARY 2012

PRILIMINARY REPORT ON THE ACCIDENT AT RANTAMBE 132 KV SWITCHYARD 21 ST FEBRUARY 2011

Small wonder. Station service voltage transformers for small power requirements

2013 Grid of the Future Symposium. Utilizing Single Phase Operation Scheme on Untransposed 765kV lines for a Stability-Limited Plant

SICOP. Bimetal Overload Relays Type 3UA5/6 & 3UC5/6. Introduction. Application

SPECIFICATION FOR PI

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

OFFSHORE WIND FEASIBILITY STUDY APPENDICES Appendix C.2 Subsea Cable Data Sheets

Cable arrangement 15 Preparation for cable installation. 15 Installation of the cables 16 Finishing of the cable installation. 17 Examples.

CAST RESIN TRANSFORMERS

SWITCHGEAR DIVISION PRODUCT PROFILES

High Voltage and Extra High Voltage Cables

Product Specifications for Phase Over Phase GOABS(r)

S P E C I F I C A T I O N

Fuji Electric. Oil immersed. Transformer FTU08A1-E-0024

Final Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description

ZX1.5-R. Gas-insulated medium voltage for railway application DISTRIBUTION SOLUTIONS. Gas-insulated medium voltage for railway application ZX1.

INSTRUCTION MANUAL OIL SEALED ROTARY VACUUM PUMP MODEL PKS-016 PKS-030 PKS-070

PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4

ZX2.2 Gas-insulated medium voltage switchgear

ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE

Power & Control Cables. U o. /U 0.6/1 kv - IEC

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

Large Air Cooled Generator Failure

These installation and maintenance instructions must be read in full and completely understood before the installation!

*(1(5$/7(&+1,&$/63(&,),&$7,2162) +9/9 ',675,%87,2175$16)250(56

Generator Termination Bus-bar Arrangement - Design requirements: Utility Perspective

100 MW Wind Generation Project

P2 : About Us. P3 : Elsewedy Transformers. P4 : Why Elsewedy Dry Type Transformer? P6 : Cast Resin Dry Transformers. P7 : Technical Data Sheets

Car Battery Charger Instructions for Use

IEC Separable Connectors 36 kv and 42 kv, 630A and 1250A Front T-Body / Coupling (Rear) T-Body Connector

Signal Power Supply Monitoring & Restoration

Installation Operation Maintenance. LSSN Butterfly Valve AGA Approved 50MM - 150MM. QAD#IM6055.REVA

Tamini is the leading Italian company in the world for the design and production of industrial, power and special transformers.

Electrical Safety. Presented By- C S Chakraverty. L&T Construction ( MMH ) Head- E&I Operation

AC/DC Arc Furnace and Ladle Furnace Transformers

Transmission Corporation of Telangana, Jawaharlal Nehru Technological University Hyderabad

NXPLUS C Single busbar. Maintenance-free for lifetime

Field Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI

FR-N1X1G1. Low voltage - Energy, cabling, signalling and control

Design specifications

Transcription:

Failure of Transformer Cable box A case study Presented by Janardan Choudhary, Executive Director (O&M) 1

INTRODUCTION The 280 MW Dhauliganga Power Station, NHPC Ltd, situated at remote place of Pithoragarh in Uttarakhand, India, was commissioned in 2005. 4 x 70 MW power is generated at 11 KV voltage level and stepped up to 220 KV level through twelve single phase bank of generator transformer and the power evacuation is done through two 220 KV line. Unit is connected to a bank of 3 nos. Single phase transformer, 29 MVA, 11 KV/220 KV/ 3, OFWF. LV side of transformer bank is directly connected to generator through isolated phase busduct and high voltage terminal of the transformer is connected to 220 KV GIS by 220KV XLPE cable through High Voltage Cable Box (HVCB). 2

