RotoTract Remote Racking Operating Manual

Similar documents
Freedom FlashGard Aftermarket Kit Installation Manual

XT and XT FlashGard. motor control center installation and maintenance manual. Instruction Booklet MN043001EN. Contents

Two-way cable interlock kit for Magnum drawout circuit breakers

Two-way cable interlock kit for Magnum fixed circuit breakers

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear rated up to 15kV, 25 and 40kA UPPER TERMINAL SET VERSION

Feeder Circuit Breaker Units Secure Support Pan and Change Door Latch

Introduction. Features. Intelligent Technologies Motor Control Center Structures

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

Quick selector reference guide. Motor Control Center Aftermarket Buckets

IB PowlVac ITE-HK Remote Racking Device

Installation Instructions For Motor Control Center (MCC) Units

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

! WARNING I.L D WARNING GENERAL INFORMATION

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

HLS Watt Halogen Illuminator Service Manual

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to:

Instructions for using Functional Test Kit on Digitrip 520 and 1150 family of Power Circuit Breaker Trip Units and Series G and FD MCCB Trip Units

Freedom FlashGard Motor Control Center Instruction Manual IM E

Cutler-Hammer. Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv I.B.

4000 SYSTEM OPERATING MANUAL

K-SERIES PUBLIC USE LIFT OPERATING INSTRUCTIONS

S-SERIES ADA TRANSIT USE OPERATING INSTRUCTIONS

O & M Manual for the EATON Generator Ready Loadcenter

Instruction Booklet IB E. Contents

Digitrip Retrofit System for Siemens-Allis RLX-1600 Breakers

1P 120/240V, 3600 RPM,

Distribution & Control

S-SERIES PUBLIC USE OPERATING INSTRUCTIONS

Digitrip Retrofit System for Allis-Chalmers LA-600 F Electrically Operated Fused Breakers

Digitrip Retrofit System for BBC LKD 8 Breakers

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

Magnum IEC Low Voltage Air Circuit Breakers

Instructions for A200, A210, A250 size 6, two- or three-pole non-reversing or reversing motor controllers

SIGNAL WORDS QUALIFIED PERSON

Digitrip RMS and Digitrip OPTIM Trip Units Used with R-Frame Circuit Breakers

Installation Instructions for Type SM Safety Handle Mechanism for L-Frame Series C Circuit Breakers and Molded Case Switches

Inverting Fault Circuit Breaker Kit for FlexPak 3000 and WebPak 3000 Digital DC Drives VAC and VAC

Design Standard. Purpose: Design Standard:

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

VCPR. User s Manual. MarTek Ltd. RAKTEK. Model VCPR. A Portable Device for Remotely Racking VCP-Style Circuit Breakers 1.0 Arc-blast Hazards

CHAPTER 22 AUTOPILOT

Magnum breaker remote racking device (MRR1000)

Model 2300JL Installation Guide

Magnum Breaker Remote Racking Device (MRR1000)

CM52 Network Protector with Arc Flash Reduction Module

Model 2300DL Installation Guide

38 kv Type VCPW-HD Simple Electrical Ground & Test Device (SEG&TD) lower terminal instruction booklet

TPM/GMT Panel Installation Guide

W-SLC Medium Voltage fused contactor truck A safe, reliable and efficient motor starter

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

CAUTION -TABLE OF CONTENTS- II. OPERATING INSTRUCTIONS

Instructions for installation, operation, and maintenance of medium voltage VC-W MR2 (integral racking)

Installation Instructions for JDB, JD, HJD, JDC, JW HJW, JWC Circuit Breakers and Molded Case Switches

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Instructions for AMPGARD 400A medium voltage starter

SOLAR-150HD. 150-Watt Dual Halogen Illuminator. Service Manual Bowdendale Avenue Jacksonville, FL 32216

Vacuum Circuit Breaker Type VAD-3

Cutler-Hammer. Installation Instructions for the ND OPTIM 550 PowerNet and/or Zone Interlock Accessories (ICK 550N, ZGK550N, ZGPK550N) I.L.