DESCRIPTION OF EVENT On 22/08/2016 all four units were running on full load (280 MW). At 13:29 hrs Unit#2 got tripped on XLPE cable differential protection of R-phase. The oil from the HVCB splashed & spilled all over the transformer The XLPE cable connected to one side of HVCB got detached from the bushing and fell apart. The sprinkler fire protection system operated and fire got extinguished promptly without much spreading of fire. From the event list it was observed that PRV and Buchholz relay of HVCB and Buchholz relay of main transformer were also operated during the event. 3

DESCRIPTION OF EVENTS- Extent of damage Cable box, insulated copper flexible cable (connecting XLPE cable and HV bushing of transformer), HV bushing of transformer and XLPE cable end termination were damaged beyond repair. Transformer also got severly damaged Radius of outer winding, i.e. HV winding, increased due to huge tensile stress caused by electromechanical force. Looseness of sector and support, deformation of lower & upper winding end support and coil clamping rings were also observed Complete Core assembly is decided to be replaced 4

Damaged and detached XLPE Cable XLPE Cable 5

XLPE cable detached from Oil to Air Bushing installed at HVCB 6

Damaged Flexible link inside the HVCB 7

RESTORATION OF UNIT The oil of the R-phase transformer of Unit#2 got contaminated with the HVCB oil which was subjected to high energy arc. The transformer was subject to huge electromagnetic force. All oil from the HVCB got drained out. Therefore, after fault DGA of HVCB oil could not be done. DGA of main transformer showed higher hydrocarbon gas content which DGA of Transformer Oil was due to mixing of HVCB oil. Gases After Before o So faulty transformer along with bushing fault and XLPE cables could not be used immediately. o To avoid further generation/capacity loss, the faulty transformer along with all other affected equipment were replaced with the spare one available at site. (ppm) fault 1. H₂ 53 0 2. H₂O 32 5 3. CO₂ 894 176 4. CO 153 3 5. C₂H₄ 104 5 6. C₂H₆ 21 0 7. CH₄ 40 1 8. C₂H₂ 5.5 0 Total down time was 21 days (including two weeks taken for arranging modified flexible link). 8

ANALYSIS & ROOT CAUSE Detailed investigation on damaged HVCB and connection of flexible link was checked in healthy transformer. It was observed that the flexible copper link (connecting XLPE cable and HV bushing of transformer) was not as per drawing. As per drg., the end connection should form L shape to maintain proper clearance to ground 9

ANALYSIS & ROOT CAUSE Existing connection: The end connection of existing link was provided with a socket bolted with connector of bushings horizontally. Horizontal Connection With time, the bend at both ends near socket joints loses rigidity (firmness) resulting into increased sag near the midpoint of the flexible link.. 10

ANALYSIS & ROOT CAUSE The sag in the existing link led to the reduced clearance with ground near halfway of the link (approx. 4 mm). As a result, Partial discharge might have started, which got ultimately converted into an arcing ground with HVCB bottom and failure. HVCB bottom side 11

PREVENTIVE ACTION Following measures were carried out to ensure the overall insulation level of flexible copper link within HVCB : Extra insulation (craft paper & paper board) was applied on flexible copper link to increase its rigidity. Modification in connection of link with the connector of the bushings. By above measures, appropriate clearnce of link to ground (HVCB bottom) was maintained over entire the span. Vertical Connection Modified rigid flexible link having L shaped end connectors was connected vertically with the connector of the bushings. 12

PREVENTIVE ACTION With modification in end connection and extra insulation, clearance between flexible copper link and HVCB surface is made uniform throughout its span All flexible links for the balance transformers has been planned to be replaced in phased manner. However, tightness of the flexible link at end connection and proper clearance with HVCB bottom has been ensured in all transformers. The depletion of oil level over time in HVCB shall also adversely affect the overall insulation level of flexible copper link. Therefore, regular monitoring of oil level in HVCB and its top up as required has been ensured. 13

RECOMMENDATIONS The transformer having oil filled HVCB must be type tested and installation/commissioning should be done as per approved drawing. Suitable alternative solution should be explored to minimise the use of oil filled High Voltage Cable Box for high voltage transformer to minimise such type of faults. 14

THANK YOU 15