SL-1000 Stairlift OWNER S MANUAL

VacClad-W type VCP-W 5 and 15 kv, 36-inch-wide switchgear components

Power Break Circuit Breakers

Models Affected: Certain 2013 Model Year Propane Vision Buses Equipped with Ford 6.8L Engines CORRECTIVE ACTION ---- PROCEDURE

Altivar 58 TRX Adjustable Speed Drive Controllers in Motor Control Centers hp, 480 V or 1 50 hp, 208/240 V Class 8998


Electric vehicle auxiliary fuses 500 Vdc, A

Installation& Maintenance Instructions

TO COME. CEP7 Solid-State Overload Relay for Motor Control Centers and Enclosed Control

ibusway for Data Center

VCPR. A Portable Device for Remotely Racking VCP-W Circuit Breakers. User s Manual

II. W-SERIES WHEELCHAIR LIFT OPERATING INSTRUCTIONS T

Freedom 2100 Motor Control Center Installation and Maintenance Manual

Installation, Operation and Maintenance Manual

Instructions for installation, operation, and maintenance of 38 kv type VacClad-W arc resistant metal-clad switchgear

Evolution Series E9000 *

BUSWAY Low Voltage (Pow-R-Flex)

Digitrip Retrofit System for Allis-Chalmers G-25 Breakers

Servo Systems KNIGHT GLOBAL CREATING A NEW STANDARD. Intelligent Assist Devices (IAD) Servo Technology Improves Productivity with Speed and Precision

SL-1000 Stairlift OWNER S MANUAL

MODEL RMS INSTALLATION INSTRUCTIONS. CONTENTS Page A. Introduction 1. Usage 2 2. How it operates 2

TIASTAR Motor Control Center Installation And Maintenance Instructions For Units Only

Centrifuge Operator / Service Manual

User s Manual. Model MDS-30. User s Manual. A Portable Actuator for Remotely Operating Cutler Hammer Magnum DS Breakers.

I-BFV.KIT Butterfly Valve Gear Operator Replacement

DSR1. User s Manual. MarTek Ltd. RAKTEK. Model DSR1. A Portable Device for Remotely Racking DS and DSII-Style Circuit Breakers. 1.0 Arc-blast Hazards

I.L. 29C121A WARNING 1. INTRODUCTION. Maximum Freq. Maximum Dielectric Voltage Current Withstand (V) (A) Voltage (V)

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Service Manual Gulf Stream Electronic Full Wall Slide Systems

Installation, Operation and Maintenance Manual

Discrete Output Modules IC697MDL753


Cutler-Hammer. Instructions for Installation, Operation, and Maintenance of the AMPGARD Reduced Voltage Soft Starter

Installation Instructions for NW, HNW, and NWC Circuit Breakers and N-frame Series C Molded Case Switches

Property of American Airlines

Series 72 Electri-SAFE On/Off Operation Including CLC Option Installation, Operation and Maintenance Instructions

INSTALLATION INSTRUCTIONS

Self-Testing Industrial Series

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

Fusetron FRN-R Class RK5 250Vac/125Vdc A, dual element, time-delay fuses

Transcription:

RotoTract Remote Racking Operating Manual Instruction Leaflet IL04300001E Effective July 2008 RotoTract Remote Racking Accessory for Use with FlashGard Motor Control Center Units Introduction RotoTract remote racking accessory allows the user of a FlashGard MCC unit to rack IN the unit retractable stabs into the CONNECTED position or rack OUT the unit retractable stabs into the WITHDRAWN position. A unit test position is available with IT. MCC units only; in this position, the unit stabs are disconnected and the unit s IT. Cover Control is powered with 24 Vdc for diagnostic purposes. Remote racking control is accomplished with a hand-held pendant station which is available with a 15-foot long cord that connects to the drive module. The drive module is powered with 120 Vac through a 4-foot cord. Accessory Kit Contents The kit (Catalog Number CHFG-RRS) comes completely contained in its own carrying case, with an installation and user manual booklet and contains: 1 RotoTract accessory module 1 Pendant station 1 ac power cord (not shown) CAUTIONS AND WARNINGS PRIOR TO USING THIS ACCESSORY, ENSURE THAT ALL AND ANY POWER SOURCES ARE REMOVED FROM THE MCC INSTALLATION. REMOTE RACKING SHALL ONLY BE PERFORMED BY QUALIFIED PERSONNEL. FlashGard Stabs Position Indicator Status The MCC unit stabs position indicators window shows the status of the unit retractable stabs: WITHDRAWN (GREEN) Indicator MCC unit stabs are disconnected from the MCC vertical bus and are in the withdrawn position and the control power is switched OFF. See Figure 1. FIGURE 1.

CONNECTED (RED) Indicator MCC unit stabs are connected to the MCC vertical bus. See Figure 2. Notes: For IT. MCC units only, the 24 Vdc control power supply is switched ON in this position. For Freedom 2100 MCC units, the control power is provided by a CPT source which is only switched ON when the unit disconnect is in an energized position and supply voltage is provided by a CPT. FlashGard Positive Shutter indication The FlashGard retractable stab mechanism mounted in the MCC unit has an integral second shutter system that operates independently to the MCC vertical bus shutter mechanism. The integral unit shutter is provided with an indicator window on the front on the unit that shows: Shutter Open RED Indicator shows that the retractable stabs are CONNECTED to the MCC vertical bus. FIGURE 2. TEST (YELLOW) INDICATOR MCC unit stabs are disconnected and are withdrawn in this position. See Figure 3. Notes: IT. MCC units only, the 24 Vdc control power supply remains switched ON and the IT. unit cover controls are operational. The test position is not available with Freedom 2100 MCC units. IT. MCC Feeder units only, with optional programmable cover controls with 24 Vdc control power. FIGURE 4. Shutter Closed GREEN Indicator providing positive indication that the stabs are retracted from the MCC vertical bus and are WITHDRAWN. FIGURE 5. TABLE 1. FLASHGARD INDICATOR STATUS FIGURE 3. FlashGard Unit Interlocking Features The MCC unit disconnect-operating handle is interlocked in the OFF position when the FlashGard is in the WITHDRAWN GREEN or TEST YELLOW stab position indicator window; with access to the racking portal open ready to receive this remote racking accessory. Close and securely latch the MCC unit door prior to mounting the remote racking accessory to the MCC unit. With the door closed and the unit in the disconnect in the OFF position, the retractable stabs are free to be racked into the CONNECTED position. In the CONNECTED position, the disconnect interlock is disengaged, enabling the disconnect-operating handle to be turned ON to energize the unit power circuitry. POSITION INDICATOR SHUTTER INDICATOR WITHDRAWN GREEN GREEN TEST YELLOW GREEN CONNECTED RED RED Instruction and Training Material Prior to any action using this accessory, ensure that all and any power sources are removed from the MCC installation. Remote racking shall only be performed by qualified personnel. 2 EATON CORPORATION Cutler-Hammer RotoTract Remote Racking Operating Manual Instruction Leaflet IL04300001E Effective: July 2008

Mount Racking System to MCC Unit 1. Mounting the RotoTract module directly to the MCC unit front panel as shown in Figures 6 and 7. 2. There are two mounting points that need to be fastened to securely attach the module to the unit, hand tighten as shown in Figure 7. 3. Connect the pendant station to the drive module, see Figure 9. 4. Connect 120 Vac cord to the drive module and then to a 120 Vac power socket, see Figure 10. It is recommended to use this accessory with an ac power socket that is protected by a Class A, ground fault circuit interrupter. Note: ac connector on drive module is fused with a Bussmann type GMA 1 amp fuse. The AMBER POWER indicator will illuminate when connected to the ac power and indicate the drive module is energized and ready to begin racking operations. FIGURE 7. Basic Operating Procedures The basic operating parameter of the racking system drive module which is controlled by the hand-held pendant station with IN and OUT push-buttons. Drive module indication: RED Pendant station IN push-button active. AMBER 120 Vac powered. GREEN Pendant station OUT push-button active. Installing a unit by operating the IN push-button operator, on the pendant station; racks the MCC unit retractable stabs into the CONNECTED position indicated by the RED flag in the window on the left side of the front panel. Racking time is approximately 12 seconds. Removing a unit by operating the OUT push-button operator, on the pendant station; racks the MCC unit retractable stabs into the WITH- DRAWN position indicated by the GREEN flag in the window on the left side of the front panel. Racking time is approximately 12 seconds. Best practice for locating the TEST position is to rack out by using the OUT push-button operator on the pendant station to the WITHDRAWN position indicated by the GREEN flag in the window on the left side of the front panel. Then, by inching the IN operator until the TEST position is indicated by the YELLOW flag in the window on the left side of the front panel. Units with 24 Vdc cover control - device island, see Figure 13; all the lights on the control panel will be illuminated when in the TEST position, indicating control power is engaged. FIGURE 8. FIGURE 9. FIGURE 6. FIGURE 10. EATON CORPORATION Cutler-Hammer RotoTract Remote Racking Operating Manual Instruction Leaflet IL04300001E Copyright 2008 3

Freewheeling Drive System Feature This feature automatically controls and limits the retractable stab moving carriage drive torque with a clutch mechanism in both the CONNECTED and WITHDRAWN position. When in freewheeling condition, the clutch mechanism makes a clicking sound. FAQ 1. The unit disconnect cannot be closed and turned ON? Removing this accessory releases an interlock that blocks the disconnect operation. The retractable stabs must be in the CONNECTED position to release the interlock blocking the disconnect operation. 1/4 turn latch and unit interlock must be fully rotated counterclockwise, see Figure 11, insert bottom left. FIGURE 11. MCC Unit Removal and Installation Procedures The removal and the installation of a MCC unit is described in the following sections. Preparation to Remove Plug-in Units: CAUTION UNITS 18 INCHES OR MORE HIGH HAVE A RETAINING SCREW AT THE LOWER EDGE OF EACH SIDE OF THE UNIT FRAME TO ADD STABILITY IN SHIPPING. THE SHIPPING SCREWS MAY BE RETAINED AND REUSED OR REMOVED AFTER INSTALLATION: UNSCREW PRIOR TO UNIT WITHDRAWAL. Removing a Unit 1. Turn unit operator OFF and keep unit door closed. At this point, the Stab Position indicator should show RED, indicating that the stabs are fully extended and connected to the vertical bus. The Shutter Indication should show RED also indicating that the shutters are open. 2. To disconnect the stabs from the vertical bus, a 3/8-inch square drive should be inserted into the Racking Receiver. The 3/8-inch square drive can either be a manual tool or a remote racking device. Rotate the square drive counterclockwise to begin to remove the stabs. If you happen to rotate clockwise, the unit should spin freely and prevent the stabs from being forced any further on the vertical bus. The Stab Position Indicator flag and the Shutter Position Indicator flag should begin to rotate to show the position of the stabs and internal shutter. It takes approximately 22 full rotations to move the stabs from the connected to the disconnect position. The disconnect position will be illustrated when the Stab Position Indicator and Shutter Position Indicator are both GREEN. 3. Open the vertical wireway door to remove any plug-in terminal blocks that might be connected to the unit (Figure 12). Please look for any additional wiring that might be terminated inside the unit. These connections will need to be removed prior to removal of the unit from the structure. 4. Turn the Unit Latch, which is located left of the unit operator (Figure 11), counterclockwise approximately 1/4 turn. 5. Open unit door and remove an interconnection wiring between units, master terminal block or external point of the motor control center. For units that contain a motor load stab, disconnection of the motor leads is not required in order to remove the unit from the structure. 6. Inspect the unit for any other material, accessories or cable that might interfere with the removal of the unit. 7. Pull the unit toward you. Guide rails that assist in the removal of the bucket will support the bucket. Visually verify that the shutter in the structure for the bucket has closed over the opening to the vertical bus. If the shutter did not close, please shut down power to the motor control center prior to replacement or repair of the shutter. 8. Close unit door by securing the door 1/4 turn latches on the right side of the door to reduce access to the unit. FIGURE 12. DISENGAGING PULL-APART TERMINAL BLOCKS 4 EATON CORPORATION Cutler-Hammer RotoTract Remote Racking Operating Manual Instruction Leaflet IL04300001E Effective: July 2008

Installation of a Unit 1. Prior to installation of the unit, verify that the unit stabs are fully withdrawn and the internal shutters are closed (Figure 14). The Unit Latch at the top of the bucket needs to be flush with the top of the bucket to prevent interference with the divider pan when installing the bucket. The unit operator needs to be in the OFF position and the unit latch should be turned down so the metal tab on the left side of the unit is inside the unit. This will prevent any interference with the structure frame when installing in the structure. 2. Open the unit door and slide the bucket into the structure. The unit uses two guide rails that are located on the left and right side bottom of the divider pan. The top wrapper of the unit has grooves on the left and right side that sit into the guide rail (Figure 17). 3. Press the unit in the structure until the front of the unit is approximately flush with the divider pan. You might feel a little resistance when sliding in the structure. This is due to the physical connection between the motor load stabs and motor load terminal block on the lower right-hand side of the unit. 4. Open the vertical wireway door to install any plug-in terminal blocks or terminal and interconnection wiring inside of the unit. Close and secure the wireway door. 5. Turn the latch located to the left of the unit operator clockwise until it is horizontal. FIGURE 14. STABS IN DISCONNECT POSITION FIGURE 15. STABS IN TEST POSITION FIGURE 16. STABS IN CONNECTED POSITION FIGURE 13. IT. FLASHGARD COMPONENTS FIGURE 17. SHUTTER-ARM LINKAGE EATON CORPORATION Cutler-Hammer RotoTract Remote Racking Operating Manual Instruction Leaflet IL04300001E Copyright 2008 5

This page intentionally left blank. 6 EATON CORPORATION Cutler-Hammer RotoTract Remote Racking Operating Manual Instruction Leaflet IL04300001E Effective: July 2008

This page intentionally left blank. EATON CORPORATION Cutler-Hammer RotoTract Remote Racking Operating Manual Instruction Leaflet IL04300001E Copyright 2008 7

Eaton Corporation Electrical Group 1000 Cherrington Parkway Moon Township, PA 15108 United States 877-ETN-CARE (877-386-2273) Eaton.com RotoTract and FlashGard are trademarks of Eaton Corporation. Bussmann is a registered trademark of Cooper Industries, Inc. 2008 Eaton Corporation All Rights Reserved Printed in USA Publication No. IL04300001E / Z7161 July 2008